BEFORE YOU BEGIN
To install the LED 2-pin plug-in lamps, please read the entire installation guide carefully
The product is not intended to be used with dimmers and emergency fixtures.
The LED 2-pin lamp is not suitable for direct connection to the mains.
Bypassing the original ballast will result in safety and regulation issues.
The existing power factor compensation capacitors worsen the power factor, but
may remain in the circuit. Furthermore, it should be taken into consideration
the maximum LED 2-pin lamps connected to one circuit breaker according to its
technical specification.
WARNING: Risk of Fire or Electric Shock. Suitable for Dry and Damp
Locations. The installation must be done by qualified electricians and all
safety instructions must be followed to avoid a risk of injury or property
damage
13W GX23 equivalent lamp
- LED5GX23/827
- LED5GX23/830
- LED5GX23/835
- LED5GX23/840
- LED5GX23/850
26W G24d equivalent lamp – Horizontal
- LED11G24d-H/827
- LED11G24d-H/830
- LED11G24d-H/835
- LED11G24d-H/840
- LED11G24d-H/8SC/120-347
26W G24d equivalent lamp – Vertical
- LED11G24d-V/827
- LED11G24d-V/830
- LED11G24d-V/835
- LED11G24d-V/840
- LED11G24d-V/8SC/120-347
Installation Instructions
-
Switch off power to the fixture.
-
Remove the existing fluorescent lamps from the fixture and dispose of them properly based on local regulations.
-
For Selectable lamps only: Adjust color temperature switch on lamp to desired setting
-
Check the socket condition in the fixture. If damaged or corroded, replace it with a new one. Insert Current LED 2-pin lamps. For G24d horizontal application, rotate the lamp so the diffuser is facing towards the fixture opening. Warning: Sockets in poor condition may result in bad electrical contact, base arcing or other safety issues.
Note: In two lamps condition, be sure to use Current LED 2-pin lamps in both sockets. Do not use one CFL and one LED lamp together on the same ballast. -
Restore power to fixture and check for proper operation.
Note: If the lamp flickers, flashes or fails on installation, the ballast is not compatible with the lamp. Remove the lamp and check the ballast compatibility list again or contact Current for technical support at 1-800-327-0097.
CAUTION
RISK OF ELECTRIC SHOCK – SUITABLE FOR DAMP LOCATIONS. Direct replacement
for 26W/8T4/Q/G24/PH or 18W/7T4/Q/G24/PH or 13W/6T4/Q/G24/PH Lamps only. Not
for use with dimmers. This lamp only operates on magnetic ballasts. If the
lamp does not light when the luminaire is energized, remove lamp from
luminaire and contact lamp manufacturer or qualified electrician. This lamp
operates only on compatible magnetic ballasts. See list at: www.LED.com
/LED2pin-compatibility.
CAUTION: If the lamp or luminaire exhibits undesirable operation
(buzzing, flickering, etc.), immediately turn off power, remove lamp from
luminaire and contact manufacturer.
WARNING: Risk of fire. Use only in place of fluorescent lamps specified
on label.
Not evaluated for use with emergency exit fixtures or emergency exit lights. Suitable for damp locations. Not for use with dimmers, electronic timers, or photocells. FOR USE ONLY WITH COMPATIBLE MAGNETIC BALLASTS. See list at: www.LED.com/LED2pin-compatibility.
FCC
This device complies with Part 18 of the FCC Rules. Operation is subject to
the following two conditions: 1) this device may not cause harmful
interference, and 2) this device must accept any interference received,
including interference that may cause undesired operation. Any changes or
modifications not expressly approved by the manufacturer could void the user’s
authority to operate the equipment.
NOTE: This product complies with Part 18 of the FCC Rules but may cause
interference to radios, televisions, wireless telephones, and remote controls.
Avoid placing this product near these devices. If interference occurs, move
the product away from the device or plug either into a different outlet. Do
not install this product near maritime safety equipment or other critical
navigation or communication equipment operating between 0.45-30 MHz. This
device complies with CAN ICES-005B.
www.LED.com
© 2022 Current Lighting Solutions, LLC. All rights reserved. GE and the GE
monogram are trademarks of the General Electric Company and are used under
license. Information and specifications subject to change without notice. All
values are design or typical values when measured under laboratory conditions.