POTTER Pull Station Fire Alarm Instruction Manual

June 9, 2024
POTTER

Pull Station Fire Alarm
Instruction Manual

Installation and Service

POTTER Pull Station Fire Alarm

Installers Note:
The station are supplied with glass rod removed. It is recommended that the station be activated and tested prior to installation of the glass rod.

  • Glass Rods and Hardware are shipped with station box.

Replacement o Glass Rod:
If broken, remove debris, then reset T-Handle to normal position. Onsert one end of new Glass Rod under Spring Tab, then with one finger, lift other end os Spring tab allowing Glass Rod to slip into place.
To Close Station:
If hex Screw Model, simply push station closed. If Key Lock Model, hold station closed then turn key counterclockwise.

POTTER Pull Station Fire Alarm - Electrical Box1

Electrical Wiring

POTTER Pull Station Fire Alarm - Electrical Wiring

Model| Terminal Block| Terminal Connecting| Switch Function| Terminal Connection| Contact Rating
---|---|---|---|---|---
LED| Switch| Ph. Jack
1P| None| None| SPST| Leeds| Leeds| Leeds| 10 amp @ 125 vac
1T| A| 2 – 3| SPST| 1(+) – 4(-)| 1 – 4| 1 – 4| 10 amp @ 125 vac
2T| A| 1-2 & 3-4| DPST| 5(+)- 6(-)| 5 – 6| 5 – 6| 10 amp @ 125 vac
3T| A| 1,2, & 3| SPDT| 5(+)- 6(-)| 5 – 6| 5 – 6| 10 amp @ 125 vac
6T| A & B| 1,2,3,5,6,7| DPDT| 4(+) – 8(-)| 4 – 8| 4 – 8| 10 amp @ 125 vac

Note: all contact ratings shown apply to closed station.

Phone Jack: 1/4
Key Switch: 3Amp©125Vac
Led: 1-1-3/4@24Vdc
Mounting Instructions on Reverse Side
firealarmresources.com