POTTER INS-250 (EU) IntelliGen Nitrogen Generator Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
INS-250 (EU) IntelliGen ™
Nitrogen Generator
Features
- potter’s Intelligen™ Controller (Patent Pending)
- Fully automates the air fill and nitrogen fill procedure
- Advance leak rate detection
- Integrated Bypass alarm
- Web Enabled – system can be monitored anywhere there is internet connectivity
- Automatically e-mails trouble alerts and maintenance reminders
- Integrated 0,37 kW (1/2HP) oil-less air compressor included to meet NFPA 13 required 30 minutes fill for 1135 L (300 Gals.) system at 2,76 BAR (40 PSI) (276 kPa).
- Handles up to 3785 L (1000 Gals.) of total sprinkler system capacity.
- Easy plug and play installation.
- 37,9 L (10 Gals.) nitrogen tank.
- Form C dry contacts for Building Management System (BMS) notification.
Description
potter’s Intelligen ™ Series of Nitrogen Generators are specifically designed
to generate on-site, 98%+ purity nitrogen for use in fire protection sprinkler
systems. When used as a supervisory gas in fire sprinkler systems, nitrogen
slows corrosion, improves the life of your system, and lowers maintenance
costs.
The INS-250 (EU) utilizes nitrogen membrane technology for gas separation.
Nitrogen membranes are highly effective and a cost conscious way of producing
on-site nitrogen. Acting as a gas filter, the nitrogen membrane separates the
oxygen and water vapor molecules in the air from the nitrogen molecules. The
high purity nitrogen gas is then piped through the air maintenance device and
into the fire protection system. As the system fills with nitrogen, the
remaining oxygen molecules in the fire protection system are exhausted by
using the Potter IntelliPurge ® Nitrogen Purge Valve.
Note: The Potter IntelliPurge ® Nitrogen Purge Valve is not CE Marked, CE
Pending.
The Potter IntelliPurge ® Nitrogen Purge Valve monitors the fire protection
system to ensure high purity nitrogen is consistent throughout the sprinkler
system.
The INS-250 (EU) is a fully assembled package ready to be connected to a new
or existing fire sprinkler system. This turn-key system includes an integrated
air compressor, nitrogen membrane, tank, all air
filtration equipment, and the Potter IntelliGen ™ Controller.
The Potter IntelliGen ™ Controller ensures the contractor the easiest setup
and operation of any nitrogen generator system in the industry.
Each unit is designed to be turned on and walk away. The built-in monitoring
capabilities will make corrections and alert you to any necessary changes.
Technical Specifications
Nitrogen Cabinet Size | 919mm (36 1/4″) H X 660mm (26″) W X 306mm (12″) D |
---|---|
Nitrogen Tank Size | 902mm (351/2″) H X 457mm (18″) W X 254mm (10″) 0 |
Weight | 59 kg (130 lbs.) |
Power Supply Available in: | 220-240V (2.6A) single phase 50HZ |
Fire Sprinkler System Connection | 1/2″ Female NPT |
Nitrogen Cabinet Mounting Holes | (2) 9,53mm (3/8-16″) 0 |
Nitrogen Tank Mounting Holes | (4) 12,7nun (1/2″) 0 |
Operating Pressure | 8,27 BAR (120 PSI) (827 kPa) |
Temperature Range | 10°C (50°F) to 43°C (110°F) |
Installation
The Potter INS-250 (EU) should be installed in a dry, clean, and well ventilated room with ambient temperatures above 10°C (50°F) at all times. Allow access to the front for service and place the unit in a location that is conveniently located near fire sprinkler system connections, a drain, and a dedicated electrical connection. The potter Intelligen ™ Nitrogen Generator should always be installed in an adequately ventilated room. Rapid release of nitrogen gas into an enclosed space displaces the oxygen and can cause asphyxiation hazard. For detailed installation and operation instructions please refer to the Potter IntelliGen™ Nitrogen Generator Manual #5403644.
Cabinet Dimensions
Fig 1
Tank Dimensions
Ordering Information
Part Number | Model | Description |
---|---|---|
1119628 | INS-250(EU), 220-240VAC 1PH 50 HZ | IntelliGenTh Nitrogen |
System-250(EU), 220-240VAC Single Phase 50 HZ
1119478| INS-PV| IntelliPurge® Nitrogen Purge Valve*
1119784| NGP-SPV| Potter Purge Valve
1119621| NGP-AMD-1| Potter Air Maintenance Device
1119504| PNA| Portable Nitrogen Analyzer
- Note: The Potter IntelliPurge ® Nitrogen Purge Valve is not CE Marked, CE Pending.
Potter Electric Signal Company, LLC • St. Louis, MO
Phone:800-325-3936 •
www.pottersignal.com
8820042 – REV C 02/19
firealarmresources.com
Documents / Resources
|
POTTER INS-250 (EU) IntelliGen Nitrogen
Generator
[pdf] Owner's Manual
INS-250 EU IntelliGen Nitrogen Generator, INS-250 EU, IntelliGen Nitrogen
Generator, Nitrogen Generator
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>