INS-2500 (EU) IntelliGen ™
Nitrogen Generator
Features
- Potter’s IntelliGen ™ Controller (Patent Pending)
- Fully automates the air fill and nitrogen fill procedure
- Advance leak rate detection
- Integrated Bypass alarm
- Web Enabled – system can be monitored anywhere there is internet connectivity
- Automatically emails trouble alerts and maintenance reminders
- 7.5 HP lubricated tank mounted air compressor included to meet NFPA 13 required 30 minutes fill for 7570 L (2,000 Gals.) system at 2,76 BAR (40 PSI) (276 kPa).
- Handles up to 90850 L (24,000 Gals.) of total sprinkler system capacity (based on NFPA 13 allowable leak rate of 0,103 BAR (1.5 PSI) (10,3 kPa) per 24 hours for a new sprinkler system).
- Three individual skids – 303 L (80 Gals.) tank mounted air compressor, nitrogen cabinet and Qty (2) 227 L (60 Gals.) nitrogen tanks.
Description
Potter’s IntelliGen ™ Series of Nitrogen Generators are specifically designed
to generate on-site, 98%+ purity nitrogen for use in fire protection sprinkler
systems. When used as a supervisory gas in fire sprinkler systems, nitrogen
slows corrosion, improves the life of your system, and lowers maintenance
costs. The INS-2500 (EU) utilizes nitrogen membrane technology for gas
separation. Nitrogen membranes are highly effective and a cost conscious way
of producing on-site nitrogen. Acting as a gas filter, the nitrogen membrane
separates the oxygen and water vapor molecules in the air from the nitrogen
molecules.
The high purity nitrogen gas is then piped through the air maintenance device
and into the fire protection system. As the system fills with nitrogen, the
remaining oxygen molecules in the fire protection system are exhausted by
using the Potter IntelliPurge ® Nitrogen Purge Valve.
Note: The Potter IntelliPurge ® Nitrogen Purge Valve is not CE Marked, CE
Pending. The Potter IntelliPurge ® Nitrogen Purge Valve monitors the fire
protection system to ensure high purity nitrogen is consistent throughout the
sprinkler system.
The INS-2500 (EU) is to be connected to a new or existing fire sprinkler
system. This system includes an air compressor, nitrogen membrane, all air
filtration equipment, tanks and the Potter IntelliGen ™ Controller. The Potter
IntelliGen ™ Controller ensures the contractor the easiest setup and operation
of any nitrogen generator system in the industry. Each unit is designed to be
turned on and walk away. The built-in monitoring capabilities will make
corrections and alert you to any necessary changes.
Technical Specifications
Compressor Package Size | 1880mm (74″) H x 940mm (37″) W x 610mm (24″) D |
---|---|
Nitrogen Cabinet Size | 1778mm (70″) H x 766mm (31″) W x 314mm (131 D |
Nitrogen Tank Size | 1346mm (53″) H x 508mm (20″) 0 |
Compressor Package Weight | 300 kg (600 Ibs) |
Nitrogen Cabinet Weight | 118 kg (26016s) |
Nitrogen Tank Weight | 159 kg (350 lbs) (2 required) |
Air Compressor Power Supply* Available in: | 380-415 VAC (11.1A) three phase 50 |
Hz
Max Operating Pressure| 10,00 BAR (145 PSI) (1,000 kPa)
Temperature Range| 10°C (50°F) to 43°C (110°F)
*Note: Requires two (2) 220 V 50 Hz connections for nitrogen cabinet and air tank blow-down solenoid.
Installation
The Potter INS-2500 (EU) should be installed in a dry, clean, and well
ventilated room with ambient temperatures above 10°C at all times. Allow
access to the front for service and place the unit in a location that is
conveniently located near fire sprinkler system connections, a drain, and a
dedicated electrical connection. The Potter IntelliGen
™ Nitrogen Generator should always be installed in an adequately ventilated
room. Rapid release of nitrogen gas into an enclosed space displaces the
oxygen and can cause an asphyxiation hazard. For detailed installation and
operation instructions please refer to the Potter IntelliGen ™ Nitrogen
Generator Manual #5403681.
Cabinet Dimensions
Fig 1
Tank Dimensions
Note: INS-2500 (EU) requires two 227 L (60 Gals.) tanks.
Compressor Dimensions
Ordering Information
Part Number | Model | Description |
---|---|---|
1119654 | INS-2500 (EU), 380-415VAC 3PH 50 HZ | IntelliGee Nitrogen System-2500 |
(EU) , 380-415VAC Three Phase
1119478| INS-PV| IntelliPurge® Nitrogen Purge Valve*
1119784| NGP-SPV| Potter Purge Valve
1119621| NGP-AMD-1| Potter Air Maintenance Device
1119504| PNA| Portable Nitrogen Analyzer
- Note: The Potter IntelliPurge ® Nitrogen Purge Valve is not CE Marked, CE Pending.
Potter Electric Signal Company, LLC • St. Louis, MO
Phone:800-325-3936
www.pottersignal.com
8820085 – REV C • 02/21
firealarmresources.com
Documents / Resources
|
POTTER INS-2500 (EU) IntelliGen Nitrogen
Generator
[pdf] Owner's Manual
INS-2500 EU IntelliGen Nitrogen Generator, INS-2500, EU IntelliGen Nitrogen
Generator, IntelliGen Nitrogen Generator, Nitrogen Generator
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>