POTTER Wet Pipe Corrosion Solutions Kit Instruction Manual

June 9, 2024
POTTER

Wet Pipe Corrosion Solutions Kit
Instruction Manual

WET PIPE CORROSION SOLUTIONS

FEATURES

Quickly removes oxygen from wet pipe systems
Extends life expectancy of sprinkler system by 2.8X
Lowers sprinkler maintenance costs
UL listed and FM approved Air Vents for fire sprinkler systems

Ordering Information

Model Description Part #
AquaN2 Kit Nitrogen Injection Manifold and Quick X-Haust Manifold 1119500
PAV Air Vent 1119720
PAAR-B Air Vent w/ Drip Pan 1030001
NCPR Nitrogen Cylinder Pressure Regulator w/Hose 1119501
PNA Nitrogen Analyzer 1119504
VSR-AT Automatic Test Flow Switch Varies

Wet System Inerting

The Potter AquaN2 Kit is designed to quickly and effectively purge oxygenated air from a wet fire protection system and replace it with high purity nitrogen gas. Reducing the oxygen levels in wet fire protection systems is essential in protecting the system from the effects of oxygen related corrosion often found at the air water interface in the fire sprinkler piping.

How It Works
Using the AquaN2 Kit, which includes the Nitrogen Injection Manifold (NIM) and the Quick X-Haust Manifold (QXM), in combination with a Potter Automatic Air Release (PAAR-B) or Potter Air Vent (PAV) and a nitrogen source, can easily remove up to 99.9% of oxygen from a wet system.
By removing as much air as possible, the fire sprinkler system will have increased performance, eliminating delayed activation or cyclic activation of vane type waterflow detectors.

Typical AquaN2 Installation

POTTER Wet Pipe Corrosion Solutions Kit - Typical
AquaN

PAV
Air Vent| PAAR-B
Air Vent with Drip Pan| NCPR
Cylinder Pressure Regulator| PNA
Portable Nitrogen Analyzer| VSR-AT
Automatic Test Flow Switch

POTTER Wet Pipe Corrosion Solutions Kit - Installation

DRY PIPE CORROSION SOLUTIONS

FEATURES
Potter’s IntelliGen™ Controller (Patent Pending)
Fully automates the air and nitrogen fill procedure
Advance leak rate detection
Integrated Bypass alarm
Web Enabled – system can be monitored anywhere there is internet connectivity and send email alerts
FM Approved per Approval Standard 1035

Ordering Information

Model Description Part #
INS Series IntelliGen™ Nitrogen Generator Varies
INS-PV IntelliPurge™ N2 Purge Valve 1119478
NGP-SPV N2 Purge Valve 1119784
NAMD Nitrogen/Air Maintenance Device 1119660
PNA N2 Analyzer 1119504
BVL Bleeder Valve 1000018
Replacement Filters Varies

Potter IntelliGen™ Nitrogen Generators

Potter’s IntelliGen™ Series of Nitrogen Generators are specifically designed to generate on-site, 98%+ purity nitrogen for use in fire protection sprinkler systems. When used as a supervisory gas in fire sprinkler systems, nitrogen slows corrosion, improves the life of a system, and lowers maintenance costs. All IntelliGen™ Nitrogen Generators use nitrogen membrane technology for gas separation. Nitrogen membranes are a highly effective and cost conscious way of producing on-site nitrogen.
All systems include an integrated air compressor, nitrogen membrane, all air filtration equipment, tanks, and the Potter IntelliGen™ Controller. Potter’s IntelliGen™ Controller ensures contractors the easiest setup and operation of any nitrogen generator system in the industry. Each unit is designed to be able to turn on and walk away. The built-in monitoring capabilities will make corrections and alert the user of any necessary changes.

Watch the Potter IntelliGen™ Nitrogen Generator overview video.
Visit:

http://pttr.us/INS-overview

Typical IntelliGen™ Installation

POTTER Wet Pipe Corrosion Solutions Kit - Typical IntelliGen Installation
1

INS-PV
IntelliPurge™ Nitrogen Purge Valve| NGP-SPV
Nitrogen Purge Valve| NAMD
Nitrogen Air Maintenance Device
POTTER Wet Pipe Corrosion Solutions Kit - Typical IntelliGen Installation
2
PNA
Portable Nitrogen Analyzer| BVL
Lever Type Bleeder Valve| Replacement Filters

POTTER Wet Pipe Corrosion Solutions Kit - Typical IntelliGen Installation
3

Potter Electric Signal Company, LLC
sales@pottersignal.com
866-956-1211
****www.pottersignal.com
firealarmresources.com