POTTER LRM-SK LRM Solenoid Kit Instructions
- June 9, 2024
- POTTER
Table of Contents
POTTER LRM-SK LRM Solenoid Kit
Features
- Designed for use with the IntelliCheck Advanced Leak Rate Monitor
- Allows users to perform leak tests on systems with dedicated air compressors or nitrogen generators
- Allows users to monitor aspects of air compression or nitrogen generator systems
Description
that utilize a dedicated air compressor or nitrogen generator. The solenoid
kit will allow a leak test of the system by isolating the air source from the
system with the LRM Controller.
The current transformer that is included with this kit will allow the user to
track run times and cycle counts on their air source as well. This will allow
the user to keep track of when to do maintenance and might make the user aware
of other issues on the air source.
The included check valve is necessary to keep water and sediment from getting
to the solenoid and air supply
Technical Specifications
Service Pressure | 175 psi |
---|---|
Service Temperature | Ambient above 32°F |
Check Valve Size and Material | 1/2” FNPT Inlet and Outlet Brass Construction |
Solenoid Size and Material | 1/2” FNPT Inlet and Outlet Brass Construction |
LRM Solenoid Kit Installation
The Solenoid Kit is required when a tank is supplying the system. LRM Solenoid Kit must be installed within reach of the provided 7 ft solenoid cable to the LRM Display
- Install ½” FNPT LRM Solenoid in-line of the air supply, after the compressor or AMD and the kit supplied 1/2” check valve. See below.
- The supplied check valve with 1/2” FNPT inlet and outlet will need to be installed inline and between the solenoid and transducer. Ensure the flow arrow on the check valve is in the direction of the supervisory gas flow. See below.
- Leak check new connections.
- Insert supplied solenoid DIN cable onto the solenoid and run the opposite end through a supplied strain relief fitting and a knockout on the LRM Housing.
- Insert wires into the bottom 3-terminals of the 10-terminal block by depressing orange tab, inserting wire, and releasing tab on the LRM Controller. See IntelliCheck Manual #5403773 for more detail.
Ordering Information
Model | Description | Stock No. |
---|---|---|
LRM-SK | LRM Solenoid Kit | 0090241 |
Customer Support
Potter Electric Signal Company, LLC
• St. Louis, MO
• Phone: 800-325-3936
• www.pottersignal.com
Read User Manual Online (PDF format)