POTTER CHS Series Selectable Candela Ceiling Mount Horn Strobe Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
CS/CHS
SELECTABLE CANDELA
CEiLiNg mouNT
Owner’s Manual
Features
-
Nominal voltage 24 VDC
-
Tamperproof field selectable candela options 15, 30, 75, 95, 115, & 150
-
Super-Slide® Bracket – Ease of Supervision Testing
-
Checkmate® – Instant Voltage Verification
-
Synchronize strobe and/or horn with Gentex AVSM Control Module
-
Prewire entire system, install mounting bracket, then install signals
-
Documented lower installation and operating costs
-
Input Terminals 12 to 18 AWG
-
Switch Selection for High or Low dBA
-
Switch Selection for 2400Hz or mechanical Tone
-
Switch Selection for Continuous or Temporal 3
-
Tamperproof re-entrant grill
-
Surface mount with the CLNGBB (Ceiling Surface Mount Back Box)
-
Silence audible while visual appliance will remain flashing (for use in accepted jurisdictions)
-
Faceplate available in red or off-white
Operating Temperature: -
32°F to 120°F (0°C to 49°C). The CS Series is not listed for outdoor use.
Unit Dimensions -
6″ (15.24 cm) x 2.6″ (6.604 cm)
Product includes a 5 year warranty
Description
The Potter CS/CHS Series is a ceiling mount strobe or horn/strobe combination
that offers dependable audible and visual alarms and the lowest current
consumption.
The CS/CHS offers tamperproof field selectable candela options of 15, 30, 75,
95, 115 and 150 candela.
The CHS horn offers a continuous or synchable temporal three in 2400Hz and
mechanical tone. All tones are easy for the professional to change in the
field by using switches. The models are shipped from the factory in the
temporal three alarm mode.
The CS Series has a very minimal operating current and has a minimum flash
rate of 1Hz regardless of input voltage.
The Ceiling Mount Series comes standard with the 4″ mounting plate which
incorporates the popular Super-Slide® feature that allows the installer to
easily test for supervision. The product also features a locking mechanism
which secures the product to the bracket without any screws showing.
The CS/CHS also features the patented Checkmate® – Instant Voltage
Verification feature which allows the installer to check the voltage drop draw
without removing the signal.
The CS Series appliances are ANSI/UL 464 and ANSI/UL 1971 listed for use with
fire protective systems.
Mounting Super-Slide®
Checkmate® Instant Voltage Verification
The access holes are provided in the back of the terminal block to allow the
voltage to be measured directly without removing the device. Typically this
would be done at the end of the line to confirm design criteria. Most
measurements will be taken using the S+ and S- locations although access is
provided to other locations.
NOTICE: CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES.
Switch Locations
Switch positions 1 and 2 in the down position to select isolated horn and strobe power inputs. Switch 3 selects between temporal or nontemporal tone. Up is temporal. Switch 4 selects between mechanical or high frequency tone. Up is mechanical. Switch 5 selects between high or low dBA. Up is high dBA.
CS Series 24 Volt Ceiling Mount Selectable Strobe
Model Number | Part Number | Nominal Voltage | Candela |
---|---|---|---|
CS-24R | 4890020 | 24 VDC | 15, 30, 75, 95, 115, 150 |
CS-24W | 4890021 | 24 VDC | 15, 30, 75, 95, 115, 150 |
CS-24PR | 4890022 | 24 VDC | 15, 30, 75, 95, 115, 150 |
CS-24PW | 4890023 | 24 VDC | 15, 30, 75, 95, 115, 150 |
CHS Series 24 Volt Ceiling Mount Selectable Horn/Strobe
Model Number| Part Number| Nominal Voltage| Candela| Reverberant dBA @ 10 ft.
per ANSI/UL 464| In Anechoic Room dBA @ 10 ft.
---|---|---|---|---|---
CHS-24R| 4890040| 24 VDC| 15, 30, 75, 95, 115, 150| 81-86| 90
CHS-24W| 4890041| 24 VDC| 15, 30, 75, 95, 115, 150| 81-86| 90
CHS-24PR| 4890042| 24 VDC| 15, 30, 75, 95, 115, 150| 81-86| 90
CHS-24PW| 4890043| 24 VDC| 15, 30, 75, 95, 115, 150| 81-86| 90
Model Designations:
C = Ceiling Mount
S = Strobe
HS = Horn/Strobe
R = Red Faceplate
W = White Faceplate
All units are available in plain (no lettering).
Plain units are non-returnable.
CS24 Product Strobe Current Ratings (mA)
| Candela| 15 cd| 30 cd| 75 cd| 95 cd| 115 cd| 150 cd
---|---|---|---|---|---|---|---
24 VDC (16-33 Volts)| 24 VDC| 72 mA| 101 mA| 167 mA| 200 mA| 214 mA| 286 mA
UL Max’| 120 mA| 120 mA| 200 mA| 220 mA| 290 mA| 321 mA
CHS24 Product Horn Decibel and Current Ratings (mA)
Horn Mode| Minimum dBA @ 10 ft.
per ANSI/UL 464 (HIGH)| Minimum dBA @ 10 ft.
per ANSI/UL 464 (LOW)| Regulated 24 VDC
Max. Operating @ High Setting (mA)
---|---|---|---
Temp 3 2400Hz| 83| 75| 23
Temp 3 Mechanical| 81| 73*| 22
Continuous 2400Hz| 86| 78| 23
Continuous Mechanical| 84| 76| 22
NOTES:
- The sound output for the temporal 3 tone is rated lower since the time the horn is off is averaged into the sound output rating. While the horn is producing a tone in the temporal 3 mode its sound pressure is the same as the continuous mode.
- For nominal and peak current across UL regulated voltage range for filtered DC power and unfiltered (FWR [Full Wave Rectified]) power, see installation manual.
- Potter does not recommend using a coded or pulsing signaling circuit with any of our strobe products.
- Operating the horn in this mode at this voltage will result in not meeting the minimum ANSI/UL 464 reverberant sound level required for public mode fire protection service.These settings are acceptable only for private mode fire alarm use. Use the high dBA setting for public mode application (not applicable when using the chime tone. The chime tone is always private mode).
- RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33VDC for 24VDC units). For strobes the UL max current is usually at the minimum listed voltage (16VDC for 24VDC units). For audibles the max current is usually at the maximum listed voltage. For unfiltered FWR ratings, see installation manual.
Architect & Engineering Specifications
The visible and audible/visible signal shall be Gentex model GCS or GCC or
approved equal and shall be listed by Underwriters Laboratories Inc. per
ANSI/UL 1971 for the GCS and ANSI/UL 464 for the GCC. The notification
appliance shall also be listed with the California State Fire Marshal (CSFM).
The notification appliance (combination audible/visible units and audible
units only) shall produce a peak sound output of 90dBA or greater as measured
at 24VDC in an anechoic chamber. The signaling appliance shall also have the
capability to silence the audible signal while leaving the visible signal
energized with the use of a single pair of power wires. Additionally, the user
shall be able to select either continuous or temporal tone output with the
temporal signal having the ability to be synchronized.
The audible/visible and visible signaling appliance shall also maintain a
minimum flash rate of 1Hz or up to 2Hz regardless of power input voltage. The
appliance shall have an operating current of 72mA or less at 24VDC for the 15
candela strobe circuit.
The appliance shall be polarized to allow for electrical supervision of the
system wiring. The unit shall be provided with a mounting bracket with
terminals with barriers for input/output wiring and be able to mount to a
single gang or double gang box or double workbox with the use of an adapter
plate. The unit shall have an input voltage range of 16-33 volts with either
direct current or full wave rectified power.
The appliance shall be capable of test supervision without disconnecting
wires, verify voltage without removing unit and be capable of mounting to a
surface back box.
Conventional CS/CHS Series Wiring Diagrams
NOTES:
- All strobes are designed to flash as specified with continuous applied voltage. Strobes should not be used on coded or pulsing signaling circuits. However, use of the Gentex AVSM control module or Gentex synchronization protocol is permitted to synchronize the strobe, horn and/or mute the horn.
- FOR SYNCHRONIZATION WIRING INFORMATION, REFERENCE AVSM CONTROL MODULE DATA SHEET (8830050) AND/OR AVSM CONTROL MODULE MANUAL FOR SYNCHRONIZATION MODULE WIRING DIAGRAMS. AVSM CONTROL MODULE DATA SHEET AND MANUAL CAN BE OBTAINED AT http://www.pottersignal.com OR CALL POTTER ELECTRIC AT 1-800-325-3936.
Potter Electric Signal Company, LLC
• St. Louis, MO 63042 USA• Cust Service:
866-572-3005
• Tech Support: 866-956-0988 • Canada
888-882-1833
• www.pottersignal.com
MFG. #8830051 – REV A
06/13
firealarmresources.com