NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the LOC-1000 module. All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further information, refer to the control panel installation instructions. The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation.
DESCRIPTION
The LOC-1000 is a local operator console which is utilized to locally control
the system, generate live voice and ECS.
The LOC-1000 communicates in conjunction with the IPA-4000V using a RS-485
connection via P-Link. It also provides common indication of Alarms,
Supervisory, Trouble and other system status and control functions. A maximum
of thirty-one (31) LOC-1000 can be employed.
The LOC-1000 is equipped with three (3) modules ; LOC-RA6500R, SB-8 and
VM-1000.
The LOC-RA6500R is a remote annunciator that provides common indication for
Alarms, Supervisory, Trouble and other system status and control functions.
The board connects in conjunction with the IPA-4000V using a 4-wire RS-485
connection via P-Link. Alternatively, the LOC-RA6500R can communicate and
receive power from a PSN-1000. The LOC1000 is equipped with a bracket to
securely mount an optional PSN-1000 power supply.
The SB-8 is the user interface for ECS control and events. It provides 8
programmable buttons, an All Call button and an
ECS Reset and Control button. The SB-8 also includes LED indicators for Ready
to Page, Trouble, Control Requested,
Remotely Controlled and Locally Controlled. Each of the 8 programmable buttons
have two corresponding LEDs to indicate activity and trouble conditions.
The VM-1000 is the voice module that generates live voice and ECS to remote
amplifiers. The VM-1000 connects to the LOC-RA6500R using a 4-wire RS-485
connection via P-Link.
SETTING THE ADDRESS
The LOC-RA6500R and VM-1000 address is set by a five (5) position dip switch, which is used to program the device address ranging from one (1) to thirty-one (31). NOTE – LOC-RA6500R and VM-1000 devices will not have the same address.
Note: Each “gray” box indicates that the dip switch is “On,” and each “white” box indicates “Off.”
INSTALLATION MANUAL: LOC-1000
The examples shown below illustrate a P-Link’s dip switch settings: the 1st example shows a P-Link module not addressed where all dip switch settings are in the default “Off” position, the 2nd illustrates an addressed P-Link module via the dip switch settings
TECHNICAL SPECIFICATIONS
Standby Current | 77 mA |
---|---|
Alarm Current | 107 mA |
Maximum Wire Length | 6500 FT |
Maximum Number of LOC-1000 | 31 |
Wire Gauge | 14AWG – 22AWG |
Operating Temperature Range | 32° to 120° F (0° to 49°C) |
Operating Humidity Range | 10% to 93% (non-condensing) |
INSTALLATION
A LOC-PSN1000 can be mounted in the upper portion of the LOC-1000 cabinet to provide additional power. The LOCPSN1000 is an intelligent 10 amp power supply and P-Link repeater. Reference the PSN-1000(E) manual for additional technical and operational information,
LOC OPERATING INSTRUCTIONS
- ECS Reset When the RESET button is pressed, all active ECS events will relinquish.
- CTRL When the CTRL button is pressed, this allows operator consoles to request control of the system when a remote operator console is in use.
- Control Requested A steady amber LED indicates a LOC-1000 is requesting control of the system.
- Remotely Controlled A steady amber LED indicates a remote operating console is currently in control.
- Locally Controlled A steady red LED indicates the local operating console is currently in control.
Potter Electric Signal Company, LLC
St. Louis, MO
Phone:800-325-3936
www.pottersignal.com
firealarmresources.com
Documents / Resources
|
POTTER LOC-1000 Local Operator
Console
[pdf] Instruction Manual
LOC-1000 Local Operator Console, LOC-1000, Local Operator Console, Operator
Console, Console
---|---
|
POTTER LOC-1000 Local Operator
Console
[pdf] Owner's Manual
LOC-1000 Local Operator Console, LOC-1000, Local Operator Console, Operator
Console
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>