ATAG Q 25SR QR-Series Central Heating Boiler Instruction Manual

June 9, 2024
1-800-Innovations

Q 25SR QR-Series Central Heating Boiler

Operating instructions Installation & Servicing Instructions

Boiler Q 25SR Q 38SR Q 51SR Q 60SR
Q 25CR Q 38CR Q 51CR
CE PIN 0063BQ3021

QR-Series

8G.51.63.02 / 01.22 Changes reserved.

Explanations of symbols and signs on the Control Tower display

DHW mode selection
Service connection Quit menu Reset
On/Off switch

Heating operation mode selection

(Commissioning function when pressing > 3 sec.

Auto

For service purposes only)

INFO PROG

1

2 No.

°

ECO °

Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx
0 4 8 12 16 20 24

Reset

ESC

OK

l 0

Info button
Confirm Manual mode
(Deaeration mode when pressing > 3 sec.)
Chimney sweeper mode (For service purposes only)

Heat to comfort setpoint value Heat to reduced setpoint value Heat to frost Protection setpoint value* Process running – please wait Burner in operation Fault messages INFO Info level activated PROG Programming active ECO Heating temporarily switched off; ECO function active Holiday function active 1 2 Reference to heating circuit Manual mode / chimney sweeper mode No. Number of operating line (parameter number)

  • Functions only in combination with QAA55. NOT with OT / On-off.

1

2 No.

°°

Operating Instructions ATAG QR-Series

2

Content Operating Instructions
1 Introduction ……………………………………………………………………………………………………………………4 2 Safety …………………………………………………………………………………………………………………………..5 3 Description of the boiler …………………………………………………………………………………………………..5 4 Display and keypad…………………………………………………………………………………………………………6 5 Replenishing the central heating system ……………………………………………………………………………8 6 Main functions of the control panel ……………………………………………………………………………………9 7 Turning the boiler off ……………………………………………………………………………………………………..12 8 Error, maintenance and warranty …………………………………………………………………………………….13 9 Disposal of the product ………………………………………………………………………………………………….13
Important! It is in your own interest that we should know that you have an ATAG boiler. Please fill out the warranty card completely and send it back to us. Then we can be fully at your service.
Content Installation & Servicing Instructions
1 Introduction ………………………………………………………………………………………………………………….16 2 Rules …………………………………………………………………………………………………………………………16 3 Scope of supply…………………………………………………………………………………………………………….18 4 Description of the boiler …………………………………………………………………………………………………18 5 Mounting the boiler………………………………………………………………………………………………………..20 6 Connecting the boiler …………………………………………………………………………………………………….20 7 External hot water cylinders ……………………………………………………………………………………………35 8 Electrical connection ……………………………………………………………………………………………………..36 9 Boiler controls ………………………………………………………………………………………………………………38 10 Commissioning the boiler……………………………………………………………………………………………….64 11 Maintenance…………………………………………………………………………………………………………………89 12 Error indication ……………………………………………………………………………………………………………..72
Annex A Technical specifications ……………………………………………………………………………………….74 Annex B System water additives ………………………………………………………………………………………..76 Annex C Dimensions ………………………………………………………………………………………………………..77 Annex D Resistance table sensors……………………………………………………………………………………..79 Annex E.1 Installation examples …………………………………………………………………………………………..80 Annex E.2 Clip-In module Starter Set / Expansion…………………………………………………………………..83 Annex F Declaration of Conformity …………………………………………………………………………………….90 Benchmark Checklist…………………………………………………………………………………………………………….82 Service Record…………………………………………………………………………………………………………………….83
3

Operating Instructions ATAG QR-Series

1 Introduction
These operating instructions describe the functioning and the operating of the ATAG Q boilers.This manual is for the end user. For installation and servicing there is an installation & servicing instructions manual for the installer. (pag. 16).
Read this manual fully before operating the boiler. In case of doubt or errors contact your installer.
ATAG Commercial UK reserves the right to change the specifications and dimensions without prior notice.
Work on the boiler must be carried out by a competent person, (Ref: Gas Safe Register) using correctly calibrated instruments with current test certification.
When replacing parts use only ATAG Service parts.
Contact details for ATAG Heating UK Ltd can be found on the back page of this manual.
The Benchmark Scheme ATAG Heating UK Ltd is a licensed member of the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing to optimise safety, efficiency and performance. Benchmark is managed and promoted by the Heating and Hotwater Industry Council. For more information visit www.centralheating.co.uk
Please ensure that the installer has fully completed the Benchmark Checklist on the inside back pages of the installation instructions supplied with the product and that you have signed it to say that you have received a full and clear explanation of its operation. The installer is legally required to complete a commissioning checklist as a means of complying with the appropriate Building Regulations (England and Wales).
All installations must be notified to Local Area Building Control either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer who should, on receipt, write the Notification Number on the Benchmark Checklist.
This product should be serviced regularly to optimise its safety, efficiency and performance. The service engineer should complete the relevant Service Record on the Benchmark Checklist after each service.
The Benchmark Checklist may be required in the event of any warranty work and as supporting documentation relating to home improvements in the optional documents section of the Home Information Pack.
4

Operating Instructions ATAG QR-Series

2

Safety

Work on the installation should only be carried out by qualified personnel with calibrated equipment. When replacing parts, only ATAG Service components may be used.

The device may be operated only by authorized persons who have been instructed on the operation and use of the device. Improper use may cause damage to the device and / or to the connected installation.

ATAG do not recommend that children play with the appliance at any time.

The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.

In case you smell gas:
– No naked flames! Do not smoke! – Do not operate electrical switches for lights or any other appliance. – Do not use a telephone – Turn off gas supply at meter – Open windows and doors – Notify any persons in the building and leave the building at once. – Call Gas company or installer only when outside the building

Protection for corrosion
Do not use any sprays, chlorine containing agents, solvents, paint etc. around the boiler or around the air intake supply entrance of the boiler. These substances have negative influences on the boiler and can lead to corrosion resulting in failure of the boiler.

Checking the water pressure
Check the water pressure in the central heating installation regularly. Use only potable water for filling. Additives only after clearance by ATAG. Contact your installer in case of doubt.

3

Description of the boiler

Operating Instructions ATAG QR-Series

Room sealed boiler The boiler retreives its combustion air from outside then discharges the flue gasses to the outside.
Condensing Retrieves heat from the flue gasses. Water condensates on the heat exchanger.
Modulating Higher or lower burning according to the heat demand.
Stainless steel Super solid kind of steel which keeps its quality for life. It will not rust or erode in contrast to composition materials, like aluminium.

The ATAG QR boiler is a room sealed, condensing and modulating central heating boiler, with or without an integrated hot water facility. This boiler is also approved for use as an open flued boiler according to flue category B23 and B33.
The boiler is provided with a compact stainless steel heat exchanger with smooth tubes. A well thought out principal using durable materials. The boiler burns gas for supplying warmth. The heat is transferred in the heat exchanger to the water in the central heating system. By cooling down the flue gasses condensate is formed. This results in high efficiency. The condensate, which has no effect on the heat exchanger and the function of the boiler, is drained through an internal siphon.
The boiler is provided with an intelligent control system (CMS Control Management System). The boiler anticipates the heat demand of the central heating system or the hot water facility.
When an outside sensor is connected to the boiler, the boiler works weather dependantly. This means that the boiler control measures the outside temperature and flow temperature. With this data the boiler calculates the optimal flow temperature for the installation.

5

4 Display and keypad

The boiler is equipped with a display and buttons on the front (behind the door).

The meaning of the keys and symbols are briefly described below.

Auto
A On/Off switch

B Back button (ESC)

INFO PROG

ECO

C Room temperature control

M

1

2 No.

°°

I

button

Xxxxxxxxxxxxxxxxxxxxx

D Confirmation button (OK)

L

Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx

E Function button for manual operation

0 4 8 12 16 20 24

F Chimney sweep function

G button

G Info button

H Reset button

H A

Reset

ESC

OK

I Operation mode button for

heating circuit(s)*

L Display

M Operating mode button for

B C DE F

DHW * The operating mode button

may be locked (Setting on

the OpenTherm thermostat)

The display shows the boiler water temperature in °C as standard and the indicators under the programs that are switched on.
Meaning of the symbols on the display:

Heat to comfort setpoint value*

Heat to reduced setpoint value*

Heat to frost Protection setpoint value*

Process running – please wait

Burner in operation

Fault messages

INFO

Info level activated

PROG

Programming active

ECO

Heating temporarily switched off; ECO function active

Holiday function active

1

2

Reference to heating circuit

Manual mode / chimney sweeper mode

No.

Number of operating line (parameter number)

  • Only works in combination with QAA55. NOT with OT / On-off thermostat In software version 5.1.0, “Operating mode button locked” is displayed when one of these buttons is pressed

Operating Instructions ATAG QR-Series

6

4.1 Boiler controls
Operating mode button for DHW (M) For switching on the DHW preparation (Bar under the water tap in the display) If the boiler control is configured via OpenTherm, no bars are visible. DHW timer program via external controller is leading
Operation mode button for heating circuit(s) (I) (Only works in combination with QAA55, NOT with OT/On-Off) For setting 4 different operating modes for heating:

Automatic clock: Automatic operation according to timer program Bar in the display visible under “AUTO” by OpenTherm

Sun 24 hr:

Heating at comfort target value

Moon 24 hr:

Heating at reduced value

Protection mode: Heating switched off, frost protection active
Information button (G) Retrieval of the following information, without influence on the control processes: Temperatures, operating condition of the heating facility/DHW, error reports
Room temperature control button (C) With this rotating button, settings can be selected and changed during programming and changing the room comfort temperature
Confirmation button OK (D) Back button ESC (B) These two buttons are needed in combination with the large rotating button (- +) for the programming and configuration of the control unit. Settings, which cannot be changed through the control elements, are provided by means of programming. By pushing the ESC button you always go one step backward, whereby modified values are not taken over. To reach the next operating level, or to store the changed values, you must push the OK button.
Manual operation function button (E) By pushing this button, the control unit is set to manual mode, whereby all pumps are running, the mixer is no longer controlled and the burner is set to 60°C (Indicated by the spanner symbol). Hold down for 3 sec. to start venting program.
Chimney sweep function button (F) MAY ONLY TO BE OPERATED BY A QUALIFIED INSTALLER! Push this button shortly, to put the boiler in the operating mode for measuring emissions; renewed pushing of the button deactivates this function, or it is automatically deactivated after 15 minutes (indicated by the spanner symbol).
Reset button (H) By pressing this button shortly, the locked condition of the burner is deactivated.
On/Off switch (A) Position 0: The entire facility and all connected electrical components are without electrical power. A protection against frost is not ensured. Position I: The entire facility and all connected electrical components are ready for operation.
7

Operating Instructions ATAG QR-Series

Filling and de-aeration of the ATAG QR and the heating installation The heating installation is filled according to the standard method. The installation must have been deaerated, both on the heating and the warm water side. The water pressure can be read off in bar, either on the analog pressure indicator or via the Info button. As soon as the heating installation has been filled and de-aerated, the boiler will be ready for operation.
During the initial commissioning or after a power failure, the control system starts the automatic de-aeration program. This function runs for approximately 16 minutes and stops automatically.

5 Replenishing the central heating system

3 sec.

The central heating installation needs to be filled with potable (drinking) water. For topping up the installation you use the filling loop according to the following procedure: (If in any doubt please contact your dealer)
1 Connect the filling loop to the cold water tap; 2 Slowly open the filling loop; 3 Open the cold water tap; 4 Fill up slowly to 1.5 to 1.7 bar:
Press I key and turn the knob to “water pressure”. Value on the display increases; 5 Close cold water tap; 6 Check whether the automatic de-aeration program has been running. If not yet de-aerated: Hold down the E button for more than 3 seconds. This function runs for approximately 16 minutes; 7 De- aerate the complete installation, start at the lowest point; 8 Check the waterpressure and if necessary top it up to 1,5 to 1,7 bar; 0 Close the filling loop.

After completion of the de-aeration program, the boiler will operate again.
Check the water pressure regularly and top up the installation when necessary. The working pressure of the installation should be between 1.5 and 1.7 bar when the installation is cold. (Note: Before topping up the pressure, first fill the hose with water, which prevents the entry of air into the heating system).
It can take a while before all air has dis-appeared from a filled installation. Especially in the first week noises can be heard which indicate the presence of air. The de-aeration of the boiler will make this air disappear, which means the water pressure will reduce during this period and therefore topping up with water will be necessary to adjust the flow water temperature.

Operating Instructions ATAG QR-Series

8

6
Button
Button

Main functions of the control panel

Action

Procedure

Setting up the required room temperature

HC2 jointly with HC1
Turn the rotating button left or right Turn the rotating button again for storing with OK button or wait for 5 sec. or push

Setting the required room temperature
for HC1 or HC2

or
2nd HC independent of HC1
Turn rotating button left/right Then push OK Turn rotating button left/right Save with OK button or wait for 5 sec. or push

Switching warm water operations ON or OFF

Push button

Factory setting

Change operating mode

1 x short push of button and then once more, short push of button

once more, short push of button

Control stop function
Action
Display of various information

1 x push button (> 3 sec) push button once more (> 3 sec)
Procedure
1 x push button push button again push button again

Push button

Operating mode according to target values that are set manually
Change of the factory setting for boiler temperature

short push of button
short push of button short push of button Rotating button turn -/+ short push of button short push of button short push of button

De-aeration function 1 x push button (> 3 sec) push button once more (> 3 sec)

Activation of chimney sweep function

Push button (> 3 sec) push button once more (> 3 sec)

Display / Function
comfort target value with blinking temperature display blinking temperature display in steps of 0.5° centigrade, from 10.0 to 30°C
Comfort value active Comfort value not active – Basic display appears after 3 sec.
Select heating circuit Heating circuit active blinking temperature display in steps of 0.5° centigrade, from 10.0 to 30°C Comfort target value active Comfort target value not active – Basic display appears after 3 sec.

Only works in combination with QAA55, NOT with OT Works with on / off controller via H8 / H9

Warm water operation ON / OFF
(segmented bar under symbol for warm water visible/invisible) – ON: Warm water preparation according to switching program – OFF: No warm water preparation – Safety function active When using OpenTherm, “operating mode button is locked” is displayed Safety functions remain active!

Automatic operating mode ON, with:
– heating operation according to timer program – Temperature target values according to heating program – Safety function active
– Summer/Winter – automatic switching active – ECO functions active (segmented bar under corresponding symbol visible)
Continuous COMFORT heating ON, with:
– Heating operation without timer program, at comfort target value – Safety function active
Continuous REDUCED heating ON, with:
– Heating operation without timer program, at reduced target value – Safety function active
– Summer/Winter – automatic switching active – ECO functions active Automatic safety mode ON, with:
– Heating operations switched off – Temperature according to frost protection value – Safety function active When using OpenTherm, “operating mode button is locked” is displayed Safety functions remain active!

304: Control stop function Basic display appears after 3 sec.

Set target value

Display / Function

INFO section is displayed

– Boiler status

– Room temperature

– Room temperature minimum

– Warm water status

– Room temperature maximum

– Status heating circuit 1 – Outdoor temperature

– Status heating circuit 2 – Minimum outdoor temperature

– Maximum outdoor temperature

– Time / date – Water temperature 1

– Error message

– Boiler temperature

– Maintenance report

– Flow temperature

(Display of the information lines depends on the configuration)

Back to basic display; INFO segment is suppressed

Manual operating mode ON (spanner symbol is visible) – Heating operations at preset boiler temperature (factory setting = 60°C)

301: Manual operation mode
operation? Blinking temperature display Set required target value

Set target value for manual

Boiler status Manual operating mode OFF (spanner symbol disappears)

312: De-aeration function ON De-aeration function OFF
Chimney sweep function ON Chimney sweep function OFF

DHW timer program via external
controller is leading
Only works in combination with QAA55, NOT with OT Works with on / off controller via H8 / H9

Operating Instructions ATAG QR-Series

RESET

Short-term reduction of room temperature at QAA75 / 78
Reset button

Push button push button again

Heating at reduced target value Heating at comfort target value

Push button (< 3 sec.) push button again > 3 sec.

Facility is manually locked, unreleased equipment is unlocked, alarm bell disappears

= Confirmation

= Abort or back to basic display

MAY ONLY BE OPERATED BY A QUALIFIED INSTALLER!

Only works in combination with QAA55, NOT with
OT/On-Off
9

6.1 Parameters end users

Basic display “Boiler temperature” – Push OK button once – Use +- rotating button for selecting for instance “Drinking water menu” – Push OK button once – Use +- rotating button, for instance in the drinking water menu, for selecting “Parameter no. 1612 – Reduced target value” – Push OK button once – Use +- rotating button to change the currently set value – Push OK button once -> the value is stored – Push 2 x ESC to return to the basic display “Boiler temperature . .”
Time programs are not active when using an OpenTherm thermostat, however, they are active when switching on and off via H8 / H9

Menu Time of day and date Operator section Time program HC 1
Time program HC 2 (When activated)
Time program 3/ HC3
Time program 4/ DHW

Line no. 1 2 3 20

Selection possibilities Hours / Minutes Day / Month Year Language

500

Preselection

501

Mo-Su: 1. Phase On

502

Mo-Su: 1. Phase Off

503

Mo-Su: 2. Phase On

504

Mo-Su: 2. Phase Off

505

Mo-Su: 3. Phase On

506

Mo-Su: 3. Phase Off

516

Default values

520

Preselection

521

Mo-Su: 1. Phase On

522

Mo-Su: 1. Phase Off

523

Mo-Su: 2. Phase On

524

Mo-Su: 2. Phase Off

525

Mo-Su: 3. Phase On

526

Mo-Su: 3. Phase Off

536

Default values

540

Preselection

541

Mo-Su: 1. Phase On

542

Mo-Su: 1. Phase Off

543

Mo-Su: 2. Phase On

544

Mo-Su: 2. Phase Off

545

Mo-Su: 3. Phase On

546

Mo-Su: 3. Phase Off

556

Default values

560

Preselection

561

Mo-Su: 1. Phase On

562

Mo-Su: 1. Phase Off

563

Mo-Su: 2. Phase On

564

Mo-Su: 2. Phase Off

565

Mo-Su: 3. Phase On

566

Mo-Su: 3. Phase Off

576

Default values

Unit hh:mm dd:MM
yyyy –
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm –

Min.

Max

00:00

23.59

01.01

31.12.

2004

2099

English, German, French, Italian, Danish, Dutch, Spanish, Czech, Slovenian, Turkish

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Factory setting –.—.—.–
German

Mo-Su 06:00 22:00 –.—.—.—.–
No Mo-Su 06:00 22:00
–.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No

Only works in combination with QAA55, NOT with OT Works with on / off controller via H8 / H9
Only if parameter 6359 is active

Operating Instructions ATAG QR-Series

10

Parameters end users

Menu Time program 5
Holidays HC1
Holidays HC2 (When activated) HC1
HC 2 (When activated) DHW Swimming pool Boiler Error

Line no. 600 601 602 603 604 605 606 616 641 642 643 648 651 652 653 658 710 712 714 720 730 1010 1012 1014 1020 1030 1600 1610 1612 2055 2056 2214 6700 6705 6706

Selection possibilities Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Period Start Day / Month Periode End Day / Month Operating level Preselection Period Start Day / Month Periode End Day / Month Operating level Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Summer/winter heating limit Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Summer/winter heating limit Operating mode Nominal setpoint Reduced setpoint Pool setpoint solar heating Pool sepoint boiler heating Setpoint manual control Error message SW Diagnose Code Burner ctrl phase lockout pos

Unit –
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
tt.MM tt.MM tt.MM tt.MM °C °C °C °C °C °C °C °C °C °C °C °C °C –

Min.

Max

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Period 1, 2, 3, 4, 5, 6, 7, 8

01.01

31.12

01.01

31.12

Frost protection, Reduced

Frost protection

Period 1, 2, 3, 4, 5, 6, 7, 8

01.01

31.12

01.01

31.12

Frost protection, Reduced

Frost protection

Value from Line no. 712

35

4

Value from Line no. 710

4

Value from Line no. 712

0.10

4.00

—/8

30

Value from Line no. 1012

35

4

Value from Line no. 1010

4

Value from Line no. 1012

0.10

4.00

—/8

30

Off, On, Eco

Value from Line no. 1612

80

8

Value from Line no. 1610

8

80

8

80

10

90

Factory setting Mo-Su 06:00 22:00 –.—.—.—.-No Period 1 –.—.–
Frost protection Period 1 –.—.–
Frost protection 20.0 16.0 10.0 1.50 20 20.0 16.0 10.0 0.8 0 Off 55 40 26 22 50
Indication only Indication only Indication only

Only works in combination
with QAA55, NOT with OT Works with on / off controller via H8 / H9

Operating Instructions ATAG QR-Series

11

6.2 Display of information

Display of information The information button can be used for displaying different information.

Possible information values Depending on the type of installation, its configuration and the operating condition, individual lines of information may not be visible.

AUTO

Room temperature

0

4

8

12

16

20

24

– Error message ( or -symbol) – Maintenance report – Room temperature – Room temperature minimum – Room temperature maximum – Boiler temperature – Outdoor temperature – Outdoor temperature minimum – Outdoor temperature maximum – DHW temperature 1 – Boiler status – DHW status – Heating circuit status 1/2 – Time / date – Customer service telephone

7

Turning the boiler off

In case of holidays, for example: Make sure there is no heat demand: set the room thermostat low*.
DHW (Hot water) Switch off DHW program: Press the DHW function button (M) until the lowest value is reached. The beam (bar) under the tap disappears. Switching on works in reverse order.
Heating (Only works in combination with QAA55, NOT with OT/On-Off) Switch off the heating program: Press the heating mode key (I) until the bar is at the far right of the display = frost protection Switching on works in reverse order.
In case of work on the central heating system: Make sure there is no heat demand: no open hot water tap and room thermostat low. Set the main switch to 0 and pull the plug out of the wall socket. When the boiler is being drained one should take into account that a part of the heating water will remain in the boiler. When risk of frost arises one should take care that the remaining central heating water in the boiler does not freeze.

Operating Instructions ATAG QR-Series

12

8 Error, maintenance and warranty

AUTO

Error

30:Flow temperature 1

Text3

Text4

0

4

8

A1U2TO 16

20

24

Maintenance

3:Maintenance interval

Text3

Text4

0

4

8

12

16

20

24

Error message / Maintenance In exceptional cases, one of the following symbols will be displayed in the default display:
Error messages An error has been detected in the boiler, when this symbol is shown. Detailed information is available by pushing the information button. With On / Off thermostat: if the thermostat is OFF (contact open), the symbol will be displayed. This does not affect the operation. No intervention required.
Maintenance or special mode When this symbol is displayed, then a maintenance report is displayed or the boiler is in special mode. Detailed information is available by pushing the information button.
If you discover any leaks from the boiler contact your installer.
The casing of the boiler consists of metal and plastic parts which can be cleaned with a normal non abrasive cleaning agent.
You can find the warranty conditions in the warranty card which is supplied with the boiler.

9 Disposal of the product
This product should be handed in at a designated collection point, e.g. by handing it in at a duly authorized reseller when purchasing a similar product, or at an authorized collection site for recycling products wich contains electrical and electronic equipment (EEE) and batteries and accumulators. Because of the potentially hazardous substances that usually accompany EEE, improper handling of this type of waste could have a possible impact on the environment and human health. Your cooperation in the proper disposal of this product will contribute to the effective usage of natural resources. For more information on recycling this product, please contact your city office, local waste disposal facilities, official service for chemical waste, landfill site, or your supplier.

Operating Instructions ATAG QR-Series

13

Explanations of symbols and signs on the Control Tower display

DHW mode selection
Service connection Quit menu Reset
On/Off switch

Heating operation mode selection

(Commissioning function when pressing > 3 sec.

Auto

For service purposes only)

INFO PROG 1 2 No.

ECO

°°

Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx
0 4 8 12 16 20 24

Reset

ESC

OK

l 0

Info button
Confirm Manual mode
(Deaeration mode when pressing > 3 sec.)
Chimney sweeper mode (For service purposes only)

Heat to comfort setpoint value Heat to reduced setpoint value Heat to frost Protection setpoint value* Process running – please wait Burner in operation Fault messages INFO Info level activated PROG Programming active ECO Heating temporarily switched off; ECO function active Holiday function active 1 2 Reference to heating circuit Manual mode / chimney sweeper mode No. Number of operating line (parameter number)

  • Only works in combination with QAA55. NOT with OT / On-off thermostat

1

2 No.

°°

Installation & Servicing Instructions ATAG QR-Series

14

Content
1 Introduction ………………………………………………………………………………………………………………….16 2 Rules …………………………………………………………………………………………………………………………16 3 Scope of the supply……………………………………………………………………………………………………….18 4 Description of the boiler …………………………………………………………………………………………………18 5 Mounting the boiler………………………………………………………………………………………………………..20 6 Connecting the boiler …………………………………………………………………………………………………….21
6.1 Central heating system ………………………………………………………………………………………..21 6.2 Expansion vessel ………………………………………………………………………………………………..23 6.3 Underfloor heating system (plastic pipes)……………………………………………………………….24 6.4 Water quality ……………………………………………………………………………………………………… 24 6.5 Gas connection …………………………………………………………………………………………………..26 6.6 Hot water supply …………………………………………………………………………………………………26 6.7 Condensation drain pipe ………………………………………………………………………………………27 6.8 Flue gas exhaust system and air supply system ……………………………………………………..29 6.8.1 Dimensions of the flue gas and air intake duct ………………………………………………………..34 7 External hot water cylinders ……………………………………………………………………………………………35 8 Electrical connection ……………………………………………………………………………………………………..36 9 Boiler controls ………………………………………………………………………………………………………………38 9.1 Explanation of the function keys ……………………………………………………………………………38 9.2 Main functions of the control panel ………………………………………………………………………..40 9.3 Parameters end users………………………………………………………………………………………….41 9.4 Parameters technician …………………………………………………………………………………………43 9.5 Menu: Heating circuits …………………………………………………………………………………………63 10 Commissioning the boiler……………………………………………………………………………………………….64 10.1 Preparations for first use………………………………………………………………………………………65 10.2 Hot water supply …………………………………………………………………………………………………65 10.3 The O2 / CO2 check on full load (Step 1/3)………………………………………………………………66 10.4 The O2 / CO2 check on low load (Step 2/3)……………………………………………………………..67 10.5 Adjustment on the gas valve (Step 3/3) ………………………………………………………………….68 11 Maintenance…………………………………………………………………………………………………………………69 11.1 Maintenance activities………………………………………………………………………………………….69 11.2 Maintenance frequency………………………………………………………………………………………..71 11.3 Warranty…………………………………………………………………………………………………………….71 12 Error indication ……………………………………………………………………………………………………………..72
Annex A Technical specifications ……………………………………………………………………………………….74 Annex B System water additives ………………………………………………………………………………………..76 Annex C Dimensions ………………………………………………………………………………………………………..77 Annex D Resistance table sensors……………………………………………………………………………………..79 Annex E.1 Installation examples …………………………………………………………………………………………..80 Annex E.2 Clip-In module Starter Set / Expansion…………………………………………………………………..83 Annex F Declaration of Conformity …………………………………………………………………………………….90
Benchmark Checklist…………………………………………………………………………………………………………….92 Service Record…………………………………………………………………………………………………………………….93
Work on the installation should only be carried out by qualified personnel with calibrated equipment and appropriate tools.
15

Installation & Servicing Instructions ATAG QR-Series

1

Introduction

These instructions describe the functioning, installation, use and primary maintenance of ATAG QR series boilers for the United Kingdom.

These instructions are intended for the use by Gas Safe Register approved contractors in connection with the installation and putting into operation of ATAG boilers. It is advisable to read these instructions thoroughly, well in advance of installation. ATAG is not liable for the consequences of mistakes or shortcomings which have found their way into the installation instructions or user’s manual. Further, ATAG reserves the right to alter its products without prior notification.

When delivering the unit, give the customer clear instructions concerning its use; present the customer with the user’s manual and card.

Each unit is fitted with an data plate. Consult the details on this plate to verify whether the unit is compliant with its intended location, e.g.: gas type, power source and exhaust classification.

On completion of the installation the installer or commissioning engineer must fill out and complete the Benchmark Commissioning Checklist found on page 92 of this manual and hand this to the customer for future record keeping. The Benchmark Service Record must also be completed by the service agent following each service call, and return to the customer. A copy of the Benchmark Commissioning Checklist must be returned to ATAG Commercial UK, along with the warranty registration card to register the appliance for the standard warranty benefits.

Relevant Installation, Service and User manuals:

– ATAG Cascade

Hydraulic cascade system

– ATAG Duopass

Flue system individual

2

Rules

Installation & Servicing Instructions ATAG QR-Series

The following regulations apply to installation of ATAG QR series boilers:
Legislation and Regulations Gas Safety (Installation and Use). All gas appliances must by law, be installed by a competent person, eg. Members of Gas Safe Register and in accordance with the current Gas Safety Regulation. Failure to install appliance correctly could lead to prosecution. All Gas Safe Register approved contractors carry a Gas Safe Register ID Card and have a registration number. You can call Gas Safe Register direct on 01256 372300
British Standards BS5440 parts 1 & 2 – Installation & Maintenance of Flues & Ventilation for gas appliances not exceeding 70kW input BS6644 – Specification for the Installation & Maintenance of hot water boilers of rated inputs between 70kW & 1.8MW BS 6798 – Installation of gas fired hot water boilers of rated input not exceeding 70 kW. BS6891 – Specification for the installation and maintenance of low pressure gas installation pipework of up to 35 mm (R11/4) BS 7074 – Application, selection and installation of expansion vessels and ancillary equipment for sealed water systems. BS 8552 – Sampling & Monitoring of Water from Building Services Closed Systems BS EN 60335 Pt1 – Safety of household and similar electrical appliances. General requirements BS EN 12828 – Heating Systems in Buildings – Design for Water Based Heating Systems) BS EN 12831 – Heating Systems in buildings: Method for calculation of the design heat load. BS EN 14336 – Heating Systems in buildings: Installation and commissioning of water based heating systems.
16

IGEM Documents IGE/UP/1&1A – Strength testing, tightness testing and direct purging of small, low pressure commercial Natural Gas installations. IGE/UP/2 – Installation pipework on commercial premises IGE/UP/10 – Installation of flued gas appliances – applicable to light commercial installations
UK Regulation Clean Air Act 1993 – applicable to light commercial installations IEE Regulations Building Regulations Gas Safety (Installation & Use) Regulations
Other Guidance BSRIA Documents BG29/2012 – (Pre-commissioning & Cleaning of Pipework Systems) BG50/2013 – Water Treatment for Closed Heating & Cooling Systems) ICOM document ‘Water Treatment & Conditioning of Commercial Heating Systems’
In addition to the above regulations this appliance must be installed in compliance with the current IEE Regulations, the Building Standards (Scotland Consolidation) Regulations. Regulations and bye laws of the Local Water Authority and the Current Health and Safety Regulation.
The Benchmark Scheme Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information.
The current, Electricity at Work Regulation must be complied with and also be in accordance with the relevant and current editions of the British Standards. The ATAG QR boiler is a certified appliance and must not be modified or installed in any way contrary to this Installation Manual. Manufacturers instructions must not be taken in any way as overriding statutory obligations. The ATAG QR is a central heating unit with an optional integrated hot water function. These units must be connected according to these instructions and all installation norms in respect of the part of the unit to be connected.
17

Installation & Servicing Instructions ATAG QR-Series

The device may be operated only by authorized persons who have been instructed on the operation and use of the device. Improper use may cause damage to the device and / or to the connected installation.
The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instructions.
ATAG do not recommend that children play with the appliance at any time.
Observe the following rules of safety: – All work on the unit must take place in a dry environment. – ATAG units may never be in operation without their housing, except in connection
with maintenance or adjustments (see Chapter 10 and 11). – Never allow electrical or electronic components to come into contact with water.
Carry out the following tasks in connection with maintenance, etc. to an already-installed unit:
– Shut down all programmes – Close the gas tap – Remove the plug from the wall socket – Close the stop cock of the unit’s intake connection
Take note of the following when maintenance or adjustments are needed: – The unit must be able to function during these activities; for this reason, the unit’s
supply voltage, gas pressure and water pressure must be maintained. Ensure that these is not a source of potential danger during these activities.
Following maintenance or other activities; always check the installation of all parts through which gas flows using leak detection fluid (LDF).
Following maintenance or other activities, always replace the housing and secure it with the screw behind the door at the front of the casing.
The following (safety) symbols may be encountered in these installation instructions and on the unit:
This symbol indicates that the unit must be stored away from frost.
This symbol indicates that the packaging and/or contents can be damaged as a result of insufficient care taken during transport.
This symbol indicates that, whilst still in its packaging, the unit must be protected from weather conditions during transport and storage.
KEY-symbol. This symbol indicates that assembly or dismantling, must be carried out.
ATTENTION symbol. This symbol indicates that extra attention must be paid in connection with a particular operation.
Useful tip or advice
18

Installation & Servicing Instructions ATAG QR-Series

3

Scope of the supply

The boiler is supplied ready for use. The supply kit is composed as follows:

· Boiler with casing;

· Gas isolation valve

· Automatic vent (inside the boiler);

· Concentric flue adapter 80/125;

· Safety valve (inside the boiler);

· Template on the package wrapper;

· Suspension bracket

· Installation instructions;

· Draining valve with T-piece;

· Operating manual;

· Fixing material consisting of plugs and · Warranty card;

screws;

· Benchmark logbook.

4

Description of the boiler

Room sealed boiler The boiler retreives its combustion air to outside then discharges the flue gasses to the outside.
Condensing Retrieves heat from the flue gasses. Water condensates on the heat exchanger.
Modulating Higher or lower burning according to the heat demand.
Stainless Super solid kind of steel which keeps its quality for life. It will not rust or erode in contrast to composition materials, like aluminium.

The ATAG QR boiler is a room sealed, condensing and modulating central heating boiler, with or without an integrated hot water facility.
The boiler is provided with a compact stainless steel heat exchanger with smooth tubes. A well thought out principal using durable materials. The boiler burns gas for supplying warmth. The heat is transferred in the heat exchanger to the water in the central heating system. By cooling down the flue gasses condensate is formed. This results in high efficiency. The condensate, which has no effect on the heat exchanger and the function of the boiler, is drained through an internal siphon.
The boiler is provided with an intelligent control system (CMS Control Management System). The boiler anticipates the heat demand of the central heating system or the hot water facility.
When an outside sensor is connected to the boiler works weather dependantly. This means that the boiler control measures the outside temperature and flow temperature. With this data the boiler calculates the optimal flow temperature for the installation.

Explanation of the type indication: Q = Type 51 = Nominal load in kW C = Combi (S = Solo)
R = Refresh

ATAG Q 51CR

The boiler has been tested according to valid CE standards and has a CE certificate and ErP & Energy Labelling EU 813/2013 & EU 1369/2017 A-rating.
Statement: No banned materials including asbestos, mercury, CFC’s have not or will not be included in the product.

Installation & Servicing Instructions ATAG QR-Series

19

4

2

13 5

8 17 16

7

6

19

9

T1 T1a
P1 T2 T3

ATAG QR

G 18

A

R

C

E

10

12 11

14 13

K

W

15

figure 4.a

Installation & Servicing Instructions ATAG QR-Series

1 heat exchanger 2 ignition unit 3 fan unit 4 air inlet damper 5 gas valve 6 safety valve 7 automatic air vent 8 ceramic burner cassette

9 cylinder DHW, 12l (combi) 10 operating panel
11 Control Tower (CMS) 12 water filter return CH 13 three-way valve 14 circulation pump (A-label)
15 thermostatic mixing valve 16 flue gas discharge

17 combustion air supply 18 type plate 19 expansion vessel, only Q25CR
and Q38CR (14 liter)

T1 flow sensor T1a secondary flow sensor (Q60SR) T2 return sensor T3 cylinder sensor DHW (combi) P1 water pressure sensor

G gas pipe A flow connection central heating R return connection central heating C condensation / safety discharge
pipe

E expansion vessel pipe K cold water pipe (combi) W hot water pipe (combi)

20

5 Mounting the boiler
Install the boiler in a well-ventilated boiler room in accordance to the actual local regulations BS5440-2:2000. The room where the boiler will be placed must always be frost free. It is NOT necessary to have a purpose provided air vent in the room or internal space in which the boiler is installed. Neither is it necessary to ventilate a cupboard or compartment in which the boiler is installed, due to the extremely low surface temperature of the boiler casing during operation. Therefore the requirements of BS 6798, Clause 12, and BS5440:2 may be disregarded. The boiler can be mounted practically to any wall with the suspension bracket and the enclosed fixing equipment. The wall must be flat and of sufficient strength in order to be able to carry the boiler weight with its water content. Above the boiler there must be at least 250 mm working space in order to be able to fit a coaxial flue system or a twin supply. On the left side of the boiler at least 50 mm and on the right side 10 mm must be reserved to allow fitting or removing of casing. The location of the boiler can be determined by using the template located inside the boiler packaging. Lift the boiler only by the boilers rear wall plate.
Lifting and carrying precautions: – Lift only a manageable weight, or ask for help. – When lifting the boiler, bend the knees, and keep the back straight and feet
apart. – Do not lift and twist at the same time. – Lift and carry the boiler close to the body. – Wear protective clothing and gloves to protect from any sharp edges.
21

Installation & Servicing Instructions ATAG QR-Series

6

Connecting the boiler

The boiler has the following connection pipes; – The central heating pipes.
These can be connected to the installation by means of compression fittings; – The gas pipe.
It is provided with a female thread into which the tail piece of the supplied gas isolation valve can be screwed; – The condensation drain pipe. It consists of an oval 24 mm plastic pipe. The drain pipe can be connected to this by means of an open connection. If the open connection is fitted in a different location, then the pipe can be lengthened by means of a 32 mm PVC sleeve; – The flue gas exhaust system and air supply system. It consists of a concentric connection 80/125 mm. The Q51SR and Q60SR are supplied with this feature for converting from the standard 2x 80 mm to concentric 80/125 mm. – Cold and hot water pipes. Only Combi boilers: These consist of 15 mm copper pipe and can be connected to the installation by means of compression fittings.
It is recommended that isolation valves are fitted to all heating and hot water connections to facilitate ease of future maintenance.
It is advisable to spray-clean all of the unit’s connecting pipes and/or to sprayclean/blow-clean the installation before connecting it to the unit.

6.1 Central heating system

Connect the central heating system according to the actual regulations.

The boiler pipes can be connected to the installation by means of compression fittings. Reducers should be used for connecting to thick-walled pipe (welded or threaded).

When removing the plastic sealing caps from the pipes, contaminated testing water may be released.

The boiler has a self-adjusting and self-protecting control system for the load and the pump capacity. This means the temperature difference between the flow and return water is checked. Table 6.1.a shows the water displacement which supplies the circulation pump at certain installation resistance.

Combi Solo

Boiler type
Q25CR Q38CR Q51CR Q25SR Q38SR Q51SR Q60SR

Pump type UPM2 20-70 20-70 20-70 20-70 20-70 20-70 20-70

Permissible installation

Water flow rate

resistance

l/min

l/h

kPa

mbar

15.8

950

25

250

24.0

1440

20

200

Low velocity header required

15.8

950

25

250

24.0

1440

20

200

Low velocity header required

Low velocity header required

Installation resistance

table 6.1.a

Installation & Servicing Instructions ATAG QR-Series

A low velocity header must be connected to the Q51CR, Q51SR and Q60SR to prevent flow problems over the boiler.
ATAG can supply the AA1OV09U Low velocity header for 1 boiler. This can be connected directly under the boiler on the flow and return pipe.

22

external installation pump with low velocity header
figure 6.1.a

If the installation resistance is higher than the stated value the pump will rotate at maximum pump capacity and the load will be adjusted until an acceptable temperature difference between flow and return water has been obtained. If, after this, the temperature difference remains to much then the boiler will switch itself off and wait until an acceptable temperature has arisen (T 20°C). If an unacceptable temperature is detected, then the control will repeatedly try to achieve water flow, and if this does not work then the boiler will switch off. If the capacity of the boiler pump is insufficient, an extra external pump can be installed in combination with a low velocity header in series with the boiler. The electrical side of this external circulation pump can be connected in the Control Panel, which means this pump switches at the same times as the boiler pump. The maximum absorbed current consumption of the external circulation pump may be 230 W (1 Amp). The extra external pump must be selected according the installation resistance and required flow.
As standard the boiler is provided with a water filter in the return pipe of the boiler. With this, possible contamination of the central heating water is prevented from ending up in the boiler. The boiler is also provided with an internal safety valve set at 3 bar. This is connected to the waste discharge together with the condensation discharge.
If all, or a substantial part of the radiators have thermostatic radiator valves or if 2-port zone valve are installed, an automatic by-pass valve must be used to prevent flow rate problems. The automatic by-pass valve used should have the same diameter as the connecting diameter of the supply and return pipe of the boiler. A decrease of pipe diameter between boiler and by-pass is not allowed. See also Annex C.
The boiler is designed to be used on sealed system only.
Additives in the installation water are only permitted in consultation with the country distributor. See chapter 6.4.
When using more than one boiler in an installation please refer to the cascade installation instructions.

Installation & Servicing Instructions ATAG QR-Series

23

6.2 Expansion vessel

The central heating system must be provided with an expansion vessel. The expansion vessel which is used should be geared to the water content of the installation. The precharge pressure depends on the installation height above the mounted expansion vessel. See table 6.2.a.

installation height above the expansion vessel
5 m 10 m 15 m choice of expansion vessel

pre-charge pressure of the expansion vessel

0,5 bar

1,0 bar

1,5 bar

table 6.2.a

The Q51CR Combi boiler is provided with an expansion vessel connection. This pipe is connected between the three way valve and boiler pump. This prevents the expanding water, during hot water production, from being closed off from the expansion vessel, when the thermostatic radiator valves are fully closed. A second expansion vessel in the installation is not a problem. The Solo boilers Q25SR and Q38SR are provided with an expansion vessel connection. When this boiler is combined with a cylinder, the expansion vessel connection is included in the internal piping of the cylinder circuit, to which the expansion vessel can be connected.
In connection with correct functioning of the boiler it is necessary for the expansion vessel to be connected to the expansion vessel pipe of the boiler.
The Solo boilers Q51SR and Q60SR are not provided with an expansion vessel connection. When one of these Solo boilers is combined with a cylinder then one has to take into account that the expansion vessel should be connected between the three-way valve and the boiler circulation pump.

Installation & Servicing Instructions ATAG QR-Series

24

6.3 Underfloor heating system (plastic pipes)
When connecting or using an underfloor heating system, designed with plastic pipes, or plastic pipes are used elsewhere in the installation,one should ensure that the plastic pipes used comply with the DIN is BS7291-1: 1990 standard. It is set out in this standard that the pipes may not have oxygen permeability higher than 0.1 g/m³.d at 40°C. If the system does not comply with this DIN standard, the underfloor heating component will have to be separated from the central heating appliance by means of a plate exchanger.
No recourse can be made to the terms of the warranty in the event of failure to observe the regulations pertaining to plastic underfloor heating pipes.
6.4 Water quality
Fill the installation with drinking water.
In most cases, a heating system can be filled with water according to national standards for water and treatment of this water is not necessary. In order to avoid problems with the CH-installations, the quality of the filling water has to meet the specifications mentioned in table 6.4.a: If the filling water does not meet the required specifications, you are advised to treat the water to such an extent that it does meet the required specifications.
The warranty becomes invalid, if the installation has not been flushed and/or the quality of the filling water does not meet the specifications recommended by ATAG Commercial UK Always contact ATAG Commercial UK in advance, if things are not clear or you wish to discuss any deviations. Without approval, the warranty becomes invalid.
Installation: – The use of groundwater, demi-water and distilled water is prohibited. (on the next page you will find an explanation of these definitions) – If the drinking water quality meets the specifications mentioned in table 6.5.a, you can start flushing the installation before installing the device. – Whilst flushing, corrosion products (magnetite), fitting products, cutting oil and other undesirable products have to be removed. – Another possibility is to remove the pollution by installing a filter. The filter type has to fit the type and grain size of the pollution. ATAG Commercial UK recommends filter usage. – In this case, the whole piping system should be taken into consideration. – The CH-installation has to be properly vented before using the system. For that purpose, we refer to the commissioning chapter. – If a regular water top up is required (>5% on an annual basis), then there is a structural problem and an installer has to solve the problem. Regularly adding fresh water to the system also adds additional calcium and oxygen implying that magnetite and calcium residues can continue. The result may be blockages and/or leakages. – The use of Frost Protection and other additives requires periodical quality checks of the filling water in accordance with the period laid down by the additives supplier. – Chemical additions are to be avoided and should only be used afterATAG Commercial UK has approved their corresponding use. – Should you wish to achieve the required water quality by using chemical additives, then this is your own responsibility. The warranty on the product delivered by ATAG Commercial UK expires, if the water quality does not meet ATAG Heating’s specifications or the chemical additives have not been approved by ATAG Commercial UK. – On installation and during additions or changes at a later stage, ATAG Commercial UK recommends to keep a record of the type of water used, its quality at the time, and if applicable, which additives and quantities were added (see Annex B – System water addetives on page 78.
25

Installation & Servicing Instructions ATAG QR-Series

Parameter

Value

Water type

Potable water Softened water

pH

6.0-8.5

Conductivity (at 20°C in µS/cm)

Max. 2500

Iron (ppm)

Max. 0.2

Hardness (°dH):

Installation volume/capacity 1-12 <20 l/kW

Installation volume/capacity 1-7 >=20 l/kW

Oxygen

No oxygen diffusion allowed during operation. Max. 5% filling water addition annually

Corrosion inhibitors

Refer to Additives Attachment

pH increasing or lowering agents

Refer to Additives Attachment

Frost Protection additives

Refer to Additives Attachment

Other chemical additives

Refer to Additives Attachment

Solid substances

Not allowed

Residues of processing water not for- Not allowed ming part of the drinking water

Water quality in DHW facility

Parameter

Value

Water type

Potable water

pH

7.0-9.5

Conductivity (at 20°C in µS/cm)

Max. 2500

Chloride (ppm)

Max. 150

Iron (ppm)

Max. 0.2

Hardness (°dH)

1-12

Number of bacterial colonies at 22°C Max. 100 (number/ml). pr EN ISO 6222

table 6.4.a table 6.4.b

– When the amount of chloride is above the required specifications mentioned above in table 6.4.b, it is necessary to apply an active anode in case of the use of a DHW cylinder. If this is not met it will void the warranty for DHW parts of the installation. – When the amount of chloride is above the required specifications mentioned above in table 6.4.b, in case of the use of a combi boiler will void the warranty for DHW parts of the boiler.

Water type definition:

Potable water: Tap water compliant with the European drinking water guideline:

98/83/EG dated 3 November 1998.

Softened water: Water with partly de-ionised calcium and magnesium.

Demi-water:

Virtually completely demineralised water (very low conductivity)

Distilled water: Water no longer containing minerals.

Installation & Servicing Instructions ATAG QR-Series

26

6.5 Gas connection
The appliance pipe is fitted with an internal thread, into which the tail piece of the gas isolation valve can be screwed. United Kingdom: The gas supply must comply to the current Gas Safety Regulations. The connection to the appliance must include a suitable method of disconnection and a gas control cock must be installed adjacent to the appliance for isolation purposes. The nominal inlet working gas pressure measured at the appliance should be 20 mbar for Nat gas (G20). Make sure that the gas pipe work does not contain dirt, particularly with new pipes. When the boiler has to be converted from natural gas to LPG, ATAG provides special kits for this purpose. Special instructions are supplied with the kit. Always check the installation of all of the parts through which gas flows using leak detection fluid (LDF).
6.6 Hot water supply
Connection of the drinking water installation should be done according to the national water laws. The sanitary water pipes can be connected to the installation by means of compression fittings. The cold water inlet on the Combi boilers must be provided with the following (counted in the water flow direction): Flow restrictor (supplied), Safety group, Expansion vessel 6bar (potable water, blue). A flow restrictor must be fitted in the cold water pipe. The flow restrictor ensures that a quantity of water is supplied which has a guaranteed outlet temperature of 60°C (assuming a cold water temperature of 10°C). The quantity of water is virtually unaffected by the water pressure. With a water pressure lower than 1.5 bar it is advisable to remove the inside mechanism of the flow restrictor.
27

Installation & Servicing Instructions ATAG QR-Series

6.7 Condensation drain pipe
ATAG Condensing boilers have the top ErP & Energy Labelling EU 813/2013 & EU 1369/2017 band A Classification for high energy efficiency in heating and domestic hot water.
All ATAG wall hung gas fired condensing boilers contain a syphonic condensate trap to collect and realease condensate.
The amount of condensate formed is determind by the type of boilers and the water temperature produced by the boiler.
Condensate pipework.
Use plastic pipework of a diameter no less than 25mm.
Routing of the pipework,
Wherever possible, the condensate pipework should be routed internally to prevent freezing. The condensate pipework must fall at least 50mm per metre towards the outlet and take the shortest possible route Support the pipe at least every 50 cm for near horizontal sections and 1 metre for vertical sections
External pipework
The pipework should be kept to a minimum and the route as vertical as possible. Do not exceed 3 metres outside the dwelling.
The condensate pipe must be run using suitable corrosion resistant materials (eg. plastic).
Terminate as close to the ground or drain as possible (below the grating and above the water level) while still allowing for safe dispersal of the condensate. Connection of a condensate drainage pipe to a drain may be subject to local building controls.
Pipework subjected to extreme cold or wind chill conditions should be in a 40mm diameter pipe.
Protect all external pipework with weather resistant insulation and, if necessary, box in, to reduce the risk of freezing.
Making it safe.
Condensate pipework must not leak, freeze or block up. Condensate traps must be filled before firing the boiler to prevent the possibility of potential harmfull flue products evacuating via the condensate route. Do not dispose condensate into a water recovery system where it is recaimed for reuse.
Condensate can be discharged into a rainwater hopper which is part of a sewer carrying both rain water and foul water.
28

Installation & Servicing Instructions ATAG QR-Series

Final discharge options.
The condensate pipe can only terminate into any one of the five areas as shown in the diagrams on this page.
Draining of the condensation water to the external rain guttering is not permitted in view of the danger of freezing.
Before putting the boiler into operation fill the syphon with 300 ml of water.

A -Condensate from boiler syphon/trap B -Sink with internal overflow C -25mm dia. Plastic condensate pipe
D -External drain or gully E -Internal soil and vent stack. F -Servicable condensate trap (75mm min.)
G -300mm x 100mm dia. sealed plastic tube. H -Ground level
J -Drainage holes facing away from the building K -Lime stone chippings L -Weather resistant insulation

Installation & Servicing Instructions ATAG QR-Series

K

Drain requirements

figure 6.7.a

29

6.8 Flue gas exhaust system and air supply system

The flue gas exhaust system and air supply system consists of: – Flue gas pipe; – Air supply pipe; – Roof or wall terminal.

The flue gas exhaust system and air supply system must comply with:

United Kingdom:

The flue gas outlet and air supply installation must comply with the current regulation

requirements:

IGE/UP/10;

Installation of flued gas appliances in industrial and commercial

premises

BS EN 1856-1; Chimneys – Requirements for metal chimneys –

Part 1: System chimney products

BS EN 1856-2; Chimneys – Requirements for metal chimneys –

Part 2: Metal liners and connecting flue pipes

BS EN 15287-1; Chimneys – Design, installation and commissioning of chimneys –

Part 1: Chimneys for non-room sealed appliances

BS EN 15287-2; Chimneys – Design, installation and commissioning of chimneys –

Part 1: Chimneys for room sealed appliances

BS EN 13384-2; Chimney – Thermal and fluid dynamic calculation methods –

Part 2: Chimneys serving more than one heating appliance

Clean Air Act; For multiple boiler application where total heat input exceeds

366.4 kW [ or 150 kW as advised within the CAAM, refer to local

authority ]

Furthermore: – Boiler Class indicated on the boiler’s type plate (Flue category)
– Locally applicable rules. – The supplier’s installation instructions

When in doubt or if you have any questions, always contact ATAG Commercial UK.

The boiler can be fitted with a parallel connected flue gas outlet and air supply system or a concentric flue gas outlet and air supply system.

Installation & Servicing Instructions ATAG QR-Series

30

The appliance connection diameter is 80/125 mm, to which the flue gas outlet and air supply system can be fitted, with or without elbow pieces. The next page descibes the conversion from concentric to parallal. The Q51SR and Q60SR boiler has a connection of 2x 80mm from factory. The boiler is supplied with a flue adapter 80/125 mm to convert the boiler from parallel to a concentric connection.
The maximum permissible pipe length is set out in Table 6.8.1.a. (see page 35)
Boiler conversion from concentric to parallel It is also possible to use a parallel pipe connection of 2x 80mm. In this case a conversion kit ‘concentric to parallel’ should be ordered. Art.nr. S4440520.

All flue gas parts, which are outside the fire resistant cover, need to be in stainless steel.

P SS
Air filter

Open boiler
BoilerClass B Free exhaust area
SS P

Installation & Servicing Instructions ATAG QR-Series

P

P

P SS

P/A

P/A

Boiler Class C Permitted only when the air
intake and the flue gas outlet are in the same pressure area.
Room sealed system

Open flued en room sealed system

P/A
figure 6.8.a
31

A
1
B
2 3
C
8 6 5 7 4
D

A. 1. Push the 2 clips slightly outwards.
B. 2. Pull the concentric adaptor out of the boiler. 3. Press the cover in the connection at the back from inside out.
C. 4. Pull the rubber seal around the bottom of the flue connector. 5. Push the flue connector in the boiler, in the boiler flue pipe until CLICK’. 6. Push the ø125mm cover over the flue connector in the ø125mm opening until CLICK’. 7. Push the rubber plug in open position in the O2 measuring opening and close the stop. 8. Push the gasket around the top of the flue connector.
D. Connect the parallel flue gas and air intake system (2x ø80mm).

boiler conversion from concentric to parallel
figure 6.8.b

Q51SR and Q60SR Boiler conversion from parallel to concentric It is possible to convert the Q51SR and Q60SR boiler from the standard 2x 80 mm parallel to a concentric flue connection ø80/125mm. In this case use the concentric flue adapter ø80/125 mm supplied with the boiler.
Conversion of the boiler should be done following the description above in reverse order.

Installation & Servicing Instructions ATAG QR-Series

32

We suggest you design a simple flue gas system and air supply system using table 6.8.a For further information about the available components of the flue gas and air supply system we recommend you consult the Duopass Flue system literature.
The ATAG flue gas system is meant, and designed, solely for the use on ATAG central heating boilers adjusted to Nat gas or LPG. The maximum flue gas temperatures are below 70°C (full load 80/60°C) The proper operation may be adversely influenced by changes of or adjustments to the correct set up. Possible warranty claims will not be honoured if incorrect changes result in non compliance with the installation manual or local rules and regulations.
The flue gas systems described in this document are solely suited for ATAG central heating boilers of the ATAG boiler range. For this purpose the CE Certificate has been supplemented under the Gastec nr: 0063BR3405, 0063BQ3021, 0063AS3538 and 0063AU3110. 0063BQ3021, 0063BT3195 en 0063CM3648 The flue gas system should be built up using only ATAG program products. Combinations with other brands or systems, without written permission from ATAG Commercial UK, are not permitted.
Horizontal flue system should always be installed with a 3 degree drop sloping towards the boiler, in order to avoid condensate lying in the flue system. The minimum gradient is 50mm/Mtr. With the condensate running back to the boiler the risk of ice forming at the terminal is reduced.
The terminal should be located where dispersal of combustion products is not impeded and with due regard for the damage or discolouration that might occur to building products in the vicinity (see fig 6.8.c).

terminal position for fan assisted boiler

minimum distance

Installation & Servicing Instructions ATAG QR-Series

figure 6.8.c

A

directly below an open window or other opening (e.g. air brick)

mm

B below gutters, soil pipes or drain pipes

mm

C below eaves

mm

D below balconies or car port roof

mm

E from vertical drain pipes and soil pipes

mm

F from internal or external corners

mm

G above ground or below balcony level

mm

H from a surface facing a terminal

mm

I from a terminal facing a terminal

mm

J

from an opening in the car port (e.g. door window) into dwelling

mm

K vertically from a terminal on the same wall

mm

L horizontally from a terminal on the same wall

mm

M horizontally from a vertical terminal to a wall

mm

300
75 200 200 75 300 300 600 1200
1200
1500 300 300

Dimensions

table 6.8.a

33

In certain weather conditions condensation may also accumulate on the outside of the air inlet pipe. Such conditions must be considered and where necessary insulation of the inlet pipe may be required. In cold and/or humid weather water vapour may condense on leaving the flue terminal. The effect of such `plumeing’ must be considered.

The terminal must not be located in a place where it is likely to cause a nuisance. For protection of combustibles, refer to IS 813 section 9.10.1. where the terminal is less than 2m (6.6ft) above a pavement or platform to which people have access (including) any balcony or flat roof the terminal must be protected by a guard of durable material. A suitable guard is available from the country distributor.

Where a terminal is fitted below a window which is hinged at the top, and where the hinge axis is horizontal, and the window opens outwards, the terminal shall
be 1m below the bottom of the window opening.

If the boiler is to be located under stairs, a smoke alarm meeting the requirements of I.S. 409 or equivalent must be fitted.

The flue must be terminated in a place not likely to cause a nuisance.

For horizontal sections, the outlet system should always be fitted on an incline (50 mm/m) sloping down towards the appliance so that no condensation water is able to accumulate in the outlet system. The chances of icicles forming on the roof outlet is minimised by causing the condensation water to run back towards the appliance. In the case of horizontal outlets the inlet system should be fitted on an incline sloping down towards the outside to prevent rainwater from coming in.

The appliance produces a white wisp of condensate (plumeing). This wisp of condensation is harmless, but can be unattractive, particularly in the case of outlets in outside walls. For wall terminals a plume management kit is available as an option.

Installation height

Cutting the pipe goes as follows: Figure 6.8.d – Cut just as much from the air intake part as from the flue gas part using a hand saw;
– Take off the burrs from the cutting edge to prevent cutting the seals;

When mounting the flue gas system, pay attention to the flow direction (See figue 6.8.e). It is not permitted to mount a system upside down and will lead to complaints.

Use a soap solvent or special grease to simplify the fitting.

Flow direction

Figure 6.8.e

Installation & Servicing Instructions ATAG QR-Series

34

6.8.1

Dimensioning of the flue gas and air intake duct

Example: A 25kW with a concentric flue gas system ø80/125mm has according to the table a maximum flue straight length of 31m In the system that is going to be put in there are 2 x 45° bends, so the maximum flue gas length is 31 ­ ( 2 x 1.9 ) = 27.2 meters.

The flue diameter is determined by the total length of the run, including for the connection pipe, elbows fittings and terminal covers etc and the type and number of boilers installed into the system.
An undersized flue pipe can lead to disorders. Look at table 6.8.1.a for the choice of the system and the correct diameter. The table below shows the maximum flue lengths with the different boiler outputs. A longer flue gas length can be achieved by increasing the diameter to ø 100mm.
Explanation table 6.8.1.a: Two pipe flue gas system: maximum noted length = distance between boiler and roof terminal A Concentric flue gas system: maximum noted length = distance between boiler and roof terminal B
When using bends the noted value behind every bend should be deducted from the maximum straight length.

16-25 kW 26-38 kW 39-60 kW

Two pipe flue system + chimney lining

A

A

ø80mm

in m

ø100mm

in m

Maximum straight length 80

31 Maximum straight length 100

40

87° bend resistance length

-1,4 87° bend resistance length

-2,1

45° bend resistance length

-0,9 45° bend resistance length

-2

Maximum straight length 80

18 Maximum straight length 100

39

87° bend resistance length

-1,4 87° bend resistance length

-2,1

45° bend resistance length

-0,9 45° bend resistance length

-2

Maximum straight length 80

6 Maximum straight length 100

18

87° bend resistance length

-1,4 87° bend resistance length

-2,1

45° bend resistance length

-0,9 45° bend resistance length

-2

Concentric flue system

16-25 kW 26-38 kW 39-60 kW

ø80/125mm Maximum straight length 80/125 87° bend resistance length 45° bend resistance length Maximum straight length 80/125 87° bend resistance length 45° bend resistance length Maximum straight length 80/125 87° bend resistance length 45° bend resistance length

Dimensions flue gas system and air supply system

B

B

in m

ø100/150mm

in m

31 Maximum straight length 100/150 40

-3 87° bend resistance length

-1,7

-1,9 45° bend resistance length

-1,3

13 Maximum straight length 100/150 34

-3 87° bend resistance length

-1,7

-1,9 45° bend resistance length

-1,3

6 Maximum straight length 100/150 10

-3 87° bend resistance length

-1,7

-1,1 45° bend resistance length

-1,3

Table 6.8.1.a

Installation & Servicing Instructions ATAG QR-Series

35

7

External hot water cylinders

Depending of the comfort preferences different external hot water cylinders can be connected to the boiler. The choice of the cylinder depends on the coil output. The coil output must comply with the boiler output.
A cylinder which is used in combination with a Q51SR or Q60SR, should have a minimal capacity of 40 kW resp. 45kW (minimal ø28mm coil). The maximum permitted pressure drop is respectively 20 and 10 kPa at a flow of respectively 1417 and 1587 l/h. See installation example E.1.b on page 83 for the hydraulic connection.

Installation & Servicing Instructions ATAG QR-Series

36

8

Electrical connection

The appliance complies with the actual Directives.
A 230V -50Hz mains electrical supply is required fused externally at 5A.
The installation must continue to comply with: United Kingdom: – the national rules for electrical installations.
The appliance must be connected to an earthed socket. this must be visible and within reach.
The following general stipulations also apply: – No changes may be made to the wiring of the appliance; – All connections should be designed in accordance with the enclosed regulations.; – Should it be necessary to change it, the mains power supply cable may only be replaced with an ATAG mains power supply cable (item No. S4396700).
The ATAG room thermostat and controls must be connected to their allocated connections. All other types or makes of room thermostats or controls which are used must have a Volt free contact.

8.1 Room thermostats
Various thermostats or controls can be connected to the ATAG QR. The following thermostats or controls can be connected at pos. 19 and 20:

– Honeywell Round Modulation

Simple digitally communicating room thermostat.

– ATAG WiZe

Extensive digitally communicating clock thermostat with push button control.

– ATAG BrainZ

Extensive digitally communicating clock thermostat with push / turn menu control.

– Or any other brand according to OpenTherm protocol.

All other types or makes of room thermostats or controls which are used must have a Volt free contact and must be connected to pos. 19 and 20.
One of the above mentioned room thermostats or controls can be connected to pos. 21 and 22 as 2nd option for, for example, an affiliated mixed group.

Installation & Servicing Instructions ATAG QR-Series

37

The Siemens QAA55 controller can be connected at positions 14 and 15.
If desired, the different controllers (OpenTherm- and Siemens controller) can be applied to different groups. See the setting in the overview below.
Depending on the desired (external) control, a basic setting must be made:

Parameter 5710 5715 5721 6351

Function Heating group 1 Heating group 2 Heating group 3 Function OT 1 connection

6352

Function OT 2 connection

6355

Room controller VG1

6356

Room controller VG2

6357

Room controller VG3

6359

External control DHW

Adjustments

Default

Application

On / Off

On

Use of heating group 1

On / Off

Off

Use of heating group 2

On / Off

Off

Use of heating group 3

External room controller 1 / 2 / 3 External room controller 1 Assign OpenTherm controller 1 to a specific heating

Or via H8 (for on / off)

group

External room controller 1 / 2 / 3 External room controller 2 Assign OpenTherm controller 2 to a specific heating

Or via H9 (for on / off)

group

Intern / Extern

External

Internal = Siemens controller Extern = OpenTherm

Intern / Extern

External

Internal = Siemens controller External = OpenTherm

Intern / Extern

Internal

Internal = Siemens contoller External = OpenTherm

None / External controller 1 / None External controller 2

None (internal controller) = Siemens controller External controller = Settings on OpenTherm controller

For weather-dependent control, the outdoor sensor 1kOhm ATAG ARZ0055U (optional) must be connected to pos. 25 and 26.

For more detailed questions regarding the components which are not supplied by ATAG, the country distributor should be contacted.

Connection terminal QR

230 V~ Acc.
NL 123

230 V~ QX1 2nd CH NL
456

230 V~ QX2 DHW/Solar NL
78 9

230 V~ QX3 DHW
N 10 11 12

QAA

n.a. Block. contact

G+ CL- CL+ 13 14 15 16 17 18

1
OT ON/OFF
19 20

2
OT ON/OFF
21 22

PT1000 23 24

Out 25 26

DHW 27 28

Installation & Servicing Instructions ATAG QR-Series

8X.35.20.00

External safety contact On/off thermostat or OpenTherm thermostat 1 On/off thermostat or OpenTherm thermostat 2 PT1000 collectorsensor sun system ATAG ARZ55 outside sensor DHW sensor 10kOhm

230 Volt for three-way valve motor Option

230 Volt for accessories (clip-in) 230 Volts for external pump 230 Volt for external control

Connection terminal

figure 8.a
38

39

Installation & Servicing Instructions ATAG QR-Series

4

FAN

1

5

L N PE

4

2

PWM

1

PUMP

321 * Adapter cable

+-

(OSS3/4 only)

IGNITION
6,3 4,0

31 42

1 2 PE GAS VALVE

3 1
IONISATION

2 63
Three way valve VC6012 (Combi only) Accessory for Solo

8X.35.20.00

** Bridge expires when connecting a security device

1kOhm
Outside sensor (Accessory)

10KOhm
DHW sensor Combi (Accessory for Solo)
Power supply Fuse 10A 230V~50Hz

**

230 V~ Acc.
NL 123

230 V~ QX1 2nd CH NL
456

230 V~ QX2 DHW/Solar NL
78 9

230 V~ QX3 DHW
N 10 11 12

QAA

n.a. Block. contact

G+ CL- CL+ 13 14 15 16 17 18

1

2

OT

OT

ON/OFF ON/OFF

19 20 21 22

PT1000 23 24

Out 25 26

DHW 27 28

0I

PE

NL

2x T 6,3A H 250V

7473a02en/0118

1 23
P
Water pressure sensor

10kOhm
T1 Flow sensor

10kOhm
T2 Return sensor

10kOhm
T1a – in OSS4 2. Flow sensor

electrical diagram

Auto

0 4 8 12 16 20 24

Reset

ESC

OK

Control unit

X4 X5
X42

X7
X22 X50

X24

X21

X20

figure 8.b

9 Boiler controls

3 sec.

After switching on and with sufficient heating pressure (> 1.0 bar), the automatic heating-side de-aeration program is executed, e.g. after filling the installation for the first time. The system is then switched to safe mode (circle symbol with dash). The display shows “De-aeration program on”. The pump (s) are switched off / on a number of times. The 3-way valve, if present, is switched to the hot water position and the pump (s) are switched off / on again a number of times. At the end of the de-aeration program, which lasts approx. 16 minutes, the boiler switches back to normal operation
The venting program can also be started manually by pressing button E for more than 3 seconds. This function runs for approximately 16 minutes.
On a call for Central Heating (DHW program is switched OFF as factory setting), a water temperature will be calculated. This calculated water temperature is called the T-set value and with this the boiler output will be controlled. On a call for central heating the boiler ignites first at low input. The input is then changed slowly to match the load required. The boiler operates in this way to avoid excessive water noises and temperature overshoot.
On a call for hot water supply the T-set value of central heating return water temperature is monitored. Depending on the amount of sanitary water which is withdrawn from the DHW cylinder, the central heating return water temperature, from which the input is adjusted, will vary.

9.1 Explanation of the function keys

Legend:

A On/Off switch

B Back button (ESC)

C Room temperature control button

D Confirmation button (OK)

L

E Function button for manual

operation

F Chimney sweep function button

G Info button

H Reset button

I Operation mode button for heating

circuit(s)

L Operating mode button for DHW

H

A

I G
B C DE F

Installation & Servicing Instructions ATAG QR-Series

40

Operating mode button for DHW (M) For switching on the DHW preparation (Bar under the water tap in the display) If the boiler control is configured via OpenTherm, no bars are visible. DHW timer program via external controller is leading
Operation mode button for heating circuit(s) (I) (Only works in combination with QAA55, NOT with OT/On-Off) For setting 4 different operating modes for heating:

Automatic clock: Automatic operation according to timer program Bar in the display visible under “AUTO” by OpenTherm

Sun 24 hr:

Heating at comfort target value

Moon 24 hr:

Heating at reduced value

Installation & Servicing Instructions ATAG QR-Series

Protection mode: Heating switched off, frost protection active
Information button (G) Retrieval of the following information, without influence on the control processes: Temperatures, operating condition of the heating facility/DHW, error reports
Room temperature control button (C) With this rotating button, settings can be selected and changed during programming and changing the room comfort temperature
Confirmation button OK (D) Back button ESC (B) These two buttons are needed in combination with the large rotating button (- +) for the programming and configuration of the control unit. Settings, which cannot be changed through the control elements, are provided by means of programming. By pushing the ESC button you always go one step backward, whereby modified values are not taken over. To reach the next operating level, or to store the changed values, you must push the OK button.
Manual operation function button (E) By pushing this button, the control unit is set to manual mode, whereby all pumps are running, the mixer is no longer controlled and the burner is set to 60°C (Indicated by the spanner symbol). Hold down for 3 sec. to start venting program.
Chimney sweep function button (F) MAY ONLY TO BE OPERATED BY A QUALIFIED INSTALLER! Push this button shortly, to put the boiler in the operating mode for measuring emissions; renewed pushing of the button deactivates this function, or it is automatically deactivated after 15 minutes (indicated by the spanner symbol).
Reset button (H) By pressing this button shortly, the locked condition of the burner is deactivated.
On/Off switch (A) Position 0: The entire facility and all connected electrical components are without electrical power. A protection against frost is not ensured. Position I: The entire facility and all connected electrical components are ready for operation.
41

9.2 Main functions of the control panel

Button Button

Action

Procedure

Setting up the required room temperature

HC2 jointly with HC1
Turn the rotating button left or right Turn the rotating button again for storing with OK button or wait for 5 sec. or push

Setting the required room temperature
for HC1 or HC2

or
2nd HC independent of HC1
Turn rotating button left/right Then push OK Turn rotating button left/right Save with OK button or wait for 5 sec. or push

Switching warm water operations ON or OFF

Push button

Factory setting

Change operating mode

1 x short push of button and then once more, short push of button

once more, short push of button

Control stop function
Action
Display of various information

1 x push button (> 3 sec) push button once more (> 3 sec)
Procedure
1 x push button push button again push button again

Push button

Operating mode according to target values that are set manually
Change of the factory setting for boiler temperature

short push of button
short push of button short push of button Rotating button turn -/+ short push of button short push of button short push of button

De-aeration function
Activation of chimney sweep function

1 x push button (> 3 sec) push button once more (> 3 sec)
Push button (> 3 sec) push button once more (> 3 sec)

Display / Function
comfort target value with blinking temperature display blinking temperature display in steps of 0.5° centigrade, from 10.0 to 30°C
Comfort value active Comfort value not active – Basic display appears after 3 sec.
Select heating circuit Heating circuit active blinking temperature display in steps of 0.5° centigrade, from 10.0 to 30°C Comfort target value active Comfort target value not active – Basic display appears after 3 sec.

Only works in combination with QAA55, NOT with OT Works with on / off controller via H8 / H9

Warm water operation ON / OFF
(segmented bar under symbol for warm water visible/invisible) – ON: Warm water preparation according to switching program – OFF: No warm water preparation – Safety function active When using OpenTherm, “operating mode button is locked” is displayed Safety functions remain active!

Automatic operating mode ON, with:
– heating operation according to timer program – Temperature target values according to heating program – Safety function active
– Summer/Winter – automatic switching active – ECO functions active (segmented bar under corresponding symbol visible)
Continuous COMFORT heating ON, with:
– Heating operation without timer program, at comfort target value – Safety function active
Continuous REDUCED heating ON, with:
– Heating operation without timer program, at reduced target value – Safety function active
– Summer/Winter – automatic switching active – ECO functions active Automatic safety mode ON, with:
– Heating operations switched off – Temperature according to frost protection value – Safety function active When using OpenTherm, “operating mode button is locked” is displayed Safety functions remain active!

304: Control stop function Basic display appears after 3 sec.

Set target value

Display / Function

INFO section is displayed

– Boiler status

– Room temperature

– Room temperature minimum

– Warm water status

– Room temperature maximum

– Status heating circuit 1 – Outdoor temperature

– Status heating circuit 2 – Minimum outdoor temperature

– Maximum outdoor temperature

– Time / date – Water temperature 1

– Error message

– Boiler temperature

– Maintenance report

– Flow temperature

(Display of the information lines depends on the configuration)

Back to basic display; INFO segment is suppressed

Manual operating mode ON (spanner symbol is visible) – Heating operations at preset boiler temperature (factory setting = 60°C)

301: Manual operation mode
operation? Blinking temperature display Set required target value

Set target value for manual

Boiler status Manual operating mode OFF (spanner symbol disappears)

312: De-aeration function ON De-aeration function OFF
Chimney sweep function ON Chimney sweep function OFF

DHW timer program via external
controller is leading
Only works in combination with QAA55, NOT with OT Works with on / off controller via H8 / H9

Installation & Servicing Instructions ATAG QR-Series

RESET

Short-term reduction of room temperature at QAA75 / 78
Reset button

Push button push button again

Heating at reduced target value Heating at comfort target value

Push button (< 3 sec.) push button again > 3 sec.

Facility is manually locked, unreleased equipment is unlocked, alarm bell disappears

= Confirmation

= Abort or back to basic display

MAY ONLY BE OPERATED BY A QUALIFIED INSTALLER!

Only works in combination with QAA55, NOT with
OT/On-Off
42

9.3 Parameters end users

Basic display “Boiler temperature” – Push OK button once – Use +- rotating button for selecting for instance “Drinking water menu” – Push OK button once – Use +- rotating button, for instance in the drinking water menu, for selecting “Parameter no. 1612 – Reduced target value” – Push OK button once – Use +- rotating button to change the currently set value – Push OK button once -> the value is stored – Push 2 x ESC to return to the basic display “Boiler temperature . .”
Time programs are not active when using an OpenTherm thermostat, however, they are active when switching on and off via H8 / H9

Menu Time of day and date Operator section Time program HC 1
Time program HC 2 (When activated)
Time program 3/ HC3
Time program 4/ DHW

Line no. 1 2 3 20

Selection possibilities Hours / Minutes Day / Month Year Language

500

Preselection

501

Mo-Su: 1. Phase On

502

Mo-Su: 1. Phase Off

503

Mo-Su: 2. Phase On

504

Mo-Su: 2. Phase Off

505

Mo-Su: 3. Phase On

506

Mo-Su: 3. Phase Off

516

Default values

520

Preselection

521

Mo-Su: 1. Phase On

522

Mo-Su: 1. Phase Off

523

Mo-Su: 2. Phase On

524

Mo-Su: 2. Phase Off

525

Mo-Su: 3. Phase On

526

Mo-Su: 3. Phase Off

536

Default values

540

Preselection

541

Mo-Su: 1. Phase On

542

Mo-Su: 1. Phase Off

543

Mo-Su: 2. Phase On

544

Mo-Su: 2. Phase Off

545

Mo-Su: 3. Phase On

546

Mo-Su: 3. Phase Off

556

Default values

560

Preselection

561

Mo-Su: 1. Phase On

562

Mo-Su: 1. Phase Off

563

Mo-Su: 2. Phase On

564

Mo-Su: 2. Phase Off

565

Mo-Su: 3. Phase On

566

Mo-Su: 3. Phase Off

576

Default values

Unit hh:mm dd:MM
yyyy –
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm –

Min.

Max

00:00

23.59

01.01

31.12.

2004

2099

English, German, French, Italian, Danish, Dutch, Spanish, Czech, Slovenian, Turkish

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Factory setting –.—.—.–
German

Mo-Su 06:00 22:00 –.—.—.—.–
No Mo-Su 06:00 22:00
–.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No

Only works in combination with QAA55, NOT with OT Works with on / off controller via H8 / H9
Only if parameter 6359 is active

Installation & Servicing Instructions ATAG QR-Series

43

Parameters end users

Menu Time program 5
Holidays HC1
Holidays HC2 (When activated) HC1
HC 2 (When activated) DHW Swimming pool Boiler Error

Line no. 600 601 602 603 604 605 606 616 641 642 643 648 651 652 653 658 710 712 714 720 730 1010 1012 1014 1020 1030 1600 1610 1612 2055 2056 2214 6700 6705 6706

Selection possibilities Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Period Start Day / Month Periode End Day / Month Operating level Preselection Period Start Day / Month Periode End Day / Month Operating level Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Summer/winter heating limit Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Summer/winter heating limit Operating mode Nominal setpoint Reduced setpoint Pool setpoint solar heating Pool sepoint boiler heating Setpoint manual control Error message SW Diagnose Code Burner ctrl phase lockout pos

Unit –
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
tt.MM tt.MM tt.MM tt.MM °C °C °C °C °C °C °C °C °C °C °C °C °C –

Min.

Max

Mo-Su, Mo-Fr, Sa-Su

Mo-Su, Mo-Fr, Sa-Su

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

00:00

24:00

Yes

No

Period 1, 2, 3, 4, 5, 6, 7, 8

01.01

31.12

01.01

31.12

Frost protection, Reduced

Frost protection

Period 1, 2, 3, 4, 5, 6, 7, 8

01.01

31.12

01.01

31.12

Frost protection, Reduced

Frost protection

Value from Line no. 712

35

4

Value from Line no. 710

4

Value from Line no. 712

0.10

4.00

—/8

30

Value from Line no. 1012

35

4

Value from Line no. 1010

4

Value from Line no. 1012

0.10

4.00

—/8

30

Off, On, Eco

Value from Line no. 1612

80

8

Value from Line no. 1610

8

80

8

80

10

90

Factory setting Mo-Su 06:00 22:00 –.—.—.—.-No Period 1 –.—.–
Frost protection Period 1 –.—.–
Frost protection 20.0 16.0 10.0 1.50 20 20.0 16.0 10.0 0.8 0 Off 55 40 26 22 50
Indication only Indication only Indication only

Only works in combination
with QAA55, NOT with OT Works with on / off controller via H8 / H9

Installation & Servicing Instructions ATAG QR-Series

44

9.4 Parameters technician

Basic display “Boiler temperature”
– Push OK button once – Push Info button for 4 sec. – Use the +- rotating button for selecting commissioning or technician level – Push OK button once – Use +- rotating button for selecting for instance “Drinking water menu” – Push OK button once – Use the +- rotating button, for instance in the drinking water menu, for selecting “Parameter no. 1612 – Reduced target value”
– Push OK button once – Use +- rotating button to change the currently set value – Push OK button once -> the value is stored – Push 2 x ESC to return to the basic display “Boiler temperature”

Overview of commissioning
parameters
The parameter lines with a grey background only become visible at the commissioning level.
The complete parameter list becomes visible at the technician level.

Menu Time of day and date
Operator section
Time program HC 1
Time program HC 2 (when activated)
Time program HC3/P
Time program 4 DHW

Line no. 1 2 3 5 6 20
22 26 27 28 44 46 70 500 501 502 503 504 505 506 516 520 521 522 523 524 525 526 536 540 541 542 543 544 545 546 556 560 561 562 563 564 565 566 576

Selection possibilities Hours / Minutes Day / Month Year Start of summertime Day / Month End of summertime Day / Month Language

Unit hh:mm dd:mm
yyyy dd:mm dd:mm

Info Operation lock Programming lock Direct adjustment Operation HC2 Operation HC3/P Software Version Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo- Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values

hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm –

Min.

Max

00:00

23.59

01.01

31.12.

2004

2099

01.01

31.12.

01.01

31.12.

English, German, French, Italian, Danish, Dutch, Spanish, Czech, Slovenian, Turkish

Temporarily, Permanently

Off, On

Off, On

Automatic storage, Storage with confirmation

Jointly with HC1, Independently

Jointly with HC1, Independently

0

99.0

Mo-Su, Mo-Fr, Sa-Su

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

Yes, No

Mo-Su, Mo-Fr, Sa-Su

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

Yes, No

Mo-Su, Mo-Fr, Sa-Su

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

Yes, No

Mo-Su, Mo-Fr, Sa-Su

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

Yes, No

Factory setting –.—.—.–
25.03. 25.10. German
Temporarily Off Off
Storage with confirmation Jointly with HC1 Jointly with HC1 Indication only Mo-Su 06:00 22:00 –.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No

Installation & Servicing Instructions ATAG QR-Series

45

Parameters technician

Menu Time program 5
Holidays HC1 Holidays HC2 (When activated) HC 1

Line no. 600 601 602 603 604 605 606 616 641 642 643 648 651 652 653 658 700
710 712 714 720 721
726 730 732 733 740 741 742 746 750 760 770 780
790 791 800 801 809 820 830 832 833 834 835 836 850 851 855 856 861 870 872 890 898 900

Selection possibilities Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Period Start Day / Month Periode End Day / Month Operating level Preselection Period Start Day / Month Periode End Day / Month Operating level Operating mode HC1
Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Heating curve parallel displacement Heating curve adaption Summer/winter heating limit 24-hour heating limit Ext’n 24-hour heating limit Flow temp setpoint min Flow temp setpoint max Flow temp setpoint room stat Delay heat request Room influence Room temp limitation Boost heating Quick setback
Optimum start control max Optimum Stop control max Reduced setp increase start Reduced setp increase end Continuous pump operation HC1 Overtemp prot pump circuit Mixing valve boost Actuator type Switching differential 2-pos Actuator running time P-Band (Xp) HC1 Integral action time (Tn) HC1 Floor curing function Floor curing setp manually Floor curing setp current Floor curing day current Excess heat draw With buffer With prim contr/system pump Flow setp readj speed ctrl Operating level change over Optg mode changeover

Unit –
hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm
dd:mm dd:mm dd:mm dd:mm –
°C °C °C °C
°C °C °C °C °C °C s % °C °C –
min min °C °C
°C
°C s °C s °C °C –

  • see page 52

Min.

Max

Mo-Su, Mo-Fr, Sa-Su

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

00:00

Yes, No

Period 1, 2, 3, 4, 5, 6, 7, 8

01.01

31.12

01.01

31.12

Frost protection, reduced

Period 1, 2, 3, 4, 5, 6, 7, 8

01.01

31.12

01.01

31.12

Frost protection, reduced

Protection, Automatic mode, Continuously comfort, Continuously reduced

Value from Line no. 712

35

Value from Line no. 714 Value from Line no. 710

4

Value from Line no. 712

0.10

4.00

-4.5

4.5

Off, On

—/8

30

—/-10

10

No, Yes

8

Value from Line no. 741

Value from Line no. 740

80

Value from Line no. 740 Value from Line no. 741

0

600

—/0

100

—/0.5

4

—/0

20

Off, Down to Reduced setpoint, Down to Frost protection setpoint

0

360

0

360

—/30

10

-30

Value from Line no. 800

Off, On

Off, On

0

50

2-position, 3-position

0

20

30

873

1

100

10

873

Off, Functional heating, Curing heating, Manual

0

0

Off, Heating mode, Always

No, Yes

No, Yes

No, Yes

Frost protection, Reduced, Comfort

None, Protection, Reduced, Comfort, Automatic

Factory setting Mo-Su 06:00 22:00 –.—.—.—.-No
Period 1 –.—.–
Frost protection Period 1 –.—.–
Frost protection Automatic mode
20.0 16.0 10.0 1.50 0.0
Off 0 -3 Yes 8 80 65 10 20 1 2 Down to Reduced setpoint
0 0 -5 -15 Off On 5 3-position 2 135 24 90 Off 25 Indication only 0 Off Yes Yes No Reduced Protection

Installation & Servicing Instructions ATAG QR-Series

46

Parameters technician

Menu HC 2 (when activated)

Line no. 1000 1010 1012 1014 1020 1021 1026 1030 1032 1033 1040 1041 1042 1046 1050 1060 1070 1080
1090 1091 1100 1101 1109 1120 1130 1132 1133 1134 1135 1136 1150 1151 1155 1156 1161 1170 1172 1190 1198 1200

Selection possibilities Operating mode HC2 Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Heating curve parallel disHeating curve adaption Summer/winter heating limit 24-hour heating limit Ext’n 24-hour heating limit Flow temp setpoint min Flow temp setpoint max Flow temp setpoint room stat Room influence Room temp limitation Boost heating Summer/winter heating limit Quick setback
Optimum start control max Optimum Stop control max Reduced setp increase start Reduced setp increase end Continuous pump operation HC2 Overtemp prot pump circuit Mixing valve boost Actuator type Switching differential 2-pos Actuator running time P-Band (Xp) HC1 Integral action time (Tn) HC1 Floor curing function Floor curing setp manually Floor curing setp current Floor curing day current Excess heat draw With buffer With prim contr/system pump Flow setp readj speed ctrl Operating level change over Optg mode changeover

  • see page 52

Unit

Min.

Max

Protection, Automatic mode, Reduced

°C

Value from Line no. 1012

35

°C

Value from Line no. 1014 Value from Line no. 1010

°C

4

Value from Line no. 1012

0.10

4.00

°C

-4.5

4.5

°C

Off, On

°C

—/8

30

°C

—/-10

10

No, Yes

°C

8

Value from Line no. 1041

°C

Value from Line no. 1040

80

°C

Value from Line no. 1040 Value from Line no. 1041

s

0

600

%

—/0

100

°C

—/0.5

4

°C

—/0

20

Off, Down to Reduced setpoint, Down to Frost protection

setpoint

min

0

360

min

0

360

°C

—/30

10

°C

-30

Value from Line no. 1100

Off, On

Off, On

°C

0

50

2-position, 3-position

°C

0

20

s

30

873

°C

1

100

s

10

873

Off, Functional heating, Curing heating, Manual

°C

0

95

°C

0

32

Off, Heating mode, Always

No, Yes

No, Yes

No, Yes

Frost protection, Reduced, Comfort

None, Protection, Reduced,

Comfort, Automatic

Factory setting Protection 20.0 16.0 10.0 0.8 0.0 Off 20 -3 Yes 8 50 50 10 20 1 2
Down to Reduced setpoint
0 0 -5 -15 Off On 5 3-position 2 135 24 90 Off 25 Indication only 0 Off Yes Yes No Reduced Protection

Installation & Servicing Instructions ATAG QR-Series

47

Parameters technician

Menu HC 3 (when activated)

Line no. 1300 1310 1312 1014 1320 1321 1326 1330 1332 1333 1340 1341 1342 1346 1350 1360 1370 1380
1390 1391 1400 1401 1409 1420 1430 1432 1433 1434 1435 1436 1450 1451 1455 1456 1461 1470 1472 1490 1498 1500

Selection possibilities Operating mode HC2 Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Heating curve parallel disHeating curve adaption Summer/winter heating limit 24-hour heating limit Ext’n 24-hour heating limit Flow temp setpoint min Flow temp setpoint max Flow temp setpoint room stat Room influence Room temp limitation Boost heating Summer/winter heating limit Quick setback
Optimum start control max Optimum Stop control max Reduced setp increase start Reduced setp increase end Continuous pump operation HC3 Overtemp prot pump circuit Mixing valve boost Actuator type Switching differential 2-pos Actuator running time P-Band (Xp) HC1 Integral action time (Tn) HC1 Floor curing function Floor curing setp manually Floor curing setp current Floor curing day current Excess heat draw With buffer With prim contr/system pump Flow setp readj speed ctrl Operating level change over Optg mode changeover

  • see page 52

Unit

Min.

Max

Protection, Automatic mode, Reduced

°C

Value from Line no. 1312

35

°C

Value from Line no. 1314 Value from Line no. 1310

°C

4

Value from Line no. 1312

0.10

4.00

°C

-4.5

4.5

°C

Off, On

°C

—/8

30

°C

—/-10

10

No, Yes

°C

8

Value from Line no. 1341

°C

Value from Line no. 1340

80

°C

Value from Line no. 1340 Value from Line no. 1341

s

0

600

%

—/0

100

°C

—/0.5

4

°C

—/0

20

Off, Down to Reduced setpoint, Down to Frost protection

setpoint

min

0

360

min

0

360

°C

—/30

10

°C

-30

Value from Line no. 1400

Off, On

Off, On

°C

0

50

2-position, 3-position

°C

0

20

s

30

873

°C

1

100

s

10

873

Off, Functional heating, Curing heating, Manual

°C

0

95

°C

0

32

Off, Heating mode, Always

No, Yes

No, Yes

No, Yes

Frost protection, Reduced, Comfort

None, Protection, Reduced,

Comfort, Automatic

Factory setting Protection 20.0 16.0 10.0 0.8 0.0 Off 20 -3 Yes 8 50 50 10 20 1 2
Down to Reduced setpoint
0 0 -5 -15 Off On 5 3-position 2 135 24 90 Off 25 Indication only 0 Off Yes Yes No Reduced Protection

Installation & Servicing Instructions ATAG QR-Series

48

Parameters technician

Menu Domestic hot water
Consumer circuit 1 Consumer circuit 2 Consumer circuit 3 Swimming pool Primary control/ System pump

Line no. 1600 1610 1612 1614 1620
1630
1640 1641 1642 1644 1645 1646 1647 1660
1661 1663 1680 1859 1874 1875 1878 1880 1909 1924 1925 1928 1930 1959 1974 1975 1978 1980 2055 2056 2065 2070 2080 2110 2111 2121 2130 2132 2133 2134 2135 2136 2150

Selection possibilities Operating mode Nominal setpoint Reduced setpoint Nominal setpoint max Release
Charging priority
Legionella function Legionella function periodically Legionella funct Day Legionella funct time Legionella funct setpoint Legionella funct duration Legionella funct circ pump Circulating pump release
Circulating pump cycling Circulation setpoint Optg mode changeover Flow temp setp cons request DHW charging priority Excess heat draw With buffer With prim contr/system pump Flow temp setp cons request DHW charging priority Excess heat draw With buffer With prim contr/system pump Flow temp setpoint DHW charging priority Excess heat draw With buffer With prim contr/system pump Pool setpoint solar heating Pool setpoint producer heating Pool charging priority solar Pool temperature maximum Pool with solar Flow temp min limitation Flow temp max limitation Syst pump on heat gen lock Mixing valve boost Actuator type Switching differential 2-pos Actuator running time P-Band (Xp Integral action time (Tn) HC1 Primary control/System pump

Unit °C °C °C –

uu:mm °C min –
°C
°C °C
°C °C °C °C °C °C °C °C s °C s –

Min.

Max

Off, On, Eco

8

80

8

80

8

80

24h/Day, Time programs HCs, Time program 4/DHW
Absolute, Shifting, None, MC shifting PC absolute
Off, Periodically, Fixed weekday

1

7

Mo,Tu,We,Th,Fr,Sa,Su

00:00

23:50

55

95

10

360

Off, On

Time program 3/HCP, DHW release, Time program 4/DHW, Time program 5
Off, On

8

80

None, Off, On

8

120

No, Yes

No, Yes No, Yes

No, Yes

8

120

No, Yes

No, Yes

No, Yes

No, Yes

8

No, Yes

No, Yes

No, Yes

No, Yes

8

80

8

80

Priority 1, Priority 2, Priority 3

8

95

No, Yes

8

95

8

95

Off, On

0

50

2-position, 3-position

0

20

30

873

1

100

10

873

Upstream of buffer, Downstream of buffer

Factory setting Off 60 40 65
combi: 24h/Day solo: Time programs HCs
Absolute
Fixed weekday 7
Montag –65 30 On
DHW release
Off 45 None 70 Yes No Yes Yes 70 Yes No Yes Yes 45 Yes No Yes Yes 26 22 Priority 3 30 Yes 8 80 Off 5 3-position 2 120 32 120 Downstream of buffer

Installation & Servicing Instructions ATAG QR-Series

49

Parameters technician

Menu Boiler

Line no. 2210 2212 2214 2236 2237 2243 2245 2250 2253 2270 2301 2305
2316 2317 2320
2321 2322

Selection possibilities Setpoint min Setpoint max Setpoint manual control P-band Xp DHW Integral action time (Tn) dhw Burner off time min SD burner off time Pump overrun time Pump overr time after DHW Return setpoint min Boiler pump on heat gen lock Impact heat generation lock
Temp differential max Temp differential nominal Pump modulation
Starting speed Pump speed min

2323

Pump speed max

Unit

Min.

Max

°C

8

95

°C

8

120

°C

8

120

°C

1

200

s

4

873

min

0

60

°C

0

80

min

0

240

min

0

20

°C

8

95

Off, On

Heating mode only, Heating and DHW

mode

°C

0

80

°C

0

80

None, Demand, Boiler setpoint,

Temp differential nominal, Burner output

%

0

100

%

0

100

%

0

100

2330

Output nominal

kW

0

2000

2331

Output basic stage

kW

0

2000

2334 2335

Output at pump speed min Output at pump speed max

%

0

%

0

2441

Max. speed at maximum output in heating mode

rpm

0

2442

Fan speed full charging max

rpm

0

100 100
1000
1000

2444

Fan speed DHW max

rpm

0

1000

2445 2446 2450
2452 2453 2454 2455 2456 2457 2460 2461 2462 2463

Fan shutdown heating mode Fan shutdown delay Controller delay
Controller delay speed Controller delay duration Switching diff on HCs Switching diff off min HCs Switching diff off max HCs Settling time HCs Switching diff on DHW Switching diff off min DHW Switching diff off max DHW Settling time DHW

Uit, Aan

s

0

200

Off, Heating mode only, DHW mode only,

Heating and DHW mode

rpm

0

10000

s

0

255

°C

0

20

°C

0

20

°C

0

20

min

0

240

°C

0

20

°C

0

20

°C

0

20

min

0

240

Factory setting
20
85
50
35
75
5
40
3
1
8
Off
Heating and DHW mode
25
20
Temp differential nominal
100
Q25SR: 60 Q38SR: 60 Q51SR: 55 Q60SR: 55 Q25CR: 60 Q38CR: 60 Q51CR: 55
Q25SR: 70 Q38SR: 100 Q51SR: 100 Q60SR: 100 Q25CR: 75 Q38CR: 100 Q51CR: 100 Q25SR: 25 Q38SR: 38 Q51SR: 51 Q60SR: 60 Q25CR: 25 Q38CR: 38 Q51CR: 51 Q25SR: 5.0 Q38SR: 6.9 Q51SR: 10.0 Q60SR: 10.0 Q25CR: 6.9 Q38CR: 6.9 Q51CR: 10.0
0
100
Q25SR: 5390 Q38SR: 5450 Q51SR: 4750 Q60SR: 5400 Q25CR: 3590 Q38CR: 5450 Q51CR: 4750 See Line no. 2444
Q25SR: 5390 Q38SR: 5450 Q51SR: 4750 Q60SR: 5400 Q25CR: 5020 Q38CR: 5450 Q51CR: 4750
Uit
3
Heating mode only
1500
30
3
5
10
1
1
6
8
1

Installation & Servicing Instructions ATAG QR-Series

50

Parameters technician

Installation & Servicing Instructions ATAG QR-Series

Menu Boiler Cascade (when activated) Solar
51

Line no. 2470 2628
2630 2655 2656 2657 2662 2663 3510
3511 3512 3530 3531 3532 3533 3534 3540 3541 3544 3560 3810 3811 3812 3813 3814 3815 3816 3817 3818 3822 3825 3826 3827 3828 3830 3831 3840 3850 3860 3865 3867 3868 3869 3870 3871 3880
3881 3884 3887

Selection possibilities Delay heat req special op Deaeration function release
Auto deaeration procedure ON time deaeration OFF time deaeration Number of repetititions Deaeration time heat circuit Deaeration time DHW Lead strategy
Output band min Output band max Release integral source seq Reset integral source seq Restart lock Switch on delay Forced time basic stage Auto source seq ch’over Auto source seq exclusion Leading source Return setpoint min Temp diff on Temp diff off Min charging temperature DHW storage tank Temperature differential ON buffer Temperature differential OFF buffer Min charging temperature buffer Temperature differential swimming pool ON Temperature differential swimming pool OFF Min charging temperature swimming pool Charging priority storage Charging time relative priority Wait time relative priority Wait time parallel operation Start delay secondary pump Collector Start function Min collector pump running time Collector frost protection temp Collector overtemperature protection Evaporation temperature of heat carrier Starting speed coll pump 1 Starting speed exch pump Starting speed buffer pump Starting speed swi pool pump Pump speed min solar Pump speed max solar Type of antifreeze added
Antifreeze concentration Volumetric flow solar pump Pulse unit yield

Unit s –
s s min min –
% % °Cmin °Cmin s min s h °C °C °C °C °C °C °C °C °C °C min min min s min s °C °C °C % % % % % %
% l/h l

Min.

Max

0

600

0: None 1: Water pressure too low 2: Water pressure too high 3: Water pressure too low or too high 4: Power-On 5: Power-On or water pressure too low 6: Power-On or water pressure too high 7: Power-On or water pressure too low/too high
Off, On

0

240

0

240

0

100

0

255

0

255

Late on early off, Late on late off, Early on late off

0

100

0

100

0

500

0

500

0

1800

0

120

0

1200

10

990

None, First, Last, First and Last

1

16

8

95

0

40

0

40

8

95

0

40

0

40

8

95

0

40

0

40

8

95

None, DHW storage tank, Buffer

2

60

1

40

0

40

0

600

5

60

5

120

-20

5

30

350

60

350

0

100

0

100

0

100

0

100

0

100

0

100

1: None (water), 2: Ethylenglycol, 3: Proplylenglykol, 4: Mixture Ethylen- and Propylenglycol

1

100

10

1500

0

100

Factory setting 0
5: Power-On or water pressure too low
Off 20 10 3 3 2 Late on early off,
40 90 100 8 300 5 60 500 None Source 1 8 8 4 30 – – – – 30 – – – – – – DHW storage tank – – – – – – 60 – – 30 –80 110 100 100 100 100 40 100 1: None (water)
30 200 10

Parameters technician

Menu DHW Storage tank

Line no. 5010 5020 5021 5022
5024 5030 5040 5050 5055 5056 5057 5060 5061 5062 5070 5085
5090 5092 5093 5101 5102 5130 5131 5140 5141 5142 5146 5148 5151

Selection possibilities Charging Flow setpoint boost Transfer boost Type of charging
Switching diff Charging time limitation Discharging protection Charging temp max Recooling temp Recooling heat gen/HCs Recooling collector El imm heater optg mode El immersion heater release El immersion heater control Automatic push Excess heat draw
With buffer With prim contr/system pump With solar integration Pump speed min Pump speed max Transfer strategy Comparison temp transfer DHW charging circuit boost DHW charging circuit boost max Delay flow set point contr Full charge with B36 Min start temp diff Q33 Charg’ cir excess superv delay

Unit

Min.

Max

Once/day, Several times/day

°C

0

30

°C

0

30

Recharging, Full charging, Full charging legio, Full

charg 1st time day, Full charg 1st time day legio

°C

0

20

min

10

600

Off, Always, Automatic

°C

8

95

°C

8

95

Off, On

Off, Summer, Always

Substitute, Summer, Always

24h/day, DHW release, Time program 4/DHW

External thermostat, DHW sensor

Off, On

Off, On

No, Yes

No, Yes

No, Yes

%

0

100

%

0

100

Off, Always, DHW release

DHW sensor B3, DHW sensor B31

°C

0

10

°C

2

20

s

0

60

No, Yes

°C

-20

20

s

0

255

Factory setting Several times/day
16 8 Full charging
5 60 Automatic 70 70 Off Always Substitute DHW release DHW sensor On On
No No Yes 100 100 Always DHW sensor B3 2 2 30 Yes 4 30

Installation & Servicing Instructions ATAG QR-Series

52

Parameters technician

Menu Configuration

Line no. 5710 5715 5721 5730
5731
5734 5736 5737 5774 5775 5840 5841 5870 5890

Selection possibilities Heating circuit 1 Heating circuit 2 Heating circuit 3 DHW sensor
DHW controlling element
Basic pos DHW div valve DHW separate circuit Optg action DHW div valve Ctrl boiler pump/DHW valve Boiler pump with DHW Solar controlling element External solar exchanger Combi storage tank Relay output QX1

5891 5892 5930

Relay output QX2 Relay output QX3 Sensor input BX1

5931

Sensor input BX2

Unit

Min.

Max

Factory setting

Off, On

On

Off, On

Off

Off, On

Off

DHW sensor B3, Thermostat,

DHW outlet sensor B38

No charging request, Charging pump,

Diverting valve

Last request, Heating circuit, DHW

DHW sensor B3 Charging pump
Last request

Off, On

Off

Position On DHW, Position On HC

Position On DHW

All requests, Request HC1/DHW only

All requests

Off, On

On

Charging pump, Diverting valve

Charging pump

Jointly, DHW storage tank, Buffer storage tank

Jointly

No, Yes

No

0: None

1:Circulating pump Q4

2:El imm heater DHW K6

3:Collector pump Q5

4:Cons circuit pump VK1 Q15

5:Boiler pump Q1

6:Bypass pump Q12

7:Alarm output K10

8:2nd pump speed HC1 Q21

9:2nd pump speed HC2 Q22

10:2nd pump speed HC3 Q23

11:Heat circuit pump HC3 Q20

12:Cons circuit pump VK2 Q18

13:System pump Q14

14:Heat gen shutoff valve Y4

15:Solid fuel boiler pump Q10

16:Time program 5 K13

17:Buffer return valve Y15

18:Solar pump ext exch K9

19:Solar ctrl elem buffer K8

20:Solar ctrl elem swi pool K18

22: Swimming pool pump Q19

25:Cascade pump Q25

26:St tank transfer pump Q11

27:DHW mixing pump Q35

28:DHW interm circ pump Q33

29:Heat request K27

30:Refrigeration request K28

33:Heat circuit pump HC1 Q2

34:Heat circuit pump HC2 Q6

35:DHW ctrl elem Q3

36:Instant heater ctrl elem Q34

38:Water filling K34

39:2nd boiler pump speed Q27

40:Status output K35

41:Status information K36

42:Flue gas damper K37

43:Fan shutdown K38

0: None

1:DHW sensor B31

2:Collector sensor B6

4:DHW circulating sensor B39

5:Buffer sensor B4

6:Buffer sensor B41

7:Flue gas temp sensor B8

8:Segment flow sensor B10

9:Solid fuel boiler sensor B22

10:DHW charging sensor B36

11:Buffer sensor B42

12:Segment return sensor B73

13:Cascade return sensor B70

14:Pool sensor B13

16:Solar flow sensor B63

17:Solar return sensor B64

19: Primary exch sensor B26

33:Heat circuit pump HC1 Q2
None DHW ctrl elem Q3
None 7:Flue gas temp sensor B8

Installation & Servicing Instructions ATAG QR-Series

53

Parameters technician

Menu Configuration

Line no. 5950

Selection possibilities Function input H1

5960
5951 5961 5953 5954 5955 5956 5970

Function input H3
Contact type H1 Contact type H3 Voltage value 1 H1 Function value 1 H1 Voltage value 2 H1 Function value 2 H1 Function input H4

5971 5973 5974 5975 5976

Contact type H4 Frequency value 1 H4 Function value 1 H4 Frequency 2 H4 Function value 2 H4

Unit

Min.

Max

0: None

1:Optg mode change HCs+DHW

2:Optg mode changeover DHW

3:Optg mode changeover HCs

4:Optg mode changeover HC1

5:Optg mode changeover HC2

6:Optg mode changeover HC3

7:Heat generation lock

8:Error/alarm message

9:Consumer request VK1

10:Consumer request VK2

11:Release swi pool source heat

12:Excess heat discharge

13:Release swi pool solar

14:Operating level DHW

15:Operating level HC1

16:Operating level HC2

17:Operating level HC3

18:Room thermostat HC1

19:Room thermostat HC2

20:Room thermostat HC3

21:DHW flow switch

22:DHW thermostat 24: Pulse count

28:Checkb sign flue gas damper

29:Start prevention

31:Boiler flow switch

32:Boiler pressure switch

51:Consumer request VK1 10V

52:Consumer request VK2 10V

54: Pressure measurement 10V

58: Preselected output 10V

NC, NO

V

0

10

-1000

5000

V

0

10

-1000

5000

0: None

1:Optg mode change HCs+DHW

2:Optg mode changeover DHW

3:Optg mode changeover HCs

4:Optg mode changeover HC1

5:Optg mode changeover HC2

6:Optg mode changeover HC3

7:Heat generation lock

8:Error/alarm message

9:Consumer request VK1

10:Consumer request VK2

11:Release swi pool source heat

12:Excess heat discharge

13:Release swi pool solar

14:Operating level DHW

15:Operating level HC1

16:Operating level HC2

17:Operating level HC3

18:Room thermostat HC1

19:Room thermostat HC2

20:Room thermostat HC3

21:DHW flow switch

22:DHW thermostat 24: Pulse count

28:Checkb sign flue gas damper

29:Start prevention

31:Boiler flow switch

32:Boiler pressure switch

50: Flow measurement Hz

NC, NO

0

1000

-1000

5000

0

1000

-1000

Factory setting None
Consumer request VK1 10V NO NO 2 200 10 850
Start prevention
NC 0 0 0 0

Installation & Servicing Instructions ATAG QR-Series

54

Parameters technician

Menu Configuration

Line no. 6016

Selection possibilities Function input H8

6017 6018

Type of contact H8 Function input H9

6019 6020 6021 6022

Type of contact H9 Function extension module 1 Function extension module 2 Function extension module 3

6024 6026 6028 6030 6031 6032 6033 6034 6035 6036 6037 6038

Funct input EX21 module 1 Funct input EX21 module 2 Funct input EX21 module 3 Relay output QX21 module 1 Relay output QX22 module 1 Relay output QX23 module 1 Relay output QX21 module 2 Relay output QX22 module 2 Relay output QX23 module 2 Relay output QX21 module 3 Relay output QX22 module 3 Relay output QX23 module 3

Unit

Min.

Max

0: None

18 Room thermostat HC1

19 Room thermostat HC2

20 Room thermostat HC1

0: Normal closed, 1: Normal opened

0: None

18 Room thermostat HC1

19 Room thermostat HC2

20 Room thermostat HC1

0: Normal closed, 1: Normal opened

0: None

1:Multifunctional

2:Heating circuit 1

3:Heating circuit 2

4:Heating circuit 3

5:Return temp controller

6:Solar DHW

7:Primary contr/system pump

0: None

25: Limit thermostat HC –

0: None

1:Circulating pump Q4

2:El imm heater DHW K6

3:Collector pump Q5 4:Cons circuit pump VK1 Q15

5:Boiler pump Q1

6:Bypass pump Q12

7:Alarm output K10

8:2nd pump speed HC1 Q21 9:2nd pump speed HC2 Q22

10:2nd pump speed HC3 Q23

11:Heat circuit pump HC3 Q20

12:Cons circuit pump VK2 Q18

13:System pump Q14

14:Heat gen shutoff valve Y4

15:Solid fuel boiler pump Q10

16:Time program 5 K13

17:Buffer return valve Y15

18:Solar pump ext exch K9

19:Solar ctrl elem buffer K8

20: Solar ctrl elem swi pool K18

22: Swimming pool pump Q19

25:Cascade pump Q25

26:St tank transfer pump Q11

27:DHW mixing pump Q35

28:DHW interm circ pump Q33

29:Heat request K27

30:Refrigeration request K28

33:Heat circuit pump HC1 Q2

34:Heat circuit pump HC2 Q6

35:DHW ctrl elem Q3

36:Instant heater ctrl elem Q34

38:Water filling K34

39:2nd boiler pump speed Q27

40:Status output K35

41:Status information K36

43: Fan shutdown K38

Factory setting 0: None
0: Normal closed 0: None
0: Normal closed No function No function No function
None None None None None None None None None None None None

Installation & Servicing Instructions ATAG QR-Series

55

Parameters technician

Menu Configuration

Line no. 6040 6041 6042 6043 6044 6045

Selection possibilities Sensor input BX21 module 1 Sensor input BX22 module 1 Sensor input BX21 module 2 Sensor input BX22 module 2 Sensor input BX21 module 3 Sensor input BX22 module 3

6046 6054 6062

Function input H2 module 1 Function input H2 module 2 Function input H2 module 3

6047 6055 6063 6049 6057 6065 6050 6058 6066

Contact type H2 module 1 Contact type H2 module 2 Contact type H2 module 3 Voltage value 1 H2 module 1 Voltage value 1 H2 module 2 Voltage value 1 H2 module 3 Function value 1 H2 module 1 Function value 1 H2 module 2 Function value 1 H2 module 3

Unit

Min.

Max

0: None

1: DHW sensor B31 2: Collector sensor B6

4: DHW circulation sensor B39

5: Buffer sensor B4

6: Buffer sensor B41

7: Flue gas temp sensor B8

8: Common flow sensor B10

9: Solid fuel boiler sensor B22 10: DHW charging sensor B36

11: Buffer sensor B42

12: Common return sensor B73

13: Cascade return sensor B70

14: Swimming pool sensor B13

16: Solar flow sensor B63

17: Solar return sensor B64

19: Primary exch sensor B26

0: None

1: Optg mode change HCs+DHW

2: Optg mode changeover DHW

3: Optg mode changeover HCs 4: Optg mode changeover HC1

5: Optg mode changeover HC2

6: Optg mode changeover HC3

7: Heat generation lock

8: Error/alarm message

9: Consumer request VK1

10: Consumer request VK2

11: Consumer request VK3

12: Excess heat discharge

13: Release swi pool solar

14: Operating level DHW

15: Operating level HC1

16: Operating level HC2

17: Operating level HC3

18: Room thermostat HC1

19: Room thermostat HC2

20: Room thermostat HC3

21: DHW flow switch

22: DHW thermostat

25: Limit thermostat HC

29: Start prevention

31: Boiler flow switch

NC, NO

V

V

0

10

V

-1000

5000

Factory setting None None None None None None
None None None
NO NO NO 0 0 0 0 0 0

Installation & Servicing Instructions ATAG QR-Series

56

Parameters technician

Installation & Servicing Instructions ATAG QR-Series

Menu Configuration
LPB
57

Line no. 6051 6059 6067 6052 6060 6068 6085 6086 6097 6098 6100 6110 6117 6118 6120 6200 6205 6212 6213 6215 6217 6220 6234 6236 6351

Selection possibilities Voltage value 2 H2 module 1 Voltage value 2 H2 module 2 Voltage value 2 H2 module 3 Function value 2 H2 module 1 Function value 2 H2 module 2 Function value 2 H2 module 3 Output P1 function selection Signal logic output P1 Sensor type collector Readjustm collector sensor Readjustm outside sensor Time constant building Central setpoint shift Setpoint reduction delay Frost protection plant Save sensors Reset to default parameters Control number heat generation 1 Control number heat generation 2 Control number storage tank Control number heating circuits Device SW version Boiler type number OEM Parameter set number OEM Function OT channel 1

6352

Function OT channel 2

6355 6356 6357 6359
6600 6601 6604 6610 6612 6620 6621 6623 6624 6625
6630 6631 6632 6640

Room controller HC1 Room controller HC2 Room controller HC3 Extern handling DHW
LPB-Adress Segment address LPB power supply function selection Display system message Alarm delay Central switch-over working area Summer/winter changeover automatic Operating mode changeover Manuall producer lock Dhw allocation
Cascade master Ext source with eco mode Outside temp limit external source accept Clock time source

Unit V V V °C °C h °C
K/min –


min –

Min.

Max

0

10

-1000

5000

0: None, 1: Boiler pump Q1

0: Standard, 1: Inverted

NTC, PT 1000

-20

20

-3

3

0

50

1

100

Off , 1 – 200

Off, On No, Yes No, Yes

0

199999

0

199999

0

199999

0

199999

0

99

0

65535

0

65535

1: By ext. room controller 1 2: By ext. room controller 2

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals