phocos ESS-L-5kWh-48V LFP Energy Storage System Instruction Manual
- June 9, 2024
- phocos
Table of Contents
phocos ESS-L-5kWh-48V LFP Energy Storage System
Abbreviations
Abbreviations
ESS-L| Energy Storage System-Lithium
BMS| Battery Management System
RoHS| Restriction of Hazardous Substances
AHJ| Authority Having Jurisdiction
About This Manual
SAVE THESE INSTRUCTIONS: This manual contains important instructions for the Any-Cell ESS-L-5kWh-48V (referred to as Any-Cell ESS-L) that shall be followed during the installation and maintenance of the Any-Cell ESS-L. Read and save this manual for future reference.
This manual describes how to install the Phocos Any-Cell Energy Storage System LFP Series (ESS-L). Read this manual before you attempt to install the product and follow the instructions throughout the installation process. If you are uncertain about any of the requirements, recommendations, or safety procedures described in this manual, contact Phocos for advice and clarification. The information included in this manual is accurate at the time of publication. However, with regard to the product design and technical specification updates, our company reserves the right to make changes at any time without prior notice. In addition, the illustrations in this manual are meant to help explain system configuration concepts and installation instructions. The illustrated items may differ from the actual items at the installation location.
Important Safety Information
For safety reasons, installers are responsible for familiarizing themselves with the contents of this manual and all warnings before performing the installation.
- WARNING: The installation of this unit may only be undertaken by qualified personnel with appropriate training. High voltages in and around the unit can cause serious injury or death. This unit must be installed in accordance with rules and regulations at the site of installation.
- CAUTION: A battery can present a risk of electrical shock, burn from high short-circuit current, fire or explosion from vented gasses. Observe proper precautions.
General safety precautions
Failure to observe the precautions described in this section can cause serious
injury to persons or damage to property. Please observe the following
precautions.
Risks of explosion
- Do not subject the Any-Cell ESS-L to strong impacts.
- Do not crush or puncture the Any-Cell ESS-L.
- Do not dispose of the Any-Cell ESS-L in a fire.
Risks of fire
Do not expose the Any-Cell ESS-L to temperatures in excess of 60°C.
- Do not place the Any-Cell ESS-L near a heat source, such as a fireplace.
- Do not expose the Any-Cell ESS-L to direct sunlight.
- Do not allow the battery connectors to touch conductive objects such as wires.
Risks of electric shock
- Do not disassemble the Any-Cell ESS-L.
- Do not touch the Any-Cell ESS-L with wet hands.
- Do not expose the Any-Cell ESS-L to moisture or liquids.
- Keep the Any-Cell ESS-L away from children and animals.
Risks of damage to the Any-Cell ESS-L
- Do not allow the Any-Cell ESS-L to come in contact with liquids.
- Do not subject the Any-Cell ESS-L to high pressures.
- Do not place any objects on top of the Any-Cell ESS-L.
Battery handling guide
- Use the Any-Cell ESS-L only as directed.
- Do not use the Any-Cell ESS-L if it is defective, appears cracked, broken or otherwise damaged, or fails to operate broken or otherwise damaged, or fails to operate.
- Do not attempt to open, disassemble, repair, tamper with, or modify the Any-Cell ESS-L. The Any-Cell ESS-L is not user serviceable.
- To protect the Any-Cell ESS-L and its components from damage when transporting, handle with care.
- Do not impact, pull, drag, or step on the Any-Cell ESS-L.
- Do not subject the Any-Cell ESS-L to any strong force.
- Do not insert foreign objects into any part of the Any-Cell ESS-L.
- Do not use cleaning solvents to clean the Any-Cell ESS-L.
Response to emergency situations
The Phocos Any-Cell ESS-L comprises multiple cells that are designed to
prevent hazards resulting from failures. However, Phocos cannot guarantee
their absolute safety.
Leaking batteries
WARNING:
If the Any-Cell ESS-L leaks electrolyte, avoid contact with the leaking liquid
or gas. Electrolyte is corrosive and contact may cause skin irritation and
chemical burns.
If one is exposed to the leaked substance, follow these steps:
- Inhalation: Evacuate the contaminated area and seek medical attention immediately.
- Eye contact: Rinse eyes with flowing water for 15 minutes and seek medical attention immediately.
- Skin contact: Wash the affected area thoroughly with soap and water and seek medical attention immediately.
- Ingestion: Induce vomiting and seek medical attention immediately.
Fire
In case there is a fire, always have an ABC or carbon dioxide extinguisher.
The Any-Cell ESS-L may catch fire when heated above 150°C.
If a fire breaks out where the Any-Cell ESS-L is installed, follow these steps
- Extinguish the fire before the Any-Cell ESS-L catches fire.
- Refer to your local AHJ to determine the best course of action in cases where it is impossible to extinguish the fire, but you may have time to move the Any-Cell ESS-L to a safe area before it catches fire.
- If the Any-Cell ESS-L has caught fire, do not try to extinguish the fire. Evacuate the area immediately.
- WARNING: If the Any-Cell ESS-L catches fire, it will produce toxic and poisonous gases. Do not approach.
Wet batteries
If the Any-Cell ESS-L is wet or submerged in water, do not try to access it.
First contact the local AHJ for advice on how to proceed. If the battery has
been recovered and cleared by the AHJ, please reach out to your distributor or
Phocos for technical assistance.
Damaged batteries
- WARNING: Damaged batteries are dangerous and must be handled with extreme caution. They are not fit for use and may pose a danger to people or property.
- If the Any-Cell ESS-L seems to be damaged, take photos, pack it in its original container, and then return it to your distributor.
- If the Any-Cell ESS-L is damaged, it may leak electrolytes or produce flammable gas. If you suspect your Any-Cell ESS-L is damaged, immediately contact Phocos for advice and information.
Regulatory Information
This product is CE and RoHS (Restriction of Hazardous Substances) compliant. Please find the CE declaration at www.phocos.com. This equipment is suitable for use in non-hazardous locations only. IEC62619, UL1973, and UN38.3 Certified.
Product Overview
The Phocos Any-Cell™ ESS-L LFP Series (ESS-L) is a Lithium Iron Phosphate (LiFePO4) battery product with an integrated BMS (Battery Management System). The Any-Cell ESS-L is shipped with features including CAN communication, under-voltage, over-voltage, over-current, over-temperature, and under- temperature protection functions. Users can expect reliable operation with the safety of an LFP system over a long cycle life. Energy storage systems implementing the Any-Cell ESS-L are expandable; up to 8 Any-Cell products may be used in parallel to increase storage capacity accordingly. Users can also expect seamless integration of their Any-Cell ESS-L with new and existing Any- Grid inverters designed for 48V battery systems.
NOTICE:
The Any-Cell ESS-L may only be used with the Any-Grid™ 48V series of hybrid
inverters with accompanying Any-Bridge™ AB-PLC-CAN gateway and monitoring
device. This device facilitates closed-loop communication between the Any-Grid
hybrid inverter and the Any-Cell ESS-L, which is necessary for normal battery
operation. Failure to include an AB-PLC-CAN in the installation of the Any-
Cell ESS-L will result in a non-functioning system.
Outline and Dimensions
Number | Description |
---|---|
① | Front Logo |
② | Handle |
③ | BMS Power Button |
④ | SOC (State of Charge) & Warning light indicator |
⑤ | Terminal Entry |
The wiring port of the Any-Cell ESS-L is accessed by removing the x4 T15 screws holding the terminal cover plate and lifting the cover plate from the unit. Please see the following pictures for details.
Number | Description | Notes |
---|---|---|
① | Terminal Cover Plate | To cover and protect the electrical connections |
②③ | Battery+ | Positive terminals of battery |
④⑤ | Battery- | Negative terminals of battery |
⑥⑦ | CAN1 ports | For battery-to-battery communication when in parallel |
⑧⑨ | CAN2 ports | For battery to Any-Bridge communication |
⑩ | Remote port | To enable installation of a remote BMS power switch |
CAN communication interface pinout (CAN1 & CAN2)
The Any-Cell ESS-L has four modular 8P8C communication connectors for CANbus
communication. CAN1 is used exclusively for battery-to-battery communication
between the BMSs of Any-Cell units when in parallel. CAN2 is used to
communicate between the BMS of one or multiple Any-Cells and the Any-Bridge
gateway device. For installers creating custom communication cables, the
pinout of an Any-Cell CAN port is shown below.
There is no difference between the two ports labeled CAN1 – they may be used interchangeably, and both connect to the same CANbus node. The same applies to the two CAN2 ports.
Pin Number | Name |
---|---|
①②③ | NC |
④ | CANH |
⑤ | CANL |
⑥⑦⑧ | NC |
No grounded shield connection is required for proper communication for local cable runs.
LED Indicators
Number | Name | LED Operation |
---|---|---|
① | BMS power button | White light, solid: BMS on |
② | 100% capacity indicator | Green light, solid: 100% SOC |
③ | 75% capacity indicator | Green light, solid: >75% SOC |
④ | 50% capacity indicator | Green light, solid: >50% SOC |
⑤ | 25% capacity indicator | Green light, solid: >25% SOC |
⑥ | Warning indicator | Yellow light, solid: Normal |
Yellow light, blinking: Warning
The warning indicator will blink when the Any-Cell BMS has encountered an error. See section 8 Troubleshooting for details.
Installation
CAUTION:
The Any-Cell ESS-L is too heavy for a single person to carry. Always have two
or more people carry the unit.
Unpacking
Cut the packing tape, open the carton, and remove the EPE foam.
Pull out the Any Cell ESS-L. Remove the Cardboard, PE bag, carton, and EPE Foam.
Packing List
The following table lists the quantity of each item included with the purchase of a Phocos Any-Cell ESS-L. If anything is damaged or missing, please contact Phocos or your distributor.
Item | Name | Purpose | Qty (pcs) |
---|---|---|---|
1 | Phocos Any-Cell ESS-L | – | 1 |
2 | CAT5e patch cables | CANbus Communication | 3 |
3 | T15 Wrench Tool | Terminal cover plate removal | 1 |
4 | M4 T15 Screws | Extra for Terminal cover plate | 2 |
5 | M6 T30 Screws | Rack Mounting | 6 |
7 | Rack Mount Brackets | Rack Mounting | 2 |
6 | M6 Phillips Hex Screws | Wall Mounting | 7 |
8 | Wall Mounting Rails | Wall Mounting | 2 |
9 | Side Support Bracket | Wall Mounting | 1 |
10 | User manual | – | 1 |
Installation Materials
The following installation materials are to be provided by the installer or
user and are not included in your Any-Cell purchase. Always check with the
local AHJ regarding best practices and regulations for electrical equipment
installations.
- Battery Wires, Terminals, DC disconnect(s), DC breaker(s) (rated as required by AHJ)
We recommend using 2-4AWG / 25-35mm^2 of a conductor with double insulation, with properly rated and crimped ring terminals for mating on an M6 bolt, at a maximum of 10ft round trip length (5ft per terminal) per Any-Cell. See 6.7 Wiring Specification and 6.10 Battery Terminal Connections for more details. Always check with your local Authority Having Jurisdiction so you can most accurately comply with local regulations and wire sizing requirements. Wires that are too thin and/or too long will result in excessive power loss and wire heating. Take caution and use best practices when determining the correct wire size and length for your application and expected loads.
Wall Mounting
Wall anchors/concrete lags to fit 10mm diameter slots in the Wall Mount
Rails (See 6.2 Packing List) For drywall and concrete wall mounting, only use
anchors rated for the weight of the Any-Cell (≥56kg). At a minimum, 4 mounting
points must be made with the wall. Mount on a vertical surface only.
Rack Mounting
- Standard 19” wide, ≥24” deep Telecom rack
- 19” wide, ≥24” deep Telecom rack shelf capable of holding the weight of the Any-Cell (≥56 kg) One shelf is required per battery unit. See 9 Specifications for more details on the Any-Cell size and weight.
Floor Mounting
A method of setting the Any-Cell off the floor 6-12” to prevent water
damage in the event of flooding. This can be accomplished with a short
rack/table, either stationary or on locking casters. Mount only on a flat
surface.
Installation Location
The Any-Cell ESS-L has an IP rating of IP20 when wall-mounted, and IP54 when
rack-mounted. Therefore, we strongly recommend only using the Any-Cell ESS-L
in indoor installations that meet the following criteria:
- The building is designed to withstand earthquakes
- The location is far away from the sea, to avoid salt water and humidity
- The floor is flat and level
- There are no flammable or explosive materials nearby
- The ambient temperature is between 15 and 30°C
- The temperature and humidity stay at a constant level
- There is minimal dust and dirt in the area
- There are no corrosive gases present, including ammonia and acid vapor
CAUTION:
If the ambient temperature is outside the operating range, the Any-Cell ESS-L
stops operating to protect itself. The optimal temperature range for the Any-
Cell ESS-L is 15 °C to 30 °C. Frequent exposure to harsh temperatures may
affect the performance and lifetime of the Any-Cell ESS-L.
Installation Options
The Any-Cell ESS-L can be installed in three configurations: mounted on the
wall, in a rack, or on the floor.
WARNING:
The Any-Cell contains hazardous levels of energy. Never work on a live
circuit. When installing and connecting the Any-Cell, ensure that the BMS is
powered OFF (button out, no lights on). Leave the terminal cover plate on
while mounting. Never pierce or strike the Any-Cell housing.
Wall Mounting
When mounting an Any-Cell to a wall, first securely anchor the rails to the
wall surface at the correct spacing. With two people, lift the Any-Cell into
position and screw in x4 M6 Phillips Hex screws to the bottom of the unit
through the holes in the rail. Attach the side support bracket to one side of
the Any-Cell using x3 M6 Phillips Hex screws.
Rack Mounting
If mounting your Any-Cell(s) within a standard 19” telecom rack, first be sure
that the shelves and rack are rated for the weight of the Any-Cell(s) you plan
to install. If necessary, attach the two included rack mount brackets to the
top of the Any-Cell (the face with the LED indicators) using x4 M6 T30 Screws,
and secure these brackets to the front rails of the telecom rack. Always have
two people move the Any-Cell.
The included rack mount brackets are not designed to support the weight of the Any-Cell. A shelf must be provided (not pictured below). Telecom rack screws are not provided. Use the hardware included with your telecom rack.
Floor Mounting
For Floor mounting installations, please ensure that the Any-Cell is not at
risk of water immersion due to flooding. The provided wall mounts may be
incorporated into a table or stand on the ground or on wheels, or the
installer/user may provide hardware to mount the Any-Cell directly to a table
or mount. We highly recommend against mounting the Any-Cell on the floor of a
basement where flooding may be common. If using a mobile floor mount or rack
with casters, always provide a locking/immobilization method for when the Any-
Cell(s) is connected and in use. Phocos cannot be held liable for damage to
the Any-Cell based on location or method of mounting, or in the event of major
flooding.
Custom mounting solutions are performed at the installer’s risk. Do not mount directly to the floor if in a basement or ground level.
Communication Connections
CANbus Communication
There are 2 ways to connect the Any-Cell ESS-L to the Any-Grid, depending on
how many units need to be connected.
- When connecting a single Any-Cell to an Any-Grid, CAN2 is used to communicate to the Any-Bridge, which is in turn connected to the Any-Grid over RS232.
- When multiple Any-Cells are used in parallel, their CAN1 and CAN2 networks must be chained respectively through each battery (Example: CAN1 of units 1, 2, and 3 connected, and CAN2 of units 1, 2, and 3 connected) with the CAN2 port of one Any-Cell connected to the Any-Bridge.
In any configuration, CAN1 of any one Any-Cell is never to be connected to CAN2 of the same or any other Any-Cell. See the diagrams below (Section 6.8 and 6.9) for more detail on these two configurations.
CANbus Termination – DIP Switches
For any configuration, the last Any-Cell connection to CAN2 must have its CAN2
DIP switch #2 set to ON. This is to ensure proper termination of the CANbus.
The Any-Bridge CAN port has built-in termination. Only one Any-Cell requires
CAN 2 DIP switch #2 to be set to ON.
For configurations using more than one Any-Cell, the first and last Any-Cell connections to CAN1 must have their CAN1 DIP switches #2 set to ON. There should only be two CAN1 DIP switches with #2 set to ON. For more detail, please see the diagrams in 6.9 Connecting multiple Any-Cells to an Any-Grid. If you experience issues with the AB-PLC-CAN communication between the Any- Cell and Any-Grid, please check CANbus termination.
WARNING:
Never work on a live circuit. When installing and connecting the Any-Cell,
ensure that the BMS is powered OFF (button out, no lights on). Additionally,
ensure the Any-Grid is de-energized and disconnected from all other power
sources (Grid and PV). Electrical installation should only be performed by a
qualified electrical technician.
Wiring Specification
The following specifications are required for wires and cables used to connect the Any-Cell ESS-L to other systems.
Battery Wires| CANbus Communication Cable(s)| Remote BMS
Power Switch Wires
---|---|---
It is recommended to use 2-4AWG / 25-35mm² of a conductor with double
insulation, crimped with M6-sized ring terminals rated for the same wire size.
Maximum 10ft round trip (per battery unit)*
These will connect the Any-Cell to the Any-Grid inverter for charging/discharging.
| It is recommended to use standard 8P8C communication cables lengths up to 10ft, i.e., the provided CAT5e 1:1 patch cables.
These will provide a communication link between the Any-Cell(s) and the Any- Bridge, which in turn communicates to the Any-Grid inverter.
| If using this optional feature, it is recommended to use 0.5 mm² of insulated wire up to 20ft round trip
These will provide a connection to an optional remote switch for powering on
the Any-Cell BMS.
(See 7.2 Remote Switch Option )
Wire lengths should be minimized for maximum performance and the least loss.
After mounting and physically installing your Any-Cell(s), we recommend first connecting the necessary communication cables between with the Any-Grid and the Any-Bridge. First, remove the terminal cover plate using the provided T15 Tool.
Please visit www.phocos.com to access the setup manual for the Any-Bridge AB-PLC-CAN gateway device. Please download the latest “PhocosLink Mobile” App from the Google Play™ store or Apple’s App Store® with an Android™ or iOS device, respectively. The Any-Cell will not communicate with the Any-Grid without an accompanying Any-Bridge. Please contact Phocos or your distributor if you experience difficulties setting up your Wi-Fi or BLE connection.
Connecting a single Any-Cell to an Any-Grid
Any-Cell CAN2 is connected to the Any-Bridge CAN port with a communication cable. No connections to CAN1 are necessary when using a single Any-Cell unit. Notice that the CAN2 DIP switch #2 is set to ON.
Connecting multiple Any-Cells to an Any-Grid
When connecting more than one battery unit in parallel to an Any-Grid, the CAN1 must be connected across all batteries. CAN2 must be connected across all batteries and to the Any-Bridge. Notice that only the first and last Any-Cell have CAN1 DIP switch #2 set to ON, and only the last Any-Cell has the CAN2 DIP switch #2 set to ON.
Battery Terminal Connections
Please see the following diagram for details regarding the battery terminal
connection. Be sure to use properly sized wires for battery wiring. See the
wiring specifications table in Wiring Specification above for the wiring gauge
and ring terminal sizing recommendation. Always consult local guidelines and
regulations to ensure you meet the requirements for the installation location.
Always minimize the length of battery wires and place the Any-Cell as close as
possible to the Any-Grid.
WARNING:
Never work on a live circuit. When installing battery terminal connections to
the Any-Cell, ensure that the BMS is powered OFF (button out, no lights on).
Additionally, ensure the Any-Grid is de-energized and disconnected from all
other power sources (Grid and PV). Electrical installation should only be
performed by a qualified electrical technician.
When multiple Any-Cells are used in parallel, the installer will need to take care in routing the current path through appropriately sized conductors. Please refer to the best practices for wiring batteries in parallel to ensure all batteries are kept balanced. Always make positive and negative connections at opposite ends of the parallel chain – failure to do so could result in battery units at different States of Charge. Always use equal lengths of wire to connect battery units. Alternatively, use two bus bars and equal-length battery wires to connect all battery terminals to a common positive and common negative electrode, which are then connected to the Any-Grid. Each Any-Cell terminal should be protected by a DC breaker or fuse of the appropriate size and rating.
The battery terminal connections should be torqued to 4.4-5.2 Nm / 3.3-3.8 lb- ft using either an insulated #3 Phillips head screwdriver or 10mm socket wrench. Failure to properly torque battery terminal connections could result in increased contact resistance (under-torque), or damaged terminals (over- torque), and will void the warranty.
Operation
At any point in time, the Any-Cell output may be enabled/disabled at the press of a button. When the BMS is powered off, the external terminals will be disconnected from the battery cells. In this state, no energy can be transferred to or from the Any-Cell. There are two options to power on the Any-Cell ESS-L BMS to enable charging and discharging:
Option A – Default BMS Power Switch
From the factory, a small red jumper is installed between PIN2 and PIN3 of the
remote port. When configured this way, simply press the metal button below the
LED indicators to power on the Any-Cell BMS to enable charging and
discharging. The Any-Cell ESS-L will power up within 25 seconds.
Option B – Remote BMS Power Switch Option
The built-in power button can be bypassed and replaced with a user-provided
switch or relay. With the system disconnected and off, remove the remote port
connector (green screw contact) using a small flathead screwdriver. Remove the
red jumper that is between PIN2 and PIN3. Install a switch between PIN1 and
PIN2 on the Remote port (See 6.7 Wiring Specification for details). Reinstall
the remote port connector within the Remote port. When the remote switch is
closed, the Any-Cell ESS-L will power up within 25 seconds.
Number | Name |
---|---|
① | Remote port |
After communication cables, battery wires (and the optional remote switch) are all installed, the Any-Cell is ready to be enabled by powering on the internal BMS. We strongly recommend double-checking that proper polarity is achieved and that good continuity is established through all points of high current contact.
CAUTION: A reverse polarity connection will damage the Any-Grid inverter.
System Startup with Any-Grid
After carefully reviewing and following the steps above to setup your Any-Cell
configuration, leave the Any-Grid de-energized from external power sources (PV
and Grid). Disconnect any AC loads from the inverter output, so that the Any-
Cell is the only load/source electrically connected to the Any-Grid.
Battery Test:
- Press the BMS power button(s) OR close the optional remote switch(es), if installed. Do this for all installed Any-Cells.
- The BMS(s) will power up within 25 seconds. During this time, the white LED ring around the power button will illuminate, and the SOC indicators will light.
- An audible “click” should be heard, indicating the safety isolation relay has closed.
- Press the Any-Grid AC load ON switch, if not already pressed in.
- The Any-Grid will detect the battery voltage and boot up. The display should power up in 10 seconds.
- Using the arrows on the Any-Grid display, scroll to the battery voltage. Ensure that it reads between 50V and 55V.
- Press the BMS power button/open the optional remote switch. An audible “click” should be heard immediately. The Any-Cell indicators should extinguish, and the Any-Grid will power down.
- Continue to 7.3.2 Any-Bridge Setup below. Ensure that AC loads remain disconnected until the Any-Bridge has been commissioned.
Any-Bridge Setup:
- Download and open the PhocosLink Mobile app on your mobile device. Ensure BLE is enabled on your device.
- If Grid power is available, supply this to the Any-Grid. Leave AC loads disconnected.
- If no Grid power is available, supply PV power to the Any-Grid.
- If no PV power is available, power on the Any-Cell BMS (See 7.1 and 7.2 above). You will have 5 minutes to complete the steps below if powering the Any-Grid with the Any-Cell only (See 7.4 Safety Shutoff Feature below).
- After the Any-Grid powers on, the Any-Bridge will receive power over RS232 and the indicators should begin to blink. See your Any-Bridge manual for details. Do not disconnect the RS232 cable while the Any-Grid is powered on. This may damage the remote display and/or the Any-Bridge.
- Pair to your Any-Bridge. You may need to refresh the BLE search screen.
- Choose “Any-Cell” as your battery type and send this to the AB-PLC-CAN.
- Press the BMS power button(s) as you did in Step 1 of the Battery Test above. The Any-Cell relay(s) will close, indicated by an audible “click.”
- Within 2 minutes, the Any-Bridge will update the Any-Grid with information from the connected Any-Cell. If Grid or PV is connected, the Any-Cell will begin to charge.
- Recommended: Follow the steps in the Any-Bridge manual to connect your Any- system to Wi-Fi and the PhocosLink Cloud.*
- You may disconnect and close the app. The Any-Bridge will monitor your Any-Cell and configure the Any-Grid battery settings automatically. You know this has been successful if the Any-Cell does not enter Safety Shutoff mode after 5 minutes.
- After verifying your setup, the terminal cover plate(s) may be reinstalled on the Any-Cell(s) wiring port. Switch the BMS(s) power OFF while reinstalling the cover plate to reduce the risk of shock. Switch the BMS(s) back on when finished.
- You may now switch back on AC loads.
Contact your installer, distributor, or Phocos if you are unable to complete any of the steps above.
Safety Shutoff Feature
If communication between the Any-Cell and the Any-Bridge is lost for more than
5 minutes, the BMS will enter a safety shutoff mode, preventing any
discharging or charging of the battery. This state can be identified if the
power button/remote switch is in the ON position and all LED indicators are
OFF. The BMS will automatically reenable its output when the communication
link is reestablished – this may take a up to five minutes after the Any-
Bridge has powered back on. Always power off the BMS if the Any-Cell will be
stored for long periods of time without an active communication link with a
powered Any-Bridge. Failure to do so could result in reduction of pack life.
When first installing the Any-Cell and AB-PLC-CAN, check that the BMS has not entered safety shutoff mode after 5 minutes of operation. Check all CANbus connections if the Any-Cell will not stay on for longer than 5 minutes.
Troubleshooting
Any-Cell Warnings
Check the warning indicator on the front of the unit to determine the state of
the Any-Cell ESS-L. A warning state is triggered when voltage, current, or
temperature, is beyond the limits set by the Any-Cell BMS. The Any-Cell ESS-L
unit’s BMS periodically reports its operating state to the Any-Bridge. When a
warning is reported, the Any-Grid immediately ceases charging or discharging
from the battery. The possible warning conditions are as follows:
Battery Over Voltage
- Likely Cause – Charging Voltage set too high / Communication error with Any-Grid
- Solution – Check that AB-PLC is connected properly, on, and operating correctly. Power cycle the Any-Grid.
Battery Under Voltage
- Likely Cause – Battery discharged past lower limit / Communication error with Any-Grid
- Solution – Check that AB-PLC is on and operating correctly. Power cycle the Any-Grid. Provide AC/PV power and allow battery to charge.
Battery Over Temperature
- Likely Cause – Ambient temperature too high
- Solution – Ensure that the installation location is suitable. Provide cooling to the installation location
Battery Under Temperature
- Likely Cause – Ambient temperature too low
- Solution – Ensure that the installation location is suitable. Provide heating to the installation location
Battery Discharge Over Current
- Likely Cause – Discharge Current set too high / Communication error with Any-Grid
- Solution – Check that AB-PLC is connected properly, on, and operating correctly. Power cycle the Any-Grid.
Battery Charge Over Current
- Likely Cause – Charge Current set too high / Communication error with Any-Grid
- Solution – Check that AB-PLC is connected properly, on, and operating correctly. Power cycle the Any-Grid.
The error state is cleared when the Any-Cell ESS-L recovers and returns to normal operation. The yellow warning light should stop blinking and return to solid.
General Issues
Most Any-Cell issues will arise from communications failure with the Any-
Bridge and/or Any-Grid. If the Any-Cell is not operating as expected or is
stuck in safety shutoff mode (See 7.4 Safety Shutoff Feature), double-check
that all communication cables between the Any-Cell(s), Any-Bridge, and Any-
Grid are connected and that the Any-Bridge is ON and seen in the PhocosLink
Mobile app. If the problem persists, please contact your distributor or
Phocos.
Specifications
Type | ESS-L-5kWh- 48V |
---|---|
Chemistry | LiFePO4 / LFP |
Nominal Voltage | 51.2 V |
System Voltage | 48 Vdc |
Capacity (kWh) | 5.12 kWh* |
Capacity (Ah) | 100 Ah |
Max. Discharge | 100 A |
Peak Discharge | 200 A |
Max. Charge | 75A |
Max DoD | 90% |
Usable Voltage Range | 50.1 V to 54.8 V |
Cycle Life (@ 25 °C) | > 6,000 Cycles @ 90% DoD |
Extensibility | Up to 8 batteries in parallel |
Idle Self-Consumption | < 3 W continuous |
Ambient Temperature | -10 to +50 °C / +14 to +122 °F |
Storage Temperature | -30 to +60 °C / -22 to +140 °F |
Max. Altitude | 2,000 m |
Humidity | 5% to 95% |
Communication | CANbus |
Dimensions (WxHxD) | 440 x 595 x 172 +/-2 mm / 17.3 x 23.4 x 6.8 in (without |
bracket)
Weight| 56 kg / 123.5 lbs.
Mounting| Wall or rack mount (wall mount hardware included)
Ingress Protection| IP20**
Certificates| UL 1642, UL1973, IEC 62619, UN38.3, CE, RoHS
Warranty| 10 years***
- Total capacity assumes a full charge cycle for properly balanced cells.
- IP20 applies when wall-mounted, and IP54 applies when rack-mounted.
- Per Phocos warranty conditions. See 10.1 Conditions below.
Warranty
Conditions
A limited warranty is provided for the Any-Cell ESS-L covering quality defects
and performance under qualifying conditions including type and length of
operation. Details of our warranty conditions can be found at
www.phocos.com.
Liability Exclusion
The manufacturer shall not be liable for damages, especially on the battery,
caused by use other than as intended or as mentioned in this manual or if the
recommendations of the battery manufacturer are neglected. The manufacturer
shall not be liable if there has been service or repair carried out by any
unauthorized person, unusual use, wrong installation, or incorrect system
design.
Phocos is not liable if:
- If the Any-Cell is opened
- If the BMS is somehow bypassed
- If the Any-Cell has burnt/damaged terminals due to:
- Higher discharge currents than the limits of the battery
- Improper cable installation
- Improper cable gauge
- Improper cable torque
Specifications are subject to change without notice. Version: 20230201