APC BR1200G-RS Power Saving Back-UPS Instruction Manual
- June 9, 2024
- APC
Table of Contents
Installation and Operation Manual
Back-UPS ® BR1200G-RS/BR1500G-RS
Inventory
Important Safety Messages
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries.
- This UPS is intended for indoor use only.
- Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
- Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
- The battery typically lasts for three to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality AC power, and frequent short duration discharges will shorten battery life.
- Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
-
Replace the battery at least every 5 years or at the end of its service life, whichever is earlier.
-
Replace the battery immediately when the UPS indicates battery replacement is necessary.
-
Replace batteries with the same number and type of batteries as originally installed in the equipment.
-
Replace the battery immediately when the UPS indicates a battery over-temperature condition, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
Failure to follow these instructions can result in minor or moderate injury and equipment damage.
For the recycling battery information, please go to apc.com/recycle -
CAUTION: Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the required precautions.
-
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
-
CAUTION: Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.
-
CAUTION: Before replacing batteries, remove conductive jewelry such as chains, wrist watches, and rings. High energy through conductive materials could cause severe burns.
-
CAUTION: Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.CAUTION: A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
– Disconnect the charging source prior to connecting or disconnecting battery terminals.
– Do not wear any metal objects including watches and rings.
– Do not lay tools or metal parts on top of batteries.
– Use tools with insulated handles.
– Wear rubber gloves and boots.
– Determine if battery is either intentionally or inadvertently grounded. Contact with any part of a grounded battery can result in electric shock and burns by high short-circuit current. The risk of such hazards can be reduced if grounds are removed during installation and maintenance by a skilled person. -
This manual can be downloaded from APC by Schneider Electric Website www.apc.com.
Connect the Battery
Charge the battery for at least 16 hours before use.
PowerChute ® Personal Edition Software
Overview
PowerChute Personal Edition Software allows you to use your computer to
access additional power protection and management features of the Back-UPS.
Using PowerChute, you can:
- Preserve work in progress during a power outage by putting your computer into Hibernate mode. When the power returns, the computer will appear exactly as it did before the power outage.
- Configure the Back-UPS management features, such as power-saving outlets, shutdown parameters, audible alarms, and more.
- Monitor and view the status of the Back-UPS, including the estimated runtime, power consumption, power event history, and more.
Available features will vary by Back-UPS model and operating system.
If you choose not to install PowerChute, the Back-UPS will still provide backup power and power protection to connected equipment. However, you will only be able to configure a limited number of features using the display interface.
Compatibility
PowerChute is compatible with Windows operating systems only. For a detailed
list of supported operating systems, go to www.apc.com,
select Software & Firmware.
For Mac operating systems, we recommend using the native shutdown application
(within System Preferences) which recognizes your battery backup and allows
you to onfigure shutdown of your system during power outages. To access this
application, connect a USB cable from the Back-UPS DATA PORT (POWERCHUTE PORT)
to a USB port on your computer, and see the documentation provided with your
computer.
Installation
Use the USB cable to connect the USB and Serial Data port on the UPS to the
USB port on your computer. Download PowerChute™ Personal Edition Software from
www.apc.com/pcpe. Select the appropriate operating
system and follow directions to download and install the software.
Connect the Equipment
Battery Backup and Surge Protected outlets
When the Back-UPS is receiving input power, the Surge Protection only outlets
and the Battery Backup with Surge Protection outlets will supply power to
connected equipment. During a power outage or other AC problems, only the
Battery Backup outlets receive power for a limited time from the Back-UPS.
Connect equipment such as printers, FAX machines, scanners, or other
peripherals that do not need battery backup power to the Surge Protection Only
outlets. These outlets provide full time protection from surges even if the
Back-UPS is switched off.
Master and Controlled outlets
To conserve electricity, when the device connected to Master Outlet goes into
Sleep or Standby mode, or turns off, the Controlled by Master device(s) will
shut down as well, saving electricity. Connect a master device, such as a
desktop computer or audio/visual receiver to the Master outlet. Connect
peripheral devices such as a printer, speakers, or a scanner to the Controlled
by Master outlets.
1 USB and Serial Data port| To use PowerChute software, connect a USB cable,
to the USB or serial port.
---|---
2 Telephone Cable Surge-protected ports| Connect one end of a
DSL/Modem/FAX/Phone cable to a telephone wall outlet and the other end to
the IN port on the Back-UPS. Connect one end of a DSL/Modem/FAX/Phone cable to
a modem,
FAX machine or telephone and the other end to the OUT port on the Back-UPS.
3 Ground screw| Connect the ground lead from additional surge suppression
devices such as a stand-alone data line surge protector.
4 Surge Protection outlets, Controlled by Master outlet| These outlets provide
surge protection during a power outage. These outlets will disconnect from
AC power during a power outage, or in the event that the Master outlet goes
into Sleep mode.
5 Surge Protection outlets| These outlets provide full-time surge protection,
when the unit is turned on or off. The Surge Protection outlets do not provide
battery backup to connected equipment. Connect a printer, scanner or other
noncritical devices that do not require battery backup protection.
6 AC Power Cable| Use this cable to connect the Back-UPS to AC power.
7 Battery Backup outlets with Surge Protection| These outlets provide battery
backup power to connected equipment for a limited period of time during power
outages and voltage fluctuations. The Battery Backup + Surge Protection
outlets provide battery power to connected equipment only when the Back-UPS is
turned on. Connect essential equipment such as a computer, computer monitor,
modem or other data sensitive devices to these outlets. Do not connect
aquarium equipment, laser printers, paper shredders, sump pumps, or fans to
these outlets as the modified sine wave output of the Back-UPS may cause these
devices to experience a decrease in performance. Do not connect surge
protectors or extension cords to these outlets.
8 Battery Backup, Controlled by Master outlet with Surge Protection| This
outlet provides surge protection for the connected device. To conserve energy
the Controlled by Master outlets will disconnect from AC power whenever the
device plugged into the MASTER outlet is turned off or goes into Standby or
Hibernation mode.
9 Master outlet| Connect the master device to this outlet, in most cases, this
will be the main computer.
In addition to providing battery backup power and surge protection, this
outlet will signal the Controlled by Master outlets to disconnect from AC
power when the master device is either turned off or goes into Standby or
Hibernation mode.
10 Gigabit Ethernet surge-protected ports| Use an Ethernet cable to connect a
modem, router or network connection to the IN port, and a
computer to the OUT port.
11 External Battery Pack connector
BR1500G-RS model only| Connect an external battery pack to provide additional
battery backup runtime.
Operation
Power Saving Feature
This Back-UPS is equipped with power saving outlets that conserve electricity.
Configure the Back-UPS to recognize a Master device, such as a computer or an
A/V receiver, and Controlled by master peripheral devices, such as a printer,
speakers, or a scanner. When the Master device goes into Standby or
Hibernation mode, or is turned off, the Controlled by Master device(s) will be
turned off.
The Back-UPS ships with this Power Saving feature DISABLED. To configure this
feature, follow the instructions below or use PowerChute software.
Notes: Devices that provide network services (such as routers, modems, or
wireless printers) should not be plugged into the Controlled outlets. The
Back-UPS ships with this Power-Saving feature DISABLED. If you wish to use
this feature, follow the instructions below:
Enable the Power Saving Controlled outlets. Press and hold MUTE and
DISPLAY buttons simultaneously for two seconds.
The Back-UPS will beep to indicate the feature is enabled. The leaf icon on
the display will illuminate.
Disable the Power Saving Controlled outlets. Press and hold MUTE and DISPLAY
buttons simultaneously for two seconds.
The Back-UPS will beep to indicate the feature is disabled. The leaf icon on
the display will extinguish.
Setting the threshold. The amount of power used by a device in Standby or
Hibernation mode varies dependant on the connected device. If the Controlled
outlets do not turn off when the Master device is in Standby or Hibernation
mode, it may be necessary to adjust the threshold at which the MASTER outlet
signals the CONTROLLED outlets to shut down.
- Be sure a master device is connected to the MASTER outlet. Place that device into Standby or Hibernation mode, or turn it off.
- Press MUTE and DISPLAY buttons simultaneously and hold for six seconds, until the leaf icon flashes three times and the Back-UPS beeps three times.
- The Back-UPS will now recognize and save the threshold level as the new threshold setting for the master device.
Power-Saving LCD Screen
The display interface can be configured to remain continuously illuminated or
to extinguish after a period of inactivity to save electricity.
- Continuous Illumination mode: Press and hold DISPLAY button for two seconds. The display will illuminate and the BackUPS will beep to confirm Continuous Illumination mode is activated.
- Power Saving mode: Press and hold DISPLAY button for two seconds. The display will extinguish and the Back-UPS will beep to confirm Power Saving mode is activated. While in Power Saving mode, the display will illuminate if a button is pressed, it will extinguish after 60 seconds of inactivity.
Back-UPS Sensitivity Settings
The Back-UPS detects and reacts to line voltage distortions by transferring to
battery backup power to protect connected equipment. In situations where
either the Back-UPS or the connected equipment is too sensitive for the input
voltage level it is necessary to adjust the transfer voltage.
- Connect the Back-UPS to a utility power source. Be sure the Back-UPS is turned off.
- Press and hold the POWER button for six seconds. The load capacity bar will flash on and off, to indicate the Back-UPS is in Program mode.
- Press the POWER button again to scroll through the menu options. The Back-UPS will beep to confirm the selection.
Refer to the table for an explanation of the transfer voltage sensitivity levels.
Generator Sensitivity | Default | Sensitive Loads |
---|---|---|
Low sensitivity 156-300 Vac
Use this setting with equipment that is
less sensitive to fluctuations in voltage
or waveform distortions.| Medium sensitivity (Default) 176-294 Vac
Use this setting under normal operating conditions.| High sensitivity 176-288
Vac
Use this setting when connected equipment is sensitive to any minor
fluctuations in voltage or waveform distortions.
Front Panel Buttons and Display Interface
Use the three buttons on the front panel of the Back-UPS and the display to
configure the Back-UPS.
Front panel
- MUTE button
- POWER button
- DISPLAY button
- Display
| On Line: The Back-UPS is supplying conditioned AC power to connected
equipment.
---|---
| Power Saving Function: The MASTER and CONTROLLED outlets are enabled. The
power saving feature is active when the master device goes into Standby or
Hibernation mode.
| Load Capacity: The load capacity percentage is indicated by the number of
load bar sections illuminated. Each bar represents 20% of the load capacity.
| Battery Charge: The battery charge level is indicated by the number of load
bar sections illuminated. When all five 1 blocks are illuminated, the Back-UPS
battery is fully charged. Each bar represents 20% of the battery charge
capacity.
| Overload: The equipment connected to the Back-UPS is drawing more power than
the voltage rating allows.
| Event: The event counter indicates the number of events that occurred to
cause the Back-UPS to switch to battery operation.
| In: Input voltage. Out: Output voltage.
| Automatic Voltage Regulation (AVR): The Back-UPS has AVR boost and trim that
automatically regulates high or low levels of input voltage without using
battery power. The Back-UPS also features AVR Bypass which temporarily
deactivates the AVR circuitry when the input voltage is within normal range.
This conserves battery power and helps to maximize battery life.
When illuminated, the Back-UPS is compensating for low input voltage.
When illuminated, the Back-UPS is compensating for high input voltage.
| System Events: An internal system event has occurred. The event number will
illuminate on the display. See “System Events” on page 7.
| Mute: An illuminated line through the icon indicates that the audible alarm
is disabled.
| Replace Battery: The battery is nearing the end of its service life. Replace
the battery.
| On Battery: The Back-UPS is supplying battery backup power to the connected
equipment, it will beep four times every 30 seconds.
Alarms and System Events
Audible Alerts
Four Beeps Every 30 Seconds| Back-UPS is running on battery. You should
consider saving any work in progress.
---|---
Continuous Beeping| Low battery condition and battery run-time is very low.
Promptly save any work in progress,
exit all open applications, and shut down the operating system.
Continuous tone| Battery Backup outputs are overloaded.
Chirps for 1 Minute every 5 hour| Battery is not able to pass the automatic
diagnostic test and should be replaced.
Event Icons
If these icons are illuminated… | This may be the problem. |
---|---|
The Back-UPS is operating on AC power, but is overloaded. Disconnect one of |
the devices connected
to the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no
longer overloaded and will
continue to operate normally.
| The Back-UPS is operating on battery power, but is overloaded. Disconnect
one of the devices connected to the Back-UPS. If the Overload icon stops
flashing, the Back-UPS is no longer overloaded and will continue to operate
normally.
| The Back-UPS is operating on AC power, but the battery is not functioning
properly.
Contact APC Customer Service to order a replacement battery.
| The Back-UPS is operating on battery power and the battery power is getting
low. Shut down all connected equipment to avoid losing unsaved data. When
possible, connect the Back-UPS to AC power to recharge the battery.
System Events
F01| On-Battery Overload| Turn the Back-UPS off. Disconnect non-essential
equipment from the Battery Backup outlets and then turn Back-UPS on.
---|---|---
F02| On-Battery Output Short| Turn the Back-UPS off. Disconnect non-essential
equipment from the Battery Backup outlets and then turn Back-UPS on.
F03| On-Battery Xcap Overload|
F04| Clamp Short|
F05| Charge Status|
F06| Relay Welding| Events F03-F09 are not user serviceable. Contact APC
Technical Support for assistance.
F07| Temperature|
F08| Fan Condition|
F09| Internal Event|
Function Button Quick-Reference
Function| Button| Timing(seconds)| UPSStatus|
Description
---|---|---|---|---
Power
POWER ON|
| 0.2| Off| Press the POWER ON/OFF button to turn on the Back-UPS and operate
on AC power. If AC input power is not available the Back-UPS will operate on
battery power.
---|---|---|---|---
POWER OFF|
| 2| On| Press the POWER ON/OFF button to turn off the Back-UPS. The Back-UPS will continue to provide surge protection to the Surge Protection outlets.
Display
Status Inquiry|
| 0.2| On| Verify the status or condition of the Back-UPS. The LCD will
illuminate for 60 seconds.
---|---|---|---|---
Power-Saving mode:
Continuous Illumination|
| 2| On| The LCD will illuminate and the Back-UPS will beep to confirm
Continuous Illumination mode is activated.
The LCD will extinguish and the Back-UPS will beep to confirm that
Power-Saving mode is activated. While in Power-Saving mode, the
LCD will illuminate if a button is pressed, then extinguish after 60
seconds of no activity.
Mute
Event Specific|
| 0.2| On| Disable any audible alarms caused by an event.
---|---|---|---|---
General Status Enable/Disable|
| 2| On| Enable or disable the audible alarms. The Mute icon will
illuminate and the Back-UPS will beep one time. The Mute feature will not
activate unless the Back-UPS is operating on battery power.
Sensitivity| | 6| Off| The Load Capacity icon will flash to indicate
the Back-UPS is in Program mode. Use the POWER ON/OFF button to scroll
through and select Low, Medium, and High sensitivity levels. The Back-UPS will
beep to confirm the selection. Refer to “Power Saving Feature” on page 5 for
details.
MASTER / CONTROLLED
outlet Enable/ Disable| ****
| 2| On| The leaf icon will extinguish to indicate the MASTER outlet feature
is disabled or illuminate to indicate the MASTER outlet feature is enabled.
The Back-UPS will beep once.
Master/Enable threshold calibration| ****
| 6| On| While calibrating the threshold setting, the device connected to the
MASTER outlet should be turned off or placed in Standby or Sleep mode. Once
the threshold setting has been selected the Power-Saving icon will flash 3
times and beep 3 times.
Self-Test (manual)|
| 6| On| The Back-UPS will run a test of the internal battery.
Note: This will happen automatically when the Back-UPS is turned on.
Event Reset| ****
| 0.2| On| When the Event screen is visible, press and hold DISPLAY, then
press the POWER button to clear the AC event counter.
Status Reset|
| 2| Event Detected| After an event has been identified, press the POWER ON/OFF button to remove the visual indication and return to standby status.
Troubleshooting
Problem| Possible Cause|
Corrective Action
---|---|---
Back-UPS will not turn on.| The Back-UPS is not connected to AC power.|
Be sure the Back-UPS is securely connected to a AC outlet.
The circuit breaker has been tripped.| Disconnect non-essential equipment from
the Back-UPS. Reset the circuit breaker. Re-connect equipment one item at a
time. If the circuit breaker trips again, disconnect the device that caused
the event.
The internal battery is not connected.| Connect the battery.
The AC input voltage is out of range.| Adjust the transfer voltage and
sensitivity range.
The Back-UPS does not provide power during a AC power outage.| Be
sure that essential equipment is not plugged into a SURGE ONLY outlet.|
Disconnect equipment from the SURGE ONLY outlet and connect to a BATTERY
BACKUP outlet.
The Back-UPS is operating on battery power, while connected to AC power.|
•The Back-UPS power cable is not securely connected to the wall outlet.
•The wall outlet is no longer receiving AC power.
•The circuit breaker has been tripped.| Be sure the plug is fully inserted
into the wall outlet. Be sure the wall outlet is receiving AC power by
checking it with another device.
The Back-UPS is running an automatic self test.| No action is necessary.
•The AC input voltage is out of range
•The frequency is out of range
•The waveform is distorted.| Adjust the transfer voltage and sensitivity
range.
The Back-UPS does not provide the expected amount of backup time.|
Battery Backup outlets may be experiencing an overload condition.|
Disconnect non-essential equipment from the Battery Backup outlets and connect
the equipment to SURGE ONLY outlets.
The battery was recently discharged due to a power outage and has not fully
recharged.| Charge the battery cartridge for 16 hours.
The battery has reached the end of its service life.| Replace the battery.
The REPLACE BATTERY indicator is illuminated.| The battery has
reached the end of its useful life.| Replace the battery.
The OVERLOAD indicator is illuminated.| The equipment connected to
the Back-UPS is drawing more power than the Back-UPS can provide.| Disconnect
non-essential equipment from the Battery Backup outlets and connect the
equipment to SURGE ONLY outlets.
The SYSTEM EVENT indicator is illuminated, all the front panel
indicators are flashing.| There is a detected internal fault.| Determine
which internal detected fault message is displayed by matching the number
displayed on the LCD with the corresponding Event Message (see System Events)
and contact APC Technical Support.
The Back-UPS is not supplying power to all of the outlets.| Power to the
CONTROLLED outlets has intentionally been turned off.| Confirm that the
correct peripherals are connected to CONTROLLED outlets. If this feature is
not desired, disable the Power-Saving MASTER and CONTROLLED outlets.
The C ONTROLLED outlets are not supplying power, even though the
ASTER device is not in sleep mode.| The MASTER outlet threshold may
be incorrectly set.| Adjust the threshold when the MASTER outlet signals the
CONTROLLED outlets to shut down.
Specifications
Model| BR1200G-RS|
BR1500G-RS
---|---|---
VA| 1200 VA| 1500 VA
Maximum Load| 720 W| 865 W
Nominal Input Voltage| 230 V
Online Input Voltage Range| 176 V- 294 V
Automatic Voltage Regulation| 188 V- 216 V +11.2% 252 V- 282 V -11.2%
Frequency Range| 50/60 Hz ± 1 Hz
On-battery wave shape| Step-approximated sine-wave
Typical Recharge Time| 8 hours
Transfer Time| 10 ms, maximum
Operating Temperature| 0 to 40 ºC (32 to 104 ºF)
Storage Temperature| -15 to 45 ºC (5 to 113 ºF)
Unit Dimensions| 30.1 × 11.2 × 39 cm (11.9 × 4.4 × 15.3 in)
Unit Weight| 12.8 kg (28.2 lbs)| 13.4 kg (29.5 lbs)
Interface| Serial, USB
On-Battery Runtime| Go to: www.apc.com
Replacement Battery| The battery cartridge typically lasts 3 to 6 years.
Environmental factors impact battery life. High temperatures, poor quality AC
power, and frequent, short deration discharges will shorten battery life. To
order replacement battery cartridge APCRBC124, refer to the APC Web site,
www.apc.com. Recycle used battery cartridges.
Humidity| 0 to 95% relative humidity, non-condensing
Pollution Degree| 2
Overvoltage category| II
Applicable power grid distribution system| TN Power system
Applicable standards| IEC 62040-1
International Protection Code| IP20
Back-UPS BR1200G-RS/BR1500G-RS Installation and Operation
APC Customer Support
Internet http://www.apc.com/support
Telephone Russia: 8 800 200-64-46 Ukraine: 0 800 502-72-20 Check Web site
listings for other countries.
Warranty
The standard warranty is two (2) years from the date of purchase. APC standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative. APC will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to APC. APC pays ground freight transportation costs to ship the replacement unit to the customer.
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
-
Review the TROUBLESHOOTING section of the manual to eliminate common problems.
-
If the problem persists, contact APC Customer Support through the APC Web site, www.apc.com.
a. Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.
b. Call APC Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the APC Web site for country specific instructions. -
Pack the unit properly to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty. For the UPS, always DISCONNECT THE BATTERY before shipping in compliance with U.S. Department of Transportation (DOT) and IATA regulations. The battery may remain in the unit.
-
Write the RMA# provided by Customer Support on the outside of the package.
-
Return the unit by insured, pre-paid carrier to the address provided by Customer Support.
© 2022 APC by Schneider Electric. APC, the APC logo, Back-UPS and PowerChute are owned by Schneider Electric Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.
EN 990-4712A
02/2022C
Documents / Resources
| APC
BR1200G-RS Power Saving Back-
UPS
[pdf] Instruction Manual
BR1200G-RS Power Saving Back-UPS, Power Saving Back-UPS, BR1200G-RS Saving
Back-UPS, Saving Back-UPS, UPS, BR1200G-RS, BR1500G-RS
---|---
References
- APC, a flagship brand of Schneider Electric - APC USA
- APC, a flagship brand of Schneider Electric - APC USA
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>