nVent 800 A Eriflex Flexibar Advanced

CATALOG NUMBER

FADV2MTC8X32X1

  • After intensive research, nVent presents ERIFLEX now proudly set a new gold standard in insulation flexible busbars: nVent ERIFLEX Flexibar Advanced. The new products are low-smoke halogen-free and flame-retardant while maintaining flexibility and
  • Reliability that our partners from nVent ERIFLEX Expect flexibility.
  • Compared to standard PVC insulation, nVent produces ERIFLEX Flexibar Advanced does not emit corrosive gases to relatively low smoke development according to ISO 5659-2. One low smoke development is characterized by Improving visibility for people who As a result, you can find the emergency exit more easily, and you allow emergency responders to view an emergency more clearly to assess. nVent ERIFLEX Flexibar Advanced means greater safety for people, less damage to electrical equipment and less environmental impact.
  • nVent ERIFLEX Flexibar Advanced contains according to IEC 60754-1 no halogens. This minimizes toxicity and it becomes an ideal product for use in indoor Spaces such as data centres, train stations and other places frequented by people, e.g. B. hospitals and
  • Schools. This also makes the use of nVent ERIFLEX easier Flexibar Advanced for certain applications, e.g. B. in submarines, electrical panels and other closed areas Environments requiring a low-emission solution are.
  • Apart from being halogen-free, nVent complies with ERIFLEX Flexibar Advanced and also meets the UL 94-V0 test standard. The section on the test procedure in which the flame retardancy is tested illustrates the self-extinguishing Characteristics. This outstanding feature of nVent ERIFLEX Flexibar Advanced is also available through the Limit oxygen index (LOI) is clear, which is 30%. At In the event of a fire, ERIFLEX Flexibar Advanced forms a limited amount of smoke and less damage to your electrical devices.

CERTIFICATIONS

nVent-800-A-Eriflex-Flexibar-Advanced-fig-2

FEATURES

  • Thin fins of tinned electrolytic copper formed into a stack
  • Full range from 19.5 mm² up to 1200 mm² and 125 A to 2800 A
  • Insulated by high-resistance, halogen-free, flame retardant and low smoke material with less than 20% contact with conductor for high flexibility
  • Easy to bend, fold or twist, improved flexibility in construction, shortening connections and less Ecological damage
  • Significantly smaller and more flexible than comparable cables in terms of current carrying capacity Better power density than cables with lower current displacement ratio Connections are made by punching and screwing directly through the copper fins or by clamping at the end of the nVent ERIFLEX Flexible.
  • No need for cable lugs, reducing installation time and improving vibration resistance Weight savings and material savings compared to wire alternatives Reduces overall installation costs
  • Traceability codes and designated item numbers are located on the product.
  • Conforms to NF EN 45545 obtaining an HL3 classification for chapters R22 and R23 100% production dielectric tested RoHS compliant
  • Tinned copper allows for copper or aluminium conductor connections.
  • Can also be made with other colours upon request (usually with an orange cover for the battery connector) Compliant to ISO 6469-1 (Electrically propelled road vehicles – Part 1: rechargeable energy storage system) – Section 6.2.2 Vibrations.

PRODUCT FEATURES

  • Article Number: 534028
  • Rated current for typical application: 800 A
  • Typical Application Current Rating, IEC: 800 A
  • Length: 2000mm
  • Finish: Tin Plated
  • Material: Copper; Thermoplastic elastomer
  • Dielectric Strength: 20
  • Flammability Rating: UL® 94V-0
  • Halogen Free Rating: UL® 2885; IEC® 60754-1; IEC® 62821-1
  • Low Smoke Rating: IEC® 61034-2; ISO 5659-2; UL® 2885
  • Smoke, Toxicity and Acidity Rating: IEC® 60754-2
  • UV Resistance Rating: UL® 854; UL® 2556
  • Insulation Elongation: 500 %
  • Insulation Thickness: 1,8 mm
  • Max Working Voltage, EN 50264-3-1: 6000 V
  • Max Working Voltage, UL/CSA/IEC: 1000 V; 1500 V
  • Working Temperature: −50 bis 115 °C
  • Certification Details: UL® 67; UL® 758
  • Complies With: IEC® 60695-2-11 (Glow Wire Test 960 °C); IEC® 61439,1; IEC® 61439,1 Class II
  • ΔT 40 K: 770 A
  • ΔT 50 K: 860 A
  • ΔT 60 K: 943 A
  • Conducting Layers: 8
  • A: 32 mm
  • B: 1 mm
  • Cross Section: 256 mm²
  • 2 Bar Current Coefficient: 1,72
  • 3 Bar Current Coefficient: 2,25
  • Unit Weight: 5,1 kg

ADDITIONAL PRODUCT DETAILS

  • ALLOWABLE CURRENT VALUES: This table shows the temperature increase with the respective current strength and the corresponding cross-section. This calculation does not take into account the heat given off by the switching device.
  • ΔT = conductor temperature – the internal temperature of the control cabinet.
  • Additional current carrying capacity values ​​can be found in the technical documentation.

DIAGRAMS

nVent-800-A-Eriflex-Flexibar-Advanced-fig-3

WARNING

  • nVent products must be used under nVent’s product information sheets and training materials installed and used. Information sheets are available at www.nVent.com and from your nVent dealer.
  • Customer Service Representative. Improper installation, misuse, misapplication or other acts inconsistent with nVent’s instructions and warnings may result in malfunctions, equipment damage, serious injury or result in death and/or cancellation of the guarantee.

CONTACT

Nordamerika

  • +1.800.753.9221
  • Option 1 – Customer Care
  • Option 2 – Technical Support

Europa

  • Netherlands:
  • +31 800-0200135
  • France:
  • +33 800 901 793

Europa

  • Germany:
  • 800 1890272
  • Other Countries:
  • +31 13 5835404

APAC

  • Shanghai:
  • + 86 21 2412 1618/19
  • Sydney:
  • +61 2 9751 8500

© 2023 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners. nVent reserves the right to change specifications without notice.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals