POTTER RTS-O Room Temperature Switch Instruction Manual
- June 9, 2024
- POTTER
Table of Contents
RTS-O / RTS-C
ROOM TEMPERATURE SWITCH
RTS-O Room Temperature Switch
RTS-O Stock No. 1010108
RTS-C Stock No. 1010109
Listings: | UL, cUL Listed |
---|---|
Enclosure: | White ABS |
Dimensions: | 2 1/16″W x 3 7/16″L x 1 1/4″H (5,2cm W x ,.7cm L x,3.2cm H) |
Sensor: | Epoxy sealed stainless steel case, bi-metallic operating mechanism. |
Contacts: | Silver clad, available normally open or normally closed. |
Electrical Rating: | 1 Amp at 24VDC |
Temperature Setting: | 40° ±5°F (4,5° ±3°C) |
Terminals: | Screw Terminals |
Mounting: | Wall Mount, Surface |
OPERATION
The normally open detector, RTS-O, will close the contact when the temperature drops below 40°F (4,5°C). The normally closed detector, RTS-C, will open the contact when the temperature drops below 40°F (4,5°C). The detector will automatically reset to the normal state when the temperature rises above 40°F (4,5°C).
INSPECTION, TESTING, & MAINTENANCE
The frequency of inspection and testing of the RTS and its associated
monitoring system shall be in accordance with applicable local and NFPA codes
and standards. Manufacturer recommends quarterly or more frequently.
Functional test can be accomplished by spraying the RTS with circuit cooler or
equivalent.
More accurate test requires exposing the RTS to 40°F ± 5°F.
The RTS requires no maintenance other than ensuring the vent holes are not
obstructed.
Note: The RTS does not have duplicate terminals. Do not use looped wire
under terminals. Break wire run to provide supervision of connections.
RTS Mounting Template
DWG. #996-3
PRINTED IN USA
Mfg. #5401019 – REV g
06/11