Installation Manual: PAD100-LED LED Module
NOTICE TO THE INSTALLER
This manual provides an overview and the installation instructions for the
PAD100-LED module. This module is only compatible with addressable fire
systems that utilize the PAD Addressable Protocol.
All terminals are power limited and should be wired in accordance with the
requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure
to follow the wiring diagrams in the following pages will cause the system to
not operate as intended. For further information, refer to the control panel
installation instructions.
The module shall only be installed with listed control panels. Refer to the
control panel installation manual for proper system operation.
Description
The PAD100-LED module uses one (1) SLC loop address when used as an
addressable indicator. The PAD100-LED is an addressable LED module used to
provide indication of a variety of system conditions. The module mounts on
either an UL Listed 2-1/2″ deep 2-gang box or 1-1/2″ deep 4″ square box.
The PAD100-LED includes one red LED to indicate the module’s status. In normal
condition, the LED flashes when the device is being polled by the control
panel. When activated, the LED will flash at a fast rate.
Setting the Address
All PAD protocol detectors and modules require an address prior to connection to the panel’s SLC loop. Each PAD device’s address (i.e., detector and/or module) is set by changing the dip switches located on the device. PAD device addresses are comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127.
Note: Each “gray” box indicates that the dip switch is “On,” and each
“white” box indicates “Off.”
The examples shown below illustrate a PAD device’s dip switch settings: the
1st example shows a device not addressed where all dip switch settings are in
the default “Off” position, the 2nd illustrates an addressed PAD device via
the dip switch settings.
Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the SLC or device.
- Power to the SLC is removed.
- Field wiring on module is correctly installed.
- Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage | 24.0V |
---|---|
Max SLC Standby Current | 240 μ A |
Max SLC Alarm Current | 240 μ A |
Operating Temperature Range | 32̊ to 120̊ F (0̊ to 49̊ C) |
Operating Humidity Range | 0 to 93% (non-condensing) |
Max no. of Module Per Loop | 127 units |
Dimensions | 4.17″ L x 4.17″ W x 1.14″ D |
Mounting Options | UL Listed 2-1/2″ deep 2-gang box or 1-1/2″ deep 4″ square |
box
Shipping Weight| 0.6 lbs
Wiring Diagrams
The wiring diagram shown below illustrates how to wire a PAD100-LED module. Additionally, an installation diagram shows how to install the module using a compatible electrical box.
Notes:
- SLC wiring style supports the Class A, Class B and Class X.
- SLC loop wiring (SLC+, SLC-) are power limited.
- Wiring for terminals SLC+, SLC- are supervised.
- All wiring is between #12 (max.) and #22 (min.).
- Wire Preparation – Strip all wires 1/4 inch from their edges as shown here:
– Stripping too much insulation may cause a ground fault.
– Stripping too little may cause a poor connection and subsequently an open circuit.
These instructions do not purport to cover all the details or variations in
the equipment described, nor provide for every possible contingency to be met
in connection with installation, operation and maintenance.
Specifications subject to change without prior notification.
For Technical Assistance contact Potter Electric Signal Company at
866-956-1211.
Actual performance is based on proper application of the product by a
qualified professional.
Should further information be desired or should particular problems arise,
which are not covered sufficiently for the purchaser’s purpose, the matter
should be referred to a distributor in your region.
Potter Electric Signal Company, LLC • St. Louis, MO • Phone:
800-325-3936 •
www.pottersignal.com
Document 5406312-A 02/16
firealarmresources.com
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>