POTTER PPAD100-MIM Micro Input Module Owner’s Manual

June 9, 2024
POTTER

POTTER PPAD100-MIM Micro Input Module Owner’s Manual
POTTER PPAD100-MIM Micro Input Module

Features

  • One Class B contact monitoring input
  • Small size allows mounting in most electrical boxes
  • SLC Class A, Class X & Class B
  • 6” Pigtail wiring connections
  • Product includes a 5 year warranty
  • UUKL Listed for Smoke Control

Description

The PAD100-MIM is used to monitor the status of an initiating device(s) that contain a normally open set of dry contacts. The module is enclosed in a plastic case to protect against inadvertent shorts and ground faults. The case can be mounted using a single screw. The PA D100-MIM has a status indicator LED to indicate communication and alarm condition. In normal condition, the LED flashes when the device is being polled by the control panel. When the input is activated, the LED will flash at a fast rate.

Application

The micro input module (PAD100-MIM) is compatible with Potter’s IPA and AFC/ARC series addressable fire alarm control panels. Generally the PA D100-MIM is used to monitor pull stations and other devices where the module is installed in an electrical box or enclosure behind the device being monitored

Technical Specifications

Operating Voltage 24.0V
Max SLC Standby Current 200μA
Max SLC Alarm Current 200μA
IDC Input Circuit Wiring Class B
Max Wiring Resistance of IDC 100 Ω
Max Wiring Capacitance of IDC 1μF
EOL Resistor 5.1K Ω
Operating Temperature Range 32 to 120ºF (0 to 49ºC)
Operating Humidity Range 0 to 93% (non-condensing)
Max no. of Module Per Loop 127 units
Dimensions 1.75” (44.5mm)L × 1.36”(34.5mm)W× .43” (11mm)D
Mounting Options 2-1/2” (64mm) deep single-gang box
Shipping Weight 0.3 lbs

Setting the Address

Each addressable SLC device must be assigned an address. The address is set using the DIP switch located on the front of the PAD100-MIM. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device:

  1. Power to the device is removed.
  2. Field wiring is correctly installed.
  3. Field wiring has no open or short circuits.

Wiring Diagram

Wiring Diagram

Ordering Information

Model Description Stock No.
PAD100-MIM Micro Input Module 3992700