Honeywell Lyric T6 Pro Wi-Fi Programmable Thermostat User Manual
- June 9, 2024
- Honeywell
Table of Contents
- Honeywell Lyric T6 Pro Wi-Fi Programmable Thermostat
- Package Includes
- Compatibility
- UWP Mounting System installation
- Wiring UWP
- Terminal designations
- Setting Slider Tabs
- Wiring
- Conventional systems
- Heat pumps systems
- Ventilation systems
- Mounting thermostat
- Installer setup – using the thermostat
- Installer setup – using the Lyric app
- Installer setup – advanced menu
- Key features
- Installer setup options (ISU) – advanced menu
- Performing a system test
- Troubleshooting
- Alerts and reminders
- Specifications
- Physical Dimensions
- Regulatory information
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Honeywell Lyric T6 Pro Wi-Fi Programmable Thermostat
Package Includes
- Lyric T6 PRO Wi-Fi Thermostat
- UWP Mounting System
- Honeywell Standard Installation Adapter (J-box adapter)
- Honeywell Decorative Cover Plate –Small; size 4-49/64 in = 121mm.
- Screws and anchors
- Professional Install Guide
- Getting Started Guide
Compatibility
- Compatible with most heating, cooling, and heat pump systems
- Required: 24 VAC power (“C” wire)
- Does not work with electric baseboard heat (120-240V)
- Does not work with millivolt systems
- Android or iOS smartphone or tablet
Customer Assistance
WEB customer.honeywell.com PHONE
1-800-633-3991
UWP Mounting System installation
-
Open package to find the UWP. See Figure 1.
-
Position the UWP on the wall. Level and mark hole positions. See Figure 2. Drill holes at marked positions, and then lightly tap supplied wall anchors into wall using a hammer.
- Drill 7/32” holes for drywall.
-
Pull the door open and insert wires through wiring hole of the UWP. See Figure 3.
-
Place the UWP over the wall anchors. Insert and tighten mounting screws supplied with the UWP. Do not overtighten. Tighten until the UWP
no longer moves. Close the door. See Figure 4.
Optional Decorative Cover Plate Installation
Use the Optional Cover Plate when:- Mounting the thermostat to an electrical junction box
- Or when you need to cover paint gap from the old thermostat.
-
Separate the Junction Box Adapter from the Cover Plate. See Figure 5.
-
Mount the Junction Box Adapter to the wall or an electrical box using any of the eight screw holes. Insert and tighten the mounting screws supplied with Cover Plate Kit. Do not over-tighten. Make sure the Adapter Plate is level. See Figure 6.
-
Attach the UWP by hanging it on the top hook of the Junction Box Adapter and then snapping the bottom of the UWP in place. See Figure 7.
-
Snap the Cover Plate onto the Junction Box Adapter. See Figure 8.
Wiring UWP
Push down on the tabs to put the wires into the inner holes of their corresponding termi nals on the UWP (one wire per terminal) until they are firmly in place. Gently tug on the wires to verify they are secure. If you need to release the wires again, push down the terminal tabs on the sides of the UWP.
Terminal designations
Conventional Systems | Heat pump systems |
---|---|
Terminal | Description |
S/S | Universal input for a wired indoor, outdoor sensor |
for a wired indoor, outdoor sensor
Y| Compressor Stage 1| Y| Compressor Stage 1
Y2| Compressor Stage 2| Y2| Compressor Stage 2
G| Fan Relay| G| Fan Relay
C
| 24VAC Common wire from secondary side of cooling transformer (if 2 transformers)| ****
C
| 24VAC Common wire from secondary side of cooling transformer
K| Connect to K on Wire Saver Module| K| Connect to K on Wire Saver Module
U/U| Universal relay for ventilation| U/U| Universal relay for ventilation
A| | L/A| Connect to compressor monitor
W| Heat Stage 1| O/B| Changeover valve for heat pumps
W2| Heat Stage 2| Aux| Backup Heat
| | E| Emergency Heat
R| 24 VAC Heating transformer| R| 24 VAC Heating transformer
Rc| 24 VAC Cooling transformer| Rc| 24 VAC Cooling transformer
- The THP9045A1023 Wire Saver Module is used on heat/cool systems when you only have four wires at the thermostat and you need a fifth wire for a common wire. Use the K terminal in place of the Y and G terminals on conventional or heat pump systems to provide control of the fan and the compressor through a single wire—the unused wire then becomes your common wire. See THP9045 instructions for more information.
- Ventilation is not available on all models. When the U slider is in the down position (2 wires), the U contacts are a dry set of contacts. If your ventilation system requires 24 volts, move the U slider to the up position (1 wire). Lower U terminal is internally jumped to the Rc terminal. In this application, you would hook up one wire from your damper to the upper U terminal and the other to the common side of the transformer.
Setting Slider Tabs
Set R Slider Tab, see Figure 9.
- Use built-in jumper (R Slider Tab) to differentiate between one or two transformer systems.
- If there is only one R wire, and it is connected to the R, Rc, or RH terminal on the old thermostat, set the slider to the up position (1 wire).
- If there is one wire connected to the R terminal and one wire connected to the Rc terminal, set the slider to the down position (2 wires).
Set U Slider Tab, see Figure 10.
- Use built-in jumper (U Slider Tab) of the universal relay to wire ventilation. Please note that ventilation is not supported on all models.
- When the U Slider Tab is in the down position (2 wires) the U contacts are a dry set of contacts.
- If the ventilator is powered by the cooling transformer, move the jumper switch to the up position (1 wire). With this switch set to 1 wire, the lower U terminal is internally jumped to the Rc terminal. In this application, hook up one wire from the vent damper to the U terminal and the other to the common side of the cooling system transformer.
Wiring
NOTES:
- Available wiring configurations differ by product models/product numbers.
- Use 18- to 22-gauge thermostat wire. A shielded cable is not required.
- Set the R Slider Tab on the UWP to the up position (1 wire) for 1 transformer system or the down position (2 wires) for 2 transformer systems. See “Setting Slider Tabs” on page 4.
- Set the U Slider Tab to the up position (1 wire) for non-powered ventilation or the down position (2 wires) for powered ventilation. See “Setting Slider Tabs” on page 4.
Conventional systems
1H/1C System (1 transformer)
- R Power
- Rc [R+Rc joined by Slider Tab]
- Y Compressor contactor
- C 24VAC common
- W Heat relay
- G Fan relay
Hot Water Relay Panel
- R Power
- Rc [R+Rc joined by Slider Tab]
- W Heat Relay
- C 24VAC common
NOTE: If the panel does not provide 24 volts AC at R and C, set the slider to down position and wire a separate transformer to Rc and C.
1H/1C System (2 transformers)
- R Power (heating transformer)
- Rc Power (cooling transformer)
- Y Compressor contactor
- C 24 VAC common from cooling transformer
- W Heat relay
- G Fan relay
Heat-only System with Fan
- R Power
- Rc [R+Rc joined by Slider Tab]
- C 24VAC common
- W Heat relay
- G Fan relay
2H/2C System (1 transformer)
- R Power
- Rc [R+Rc joined by Slider Tab]
- Y Compressor contactor (stage 1)
- C 24VAC common
- W Heat relay (stage 1)
- G Fan relay
- W2 Heat relay (stage 2)
- Y2 Compressor contactor (stage 2)
Cool-only System with Fan
- R Power
- Rc [R+Rc joined by Slider Tab]
- Y Compressor contactor
- C 24VAC common
- G Fan relay
Heat pumps systems
1H/1C Heat Pump System
- R Power
- Rc [R+Rc joined by Slider Tab]
- Y Compressor contactor
- C 24VAC common
- O/B Changeover valve
- G Fan relay
2H/2C Heat Pump System
- R Power
- Rc [R+Rc joined by Slider Tab]
- Y Compressor contactor (stage 1)
- C 24VAC common
- O/B Changeover valve
- G Fan relay
- Y2 Compressor contactor (stage 2)
- L Heat pump fault input
2H/1C Heat Pump System
- R Power
- Rc [R+Rc joined by Slider Tab]
- Y Compressor contactor
- C 24VAC common
- O/B Changeover valve
- G Fan relay
- Aux Auxiliary heat
- E Emergency heat relay
- L Heat pump fault input
3H/2C Heat Pump System
- R Power
- Rc [R+Rc joined by Slider Tab]
- Y Compressor contactor (stage 1)
- C 24VAC common
- O/B Changeover valve
- G Fan relay
- Aux Auxiliary heat
- E Emergency heat relay
- Y2 Compressor contactor (stage 2)
- L Heat pump fault input
NOTE: This application is not supported by all models of the thermostat.
Ventilation systems
NOTE: Ventilation is not available on all models. Using U Slider Tab
Wired to ERV/HRV whole house ventilator with internal power supply .
Wired to fresh air damper powered by furnace transformer.
Mounting thermostat
- Push excess wire back into the wall opening.
- Close the UWP door. It should remain closed without bulging.
- Align the UWP with the thermostat, and push gently until the thermostat snaps in place.
- If needed, gently pull to remove the thermostat from the UWP
Installer setup – using the thermostat
Setup using the thermostat
- After the Lyric thermostat has powered up, touch START SETUP on the thermostat. You’ll be asked if you want to perform setup via Lyric app. Touch No.
- Touch to toggle between Installer Set Up (ISU) options.
- Touch Edit or touch text area, and then touch to edit default setup option.
- Touch Done or touch text area to confirm the setting or press Cancel.
- Touch to continue to setup another ISU option.
NOTES:
- To see a list of all setup parameters, go to “Installer setup options (ISU) –advanced menu” on page 11. The thermostat displays the ISU name and the ISU number.
- To finish setup and save your settings, scroll to the Finish screen at the end of the ISU list.
- Touch Select or touch text area to save changes and exit, or touch to return to initial setup screen.
Installer setup – using the Lyric app
Setup using the Lyric app
Download the Lyric app from App Store or Google Play to use a hidden PRO
installation feature that will allow you to configure the thermostat and
personally invite your customer to connect to the installed thermostat at the
same time.
Enter Contractor Mode
To enter Contractor Mode, press and hold the Lyric logo for 5 seconds. Then tap Confirm to begin using Contractor Mode. Follow steps to personally invite your customer to connect their Lyric App.
Installer setup – advanced menu
To access the advanced menu, press and hold the Menu button for 5 seconds. Touch or to go through the options in the advanced menu.
Advanced menu options
Device Setup
This is used to access the device’s ISU setting.
Screen Lock
The thermostat touchscreen can be set to lock fully or partially.
Rater View
A read-only place to view all the ventilation settings.
System Test
Test the heating and cooling system.
Range Stop (Temperature)
Set the minimum, maximum, cool, and heat temperature set points.
Reset
Access all reset options on the thermostat. This is the only place to access
factory reset.
Key features
The screen will wake up by pressing the center area of the displayed temperature. The screen will stay lit for 45 seconds. Brightness can be adjusted in the Menu.
Installer setup options (ISU) – advanced menu
Table 1.
# ISU | ISU Name | ISU Options (defaults in bold) | Notes |
---|---|---|---|
120 | Schedule Type | No Schedule |
MO-SU = Every day the same MO-FR, SA, SU = 5-1-1 schedule
MO-FR, SA-SU = 5-2 schedule
Each Day = Every day individual
| You can change default MO-FR, SA-SU schedule here. To edit periods during
days, temperature setpoints, or to turn Schedule On/Off, from the home screen,
go to ME N U / S C HE D U L E.
125| Temp Scale| F a h r e nh e i t ,
Celsius|
130| Outdoor Temp| No, Wired, Internet| Select outdoor temperature data
source. This ISU automatically defaults to Internet when registered to Lyric
app and no wired outdoor sensor is selected. We recommend using a wired
outdoor sensor connected to the “S” terminals on the UWP. (See “Wiring” on
page 5.)
An outdoor temperature is required to set the following ISUs: ISU 355 Compressor Lockout, ISU 356 Aux
Heat Lockout, ISU 1013 Low Outdoor Temperature Ventilation Lockout, ISU 1014 High Outdoor Temperature Ventilation Lockout, and ISU 1015 High Outdoor Dew Point Ventilation Lockout.
200| System Type| Conventional Forced Air
Heat Pump Boiler
Cool Only
| Basic selection of system your thermostat will control.
205| Equipment Type| Conventional Forced Air Heat:
Standard Gas (STD GAS), High Efficiency Gas (EFF GAS) , Oil, Electric, Fan Coil
| This option selects the equipment type your thermostat will control. Note:
This option is NOT displayed if ISU 200 is set to Cool Only.
| | Heat Pump:
Air To Air, Geothermal
|
| | Boiler:
Hot Water , Steam
|
218| Reversing Valve| 0/B on Cool, 0/B on Heat| This ISU is only
displayed if ISU 200 is set to Heat Pump. Select whether reversing valve O/B
should energize on cool or on heat
220| Cool Stages (#200=Conv./ 200=HP)| 0, 1 , 2|
221| Heat Stages/Aux/E Stages (#200=Conv./ 200=HP)| Heat Stages: 0, 1 , 2
AUX/E Stages: 0 , 1
| Maximum of 2 Heat Stages for conventional systems. Maximum of 1 Aux/E stages
for heat pump systems.
230| Fan Control| Equipment, Thermostat| This ISU is only displayed if
ISU 205 is set to Electric Forced Air or Fan Coil.
253| Aux/E Control| Both Aux/E, Either Aux/E| Set “EITHER AUX/E” if you
want to setup and control Auxiliary and Emergency heating separately . This
ISU is only displayed if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E
stages = 1.
255| Aux Heat Type| Electric, Gas/Oil (or Fossil Forced Air)| This ISU is
displayed only if ISU 200 is set to heat pump AND if ISU 221 Aux/E heat stages
= 1. Note: Options of this ISU may vary depending on the model of the
thermostat.
# ISU| ISU Name| ISU Options (defaults in bold)| Notes
---|---|---|---
256| EM Heat Type| Electric, Gas/Oil (or Fossil Forced Air)| This ISU is
displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages
= 1 AND if ISU 253 is set to run AUX/E heat separately.
Note: This ISU may not be available at all on some models.
260| Fossil Kit Control| Thermostat, External (Fossil Fuel Kit Controls Backup Heat)| This ISU is displayed only if ISU 200 is set to Heat Pump AND if ISU 221 Aux/E heat stages = 1, AND if ISU 256 is set to Gas/Oil.
Note: This ISU may not be available at all on some models.
300| Auto Changeover| On, Off| OFF: The user must select heating or cooling as needed to maintain the desired indoor temperature.
ON (Automatic): On (enabled) Allows user to select Auto Changeover as one of the system modes from the home screen. In auto mode, the thermostat can control either heating or cooling to maintain the desired indoor temperature.
303| Auto Differential| 0 °F to 5 °F or 0.0 °C to 2.5 °C| Differential is the minimum number of degrees allowed between the heat and cool setpoints when the thermo- stat is in auto-changeover.
Differential is NOT deadband. The deadband temperature between when heating (or cooling) cycles on and cycles off to maintain setpoint is not adjustable. Honeywell uses an algorithm that fixes deadband at 0 °F. This algorithm is more advanced than on previous thermostats.
305| High Cool Stage Finish| Yes, No| This ISU is only displayed when the
thermostat is set to 2 cool stages. When set to YES, this feature keeps the
higher stage of the cooling equipment running until the desired setpoint is
reached.
306| High Heat Stage Finish| Yes, No| This ISU is only displayed when the
thermostat is set to 2 or more heat stages. When set to YES, this feature
keeps the higher stage of the heating equipment running until the desired
setpoint is reached.
340| Aux Heat Droop| 0 = Comfort; 2 °F to 15 °F from setpoint (in 1 °F
incre- ments) or 1.0 °C to 7.5 °C from setpoint (in 0.5 °C increments)| Aux
heat droop can be set on heat pump systems with an auxiliary heat stage. The
Comfort setting is NOT available for Dual Fuel systems. Default setting is 0
°F (Comfort) for Electric while 2 °F for Gas/Oil. The indoor temperature must
drop to the selected droop setting before the thermostat will turn Aux Heat
on. For example, if Aux Heat is set to 2 °F (1.0 °C), the indoor temperature
must be 2 ° F (1.0 ° C) away from the setpoint before Aux Heat turns on. When
set to Comfort, the thermostat will use Aux Heat as needed to keep the indoor
tem- perature within 1 °F (0.5 ° C) degree of the setpoint.
350| Up Stage Timer Aux Heat| Off, 30, 45, 60, 75, 90 minutes
2, 3, 4, 5, 6, 8, 10, 12, 14, 16 hours
| The Auxiliary Heat Upstage Timer starts when the highest stage of the
previous heating equipment type turns on. Auxiliary heat will be used (if
needed) when the timer expires. This ISU is only displayed when ISU 340 (AUX
Heat Droop) is set to 2 °F or higher.
355| Balance Point (Compressor Lockout)| Off, 5 °F to 60 °F (in 5 °F
increments) or -15.0 °C to 15.5 °C (in 2.5 °C or 3.0 °C increments)|
Compressor Lockout requires an outdoor temperature. Set Compressor Lockout to
the temperature below which it is inefficient to run the heat pump. When
outside temperature is below this setting, thermostat will lockout heat pump
and run Aux Heat only. This ISU is only displayed if ISU 130 = Wired or
Internet, ISU 200 is set to Heat Pump, ISU 221 Aux/E stages = 1, AND ISU 260
is set to Thermostat. We recommend using a wired remote sensor as an outdoor
temperature source.
Default is 40 °F if ISU 205 Heating Equipment is Air to Air Heat Pump and ISU 255 Aux Heat Type is Gas/Oil. Default is Off if ISU 205 Heating Equipment is Air to Air Heat Pump and ISU 255 Aux Heat Type is Electric. Default is Off if ISU 205 Heating Equipment is Geothermal.
Compressor Lockout is optional for any type of heat pump (Air to Air Heat Pump, Geothermal Heat Pump).
# ISU | ISU Name | ISU Options (defaults in bold) | Notes |
---|---|---|---|
356 | Aux Heat Lock Out (Aux Heat Outdoor Lockout) | Off, 5 °F to 65 °F (in |
5 °F increments) or
-15.0 °C to 18.5 °C (in 2.5 °C or 3.0 °C increments)
| Aux Heat Lockout requires an outdoor temperature. Set Aux Heat Lockout to
optimize energy bills and to not allow it to run the more expensive Aux Heat
source above certain outdoor temperature limit. This ISU is only displayed if
ISU 200 is set to Heat Pump, AND ISU 260 is set to Thermostat control AND if
ISU 221 Aux/E stages = 1.
365| Cool 1 CPH (Cooling cycle rate stage 1)| 1 – 6 CPH (3 CPH)| This ISU
is only displayed when Cool /Compressor Stages is set to 1 or more stages.
Cycle rate limits the maxi- mum number of times the system can cycle in a 1
hour period measured at a 50% load. For example, when set to 3 CPH, at a 50%
load, the most the system will cycle is 3 times per hour (10 minutes on, 10
minutes off). The system cycles less often when load conditions are less than
or greater than a 50% load.
366| Cool 2 CPH (Cooling cycle rate stage 2)| 1 – 6 CPH (3 CPH)| This ISU
is only displayed when Cool /Compressor Stages is set to 2.
370| Heat 1 CPH (Heating cycle rate stage 1)| 1 – 12 CPH| This ISU is only
displayed when Heat Stages is set to 1 stage or more stages. Cycle rate limits
the maximum number of times the system can cycle in a 1 hour period measured
at a 50% load. For example, when set to 3 CPH, at a 50% load, the most the
system will cycle is 3 times per hour (10 minutes on, 10 minutes off). The
system cycles less often when load conditions are less than or greater than a
50% load. The recommended (default) cycle rate settings are below for each
heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot
Water Radiant Heat = 3 CPH; Steam = 1 CPH.
371| Heat 2 CPH (Heating cycle rate stage 2)| 1 – 12 CPH| This ISU is only displayed when Heat Stages is set to 2 stages. The recommended (default) cycle rate settings are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH; Fan Coil = 3 CPH; Hot Water Radiant Heat = 3 CPH; Steam = 1 CPH.
375| Aux Heat CPH (Heating cycle rate Auxiliary Heat)| 1 – 12 CPH| This ISU is only displayed when ISU 200 = Heat Pump and ISU 221=1. It is only displayed when Auxiliary Heat is configured. The recommended cycle rate settings are below for each heating equipment type:
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3 CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH.
378| EM Heat CPH (Heating cycle rate Emergency Heat)| 1 – 12 CPH| This ISU is only displayed when Emergency Heat is configured and ISU 253: Aux/E Terminal Control is set to control Aux and E heat Independently. The recommended cycle rate settings are below for each heating equip- ment type:
Standard Efficiency Gas Forced Air = 5 CPH; High Efficiency Gas Forced Air = 3
CPH; Oil Forced Air = 5 CPH; Electric Forced Air = 9 CPH.
387| Compressor Protection| Off, 1 – 5 minutes| The thermostat has a
built in compressor protection (minimum off timer) that prevents the
compressor from restarting too early after a shutdown. The minimum-off timer
is activated after the compressor turns off. If there is a call during the
minimum-off timer, the thermostat shows “Wait” in the display. This ISU is
displayed if ISU 220 is set to at least 1 stage.
390| Ext Fan Run Time in Cool| Off , 30, 60, 90 seconds
2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutes
| After the call for cooling ends, the thermostat keeps the fan on for the
selected amount of time for increased efficiency. This may reintroduce
humidity into the living space. This ISU is displayed if ISU 220 is set to at
least 1 stage.
# ISU| ISU Name| ISU Options (defaults in bold)| Notes
---|---|---|---
391| Ext Fan Run Time in Heat| Off , 30, 60, 90 seconds
2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 15 minutes
| After the call for heating ends, the thermostat keeps the fan on for the
selected amount of time for increased efficiency. This ISU is displayed if ISU
230 is set to Thermostat Controls Fan.
425| Adaptive Recovery| On, Off| Adaptive Intelligent Recovery (AIR) is a
comfort setting. Heating or cooling equipment will turn on earlier, ensuring
the indoor temperature will match the setpoint at the scheduled time.
429| Max Cool Temperature| from Min. Cool Temp. to 99 °F or to 37.0 °C (90
°F or 32 °C)| The user cannot set the cooling temperature above this level.
430| Min Cool Temperature| from 50 °F or 10.0 °C to Max. Cool Temp. (50 °F
or 10 °C)| The user cannot set the cooling temperature below this level.
431| Max Heat Temperature| from Min. Heat Temp. to 90 °F or to 32.0 °C (90
°F or 32 °C)| The user cannot set the heating temperature above this level.
432| Min Heat Temperature| from 40 °F or 4.4 °C to Max. Heat Temp. (50 °F or
10 °C)| The user cannot set the heating temperature below this level.
435| Lock Screen| None, Partial, Full| Unlocked: User has access to
all thermostat settings. Partially Locked: User can modify only
temperature settings.
Fully Locked: User cannot modify any settings. Screen will be locked by default factory code and cannot be changed. This code is displayed for a short time, when you are about to lock the thermostat screen. Please note the code in safe place for future reference.
500| Indoor Sensor| Yes, No| Set this ISU when you want to wire a remote
indoor sensor to the “S” terminals on the UWP – see “Wiring” on page 5. This
ISU is only displayed only if ISU 130 is set to NO wired outdoor sensor
configured
515| Sensor type| 10k, 20k| Choose resistance type of wired indoor
sensor. This ISU is only displayed when indoor sensor is configured – ISU 500.
520| Temperature Control| Thermostat, Wired, Average| This ISU is only
displayed when indoor sensor is configured – ISU 500. You can choose what
temperature source to be used or you can ask thermostat to use both thermostat
and remote sensors for higher accuracy of measurement.
702| Air Filters| 0 – 2| This ISU refers to the number of air filters in
the system.
711| Air Filter 1 Reminder| Off
10, 20, 30, 45, 60, 90, 120, 150 Run Time Days
30, 45, 60, 75 Days
3, 4, 5, 6, 9, 12, 15 Months
| Choose either calendar or equipment run time-based reminder.
712| Air Filter 2 Reminder| Off
10, 20, 30, 45, 60, 90, 120, 150 Run Time Days
30, 45, 60, 75 Days
3, 4, 5, 6, 9, 12, 15 Months
| Choose either calendar or equipment run time-based reminder.
810| Hum Pad Reminder| Off
6, 12 Calendar Months
|
921| Dehum Filter Reminder| Off
30, 60 Calendar Days
3 – 12 Calendar Months (in 1 month increments)
|
# ISU| ISU Name| ISU Options (defaults in bold)| Notes
---|---|---|---
1000| Vent Type| None, ERV/HRV, Passive, Fresh Air Damper| None: The
thermostat does not control ventilation.
ERV/HRV: The thermostat controls an Energy Recovery Ventilator or Heat Recovery Ventilator for ventila- tion.
Passive (Fan Only) : The thermostat turns on the fan for ventilation. When set to passive fan, the thermo- stat does not control a damper or ventilator. The passive ventilation/passive fan setting only runs the indoor blower fan. This setting does not open a damper or run a ventilator. To use this setting for ventilation, the home would need to be set-up with a pipe from outdoors into the return duct that is either permanently open or has a damper that automatically opens whenever the blower fan is on.
Note: Some models only offer the passive fan setting.
1005| Vent Method| ASHRAE 2010, ASHRAE 2013 , Percent On Time| Note:
Options of this ISU may vary depending on the model of the thermostat.
1006| Vent Fan Control| Thermostat, Equipment| Thermostat: The
thermostat turns on the ventilation and the fan when ventilation is needed.
Equipment: Ventilation equipment controls the blower fan.
1007| Bedrooms| 1 – 6 (2)| This ISU is only displayed when ISU 1005
Ventilation Method is set to ASHRAE 2010 or 2013.
1008| Home Size| 1000 – 5000 Sq. Ft. (1000 Sq. Ft.)| This ISU is only
displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013.
1009| Vent Rate| 30 – 350CFM (in 5CFM increments) (150CFM)| This ISU is
only displayed when ISU 1005 Ventilation Method is set to ASHRAE 2010 or 2013.
1011| Vent Percent On Time| 10% – 100% (30%)| The thermostat operates
ventilation equipment based on a percentage entered in the installer setup
(ISU 1012). For example, if Percent on Time is set to 50%, the ventilation
equipment will run at random times dur- ing a 1 hour period until it reaches a
50% run time (approximately 30 minutes). This ISU is only displayed if ISU
1005 is set to Percent On Time.
1012| Vent Priority| Lockouts, ASHRAE| Lockouts are Priority: The
thermostat places a priority on lockouts versus the ASHRAE ventilation
standard. The thermostat will not run ventilation during the following lockout
conditions (if configured), unless you manually call for ventilation:
Lockout Ventilation during Outdoor Conditions (ISU 1013, 1014 and 1015).
Lockout Ventilation during “Sleep” program periods. Note: This option is set by the user on the Ventilation screen in the Menu.
ASHRAE is Priority: ASHRAE requires additional ventilation following a long off cycle. The thermostat meets the ASHRAE ventilation standard by running additional ventilation when outdoor conditions are favor- able. If ASHRAE cannot be met when outdoor conditions are favorable, the thermostat will override the outdoor lockouts and run ventilation. When using this option, it is recommended that you increase the rate (CFM) of the ventilation equipment to meet the ASHRAE ventilation standard in a shorter run time. The ability to lockout ventilation during the “Sleep” is not an option when you select ASHRAE is Priority.
1013| Low Outdoor Temp Vent Lockout| Off, -20 °F to -40 °F (in 5 °F increments) or
-28.0 °C to -4.0 °C (in 2.0 °C increments)
| ISU 130 must be set to Wired or Internet. This ISU is only displayed when
ISU 1000 Ventilation Type is set to ERV / HRV or Fresh Air Damper.
1014| High Outdoor Temp Vent Lockout| Off, 80 °F to 110 °F (in 5 °F
increments) or 26 °C to 44 °C (in 2 °C increments)| ISU 130 must be set to
Wired or Internet. This ISU is only displayed when ISU 1000 Ventilation Type
is set to ERV / HRV or Fresh Air Damper.
1015| High Outdoor Dewpoint Vent Lockout| Off, 65 °F to 85 °F (in 5 °F
increments) or 18 °C to 30 °C (in 2 °C increments)| ISU 130 must be set to
Internet. This ISU is only displayed if ISU 1000 Ventilation Type is set to
ERV/ HRV or Fresh Air Damper.
# ISU| ISU Name| ISU Options (defaults in bold)| Notes
---|---|---|---
1017| Vent Core Reminder| Off, 3, 6, 9, 12 months| This ISU is displayed
only if ISU 1000 is set to ERV/HRV.
1018| Vent Filter Reminder| Off, 3, 6, 9, 12 months|
1100| UV Devices| 0 – 2| Some systems may have two UV devices, one for
the A-Coil and another for Air Treatment. A replacement reminder can be setup
for each one separately.
1105| UV Bulb 1 Reminder| Off, 6, 12, 24 months|
1106| UV Bulb 2 Reminder| Off, 6, 12, 24 months|
1401| Idle Brightness| 0= Off, 0 – 5| Adjust brightness of an inactive
backlight (idle screen) from default 0 (backlight off) to 5 (maximum
brightness).
1410| Clock Format| 12 hour, 24 hour|
1415| Daylight Saving| On, Off| Set to Off in areas that do not follow
Daylight Saving Time.
1420| Temp Offset| Off, -3 °F to 3 °F (in 1 °F increments) or
-1.5 °C to 1.5 °C (in 0.5 °C increments)
| 0 °F – No difference in displayed temperature and the actual room temperature. The thermostat can display up to 3 °F (1.5 C) lower or higher than the actual measured temperature.
Performing a system test
You can test the system setup in ADVANCED MENU under SYSTEM TEST option.
- Press and hold Menu on the Lyric thermostat for 5 seconds to access ADVANCED MENU options.
- Touch to go to SYSTEM TEST.
- Touch Select or touch text area.
- Touch to select system test type. Touch Select or touch text area.
- For the heat test and cool test, use to activate each stage of the equipment. For the fan test, use to turn the fan on and off.
NOTE: The clock is used as a timer while the stages are running. The Heat On and Cool On indicators are displayed when the system test is running.
Viewing equipment status
You can see the status of thermostat-controlled equipment in the Menu under
the EQMT STATUS option.
-
Touch Menu on your thermostat.
-
Touch go to EQMT STATUS.
Touch Select or touch the text area. -
Touch view the statuses of all the equipment the thermostat is controlling. Depending on what feature the thermostat supports or how it was installed, the Equipment Status screen reports data for the following systems:
- Heating and cooling
- Fan
- Ventilation (available on certain models only)
Troubleshooting
Screen is blank
- Check the circuit breaker and reset if necessary.
- Make sure power switch at the heating and cooling system is on.
- Make sure the furnace door is closed securely.
Screen is difficult to read
- Change the screen brightness in the thermostat Menu. Increase brightness intensity for the inactive backlight of the thermostat screen (max. is level 5).
Heating or cooling system does not respond
- Touch Mode to set system to Heat. Make sure the temperature is set higher than the Inside temperature.
- Touch Mode to set system to Cool. Make sure the temperature is set lower than the Inside temperature.
- Check circuit breaker and reset if necessary.
- Make sure power switch at heating & cooling system is on.
- Make sure furnace door is closed securely.
Alerts and reminders
Alerts and reminders are displayed via the alert symbol and alert number in the clock area on the home screen. You can read more information about active alerts, snooze or dismiss non-critical alerts in Menu/Alerts.
Number | Alert/Reminder | Definition |
---|---|---|
164 | Heat Pump Needs Service | Heat pump needs service. Contact dealer to |
diagnose and service heat pump.
168| Wi-Fi Radio Error| The wireless module is not operating. Wireless
features are not available. Please contact dealer to replace the thermostat.
170| Internal Memory Error| The memory of the thermostat has encountered an
error. Please contact dealer for assistance.
171| Set the Date and Time| Set the date and time on your thermostat. The date
and time are required for certain features to operate, like the program
schedule.
173| Thermostat Temperature Sensor Error| The sensor of the thermostat has
encountered an error. Please contact dealer to replace the Thermostat.
175| AC Power Resumed| AC power resumed to thermostat after power loss.
177| Indoor Temperature Sensor Error| Wired indoor temperature sensor is not
connected or there is a wiring short. Please contact dealer for assistance.
178| Outdoor Temperature Sensor Error| Wired outdoor temperature sensor is not
connected or there is a wiring short. Please contact dealer for assistance.
Number| Alert/Reminder| Definition
---|---|---
181| Replace Air Filter (1)| Replace air filter (1). Reset the timer by
touching the “dismiss” button on thermostat screen after it is replaced.
182| Replace Air Filter (2)| Replace air filter (2). Reset the timer by
touching the “dismiss” button on thermostat screen after it is replaced.
183| Clean Humidifier Tank and Replace Water Filter| Clean humidifier tank and
replace the water filter, or contact dealer to do this for you. Reset the
timer by touching the “dismiss” button on the thermostat screen after it is
replaced.
184| Replace Humidifier Pad| Replace humidifier pad. Reset the timer by
touching the “dismiss” button on the thermostat screen after it is replaced.
185| Replace Dehumidifier Filter| Replace the dehumidifier filter. Reset the
timer by touching “dismiss” button on thermostat screen after it is replaced.
186| Clean Ventilator Core| Clean ventilator core. Reset the timer by touching
the “dismiss” button on thermostat screen after it is replaced.
187| Clean or Replace Ventilator Filter| Clean or replace ventilator filter.
Reset the timer by touching the “dismiss” button on thermostat screen after it
is replaced.
188| Replace UV Bulb (1)| Replace UV Bulb (1). Reset the timer by touching
the “dismiss” button on thermostat screen after it is replaced.
189| Replace UV Bulb (2)| Replace UV Bulb (2). Reset the timer by touching
the “dismiss” button on thermostat screen after it is replaced.
210| Register Online For Outdoor Temperature| Online registration is required
to receive outdoor temperature from the Internet. Outdoor temperature is
needed for your current system setup. Download the Lyric app to register your
thermostat.
388| Register Online for Remote Access and Outdoor Temperature| Online
registration is required for remote access and outdoor temperature. Download
the Lyric app to register your thermostat.
399| No Internet| The connection to the Internet has been lost. Please check
your network settings.
400| No Wi-Fi Signal| The Wi-Fi signal has been lost. Please wait for the
thermostat to reconnect or select a new Wi-Fi network. Follow steps in the
Lyric app
508| Wi-Fi Not Configured| Please download the Lyric app and follow the steps
to connect the thermostat to your Wi-Fi network.
CAUTION: ELECTRICAL HAZARD
Can cause electrical shock or equipment damage. Disconnect power before
beginning installation.
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection is bypassed during testing. To prevent equipment damage,
avoid cycling the compressor quickly.
CAUTION: MERCURY NOTICE
If this product is replacing a control that contains mercury in a sealed tube,
do not place the old control in the trash. Contact your local waste management
authority for instructions regarding recycling and proper disposal.
Specifications
Temperature Ranges
Heat: 40 °F to 90 °F (4.5 °C to 32.0 °C) Cool: 50 °F to 99 °F (10.0 °C to 37.0
°C)
Operating Ambient Temperature
37 °F to 102 °F (2.8 °C to 38.9 °C)
Shipping Temperature
-20 °F to 120 °F (-28.9 °C to 48.9 °C)
Operating Relative Humidity
5% to 90% (non-condensing)
Electrical Ratings
Terminal | Voltage (50/60Hz) | Running Current |
---|---|---|
W Heating | 20-30 Vac | 0.02-1.0 A |
(Powerpile) | 750 mV DC | 100 mA DC |
W2 (Aux) Heating | 20-30 Vac | 0.02-1.0 A |
E Emergency Heat | 20-30 Vac | 0.02-0.5 A |
Y Compressor Stage 1 | 20-30 Vac | 0.02-1.0 A |
Y2 Compressor Stage 2 | 20-30 Vac | 0.02-1.0 A |
G Fan | 20-30 Vac | 0.02-0.5 A |
O/B Changeover | 20-30 Vac | 0.02-0.5 A |
L/A Input | 20-30 Vac | 0.02-0.5 A |
U Universal | 20-30 Vac | 0.02-0.5 A |
Power Consumption Backlight On: 1.48VA Backlight Off: 0.88VA
Physical Dimensions
in inches (mm) (H x W x D)
- Lyric T6 PRO Wi-Fi Thermostat (TH6320WF2003): 4-5/64 x 4-5/64 x 1-1/16 (104 x 104 x 27)
- Lyric T6 PRO Wi-Fi Thermostat (TH6220WF2006): 4-5/64 x 4-5/64 x 1-1/16 (104 x 104 x 27)
- UWP Mounting System (THP2600A1009): 2- 9/32 x 2-13/64 x 2-43/64 (58 x 56 x 10)
- Standard Installation Adapter (THP2400A1076): 3- 29/32 x 3-57/64 x 21/32 (99 x 99 x 17)
- Decorative Cover Plate – Small (THP2400A1050): 4- 49/64 x 4-49/64 x 11/32 (121 x 121 x 9)
- Decorative Cover Plate – Large (THP2400A1068): 6-7/64 x 6-7/64 x 9/32 (155 x 155 x 7)
5-year limited warranty
For Warranty information go to
http://customer.honeywell.com
Regulatory information
FCC REGULATIONS
§ 15.19 (a)(3)
This device complies with part 15 of the FCC Rules. Operation is subject to
the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
IC REGULATIONS
RSS-GEN
This device complies with Industry Canada’s license-exempt RSSs.
Operation is subject to the following two conditions:
- This device may not cause interference; and
- This device must accept any interference, including interference that may cause undesired operation of the device.
FCC Warning (Part 15.21) (USA only)
Changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate the equipment.
Automation and Control Systems Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 http://customer.honeywell.com
® U.S. Registered Trademark.
© 2016 Honeywell International Inc. 33-00153—07 M.S. Rev. 08-16 Printed in
U.S.A.
Download PDF:Honeywell Lyric T6 Pro Wi-Fi Programmable Thermostat User Manual
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>