POTTER Wet Pipe Corrosion Solutions Kit Instruction Manual
- June 9, 2024
- POTTER
Table of Contents
Wet Pipe Corrosion Solutions Kit
Instruction Manual
WET PIPE CORROSION SOLUTIONS
FEATURES
Quickly removes oxygen from wet pipe systems
Extends life expectancy of sprinkler system by 2.8X
Lowers sprinkler maintenance costs
UL listed and FM approved Air Vents for fire sprinkler systems
Ordering Information
Model | Description | Part # |
---|---|---|
AquaN2 Kit | Nitrogen Injection Manifold and Quick X-Haust Manifold | 1119500 |
PAV | Air Vent | 1119720 |
PAAR-B | Air Vent w/ Drip Pan | 1030001 |
NCPR | Nitrogen Cylinder Pressure Regulator w/Hose | 1119501 |
PNA | Nitrogen Analyzer | 1119504 |
VSR-AT | Automatic Test Flow Switch | Varies |
Wet System Inerting
The Potter AquaN2 Kit is designed to quickly and effectively purge oxygenated air from a wet fire protection system and replace it with high purity nitrogen gas. Reducing the oxygen levels in wet fire protection systems is essential in protecting the system from the effects of oxygen related corrosion often found at the air water interface in the fire sprinkler piping.
How It Works
Using the AquaN2 Kit, which includes the Nitrogen Injection Manifold (NIM) and
the Quick X-Haust Manifold (QXM), in combination with a Potter Automatic Air
Release (PAAR-B) or Potter Air Vent (PAV) and a nitrogen source, can easily
remove up to 99.9% of oxygen from a wet system.
By removing as much air as possible, the fire sprinkler system will have
increased performance, eliminating delayed activation or cyclic activation of
vane type waterflow detectors.
Typical AquaN2 Installation
PAV
Air Vent| PAAR-B
Air Vent with Drip Pan| NCPR
Cylinder Pressure Regulator| PNA
Portable Nitrogen Analyzer| VSR-AT
Automatic Test Flow Switch
DRY PIPE CORROSION SOLUTIONS
FEATURES
Potter’s IntelliGen™ Controller (Patent Pending)
Fully automates the air and nitrogen fill procedure
Advance leak rate detection
Integrated Bypass alarm
Web Enabled – system can be monitored anywhere there is internet connectivity
and send email alerts
FM Approved per Approval Standard 1035
Ordering Information
Model | Description | Part # |
---|---|---|
INS Series | IntelliGen™ Nitrogen Generator | Varies |
INS-PV | IntelliPurge™ N2 Purge Valve | 1119478 |
NGP-SPV | N2 Purge Valve | 1119784 |
NAMD | Nitrogen/Air Maintenance Device | 1119660 |
PNA | N2 Analyzer | 1119504 |
BVL | Bleeder Valve | 1000018 |
– | Replacement Filters | Varies |
Potter IntelliGen™ Nitrogen Generators
Potter’s IntelliGen™ Series of Nitrogen Generators are specifically designed
to generate on-site, 98%+ purity nitrogen for use in fire protection sprinkler
systems. When used as a supervisory gas in fire sprinkler systems, nitrogen
slows corrosion, improves the life of a system, and lowers maintenance costs.
All IntelliGen™ Nitrogen Generators use nitrogen membrane technology for gas
separation. Nitrogen membranes are a highly effective and cost conscious way
of producing on-site nitrogen.
All systems include an integrated air compressor, nitrogen membrane, all air
filtration equipment, tanks, and the Potter IntelliGen™ Controller. Potter’s
IntelliGen™ Controller ensures contractors the easiest setup and operation of
any nitrogen generator system in the industry. Each unit is designed to be
able to turn on and walk away. The built-in monitoring capabilities will make
corrections and alert the user of any necessary changes.
Watch the Potter IntelliGen™ Nitrogen Generator overview video.
Visit:
Typical IntelliGen™ Installation
INS-PV
IntelliPurge™ Nitrogen Purge Valve| NGP-SPV
Nitrogen Purge Valve| NAMD
Nitrogen Air Maintenance Device
PNA
Portable Nitrogen Analyzer| BVL
Lever Type Bleeder Valve| Replacement Filters
Potter Electric Signal Company, LLC
sales@pottersignal.com
866-956-1211
****www.pottersignal.com
firealarmresources.com
References
- Fire Alarm Resources | Download fire alarm documents
- YouTube
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)