POTTER MCM Miniature Contact Module Instruction Manual
- June 9, 2024
- POTTER
Table of Contents
MCM Miniature Contact Module
TN51314e<0>
Effective 01.06, 2011
Installation Manual MCM Miniature Contact Module
NOTICE TO THE INSTALLER This manual provides an overview and the installation
instructions for the MCM module. This module is only compatible with
addressable fire systems that utilize the Potter/Nohmi addressable protocol.
All terminals are power limited and should be wired in accordance with the
requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure
to follow the wiring diagrams in the following pages will cause the system to
not operate as intended. For further information, refer to the control panel
installation instructions. The module shall only be installed with listed
control panels. Refer to the control panel installation manual for proper
system operation.
1. Description
The miniature contact module (MCM) module is used to monitor the contact
status of an initiating device that contains a normally open contact. When the
Normally-open contact is selected, and the contact is shorted, the MCM reports
its condition to FACP. The MCM supervises an open circuit of wiring connected
to the terminal C and NO. The MCM is generally used to monitor pull stations
and other devices where the module is installed in an electrical box or
enclosure. The contact utilizes a terminal block that is covered in accordance
with UL requirements to protect from inadvertent shorts and ground faults.
2. Setting the Address
Each addressable module, smoke sensor, heat detector and combination
sensor/detector must have the address set prior connecting the device to the
SLC loop. The address is set using the hand held device programmer. Prior to
connecting a device to the SLC loop, the following precautions should be taken
to prevent potential damage to SLC or device. Verify the following before
proceeding. Document discrepancies and notify appropriate personnel. 1. Power
in the Addressable Module is removed 2. Field wiring on the module is
correctly installed. 3. Field wiring has no open or short circuits
firealarmresources.com
3. Wiring diagram
SS+ C NO
SLC Loop
From FACP or previous module
To the next module
End of line resistor 5.1k ohm 1/ 2W
Figure 1: Wiring diagram in case of supervising Normally-open contact
Note: 1) SLC wiring style is applicable to the NFPA Class A (Style 6, 7) &
Class B (Style 4). 2) IDC wiring style is applicable to the NFPA Class B
(Style B). 3) SLC loop wiring (S+, S-) and initiating device wiring (C, NO)
are power limited. 4) Wiring for terminals S+, S- are supervised. 5) Wiring
for terminals C, NO are supervised. 6) This addressable module does not
support 2-wire detectors. 7) All wiring is between #14 (2.08 mm2) (max.) and
22 (0.32 mm2) (min.). 8) Wire Preparation Strip all wires 1/4 inch from their
edges as follows:
1/4 inch (6.4 mm)
Note: a) Stripping too much insulation may cause ground fault b) Stripping too
little may cause a poor connection and subsequently an open circuit
firealarmresources.com
4. Specifications
No.
Item
1 Rated voltage range of SLC input power (S+,S-) 2 Maximum SLC 24 VDC standby current (S+,S-) 3 Maximum SLC 24 VDC alarm current (S+,S-) 4 IDC input circuit wiring style 5 End-of-line resistor for IDC
6 Maximum wiring resistance of IDC 7 Maximum wiring capacitance of IDC 8 Operating temperature range 9 Operating humidity range 10 Maximum no. of module per loop 11 Dimensions
12 Applicable electrical box for installation
Specification
22.0 to 24.0V 250A 250A Class B (Style B) 5.1k,1/2W
100 1F 32 to 120F (0 to 49C) 0 to 93% (non-condensing) 127 units 2.58″(65.5mm)
(H) × 2.32″(59mm) (W) × 0.94″(24mm) (D) 2-1/2″(64mm)deep single-gang box
These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in connection with instillation, operation and maintenance. Specifications subject to change without prior notification For Technical Assistance contact Potter Electric Signal Company at 800-325-3936 Actual performance is based on proper application of the product by a qualified professional. Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to Nohmi or a distributor in your region.
Potter Electric Signal Company, LLC 1609 Park 370 Place, Hazelwood, MO 63042
USA
Telephone: (866)956-1211 URL: http://www.pottersignal.com