ATAG Q 25SR QR-Series Central Heating Boiler Instruction Manual
- June 9, 2024
- 1-800-Innovations
Table of Contents
Q 25SR QR-Series Central Heating Boiler
Operating instructions Installation & Servicing Instructions
Boiler Q 25SR Q 38SR Q 51SR Q 60SR
Q 25CR Q 38CR Q 51CR
CE PIN 0063BQ3021
QR-Series
8G.51.63.02 / 01.22 Changes reserved.
Explanations of symbols and signs on the Control Tower display
DHW mode selection
Service connection Quit menu Reset
On/Off switch
Heating operation mode selection
(Commissioning function when pressing > 3 sec.
Auto
For service purposes only)
INFO PROG
1
2 No.
°
ECO °
Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx
0 4 8 12 16 20 24
Reset
ESC
OK
l 0
Info button
Confirm Manual mode
(Deaeration mode when pressing > 3 sec.)
Chimney sweeper mode (For service purposes only)
Heat to comfort setpoint value Heat to reduced setpoint value Heat to frost Protection setpoint value* Process running – please wait Burner in operation Fault messages INFO Info level activated PROG Programming active ECO Heating temporarily switched off; ECO function active Holiday function active 1 2 Reference to heating circuit Manual mode / chimney sweeper mode No. Number of operating line (parameter number)
- Functions only in combination with QAA55. NOT with OT / On-off.
1
2 No.
°°
Operating Instructions ATAG QR-Series
2
Content Operating Instructions
1 Introduction ……………………………………………………………………………………………………………………4 2 Safety
…………………………………………………………………………………………………………………………..5 3 Description of the boiler
…………………………………………………………………………………………………..5 4 Display and
keypad…………………………………………………………………………………………………………6 5 Replenishing the central
heating system ……………………………………………………………………………8 6 Main functions of the control
panel ……………………………………………………………………………………9 7 Turning the boiler off
……………………………………………………………………………………………………..12 8 Error, maintenance and warranty
…………………………………………………………………………………….13 9 Disposal of the product
………………………………………………………………………………………………….13
Important! It is in your own interest that we should know that you have an
ATAG boiler. Please fill out the warranty card completely and send it back to
us. Then we can be fully at your service.
Content Installation & Servicing Instructions
1 Introduction ………………………………………………………………………………………………………………….16 2 Rules
…………………………………………………………………………………………………………………………16 3 Scope of
supply…………………………………………………………………………………………………………….18 4 Description of the boiler
…………………………………………………………………………………………………18 5 Mounting the
boiler………………………………………………………………………………………………………..20 6 Connecting the boiler
…………………………………………………………………………………………………….20 7 External hot water cylinders
……………………………………………………………………………………………35 8 Electrical connection
……………………………………………………………………………………………………..36 9 Boiler controls
………………………………………………………………………………………………………………38 10 Commissioning the
boiler……………………………………………………………………………………………….64 11
Maintenance…………………………………………………………………………………………………………………89 12 Error indication
……………………………………………………………………………………………………………..72
Annex A Technical specifications ……………………………………………………………………………………….74 Annex B
System water additives ………………………………………………………………………………………..76 Annex C
Dimensions ………………………………………………………………………………………………………..77 Annex D Resistance
table sensors……………………………………………………………………………………..79 Annex E.1 Installation
examples …………………………………………………………………………………………..80 Annex E.2 Clip-In module
Starter Set / Expansion…………………………………………………………………..83 Annex F Declaration of
Conformity …………………………………………………………………………………….90 Benchmark
Checklist…………………………………………………………………………………………………………….82 Service
Record…………………………………………………………………………………………………………………….83
3
Operating Instructions ATAG QR-Series
1 Introduction
These operating instructions describe the functioning and the operating of the
ATAG Q boilers.This manual is for the end user. For installation and servicing
there is an installation & servicing instructions manual for the installer.
(pag. 16).
Read this manual fully before operating the boiler. In case of doubt or errors
contact your installer.
ATAG Commercial UK reserves the right to change the specifications and
dimensions without prior notice.
Work on the boiler must be carried out by a competent person, (Ref: Gas Safe
Register) using correctly calibrated instruments with current test
certification.
When replacing parts use only ATAG Service parts.
Contact details for ATAG Heating UK Ltd can be found on the back page of this
manual.
The Benchmark Scheme ATAG Heating UK Ltd is a licensed member of the Benchmark
Scheme which aims to improve the standards of installation and commissioning
of domestic heating and hot water systems in the UK and to encourage regular
servicing to optimise safety, efficiency and performance. Benchmark is managed
and promoted by the Heating and Hotwater Industry Council. For more
information visit www.centralheating.co.uk
Please ensure that the installer has fully completed the Benchmark Checklist
on the inside back pages of the installation instructions supplied with the
product and that you have signed it to say that you have received a full and
clear explanation of its operation. The installer is legally required to
complete a commissioning checklist as a means of complying with the
appropriate Building Regulations (England and Wales).
All installations must be notified to Local Area Building Control either
directly or through a Competent Persons Scheme. A Building Regulations
Compliance Certificate will then be issued to the customer who should, on
receipt, write the Notification Number on the Benchmark Checklist.
This product should be serviced regularly to optimise its safety, efficiency
and performance. The service engineer should complete the relevant Service
Record on the Benchmark Checklist after each service.
The Benchmark Checklist may be required in the event of any warranty work and
as supporting documentation relating to home improvements in the optional
documents section of the Home Information Pack.
4
Operating Instructions ATAG QR-Series
2
Safety
Work on the installation should only be carried out by qualified personnel with calibrated equipment. When replacing parts, only ATAG Service components may be used.
The device may be operated only by authorized persons who have been instructed on the operation and use of the device. Improper use may cause damage to the device and / or to the connected installation.
ATAG do not recommend that children play with the appliance at any time.
The appliance is not to be used by children or persons with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
In case you smell gas:
– No naked flames! Do not smoke! – Do not operate electrical switches for
lights or any other appliance. – Do not use a telephone – Turn off gas supply
at meter – Open windows and doors – Notify any persons in the building and
leave the building at once. – Call Gas company or installer only when outside
the building
Protection for corrosion
Do not use any sprays, chlorine containing agents, solvents, paint etc. around
the boiler or around the air intake supply entrance of the boiler. These
substances have negative influences on the boiler and can lead to corrosion
resulting in failure of the boiler.
Checking the water pressure
Check the water pressure in the central heating installation regularly. Use
only potable water for filling. Additives only after clearance by ATAG.
Contact your installer in case of doubt.
3
Description of the boiler
Operating Instructions ATAG QR-Series
Room sealed boiler The boiler retreives its combustion air from outside then
discharges the flue gasses to the outside.
Condensing Retrieves heat from the flue gasses. Water condensates on the heat
exchanger.
Modulating Higher or lower burning according to the heat demand.
Stainless steel Super solid kind of steel which keeps its quality for life. It
will not rust or erode in contrast to composition materials, like aluminium.
The ATAG QR boiler is a room sealed, condensing and modulating central heating
boiler, with or without an integrated hot water facility. This boiler is also
approved for use as an open flued boiler according to flue category B23 and
B33.
The boiler is provided with a compact stainless steel heat exchanger with
smooth tubes. A well thought out principal using durable materials. The boiler
burns gas for supplying warmth. The heat is transferred in the heat exchanger
to the water in the central heating system. By cooling down the flue gasses
condensate is formed. This results in high efficiency. The condensate, which
has no effect on the heat exchanger and the function of the boiler, is drained
through an internal siphon.
The boiler is provided with an intelligent control system (CMS Control
Management System). The boiler anticipates the heat demand of the central
heating system or the hot water facility.
When an outside sensor is connected to the boiler, the boiler works weather
dependantly. This means that the boiler control measures the outside
temperature and flow temperature. With this data the boiler calculates the
optimal flow temperature for the installation.
5
4 Display and keypad
The boiler is equipped with a display and buttons on the front (behind the door).
The meaning of the keys and symbols are briefly described below.
Auto
A On/Off switch
B Back button (ESC)
INFO PROG
ECO
C Room temperature control
M
1
2 No.
°°
I
button
Xxxxxxxxxxxxxxxxxxxxx
D Confirmation button (OK)
L
Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx
E Function button for manual operation
0 4 8 12 16 20 24
F Chimney sweep function
G button
G Info button
H Reset button
H A
Reset
ESC
OK
I Operation mode button for
heating circuit(s)*
L Display
M Operating mode button for
B C DE F
DHW * The operating mode button
may be locked (Setting on
the OpenTherm thermostat)
The display shows the boiler water temperature in °C as standard and the
indicators under the programs that are switched on.
Meaning of the symbols on the display:
Heat to comfort setpoint value*
Heat to reduced setpoint value*
Heat to frost Protection setpoint value*
Process running – please wait
Burner in operation
Fault messages
INFO
Info level activated
PROG
Programming active
ECO
Heating temporarily switched off; ECO function active
Holiday function active
1
2
Reference to heating circuit
Manual mode / chimney sweeper mode
No.
Number of operating line (parameter number)
- Only works in combination with QAA55. NOT with OT / On-off thermostat In software version 5.1.0, “Operating mode button locked” is displayed when one of these buttons is pressed
Operating Instructions ATAG QR-Series
6
4.1 Boiler controls
Operating mode button for DHW (M) For switching on the DHW preparation (Bar
under the water tap in the display) If the boiler control is configured via
OpenTherm, no bars are visible. DHW timer program via external controller is
leading
Operation mode button for heating circuit(s) (I) (Only works in combination
with QAA55, NOT with OT/On-Off) For setting 4 different operating modes for
heating:
Automatic clock: Automatic operation according to timer program Bar in the display visible under “AUTO” by OpenTherm
Sun 24 hr:
Heating at comfort target value
Moon 24 hr:
Heating at reduced value
Protection mode: Heating switched off, frost protection active
Information button (G) Retrieval of the following information, without
influence on the control processes: Temperatures, operating condition of the
heating facility/DHW, error reports
Room temperature control button (C) With this rotating button, settings can be
selected and changed during programming and changing the room comfort
temperature
Confirmation button OK (D) Back button ESC (B) These two buttons are needed in
combination with the large rotating button (- +) for the programming and
configuration of the control unit. Settings, which cannot be changed through
the control elements, are provided by means of programming. By pushing the ESC
button you always go one step backward, whereby modified values are not taken
over. To reach the next operating level, or to store the changed values, you
must push the OK button.
Manual operation function button (E) By pushing this button, the control unit
is set to manual mode, whereby all pumps are running, the mixer is no longer
controlled and the burner is set to 60°C (Indicated by the spanner symbol).
Hold down for 3 sec. to start venting program.
Chimney sweep function button (F) MAY ONLY TO BE OPERATED BY A QUALIFIED
INSTALLER! Push this button shortly, to put the boiler in the operating mode
for measuring emissions; renewed pushing of the button deactivates this
function, or it is automatically deactivated after 15 minutes (indicated by
the spanner symbol).
Reset button (H) By pressing this button shortly, the locked condition of the
burner is deactivated.
On/Off switch (A) Position 0: The entire facility and all connected electrical
components are without electrical power. A protection against frost is not
ensured. Position I: The entire facility and all connected electrical
components are ready for operation.
7
Operating Instructions ATAG QR-Series
Filling and de-aeration of the ATAG QR and the heating installation The
heating installation is filled according to the standard method. The
installation must have been deaerated, both on the heating and the warm water
side. The water pressure can be read off in bar, either on the analog pressure
indicator or via the Info button. As soon as the heating installation has been
filled and de-aerated, the boiler will be ready for operation.
During the initial commissioning or after a power failure, the control system
starts the automatic de-aeration program. This function runs for approximately
16 minutes and stops automatically.
5 Replenishing the central heating system
3 sec.
The central heating installation needs to be filled with potable (drinking)
water. For topping up the installation you use the filling loop according to
the following procedure: (If in any doubt please contact your dealer)
1 Connect the filling loop to the cold water tap; 2 Slowly open the filling
loop; 3 Open the cold water tap; 4 Fill up slowly to 1.5 to 1.7 bar:
Press I key and turn the knob to “water pressure”. Value on the display
increases; 5 Close cold water tap; 6 Check whether the automatic de-aeration
program has been running. If not yet de-aerated: Hold down the E button for
more than 3 seconds. This function runs for approximately 16 minutes; 7 De-
aerate the complete installation, start at the lowest point; 8 Check the
waterpressure and if necessary top it up to 1,5 to 1,7 bar; 0 Close the
filling loop.
After completion of the de-aeration program, the boiler will operate again.
Check the water pressure regularly and top up the installation when necessary.
The working pressure of the installation should be between 1.5 and 1.7 bar
when the installation is cold. (Note: Before topping up the pressure, first
fill the hose with water, which prevents the entry of air into the heating
system).
It can take a while before all air has dis-appeared from a filled
installation. Especially in the first week noises can be heard which indicate
the presence of air. The de-aeration of the boiler will make this air
disappear, which means the water pressure will reduce during this period and
therefore topping up with water will be necessary to adjust the flow water
temperature.
Operating Instructions ATAG QR-Series
8
6
Button
Button
Main functions of the control panel
Action
Procedure
Setting up the required room temperature
HC2 jointly with HC1
Turn the rotating button left or right Turn the rotating button again for
storing with OK button or wait for 5 sec. or push
Setting the required room temperature
for HC1 or HC2
or
2nd HC independent of HC1
Turn rotating button left/right Then push OK Turn rotating button left/right
Save with OK button or wait for 5 sec. or push
Switching warm water operations ON or OFF
Push button
Factory setting
Change operating mode
1 x short push of button and then once more, short push of button
once more, short push of button
Control stop function
Action
Display of various information
1 x push button (> 3 sec) push button once more (> 3 sec)
Procedure
1 x push button push button again push button again
Push button
Operating mode according to target values that are set manually
Change of the factory setting for boiler temperature
short push of button
short push of button short push of button Rotating button turn -/+ short push
of button short push of button short push of button
De-aeration function 1 x push button (> 3 sec) push button once more (> 3 sec)
Activation of chimney sweep function
Push button (> 3 sec) push button once more (> 3 sec)
Display / Function
comfort target value with blinking temperature display blinking temperature
display in steps of 0.5° centigrade, from 10.0 to 30°C
Comfort value active Comfort value not active – Basic display appears after 3
sec.
Select heating circuit Heating circuit active blinking temperature display in
steps of 0.5° centigrade, from 10.0 to 30°C Comfort target value active
Comfort target value not active – Basic display appears after 3 sec.
Only works in combination with QAA55, NOT with OT Works with on / off controller via H8 / H9
Warm water operation ON / OFF
(segmented bar under symbol for warm water visible/invisible) – ON: Warm water
preparation according to switching program – OFF: No warm water preparation –
Safety function active When using OpenTherm, “operating mode button is locked”
is displayed Safety functions remain active!
Automatic operating mode ON, with:
– heating operation according to timer program – Temperature target values
according to heating program – Safety function active
– Summer/Winter – automatic switching active – ECO functions active (segmented
bar under corresponding symbol visible)
Continuous COMFORT heating ON, with:
– Heating operation without timer program, at comfort target value – Safety
function active
Continuous REDUCED heating ON, with:
– Heating operation without timer program, at reduced target value – Safety
function active
– Summer/Winter – automatic switching active – ECO functions active Automatic
safety mode ON, with:
– Heating operations switched off – Temperature according to frost protection
value – Safety function active When using OpenTherm, “operating mode button is
locked” is displayed Safety functions remain active!
304: Control stop function Basic display appears after 3 sec.
Set target value
Display / Function
INFO section is displayed
– Boiler status
– Room temperature
– Room temperature minimum
– Warm water status
– Room temperature maximum
– Status heating circuit 1 – Outdoor temperature
– Status heating circuit 2 – Minimum outdoor temperature
– Maximum outdoor temperature
– Time / date – Water temperature 1
– Error message
– Boiler temperature
– Maintenance report
– Flow temperature
(Display of the information lines depends on the configuration)
Back to basic display; INFO segment is suppressed
Manual operating mode ON (spanner symbol is visible) – Heating operations at preset boiler temperature (factory setting = 60°C)
301: Manual operation mode
operation? Blinking temperature display Set required target value
Set target value for manual
Boiler status Manual operating mode OFF (spanner symbol disappears)
312: De-aeration function ON De-aeration function OFF
Chimney sweep function ON Chimney sweep function OFF
DHW timer program via external
controller is leading
Only works in combination with QAA55, NOT with OT Works with on / off
controller via H8 / H9
Operating Instructions ATAG QR-Series
RESET
Short-term reduction of room temperature at QAA75 / 78
Reset button
Push button push button again
Heating at reduced target value Heating at comfort target value
Push button (< 3 sec.) push button again > 3 sec.
Facility is manually locked, unreleased equipment is unlocked, alarm bell disappears
= Confirmation
= Abort or back to basic display
MAY ONLY BE OPERATED BY A QUALIFIED INSTALLER!
Only works in combination with QAA55, NOT with
OT/On-Off
9
6.1 Parameters end users
Basic display “Boiler temperature” – Push OK button once – Use +- rotating
button for selecting for instance “Drinking water menu” – Push OK button once
– Use +- rotating button, for instance in the drinking water menu, for
selecting “Parameter no. 1612 – Reduced target value” – Push OK button once –
Use +- rotating button to change the currently set value – Push OK button once
-> the value is stored – Push 2 x ESC to return to the basic display “Boiler
temperature . .”
Time programs are not active when using an OpenTherm thermostat, however, they
are active when switching on and off via H8 / H9
Menu Time of day and date Operator section Time program HC 1
Time program HC 2 (When activated)
Time program 3/ HC3
Time program 4/ DHW
Line no. 1 2 3 20
Selection possibilities Hours / Minutes Day / Month Year Language
500
Preselection
501
Mo-Su: 1. Phase On
502
Mo-Su: 1. Phase Off
503
Mo-Su: 2. Phase On
504
Mo-Su: 2. Phase Off
505
Mo-Su: 3. Phase On
506
Mo-Su: 3. Phase Off
516
Default values
520
Preselection
521
Mo-Su: 1. Phase On
522
Mo-Su: 1. Phase Off
523
Mo-Su: 2. Phase On
524
Mo-Su: 2. Phase Off
525
Mo-Su: 3. Phase On
526
Mo-Su: 3. Phase Off
536
Default values
540
Preselection
541
Mo-Su: 1. Phase On
542
Mo-Su: 1. Phase Off
543
Mo-Su: 2. Phase On
544
Mo-Su: 2. Phase Off
545
Mo-Su: 3. Phase On
546
Mo-Su: 3. Phase Off
556
Default values
560
Preselection
561
Mo-Su: 1. Phase On
562
Mo-Su: 1. Phase Off
563
Mo-Su: 2. Phase On
564
Mo-Su: 2. Phase Off
565
Mo-Su: 3. Phase On
566
Mo-Su: 3. Phase Off
576
Default values
Unit hh:mm dd:MM
yyyy –
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
uu:mm uu:mm uu:mm uu:mm uu:mm –
Min.
Max
00:00
23.59
01.01
31.12.
2004
2099
English, German, French, Italian, Danish, Dutch, Spanish, Czech, Slovenian, Turkish
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Factory setting –.—.—.–
German
Mo-Su 06:00 22:00 –.—.—.—.–
No Mo-Su 06:00 22:00
–.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No
Only works in combination with QAA55, NOT with OT Works with on / off
controller via H8 / H9
Only if parameter 6359 is active
Operating Instructions ATAG QR-Series
10
Parameters end users
Menu Time program 5
Holidays HC1
Holidays HC2 (When activated) HC1
HC 2 (When activated) DHW Swimming pool Boiler Error
Line no. 600 601 602 603 604 605 606 616 641 642 643 648 651 652 653 658 710 712 714 720 730 1010 1012 1014 1020 1030 1600 1610 1612 2055 2056 2214 6700 6705 6706
Selection possibilities Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Period Start Day / Month Periode End Day / Month Operating level Preselection Period Start Day / Month Periode End Day / Month Operating level Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Summer/winter heating limit Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Summer/winter heating limit Operating mode Nominal setpoint Reduced setpoint Pool setpoint solar heating Pool sepoint boiler heating Setpoint manual control Error message SW Diagnose Code Burner ctrl phase lockout pos
Unit –
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
tt.MM tt.MM tt.MM tt.MM °C °C °C °C °C °C °C °C °C °C °C °C °C –
–
–
Min.
Max
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Period 1, 2, 3, 4, 5, 6, 7, 8
01.01
31.12
01.01
31.12
Frost protection, Reduced
Frost protection
Period 1, 2, 3, 4, 5, 6, 7, 8
01.01
31.12
01.01
31.12
Frost protection, Reduced
Frost protection
Value from Line no. 712
35
4
Value from Line no. 710
4
Value from Line no. 712
0.10
4.00
—/8
30
Value from Line no. 1012
35
4
Value from Line no. 1010
4
Value from Line no. 1012
0.10
4.00
—/8
30
Off, On, Eco
Value from Line no. 1612
80
8
Value from Line no. 1610
8
80
8
80
10
90
–
–
–
–
–
–
Factory setting Mo-Su 06:00 22:00 –.—.—.—.-No Period 1 –.—.–
Frost protection Period 1 –.—.–
Frost protection 20.0 16.0 10.0 1.50 20 20.0 16.0 10.0 0.8 0 Off 55 40 26 22
50
Indication only Indication only Indication only
Only works in combination
with QAA55, NOT with OT Works with on / off controller via H8 / H9
Operating Instructions ATAG QR-Series
11
6.2 Display of information
Display of information The information button can be used for displaying different information.
Possible information values Depending on the type of installation, its configuration and the operating condition, individual lines of information may not be visible.
AUTO
Room temperature
0
4
8
12
16
20
24
– Error message ( or -symbol) – Maintenance report – Room temperature – Room temperature minimum – Room temperature maximum – Boiler temperature – Outdoor temperature – Outdoor temperature minimum – Outdoor temperature maximum – DHW temperature 1 – Boiler status – DHW status – Heating circuit status 1/2 – Time / date – Customer service telephone
7
Turning the boiler off
In case of holidays, for example: Make sure there is no heat demand: set the
room thermostat low*.
DHW (Hot water) Switch off DHW program: Press the DHW function button (M)
until the lowest value is reached. The beam (bar) under the tap disappears.
Switching on works in reverse order.
Heating (Only works in combination with QAA55, NOT with OT/On-Off) Switch off
the heating program: Press the heating mode key (I) until the bar is at the
far right of the display = frost protection Switching on works in reverse
order.
In case of work on the central heating system: Make sure there is no heat
demand: no open hot water tap and room thermostat low. Set the main switch to
0 and pull the plug out of the wall socket. When the boiler is being drained
one should take into account that a part of the heating water will remain in
the boiler. When risk of frost arises one should take care that the remaining
central heating water in the boiler does not freeze.
Operating Instructions ATAG QR-Series
12
8 Error, maintenance and warranty
AUTO
Error
30:Flow temperature 1
Text3
Text4
0
4
8
A1U2TO 16
20
24
Maintenance
3:Maintenance interval
Text3
Text4
0
4
8
12
16
20
24
Error message / Maintenance In exceptional cases, one of the following symbols
will be displayed in the default display:
Error messages An error has been detected in the boiler, when this symbol is
shown. Detailed information is available by pushing the information button.
With On / Off thermostat: if the thermostat is OFF (contact open), the symbol
will be displayed. This does not affect the operation. No intervention
required.
Maintenance or special mode When this symbol is displayed, then a maintenance
report is displayed or the boiler is in special mode. Detailed information is
available by pushing the information button.
If you discover any leaks from the boiler contact your installer.
The casing of the boiler consists of metal and plastic parts which can be
cleaned with a normal non abrasive cleaning agent.
You can find the warranty conditions in the warranty card which is supplied
with the boiler.
9 Disposal of the product
This product should be handed in at a designated collection point, e.g. by
handing it in at a duly authorized reseller when purchasing a similar product,
or at an authorized collection site for recycling products wich contains
electrical and electronic equipment (EEE) and batteries and accumulators.
Because of the potentially hazardous substances that usually accompany EEE,
improper handling of this type of waste could have a possible impact on the
environment and human health. Your cooperation in the proper disposal of this
product will contribute to the effective usage of natural resources. For more
information on recycling this product, please contact your city office, local
waste disposal facilities, official service for chemical waste, landfill site,
or your supplier.
Operating Instructions ATAG QR-Series
13
Explanations of symbols and signs on the Control Tower display
DHW mode selection
Service connection Quit menu Reset
On/Off switch
Heating operation mode selection
(Commissioning function when pressing > 3 sec.
Auto
For service purposes only)
INFO PROG 1 2 No.
ECO
°°
Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx Xxxxxxxxxxxxxxxxxxxxx
0 4 8 12 16 20 24
Reset
ESC
OK
l 0
Info button
Confirm Manual mode
(Deaeration mode when pressing > 3 sec.)
Chimney sweeper mode (For service purposes only)
Heat to comfort setpoint value Heat to reduced setpoint value Heat to frost Protection setpoint value* Process running – please wait Burner in operation Fault messages INFO Info level activated PROG Programming active ECO Heating temporarily switched off; ECO function active Holiday function active 1 2 Reference to heating circuit Manual mode / chimney sweeper mode No. Number of operating line (parameter number)
- Only works in combination with QAA55. NOT with OT / On-off thermostat
1
2 No.
°°
Installation & Servicing Instructions ATAG QR-Series
14
Content
1 Introduction ………………………………………………………………………………………………………………….16 2 Rules
…………………………………………………………………………………………………………………………16 3 Scope of the
supply……………………………………………………………………………………………………….18 4 Description of the boiler
…………………………………………………………………………………………………18 5 Mounting the
boiler………………………………………………………………………………………………………..20 6 Connecting the boiler
…………………………………………………………………………………………………….21
6.1 Central heating system ………………………………………………………………………………………..21 6.2 Expansion
vessel ………………………………………………………………………………………………..23 6.3 Underfloor heating system
(plastic pipes)……………………………………………………………….24 6.4 Water quality
……………………………………………………………………………………………………… 24 6.5 Gas connection
…………………………………………………………………………………………………..26 6.6 Hot water supply
…………………………………………………………………………………………………26 6.7 Condensation drain pipe
………………………………………………………………………………………27 6.8 Flue gas exhaust system and air supply
system ……………………………………………………..29 6.8.1 Dimensions of the flue gas and air
intake duct ………………………………………………………..34 7 External hot water cylinders
……………………………………………………………………………………………35 8 Electrical connection
……………………………………………………………………………………………………..36 9 Boiler controls
………………………………………………………………………………………………………………38 9.1 Explanation of the function
keys ……………………………………………………………………………38 9.2 Main functions of the control panel
………………………………………………………………………..40 9.3 Parameters end
users………………………………………………………………………………………….41 9.4 Parameters technician
…………………………………………………………………………………………43 9.5 Menu: Heating circuits
…………………………………………………………………………………………63 10 Commissioning the
boiler……………………………………………………………………………………………….64 10.1 Preparations for first
use………………………………………………………………………………………65 10.2 Hot water supply
…………………………………………………………………………………………………65 10.3 The O2 / CO2 check on full load
(Step 1/3)………………………………………………………………66 10.4 The O2 / CO2 check on low load (Step
2/3)……………………………………………………………..67 10.5 Adjustment on the gas valve (Step 3/3)
………………………………………………………………….68 11
Maintenance…………………………………………………………………………………………………………………69 11.1 Maintenance
activities………………………………………………………………………………………….69 11.2 Maintenance
frequency………………………………………………………………………………………..71 11.3
Warranty…………………………………………………………………………………………………………….71 12 Error indication
……………………………………………………………………………………………………………..72
Annex A Technical specifications ……………………………………………………………………………………….74 Annex B
System water additives ………………………………………………………………………………………..76 Annex C
Dimensions ………………………………………………………………………………………………………..77 Annex D Resistance
table sensors……………………………………………………………………………………..79 Annex E.1 Installation
examples …………………………………………………………………………………………..80 Annex E.2 Clip-In module
Starter Set / Expansion…………………………………………………………………..83 Annex F Declaration of
Conformity …………………………………………………………………………………….90
Benchmark Checklist…………………………………………………………………………………………………………….92 Service
Record…………………………………………………………………………………………………………………….93
Work on the installation should only be carried out by qualified personnel
with calibrated equipment and appropriate tools.
15
Installation & Servicing Instructions ATAG QR-Series
1
Introduction
These instructions describe the functioning, installation, use and primary maintenance of ATAG QR series boilers for the United Kingdom.
These instructions are intended for the use by Gas Safe Register approved contractors in connection with the installation and putting into operation of ATAG boilers. It is advisable to read these instructions thoroughly, well in advance of installation. ATAG is not liable for the consequences of mistakes or shortcomings which have found their way into the installation instructions or user’s manual. Further, ATAG reserves the right to alter its products without prior notification.
When delivering the unit, give the customer clear instructions concerning its use; present the customer with the user’s manual and card.
Each unit is fitted with an data plate. Consult the details on this plate to verify whether the unit is compliant with its intended location, e.g.: gas type, power source and exhaust classification.
On completion of the installation the installer or commissioning engineer must fill out and complete the Benchmark Commissioning Checklist found on page 92 of this manual and hand this to the customer for future record keeping. The Benchmark Service Record must also be completed by the service agent following each service call, and return to the customer. A copy of the Benchmark Commissioning Checklist must be returned to ATAG Commercial UK, along with the warranty registration card to register the appliance for the standard warranty benefits.
Relevant Installation, Service and User manuals:
– ATAG Cascade
Hydraulic cascade system
– ATAG Duopass
Flue system individual
2
Rules
Installation & Servicing Instructions ATAG QR-Series
The following regulations apply to installation of ATAG QR series boilers:
Legislation and Regulations Gas Safety (Installation and Use). All gas
appliances must by law, be installed by a competent person, eg. Members of Gas
Safe Register and in accordance with the current Gas Safety Regulation.
Failure to install appliance correctly could lead to prosecution. All Gas Safe
Register approved contractors carry a Gas Safe Register ID Card and have a
registration number. You can call Gas Safe Register direct on 01256 372300
British Standards BS5440 parts 1 & 2 – Installation & Maintenance of Flues &
Ventilation for gas appliances not exceeding 70kW input BS6644 – Specification
for the Installation & Maintenance of hot water boilers of rated inputs
between 70kW & 1.8MW BS 6798 – Installation of gas fired hot water boilers of
rated input not exceeding 70 kW. BS6891 – Specification for the installation
and maintenance of low pressure gas installation pipework of up to 35 mm
(R11/4) BS 7074 – Application, selection and installation of expansion vessels
and ancillary equipment for sealed water systems. BS 8552 – Sampling &
Monitoring of Water from Building Services Closed Systems BS EN 60335 Pt1 –
Safety of household and similar electrical appliances. General requirements BS
EN 12828 – Heating Systems in Buildings – Design for Water Based Heating
Systems) BS EN 12831 – Heating Systems in buildings: Method for calculation of
the design heat load. BS EN 14336 – Heating Systems in buildings: Installation
and commissioning of water based heating systems.
16
IGEM Documents IGE/UP/1&1A – Strength testing, tightness testing and direct
purging of small, low pressure commercial Natural Gas installations. IGE/UP/2
– Installation pipework on commercial premises IGE/UP/10 – Installation of
flued gas appliances – applicable to light commercial installations
UK Regulation Clean Air Act 1993 – applicable to light commercial
installations IEE Regulations Building Regulations Gas Safety (Installation &
Use) Regulations
Other Guidance BSRIA Documents BG29/2012 – (Pre-commissioning & Cleaning of
Pipework Systems) BG50/2013 – Water Treatment for Closed Heating & Cooling
Systems) ICOM document ‘Water Treatment & Conditioning of Commercial Heating
Systems’
In addition to the above regulations this appliance must be installed in
compliance with the current IEE Regulations, the Building Standards (Scotland
Consolidation) Regulations. Regulations and bye laws of the Local Water
Authority and the Current Health and Safety Regulation.
The Benchmark Scheme Benchmark places responsibilities on both manufacturers
and installers. The purpose is to ensure that customers are provided with the
correct equipment for their needs, that it is installed, commissioned and
serviced in accordance with the manufacturer’s instructions by competent
persons and that it meets the requirements of the appropriate Building
Regulations. The Benchmark Checklist can be used to demonstrate compliance
with Building Regulations and should be provided to the customer for future
reference.
Installers are required to carry out installation, commissioning and servicing
work in accordance with the Benchmark Code of Practice which is available from
the Heating and Hotwater Industry Council who manage and promote the Scheme.
Visit www.centralheating.co.uk for more information.
The current, Electricity at Work Regulation must be complied with and also be
in accordance with the relevant and current editions of the British Standards.
The ATAG QR boiler is a certified appliance and must not be modified or
installed in any way contrary to this Installation Manual. Manufacturers
instructions must not be taken in any way as overriding statutory obligations.
The ATAG QR is a central heating unit with an optional integrated hot water
function. These units must be connected according to these instructions and
all installation norms in respect of the part of the unit to be connected.
17
Installation & Servicing Instructions ATAG QR-Series
The device may be operated only by authorized persons who have been instructed
on the operation and use of the device. Improper use may cause damage to the
device and / or to the connected installation.
The appliance is not to be used by children or persons with reduced physical,
sensory or mental capabilities, or lack of experience and knowledge, unless
they have been given supervision or instructions.
ATAG do not recommend that children play with the appliance at any time.
Observe the following rules of safety: – All work on the unit must take place
in a dry environment. – ATAG units may never be in operation without their
housing, except in connection
with maintenance or adjustments (see Chapter 10 and 11). – Never allow
electrical or electronic components to come into contact with water.
Carry out the following tasks in connection with maintenance, etc. to an
already-installed unit:
– Shut down all programmes – Close the gas tap – Remove the plug from the wall
socket – Close the stop cock of the unit’s intake connection
Take note of the following when maintenance or adjustments are needed: – The
unit must be able to function during these activities; for this reason, the
unit’s
supply voltage, gas pressure and water pressure must be maintained. Ensure
that these is not a source of potential danger during these activities.
Following maintenance or other activities; always check the installation of
all parts through which gas flows using leak detection fluid (LDF).
Following maintenance or other activities, always replace the housing and
secure it with the screw behind the door at the front of the casing.
The following (safety) symbols may be encountered in these installation
instructions and on the unit:
This symbol indicates that the unit must be stored away from frost.
This symbol indicates that the packaging and/or contents can be damaged as a
result of insufficient care taken during transport.
This symbol indicates that, whilst still in its packaging, the unit must be
protected from weather conditions during transport and storage.
KEY-symbol. This symbol indicates that assembly or dismantling, must be
carried out.
ATTENTION symbol. This symbol indicates that extra attention must be paid in
connection with a particular operation.
Useful tip or advice
18
Installation & Servicing Instructions ATAG QR-Series
3
Scope of the supply
The boiler is supplied ready for use. The supply kit is composed as follows:
· Boiler with casing;
· Gas isolation valve
· Automatic vent (inside the boiler);
· Concentric flue adapter 80/125;
· Safety valve (inside the boiler);
· Template on the package wrapper;
· Suspension bracket
· Installation instructions;
· Draining valve with T-piece;
· Operating manual;
· Fixing material consisting of plugs and · Warranty card;
screws;
· Benchmark logbook.
4
Description of the boiler
Room sealed boiler The boiler retreives its combustion air to outside then
discharges the flue gasses to the outside.
Condensing Retrieves heat from the flue gasses. Water condensates on the heat
exchanger.
Modulating Higher or lower burning according to the heat demand.
Stainless Super solid kind of steel which keeps its quality for life. It will
not rust or erode in contrast to composition materials, like aluminium.
The ATAG QR boiler is a room sealed, condensing and modulating central heating
boiler, with or without an integrated hot water facility.
The boiler is provided with a compact stainless steel heat exchanger with
smooth tubes. A well thought out principal using durable materials. The boiler
burns gas for supplying warmth. The heat is transferred in the heat exchanger
to the water in the central heating system. By cooling down the flue gasses
condensate is formed. This results in high efficiency. The condensate, which
has no effect on the heat exchanger and the function of the boiler, is drained
through an internal siphon.
The boiler is provided with an intelligent control system (CMS Control
Management System). The boiler anticipates the heat demand of the central
heating system or the hot water facility.
When an outside sensor is connected to the boiler works weather dependantly.
This means that the boiler control measures the outside temperature and flow
temperature. With this data the boiler calculates the optimal flow temperature
for the installation.
Explanation of the type indication: Q = Type 51 = Nominal load in kW C = Combi
(S = Solo)
R = Refresh
ATAG Q 51CR
The boiler has been tested according to valid CE standards and has a CE
certificate and ErP & Energy Labelling EU 813/2013 & EU 1369/2017 A-rating.
Statement: No banned materials including asbestos, mercury, CFC’s have not or
will not be included in the product.
Installation & Servicing Instructions ATAG QR-Series
19
4
2
13 5
8 17 16
7
6
19
9
T1 T1a
P1 T2 T3
ATAG QR
G 18
A
R
C
E
10
12 11
14 13
K
W
15
figure 4.a
Installation & Servicing Instructions ATAG QR-Series
1 heat exchanger 2 ignition unit 3 fan unit 4 air inlet damper 5 gas valve 6 safety valve 7 automatic air vent 8 ceramic burner cassette
9 cylinder DHW, 12l (combi) 10 operating panel
11 Control Tower (CMS) 12 water filter return CH 13 three-way valve 14
circulation pump (A-label)
15 thermostatic mixing valve 16 flue gas discharge
17 combustion air supply 18 type plate 19 expansion vessel, only Q25CR
and Q38CR (14 liter)
T1 flow sensor T1a secondary flow sensor (Q60SR) T2 return sensor T3 cylinder sensor DHW (combi) P1 water pressure sensor
G gas pipe A flow connection central heating R return connection central
heating C condensation / safety discharge
pipe
E expansion vessel pipe K cold water pipe (combi) W hot water pipe (combi)
20
5 Mounting the boiler
Install the boiler in a well-ventilated boiler room in accordance to the
actual local regulations BS5440-2:2000. The room where the boiler will be
placed must always be frost free. It is NOT necessary to have a purpose
provided air vent in the room or internal space in which the boiler is
installed. Neither is it necessary to ventilate a cupboard or compartment in
which the boiler is installed, due to the extremely low surface temperature of
the boiler casing during operation. Therefore the requirements of BS 6798,
Clause 12, and BS5440:2 may be disregarded. The boiler can be mounted
practically to any wall with the suspension bracket and the enclosed fixing
equipment. The wall must be flat and of sufficient strength in order to be
able to carry the boiler weight with its water content. Above the boiler there
must be at least 250 mm working space in order to be able to fit a coaxial
flue system or a twin supply. On the left side of the boiler at least 50 mm
and on the right side 10 mm must be reserved to allow fitting or removing of
casing. The location of the boiler can be determined by using the template
located inside the boiler packaging. Lift the boiler only by the boilers rear
wall plate.
Lifting and carrying precautions: – Lift only a manageable weight, or ask for
help. – When lifting the boiler, bend the knees, and keep the back straight
and feet
apart. – Do not lift and twist at the same time. – Lift and carry the boiler
close to the body. – Wear protective clothing and gloves to protect from any
sharp edges.
21
Installation & Servicing Instructions ATAG QR-Series
6
Connecting the boiler
The boiler has the following connection pipes; – The central heating pipes.
These can be connected to the installation by means of compression fittings; –
The gas pipe.
It is provided with a female thread into which the tail piece of the supplied
gas isolation valve can be screwed; – The condensation drain pipe. It consists
of an oval 24 mm plastic pipe. The drain pipe can be connected to this by
means of an open connection. If the open connection is fitted in a different
location, then the pipe can be lengthened by means of a 32 mm PVC sleeve; –
The flue gas exhaust system and air supply system. It consists of a concentric
connection 80/125 mm. The Q51SR and Q60SR are supplied with this feature for
converting from the standard 2x 80 mm to concentric 80/125 mm. – Cold and hot
water pipes. Only Combi boilers: These consist of 15 mm copper pipe and can be
connected to the installation by means of compression fittings.
It is recommended that isolation valves are fitted to all heating and hot
water connections to facilitate ease of future maintenance.
It is advisable to spray-clean all of the unit’s connecting pipes and/or to
sprayclean/blow-clean the installation before connecting it to the unit.
6.1 Central heating system
Connect the central heating system according to the actual regulations.
The boiler pipes can be connected to the installation by means of compression fittings. Reducers should be used for connecting to thick-walled pipe (welded or threaded).
When removing the plastic sealing caps from the pipes, contaminated testing water may be released.
The boiler has a self-adjusting and self-protecting control system for the load and the pump capacity. This means the temperature difference between the flow and return water is checked. Table 6.1.a shows the water displacement which supplies the circulation pump at certain installation resistance.
Combi Solo
Boiler type
Q25CR Q38CR Q51CR Q25SR Q38SR Q51SR Q60SR
Pump type UPM2 20-70 20-70 20-70 20-70 20-70 20-70 20-70
Permissible installation
Water flow rate
resistance
l/min
l/h
kPa
mbar
15.8
950
25
250
24.0
1440
20
200
Low velocity header required
15.8
950
25
250
24.0
1440
20
200
Low velocity header required
Low velocity header required
Installation resistance
table 6.1.a
Installation & Servicing Instructions ATAG QR-Series
A low velocity header must be connected to the Q51CR, Q51SR and Q60SR to
prevent flow problems over the boiler.
ATAG can supply the AA1OV09U Low velocity header for 1 boiler. This can be
connected directly under the boiler on the flow and return pipe.
22
external installation pump with low velocity header
figure 6.1.a
If the installation resistance is higher than the stated value the pump will
rotate at maximum pump capacity and the load will be adjusted until an
acceptable temperature difference between flow and return water has been
obtained. If, after this, the temperature difference remains to much then the
boiler will switch itself off and wait until an acceptable temperature has
arisen (T 20°C). If an unacceptable temperature is detected, then the control
will repeatedly try to achieve water flow, and if this does not work then the
boiler will switch off. If the capacity of the boiler pump is insufficient, an
extra external pump can be installed in combination with a low velocity header
in series with the boiler. The electrical side of this external circulation
pump can be connected in the Control Panel, which means this pump switches at
the same times as the boiler pump. The maximum absorbed current consumption of
the external circulation pump may be 230 W (1 Amp). The extra external pump
must be selected according the installation resistance and required flow.
As standard the boiler is provided with a water filter in the return pipe of
the boiler. With this, possible contamination of the central heating water is
prevented from ending up in the boiler. The boiler is also provided with an
internal safety valve set at 3 bar. This is connected to the waste discharge
together with the condensation discharge.
If all, or a substantial part of the radiators have thermostatic radiator
valves or if 2-port zone valve are installed, an automatic by-pass valve must
be used to prevent flow rate problems. The automatic by-pass valve used should
have the same diameter as the connecting diameter of the supply and return
pipe of the boiler. A decrease of pipe diameter between boiler and by-pass is
not allowed. See also Annex C.
The boiler is designed to be used on sealed system only.
Additives in the installation water are only permitted in consultation with
the country distributor. See chapter 6.4.
When using more than one boiler in an installation please refer to the cascade
installation instructions.
Installation & Servicing Instructions ATAG QR-Series
23
6.2 Expansion vessel
The central heating system must be provided with an expansion vessel. The expansion vessel which is used should be geared to the water content of the installation. The precharge pressure depends on the installation height above the mounted expansion vessel. See table 6.2.a.
installation height above the expansion vessel
5 m 10 m 15 m choice of expansion vessel
pre-charge pressure of the expansion vessel
0,5 bar
1,0 bar
1,5 bar
table 6.2.a
The Q51CR Combi boiler is provided with an expansion vessel connection. This
pipe is connected between the three way valve and boiler pump. This prevents
the expanding water, during hot water production, from being closed off from
the expansion vessel, when the thermostatic radiator valves are fully closed.
A second expansion vessel in the installation is not a problem. The Solo
boilers Q25SR and Q38SR are provided with an expansion vessel connection. When
this boiler is combined with a cylinder, the expansion vessel connection is
included in the internal piping of the cylinder circuit, to which the
expansion vessel can be connected.
In connection with correct functioning of the boiler it is necessary for the
expansion vessel to be connected to the expansion vessel pipe of the boiler.
The Solo boilers Q51SR and Q60SR are not provided with an expansion vessel
connection. When one of these Solo boilers is combined with a cylinder then
one has to take into account that the expansion vessel should be connected
between the three-way valve and the boiler circulation pump.
Installation & Servicing Instructions ATAG QR-Series
24
6.3 Underfloor heating system (plastic pipes)
When connecting or using an underfloor heating system, designed with plastic
pipes, or plastic pipes are used elsewhere in the installation,one should
ensure that the plastic pipes used comply with the DIN is BS7291-1: 1990
standard. It is set out in this standard that the pipes may not have oxygen
permeability higher than 0.1 g/m³.d at 40°C. If the system does not comply
with this DIN standard, the underfloor heating component will have to be
separated from the central heating appliance by means of a plate exchanger.
No recourse can be made to the terms of the warranty in the event of failure
to observe the regulations pertaining to plastic underfloor heating pipes.
6.4 Water quality
Fill the installation with drinking water.
In most cases, a heating system can be filled with water according to national
standards for water and treatment of this water is not necessary. In order to
avoid problems with the CH-installations, the quality of the filling water has
to meet the specifications mentioned in table 6.4.a: If the filling water does
not meet the required specifications, you are advised to treat the water to
such an extent that it does meet the required specifications.
The warranty becomes invalid, if the installation has not been flushed and/or
the quality of the filling water does not meet the specifications recommended
by ATAG Commercial UK Always contact ATAG Commercial UK in advance, if things
are not clear or you wish to discuss any deviations. Without approval, the
warranty becomes invalid.
Installation: – The use of groundwater, demi-water and distilled water is
prohibited. (on the next page you will find an explanation of these
definitions) – If the drinking water quality meets the specifications
mentioned in table 6.5.a, you can start flushing the installation before
installing the device. – Whilst flushing, corrosion products (magnetite),
fitting products, cutting oil and other undesirable products have to be
removed. – Another possibility is to remove the pollution by installing a
filter. The filter type has to fit the type and grain size of the pollution.
ATAG Commercial UK recommends filter usage. – In this case, the whole piping
system should be taken into consideration. – The CH-installation has to be
properly vented before using the system. For that purpose, we refer to the
commissioning chapter. – If a regular water top up is required (>5% on an
annual basis), then there is a structural problem and an installer has to
solve the problem. Regularly adding fresh water to the system also adds
additional calcium and oxygen implying that magnetite and calcium residues can
continue. The result may be blockages and/or leakages. – The use of Frost
Protection and other additives requires periodical quality checks of the
filling water in accordance with the period laid down by the additives
supplier. – Chemical additions are to be avoided and should only be used
afterATAG Commercial UK has approved their corresponding use. – Should you
wish to achieve the required water quality by using chemical additives, then
this is your own responsibility. The warranty on the product delivered by ATAG
Commercial UK expires, if the water quality does not meet ATAG Heating’s
specifications or the chemical additives have not been approved by ATAG
Commercial UK. – On installation and during additions or changes at a later
stage, ATAG Commercial UK recommends to keep a record of the type of water
used, its quality at the time, and if applicable, which additives and
quantities were added (see Annex B – System water addetives on page 78.
25
Installation & Servicing Instructions ATAG QR-Series
Parameter
Value
Water type
Potable water Softened water
pH
6.0-8.5
Conductivity (at 20°C in µS/cm)
Max. 2500
Iron (ppm)
Max. 0.2
Hardness (°dH):
Installation volume/capacity 1-12 <20 l/kW
Installation volume/capacity 1-7 >=20 l/kW
Oxygen
No oxygen diffusion allowed during operation. Max. 5% filling water addition annually
Corrosion inhibitors
Refer to Additives Attachment
pH increasing or lowering agents
Refer to Additives Attachment
Frost Protection additives
Refer to Additives Attachment
Other chemical additives
Refer to Additives Attachment
Solid substances
Not allowed
Residues of processing water not for- Not allowed ming part of the drinking water
Water quality in DHW facility
Parameter
Value
Water type
Potable water
pH
7.0-9.5
Conductivity (at 20°C in µS/cm)
Max. 2500
Chloride (ppm)
Max. 150
Iron (ppm)
Max. 0.2
Hardness (°dH)
1-12
Number of bacterial colonies at 22°C Max. 100 (number/ml). pr EN ISO 6222
table 6.4.a table 6.4.b
– When the amount of chloride is above the required specifications mentioned above in table 6.4.b, it is necessary to apply an active anode in case of the use of a DHW cylinder. If this is not met it will void the warranty for DHW parts of the installation. – When the amount of chloride is above the required specifications mentioned above in table 6.4.b, in case of the use of a combi boiler will void the warranty for DHW parts of the boiler.
Water type definition:
Potable water: Tap water compliant with the European drinking water guideline:
98/83/EG dated 3 November 1998.
Softened water: Water with partly de-ionised calcium and magnesium.
Demi-water:
Virtually completely demineralised water (very low conductivity)
Distilled water: Water no longer containing minerals.
Installation & Servicing Instructions ATAG QR-Series
26
6.5 Gas connection
The appliance pipe is fitted with an internal thread, into which the tail
piece of the gas isolation valve can be screwed. United Kingdom: The gas
supply must comply to the current Gas Safety Regulations. The connection to
the appliance must include a suitable method of disconnection and a gas
control cock must be installed adjacent to the appliance for isolation
purposes. The nominal inlet working gas pressure measured at the appliance
should be 20 mbar for Nat gas (G20). Make sure that the gas pipe work does not
contain dirt, particularly with new pipes. When the boiler has to be converted
from natural gas to LPG, ATAG provides special kits for this purpose. Special
instructions are supplied with the kit. Always check the installation of all
of the parts through which gas flows using leak detection fluid (LDF).
6.6 Hot water supply
Connection of the drinking water installation should be done according to the
national water laws. The sanitary water pipes can be connected to the
installation by means of compression fittings. The cold water inlet on the
Combi boilers must be provided with the following (counted in the water flow
direction): Flow restrictor (supplied), Safety group, Expansion vessel 6bar
(potable water, blue). A flow restrictor must be fitted in the cold water
pipe. The flow restrictor ensures that a quantity of water is supplied which
has a guaranteed outlet temperature of 60°C (assuming a cold water temperature
of 10°C). The quantity of water is virtually unaffected by the water pressure.
With a water pressure lower than 1.5 bar it is advisable to remove the inside
mechanism of the flow restrictor.
27
Installation & Servicing Instructions ATAG QR-Series
6.7 Condensation drain pipe
ATAG Condensing boilers have the top ErP & Energy Labelling EU 813/2013 & EU
1369/2017 band A Classification for high energy efficiency in heating and
domestic hot water.
All ATAG wall hung gas fired condensing boilers contain a syphonic condensate
trap to collect and realease condensate.
The amount of condensate formed is determind by the type of boilers and the
water temperature produced by the boiler.
Condensate pipework.
Use plastic pipework of a diameter no less than 25mm.
Routing of the pipework,
Wherever possible, the condensate pipework should be routed internally to
prevent freezing. The condensate pipework must fall at least 50mm per metre
towards the outlet and take the shortest possible route Support the pipe at
least every 50 cm for near horizontal sections and 1 metre for vertical
sections
External pipework
The pipework should be kept to a minimum and the route as vertical as
possible. Do not exceed 3 metres outside the dwelling.
The condensate pipe must be run using suitable corrosion resistant materials
(eg. plastic).
Terminate as close to the ground or drain as possible (below the grating and
above the water level) while still allowing for safe dispersal of the
condensate. Connection of a condensate drainage pipe to a drain may be subject
to local building controls.
Pipework subjected to extreme cold or wind chill conditions should be in a
40mm diameter pipe.
Protect all external pipework with weather resistant insulation and, if
necessary, box in, to reduce the risk of freezing.
Making it safe.
Condensate pipework must not leak, freeze or block up. Condensate traps must
be filled before firing the boiler to prevent the possibility of potential
harmfull flue products evacuating via the condensate route. Do not dispose
condensate into a water recovery system where it is recaimed for reuse.
Condensate can be discharged into a rainwater hopper which is part of a sewer
carrying both rain water and foul water.
28
Installation & Servicing Instructions ATAG QR-Series
Final discharge options.
The condensate pipe can only terminate into any one of the five areas as shown
in the diagrams on this page.
Draining of the condensation water to the external rain guttering is not
permitted in view of the danger of freezing.
Before putting the boiler into operation fill the syphon with 300 ml of water.
A -Condensate from boiler syphon/trap B -Sink with internal overflow C -25mm
dia. Plastic condensate pipe
D -External drain or gully E -Internal soil and vent stack. F -Servicable
condensate trap (75mm min.)
G -300mm x 100mm dia. sealed plastic tube. H -Ground level
J -Drainage holes facing away from the building K -Lime stone chippings L
-Weather resistant insulation
Installation & Servicing Instructions ATAG QR-Series
K
Drain requirements
figure 6.7.a
29
6.8 Flue gas exhaust system and air supply system
The flue gas exhaust system and air supply system consists of: – Flue gas pipe; – Air supply pipe; – Roof or wall terminal.
The flue gas exhaust system and air supply system must comply with:
United Kingdom:
The flue gas outlet and air supply installation must comply with the current regulation
requirements:
IGE/UP/10;
Installation of flued gas appliances in industrial and commercial
premises
BS EN 1856-1; Chimneys – Requirements for metal chimneys –
Part 1: System chimney products
BS EN 1856-2; Chimneys – Requirements for metal chimneys –
Part 2: Metal liners and connecting flue pipes
BS EN 15287-1; Chimneys – Design, installation and commissioning of chimneys –
Part 1: Chimneys for non-room sealed appliances
BS EN 15287-2; Chimneys – Design, installation and commissioning of chimneys –
Part 1: Chimneys for room sealed appliances
BS EN 13384-2; Chimney – Thermal and fluid dynamic calculation methods –
Part 2: Chimneys serving more than one heating appliance
Clean Air Act; For multiple boiler application where total heat input exceeds
366.4 kW [ or 150 kW as advised within the CAAM, refer to local
authority ]
Furthermore: – Boiler Class indicated on the boiler’s type plate (Flue
category)
– Locally applicable rules. – The supplier’s installation instructions
When in doubt or if you have any questions, always contact ATAG Commercial UK.
The boiler can be fitted with a parallel connected flue gas outlet and air supply system or a concentric flue gas outlet and air supply system.
Installation & Servicing Instructions ATAG QR-Series
30
The appliance connection diameter is 80/125 mm, to which the flue gas outlet
and air supply system can be fitted, with or without elbow pieces. The next
page descibes the conversion from concentric to parallal. The Q51SR and Q60SR
boiler has a connection of 2x 80mm from factory. The boiler is supplied with a
flue adapter 80/125 mm to convert the boiler from parallel to a concentric
connection.
The maximum permissible pipe length is set out in Table 6.8.1.a. (see page 35)
Boiler conversion from concentric to parallel It is also possible to use a
parallel pipe connection of 2x 80mm. In this case a conversion kit ‘concentric
to parallel’ should be ordered. Art.nr. S4440520.
All flue gas parts, which are outside the fire resistant cover, need to be in stainless steel.
P SS
Air filter
Open boiler
BoilerClass B Free exhaust area
SS P
Installation & Servicing Instructions ATAG QR-Series
P
P
P SS
P/A
P/A
Boiler Class C Permitted only when the air
intake and the flue gas outlet are in the same pressure area.
Room sealed system
Open flued en room sealed system
P/A
figure 6.8.a
31
A
1
B
2 3
C
8 6 5 7 4
D
A. 1. Push the 2 clips slightly outwards.
B. 2. Pull the concentric adaptor out of the boiler. 3. Press the cover in the
connection at the back from inside out.
C. 4. Pull the rubber seal around the bottom of the flue connector. 5. Push
the flue connector in the boiler, in the boiler flue pipe until CLICK’. 6. Push the ø125mm cover over the flue connector in the ø125mm opening until
CLICK’. 7. Push the rubber plug in open position in the O2 measuring opening
and close the stop. 8. Push the gasket around the top of the flue connector.
D. Connect the parallel flue gas and air intake system (2x ø80mm).
boiler conversion from concentric to parallel
figure 6.8.b
Q51SR and Q60SR Boiler conversion from parallel to concentric It is possible
to convert the Q51SR and Q60SR boiler from the standard 2x 80 mm parallel to a
concentric flue connection ø80/125mm. In this case use the concentric flue
adapter ø80/125 mm supplied with the boiler.
Conversion of the boiler should be done following the description above in
reverse order.
Installation & Servicing Instructions ATAG QR-Series
32
We suggest you design a simple flue gas system and air supply system using
table 6.8.a For further information about the available components of the flue
gas and air supply system we recommend you consult the Duopass Flue system
literature.
The ATAG flue gas system is meant, and designed, solely for the use on ATAG
central heating boilers adjusted to Nat gas or LPG. The maximum flue gas
temperatures are below 70°C (full load 80/60°C) The proper operation may be
adversely influenced by changes of or adjustments to the correct set up.
Possible warranty claims will not be honoured if incorrect changes result in
non compliance with the installation manual or local rules and regulations.
The flue gas systems described in this document are solely suited for ATAG
central heating boilers of the ATAG boiler range. For this purpose the CE
Certificate has been supplemented under the Gastec nr: 0063BR3405, 0063BQ3021,
0063AS3538 and 0063AU3110. 0063BQ3021, 0063BT3195 en 0063CM3648 The flue gas
system should be built up using only ATAG program products. Combinations with
other brands or systems, without written permission from ATAG Commercial UK,
are not permitted.
Horizontal flue system should always be installed with a 3 degree drop sloping
towards the boiler, in order to avoid condensate lying in the flue system. The
minimum gradient is 50mm/Mtr. With the condensate running back to the boiler
the risk of ice forming at the terminal is reduced.
The terminal should be located where dispersal of combustion products is not
impeded and with due regard for the damage or discolouration that might occur
to building products in the vicinity (see fig 6.8.c).
terminal position for fan assisted boiler
minimum distance
Installation & Servicing Instructions ATAG QR-Series
figure 6.8.c
A
directly below an open window or other opening (e.g. air brick)
mm
B below gutters, soil pipes or drain pipes
mm
C below eaves
mm
D below balconies or car port roof
mm
E from vertical drain pipes and soil pipes
mm
F from internal or external corners
mm
G above ground or below balcony level
mm
H from a surface facing a terminal
mm
I from a terminal facing a terminal
mm
J
from an opening in the car port (e.g. door window) into dwelling
mm
K vertically from a terminal on the same wall
mm
L horizontally from a terminal on the same wall
mm
M horizontally from a vertical terminal to a wall
mm
300
75 200 200 75 300 300 600 1200
1200
1500 300 300
Dimensions
table 6.8.a
33
In certain weather conditions condensation may also accumulate on the outside of the air inlet pipe. Such conditions must be considered and where necessary insulation of the inlet pipe may be required. In cold and/or humid weather water vapour may condense on leaving the flue terminal. The effect of such `plumeing’ must be considered.
The terminal must not be located in a place where it is likely to cause a nuisance. For protection of combustibles, refer to IS 813 section 9.10.1. where the terminal is less than 2m (6.6ft) above a pavement or platform to which people have access (including) any balcony or flat roof the terminal must be protected by a guard of durable material. A suitable guard is available from the country distributor.
Where a terminal is fitted below a window which is hinged at the top, and
where the hinge axis is horizontal, and the window opens outwards, the
terminal shall
be 1m below the bottom of the window opening.
If the boiler is to be located under stairs, a smoke alarm meeting the requirements of I.S. 409 or equivalent must be fitted.
The flue must be terminated in a place not likely to cause a nuisance.
For horizontal sections, the outlet system should always be fitted on an incline (50 mm/m) sloping down towards the appliance so that no condensation water is able to accumulate in the outlet system. The chances of icicles forming on the roof outlet is minimised by causing the condensation water to run back towards the appliance. In the case of horizontal outlets the inlet system should be fitted on an incline sloping down towards the outside to prevent rainwater from coming in.
The appliance produces a white wisp of condensate (plumeing). This wisp of condensation is harmless, but can be unattractive, particularly in the case of outlets in outside walls. For wall terminals a plume management kit is available as an option.
Installation height
Cutting the pipe goes as follows: Figure 6.8.d – Cut just as much from the air
intake part as from the flue gas part using a hand saw;
– Take off the burrs from the cutting edge to prevent cutting the seals;
When mounting the flue gas system, pay attention to the flow direction (See figue 6.8.e). It is not permitted to mount a system upside down and will lead to complaints.
Use a soap solvent or special grease to simplify the fitting.
Flow direction
Figure 6.8.e
Installation & Servicing Instructions ATAG QR-Series
34
6.8.1
Dimensioning of the flue gas and air intake duct
Example: A 25kW with a concentric flue gas system ø80/125mm has according to the table a maximum flue straight length of 31m In the system that is going to be put in there are 2 x 45° bends, so the maximum flue gas length is 31 ( 2 x 1.9 ) = 27.2 meters.
The flue diameter is determined by the total length of the run, including for
the connection pipe, elbows fittings and terminal covers etc and the type and
number of boilers installed into the system.
An undersized flue pipe can lead to disorders. Look at table 6.8.1.a for the
choice of the system and the correct diameter. The table below shows the
maximum flue lengths with the different boiler outputs. A longer flue gas
length can be achieved by increasing the diameter to ø 100mm.
Explanation table 6.8.1.a: Two pipe flue gas system: maximum noted length =
distance between boiler and roof terminal A Concentric flue gas system:
maximum noted length = distance between boiler and roof terminal B
When using bends the noted value behind every bend should be deducted from the
maximum straight length.
16-25 kW 26-38 kW 39-60 kW
Two pipe flue system + chimney lining
A
A
ø80mm
in m
ø100mm
in m
Maximum straight length 80
31 Maximum straight length 100
40
87° bend resistance length
-1,4 87° bend resistance length
-2,1
45° bend resistance length
-0,9 45° bend resistance length
-2
Maximum straight length 80
18 Maximum straight length 100
39
87° bend resistance length
-1,4 87° bend resistance length
-2,1
45° bend resistance length
-0,9 45° bend resistance length
-2
Maximum straight length 80
6 Maximum straight length 100
18
87° bend resistance length
-1,4 87° bend resistance length
-2,1
45° bend resistance length
-0,9 45° bend resistance length
-2
Concentric flue system
16-25 kW 26-38 kW 39-60 kW
ø80/125mm Maximum straight length 80/125 87° bend resistance length 45° bend resistance length Maximum straight length 80/125 87° bend resistance length 45° bend resistance length Maximum straight length 80/125 87° bend resistance length 45° bend resistance length
Dimensions flue gas system and air supply system
B
B
in m
ø100/150mm
in m
31 Maximum straight length 100/150 40
-3 87° bend resistance length
-1,7
-1,9 45° bend resistance length
-1,3
13 Maximum straight length 100/150 34
-3 87° bend resistance length
-1,7
-1,9 45° bend resistance length
-1,3
6 Maximum straight length 100/150 10
-3 87° bend resistance length
-1,7
-1,1 45° bend resistance length
-1,3
Table 6.8.1.a
Installation & Servicing Instructions ATAG QR-Series
35
7
External hot water cylinders
Depending of the comfort preferences different external hot water cylinders
can be connected to the boiler. The choice of the cylinder depends on the coil
output. The coil output must comply with the boiler output.
A cylinder which is used in combination with a Q51SR or Q60SR, should have a
minimal capacity of 40 kW resp. 45kW (minimal ø28mm coil). The maximum
permitted pressure drop is respectively 20 and 10 kPa at a flow of
respectively 1417 and 1587 l/h. See installation example E.1.b on page 83 for
the hydraulic connection.
Installation & Servicing Instructions ATAG QR-Series
36
8
Electrical connection
The appliance complies with the actual Directives.
A 230V -50Hz mains electrical supply is required fused externally at 5A.
The installation must continue to comply with: United Kingdom: – the national
rules for electrical installations.
The appliance must be connected to an earthed socket. this must be visible and
within reach.
The following general stipulations also apply: – No changes may be made to the
wiring of the appliance; – All connections should be designed in accordance
with the enclosed regulations.; – Should it be necessary to change it, the
mains power supply cable may only be replaced with an ATAG mains power supply
cable (item No. S4396700).
The ATAG room thermostat and controls must be connected to their allocated
connections. All other types or makes of room thermostats or controls which
are used must have a Volt free contact.
8.1 Room thermostats
Various thermostats or controls can be connected to the ATAG QR. The following
thermostats or controls can be connected at pos. 19 and 20:
– Honeywell Round Modulation
Simple digitally communicating room thermostat.
– ATAG WiZe
Extensive digitally communicating clock thermostat with push button control.
– ATAG BrainZ
Extensive digitally communicating clock thermostat with push / turn menu control.
– Or any other brand according to OpenTherm protocol.
All other types or makes of room thermostats or controls which are used must
have a Volt free contact and must be connected to pos. 19 and 20.
One of the above mentioned room thermostats or controls can be connected to
pos. 21 and 22 as 2nd option for, for example, an affiliated mixed group.
Installation & Servicing Instructions ATAG QR-Series
37
The Siemens QAA55 controller can be connected at positions 14 and 15.
If desired, the different controllers (OpenTherm- and Siemens controller) can
be applied to different groups. See the setting in the overview below.
Depending on the desired (external) control, a basic setting must be made:
Parameter 5710 5715 5721 6351
Function Heating group 1 Heating group 2 Heating group 3 Function OT 1 connection
6352
Function OT 2 connection
6355
Room controller VG1
6356
Room controller VG2
6357
Room controller VG3
6359
External control DHW
Adjustments
Default
Application
On / Off
On
Use of heating group 1
On / Off
Off
Use of heating group 2
On / Off
Off
Use of heating group 3
External room controller 1 / 2 / 3 External room controller 1 Assign OpenTherm controller 1 to a specific heating
Or via H8 (for on / off)
group
External room controller 1 / 2 / 3 External room controller 2 Assign OpenTherm controller 2 to a specific heating
Or via H9 (for on / off)
group
Intern / Extern
External
Internal = Siemens controller Extern = OpenTherm
Intern / Extern
External
Internal = Siemens controller External = OpenTherm
Intern / Extern
Internal
Internal = Siemens contoller External = OpenTherm
None / External controller 1 / None External controller 2
None (internal controller) = Siemens controller External controller = Settings on OpenTherm controller
For weather-dependent control, the outdoor sensor 1kOhm ATAG ARZ0055U (optional) must be connected to pos. 25 and 26.
For more detailed questions regarding the components which are not supplied by ATAG, the country distributor should be contacted.
Connection terminal QR
230 V~ Acc.
NL 123
230 V~ QX1 2nd CH NL
456
230 V~ QX2 DHW/Solar NL
78 9
230 V~ QX3 DHW
N 10 11 12
QAA
n.a. Block. contact
G+ CL- CL+ 13 14 15 16 17 18
1
OT ON/OFF
19 20
2
OT ON/OFF
21 22
PT1000 23 24
Out 25 26
DHW 27 28
Installation & Servicing Instructions ATAG QR-Series
8X.35.20.00
External safety contact On/off thermostat or OpenTherm thermostat 1 On/off thermostat or OpenTherm thermostat 2 PT1000 collectorsensor sun system ATAG ARZ55 outside sensor DHW sensor 10kOhm
230 Volt for three-way valve motor Option
230 Volt for accessories (clip-in) 230 Volts for external pump 230 Volt for external control
Connection terminal
figure 8.a
38
39
Installation & Servicing Instructions ATAG QR-Series
4
FAN
1
5
L N PE
4
2
PWM
1
PUMP
321 * Adapter cable
+-
(OSS3/4 only)
IGNITION
6,3 4,0
31 42
1 2 PE GAS VALVE
3 1
IONISATION
2 63
Three way valve VC6012 (Combi only) Accessory for Solo
8X.35.20.00
** Bridge expires when connecting a security device
1kOhm
Outside sensor (Accessory)
10KOhm
DHW sensor Combi (Accessory for Solo)
Power supply Fuse 10A 230V~50Hz
**
230 V~ Acc.
NL 123
230 V~ QX1 2nd CH NL
456
230 V~ QX2 DHW/Solar NL
78 9
230 V~ QX3 DHW
N 10 11 12
QAA
n.a. Block. contact
G+ CL- CL+ 13 14 15 16 17 18
1
2
OT
OT
ON/OFF ON/OFF
19 20 21 22
PT1000 23 24
Out 25 26
DHW 27 28
0I
PE
NL
2x T 6,3A H 250V
7473a02en/0118
1 23
P
Water pressure sensor
10kOhm
T1 Flow sensor
10kOhm
T2 Return sensor
10kOhm
T1a – in OSS4 2. Flow sensor
electrical diagram
Auto
0 4 8 12 16 20 24
Reset
ESC
OK
Control unit
X4 X5
X42
X7
X22 X50
X24
X21
X20
figure 8.b
9 Boiler controls
3 sec.
After switching on and with sufficient heating pressure (> 1.0 bar), the
automatic heating-side de-aeration program is executed, e.g. after filling the
installation for the first time. The system is then switched to safe mode
(circle symbol with dash). The display shows “De-aeration program on”. The
pump (s) are switched off / on a number of times. The 3-way valve, if present,
is switched to the hot water position and the pump (s) are switched off / on
again a number of times. At the end of the de-aeration program, which lasts
approx. 16 minutes, the boiler switches back to normal operation
The venting program can also be started manually by pressing button E for more
than 3 seconds. This function runs for approximately 16 minutes.
On a call for Central Heating (DHW program is switched OFF as factory
setting), a water temperature will be calculated. This calculated water
temperature is called the T-set value and with this the boiler output will be
controlled. On a call for central heating the boiler ignites first at low
input. The input is then changed slowly to match the load required. The boiler
operates in this way to avoid excessive water noises and temperature
overshoot.
On a call for hot water supply the T-set value of central heating return water
temperature is monitored. Depending on the amount of sanitary water which is
withdrawn from the DHW cylinder, the central heating return water temperature,
from which the input is adjusted, will vary.
9.1 Explanation of the function keys
Legend:
A On/Off switch
B Back button (ESC)
C Room temperature control button
D Confirmation button (OK)
L
E Function button for manual
operation
F Chimney sweep function button
G Info button
H Reset button
I Operation mode button for heating
circuit(s)
L Operating mode button for DHW
H
A
I G
B C DE F
Installation & Servicing Instructions ATAG QR-Series
40
Operating mode button for DHW (M) For switching on the DHW preparation (Bar
under the water tap in the display) If the boiler control is configured via
OpenTherm, no bars are visible. DHW timer program via external controller is
leading
Operation mode button for heating circuit(s) (I) (Only works in combination
with QAA55, NOT with OT/On-Off) For setting 4 different operating modes for
heating:
Automatic clock: Automatic operation according to timer program Bar in the display visible under “AUTO” by OpenTherm
Sun 24 hr:
Heating at comfort target value
Moon 24 hr:
Heating at reduced value
Installation & Servicing Instructions ATAG QR-Series
Protection mode: Heating switched off, frost protection active
Information button (G) Retrieval of the following information, without
influence on the control processes: Temperatures, operating condition of the
heating facility/DHW, error reports
Room temperature control button (C) With this rotating button, settings can be
selected and changed during programming and changing the room comfort
temperature
Confirmation button OK (D) Back button ESC (B) These two buttons are needed in
combination with the large rotating button (- +) for the programming and
configuration of the control unit. Settings, which cannot be changed through
the control elements, are provided by means of programming. By pushing the ESC
button you always go one step backward, whereby modified values are not taken
over. To reach the next operating level, or to store the changed values, you
must push the OK button.
Manual operation function button (E) By pushing this button, the control unit
is set to manual mode, whereby all pumps are running, the mixer is no longer
controlled and the burner is set to 60°C (Indicated by the spanner symbol).
Hold down for 3 sec. to start venting program.
Chimney sweep function button (F) MAY ONLY TO BE OPERATED BY A QUALIFIED
INSTALLER! Push this button shortly, to put the boiler in the operating mode
for measuring emissions; renewed pushing of the button deactivates this
function, or it is automatically deactivated after 15 minutes (indicated by
the spanner symbol).
Reset button (H) By pressing this button shortly, the locked condition of the
burner is deactivated.
On/Off switch (A) Position 0: The entire facility and all connected electrical
components are without electrical power. A protection against frost is not
ensured. Position I: The entire facility and all connected electrical
components are ready for operation.
41
9.2 Main functions of the control panel
Button Button
Action
Procedure
Setting up the required room temperature
HC2 jointly with HC1
Turn the rotating button left or right Turn the rotating button again for
storing with OK button or wait for 5 sec. or push
Setting the required room temperature
for HC1 or HC2
or
2nd HC independent of HC1
Turn rotating button left/right Then push OK Turn rotating button left/right
Save with OK button or wait for 5 sec. or push
Switching warm water operations ON or OFF
Push button
Factory setting
Change operating mode
1 x short push of button and then once more, short push of button
once more, short push of button
Control stop function
Action
Display of various information
1 x push button (> 3 sec) push button once more (> 3 sec)
Procedure
1 x push button push button again push button again
Push button
Operating mode according to target values that are set manually
Change of the factory setting for boiler temperature
short push of button
short push of button short push of button Rotating button turn -/+ short push
of button short push of button short push of button
De-aeration function
Activation of chimney sweep function
1 x push button (> 3 sec) push button once more (> 3 sec)
Push button (> 3 sec) push button once more (> 3 sec)
Display / Function
comfort target value with blinking temperature display blinking temperature
display in steps of 0.5° centigrade, from 10.0 to 30°C
Comfort value active Comfort value not active – Basic display appears after 3
sec.
Select heating circuit Heating circuit active blinking temperature display in
steps of 0.5° centigrade, from 10.0 to 30°C Comfort target value active
Comfort target value not active – Basic display appears after 3 sec.
Only works in combination with QAA55, NOT with OT Works with on / off controller via H8 / H9
Warm water operation ON / OFF
(segmented bar under symbol for warm water visible/invisible) – ON: Warm water
preparation according to switching program – OFF: No warm water preparation –
Safety function active When using OpenTherm, “operating mode button is locked”
is displayed Safety functions remain active!
Automatic operating mode ON, with:
– heating operation according to timer program – Temperature target values
according to heating program – Safety function active
– Summer/Winter – automatic switching active – ECO functions active (segmented
bar under corresponding symbol visible)
Continuous COMFORT heating ON, with:
– Heating operation without timer program, at comfort target value – Safety
function active
Continuous REDUCED heating ON, with:
– Heating operation without timer program, at reduced target value – Safety
function active
– Summer/Winter – automatic switching active – ECO functions active Automatic
safety mode ON, with:
– Heating operations switched off – Temperature according to frost protection
value – Safety function active When using OpenTherm, “operating mode button is
locked” is displayed Safety functions remain active!
304: Control stop function Basic display appears after 3 sec.
Set target value
Display / Function
INFO section is displayed
– Boiler status
– Room temperature
– Room temperature minimum
– Warm water status
– Room temperature maximum
– Status heating circuit 1 – Outdoor temperature
– Status heating circuit 2 – Minimum outdoor temperature
– Maximum outdoor temperature
– Time / date – Water temperature 1
– Error message
– Boiler temperature
– Maintenance report
– Flow temperature
(Display of the information lines depends on the configuration)
Back to basic display; INFO segment is suppressed
Manual operating mode ON (spanner symbol is visible) – Heating operations at preset boiler temperature (factory setting = 60°C)
301: Manual operation mode
operation? Blinking temperature display Set required target value
Set target value for manual
Boiler status Manual operating mode OFF (spanner symbol disappears)
312: De-aeration function ON De-aeration function OFF
Chimney sweep function ON Chimney sweep function OFF
DHW timer program via external
controller is leading
Only works in combination with QAA55, NOT with OT Works with on / off
controller via H8 / H9
Installation & Servicing Instructions ATAG QR-Series
RESET
Short-term reduction of room temperature at QAA75 / 78
Reset button
Push button push button again
Heating at reduced target value Heating at comfort target value
Push button (< 3 sec.) push button again > 3 sec.
Facility is manually locked, unreleased equipment is unlocked, alarm bell disappears
= Confirmation
= Abort or back to basic display
MAY ONLY BE OPERATED BY A QUALIFIED INSTALLER!
Only works in combination with QAA55, NOT with
OT/On-Off
42
9.3 Parameters end users
Basic display “Boiler temperature” – Push OK button once – Use +- rotating
button for selecting for instance “Drinking water menu” – Push OK button once
– Use +- rotating button, for instance in the drinking water menu, for
selecting “Parameter no. 1612 – Reduced target value” – Push OK button once –
Use +- rotating button to change the currently set value – Push OK button once
-> the value is stored – Push 2 x ESC to return to the basic display “Boiler
temperature . .”
Time programs are not active when using an OpenTherm thermostat, however, they
are active when switching on and off via H8 / H9
Menu Time of day and date Operator section Time program HC 1
Time program HC 2 (When activated)
Time program 3/ HC3
Time program 4/ DHW
Line no. 1 2 3 20
Selection possibilities Hours / Minutes Day / Month Year Language
500
Preselection
501
Mo-Su: 1. Phase On
502
Mo-Su: 1. Phase Off
503
Mo-Su: 2. Phase On
504
Mo-Su: 2. Phase Off
505
Mo-Su: 3. Phase On
506
Mo-Su: 3. Phase Off
516
Default values
520
Preselection
521
Mo-Su: 1. Phase On
522
Mo-Su: 1. Phase Off
523
Mo-Su: 2. Phase On
524
Mo-Su: 2. Phase Off
525
Mo-Su: 3. Phase On
526
Mo-Su: 3. Phase Off
536
Default values
540
Preselection
541
Mo-Su: 1. Phase On
542
Mo-Su: 1. Phase Off
543
Mo-Su: 2. Phase On
544
Mo-Su: 2. Phase Off
545
Mo-Su: 3. Phase On
546
Mo-Su: 3. Phase Off
556
Default values
560
Preselection
561
Mo-Su: 1. Phase On
562
Mo-Su: 1. Phase Off
563
Mo-Su: 2. Phase On
564
Mo-Su: 2. Phase Off
565
Mo-Su: 3. Phase On
566
Mo-Su: 3. Phase Off
576
Default values
Unit hh:mm dd:MM
yyyy –
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
uu:mm uu:mm uu:mm uu:mm uu:mm –
Min.
Max
00:00
23.59
01.01
31.12.
2004
2099
English, German, French, Italian, Danish, Dutch, Spanish, Czech, Slovenian, Turkish
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Factory setting –.—.—.–
German
Mo-Su 06:00 22:00 –.—.—.—.–
No Mo-Su 06:00 22:00
–.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No
Only works in combination with QAA55, NOT with OT Works with on / off
controller via H8 / H9
Only if parameter 6359 is active
Installation & Servicing Instructions ATAG QR-Series
43
Parameters end users
Menu Time program 5
Holidays HC1
Holidays HC2 (When activated) HC1
HC 2 (When activated) DHW Swimming pool Boiler Error
Line no. 600 601 602 603 604 605 606 616 641 642 643 648 651 652 653 658 710 712 714 720 730 1010 1012 1014 1020 1030 1600 1610 1612 2055 2056 2214 6700 6705 6706
Selection possibilities Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Period Start Day / Month Periode End Day / Month Operating level Preselection Period Start Day / Month Periode End Day / Month Operating level Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Summer/winter heating limit Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve slope Summer/winter heating limit Operating mode Nominal setpoint Reduced setpoint Pool setpoint solar heating Pool sepoint boiler heating Setpoint manual control Error message SW Diagnose Code Burner ctrl phase lockout pos
Unit –
uu:mm uu:mm uu:mm uu:mm uu:mm uu:mm
tt.MM tt.MM tt.MM tt.MM °C °C °C °C °C °C °C °C °C °C °C °C °C –
–
–
Min.
Max
Mo-Su, Mo-Fr, Sa-Su
Mo-Su, Mo-Fr, Sa-Su
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
00:00
24:00
Yes
No
Period 1, 2, 3, 4, 5, 6, 7, 8
01.01
31.12
01.01
31.12
Frost protection, Reduced
Frost protection
Period 1, 2, 3, 4, 5, 6, 7, 8
01.01
31.12
01.01
31.12
Frost protection, Reduced
Frost protection
Value from Line no. 712
35
4
Value from Line no. 710
4
Value from Line no. 712
0.10
4.00
—/8
30
Value from Line no. 1012
35
4
Value from Line no. 1010
4
Value from Line no. 1012
0.10
4.00
—/8
30
Off, On, Eco
Value from Line no. 1612
80
8
Value from Line no. 1610
8
80
8
80
10
90
–
–
–
–
–
–
Factory setting Mo-Su 06:00 22:00 –.—.—.—.-No Period 1 –.—.–
Frost protection Period 1 –.—.–
Frost protection 20.0 16.0 10.0 1.50 20 20.0 16.0 10.0 0.8 0 Off 55 40 26 22
50
Indication only Indication only Indication only
Only works in combination
with QAA55, NOT with OT Works with on / off controller via H8 / H9
Installation & Servicing Instructions ATAG QR-Series
44
9.4 Parameters technician
Basic display “Boiler temperature”
– Push OK button once – Push Info button for 4 sec. – Use the +- rotating
button for selecting commissioning or technician level – Push OK button once –
Use +- rotating button for selecting for instance “Drinking water menu” – Push
OK button once – Use the +- rotating button, for instance in the drinking
water menu, for selecting “Parameter no. 1612 – Reduced target value”
– Push OK button once – Use +- rotating button to change the currently set
value – Push OK button once -> the value is stored – Push 2 x ESC to return to
the basic display “Boiler temperature”
Overview of commissioning
parameters
The parameter lines with a grey background only become visible at the
commissioning level.
The complete parameter list becomes visible at the technician level.
Menu Time of day and date
Operator section
Time program HC 1
Time program HC 2 (when activated)
Time program HC3/P
Time program 4 DHW
Line no. 1 2 3 5 6 20
22 26 27 28 44 46 70 500 501 502 503 504 505 506 516 520 521 522 523 524 525
526 536 540 541 542 543 544 545 546 556 560 561 562 563 564 565 566 576
Selection possibilities Hours / Minutes Day / Month Year Start of summertime Day / Month End of summertime Day / Month Language
Unit hh:mm dd:mm
yyyy dd:mm dd:mm
–
Info Operation lock Programming lock Direct adjustment Operation HC2 Operation HC3/P Software Version Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo- Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off Default values
hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm –
Min.
Max
00:00
23.59
01.01
31.12.
2004
2099
01.01
31.12.
01.01
31.12.
English, German, French, Italian, Danish, Dutch, Spanish, Czech, Slovenian, Turkish
Temporarily, Permanently
Off, On
Off, On
Automatic storage, Storage with confirmation
Jointly with HC1, Independently
Jointly with HC1, Independently
0
99.0
Mo-Su, Mo-Fr, Sa-Su
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
Yes, No
Mo-Su, Mo-Fr, Sa-Su
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
Yes, No
Mo-Su, Mo-Fr, Sa-Su
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
Yes, No
Mo-Su, Mo-Fr, Sa-Su
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
Yes, No
Factory setting –.—.—.–
25.03. 25.10. German
Temporarily Off Off
Storage with confirmation Jointly with HC1 Jointly with HC1 Indication only
Mo-Su 06:00 22:00 –.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No Mo-Su 06:00 22:00
–.—.—.—.-No Mo-Su 06:00 22:00 –.—.—.—.-No
Installation & Servicing Instructions ATAG QR-Series
45
Parameters technician
Menu Time program 5
Holidays HC1 Holidays HC2 (When activated) HC 1
Line no. 600 601 602 603 604 605 606 616 641 642 643 648 651 652 653 658 700
710 712 714 720 721
726 730 732 733 740 741 742 746 750 760 770 780
790 791 800 801 809 820 830 832 833 834 835 836 850 851 855 856 861 870
872 890 898 900
Selection possibilities Preselection Mo-Su: 1. Phase On Mo-Su: 1. Phase Off
Mo-Su: 2. Phase On Mo-Su: 2. Phase Off Mo-Su: 3. Phase On Mo-Su: 3. Phase Off
Default values Preselection Period Start Day / Month Periode End Day / Month
Operating level Preselection Period Start Day / Month Periode End Day / Month
Operating level Operating mode HC1
Comfort setpoint Reduced setpoint Frost protection setpoint Heating curve
slope Heating curve parallel displacement Heating curve adaption Summer/winter
heating limit 24-hour heating limit Ext’n 24-hour heating limit Flow temp
setpoint min Flow temp setpoint max Flow temp setpoint room stat Delay heat
request Room influence Room temp limitation Boost heating Quick setback
Optimum start control max Optimum Stop control max Reduced setp increase start
Reduced setp increase end Continuous pump operation HC1 Overtemp prot pump
circuit Mixing valve boost Actuator type Switching differential 2-pos Actuator
running time P-Band (Xp) HC1 Integral action time (Tn) HC1 Floor curing
function Floor curing setp manually Floor curing setp current Floor curing day
current Excess heat draw With buffer With prim contr/system pump Flow setp
readj speed ctrl Operating level change over Optg mode changeover
Unit –
hh:mm hh:mm hh:mm hh:mm hh:mm hh:mm
dd:mm dd:mm dd:mm dd:mm –
°C °C °C °C
°C °C °C °C °C °C s % °C °C –
min min °C °C
°C
°C s °C s °C °C –
- see page 52
Min.
Max
Mo-Su, Mo-Fr, Sa-Su
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
00:00
Yes, No
Period 1, 2, 3, 4, 5, 6, 7, 8
01.01
31.12
01.01
31.12
Frost protection, reduced
Period 1, 2, 3, 4, 5, 6, 7, 8
01.01
31.12
01.01
31.12
Frost protection, reduced
Protection, Automatic mode, Continuously comfort, Continuously reduced
Value from Line no. 712
35
Value from Line no. 714 Value from Line no. 710
4
Value from Line no. 712
0.10
4.00
-4.5
4.5
Off, On
—/8
30
—/-10
10
No, Yes
8
Value from Line no. 741
Value from Line no. 740
80
Value from Line no. 740 Value from Line no. 741
0
600
—/0
100
—/0.5
4
—/0
20
Off, Down to Reduced setpoint, Down to Frost protection setpoint
0
360
0
360
—/30
10
-30
Value from Line no. 800
Off, On
Off, On
0
50
2-position, 3-position
0
20
30
873
1
100
10
873
Off, Functional heating, Curing heating, Manual
0
–
0
Off, Heating mode, Always
No, Yes
No, Yes
No, Yes
Frost protection, Reduced, Comfort
None, Protection, Reduced, Comfort, Automatic
Factory setting Mo-Su 06:00 22:00 –.—.—.—.-No
Period 1 –.—.–
Frost protection Period 1 –.—.–
Frost protection Automatic mode
20.0 16.0 10.0 1.50 0.0
Off 0 -3 Yes 8 80 65 10 20 1 2 Down to Reduced setpoint
0 0 -5 -15 Off On 5 3-position 2 135 24 90 Off 25 Indication only 0 Off Yes
Yes No Reduced Protection
Installation & Servicing Instructions ATAG QR-Series
46
Parameters technician
Menu HC 2 (when activated)
Line no. 1000 1010 1012 1014 1020 1021 1026 1030 1032 1033 1040 1041 1042 1046
1050 1060 1070 1080
1090 1091 1100 1101 1109 1120 1130 1132 1133 1134 1135 1136 1150 1151 1155
1156 1161 1170 1172 1190 1198 1200
Selection possibilities Operating mode HC2 Comfort setpoint Reduced setpoint
Frost protection setpoint Heating curve slope Heating curve parallel
disHeating curve adaption Summer/winter heating limit 24-hour heating limit
Ext’n 24-hour heating limit Flow temp setpoint min Flow temp setpoint max Flow
temp setpoint room stat Room influence Room temp limitation Boost heating
Summer/winter heating limit Quick setback
Optimum start control max Optimum Stop control max Reduced setp increase start
Reduced setp increase end Continuous pump operation HC2 Overtemp prot pump
circuit Mixing valve boost Actuator type Switching differential 2-pos Actuator
running time P-Band (Xp) HC1 Integral action time (Tn) HC1 Floor curing
function Floor curing setp manually Floor curing setp current Floor curing day
current Excess heat draw With buffer With prim contr/system pump Flow setp
readj speed ctrl Operating level change over Optg mode changeover
- see page 52
Unit
Min.
Max
–
Protection, Automatic mode, Reduced
°C
Value from Line no. 1012
35
°C
Value from Line no. 1014 Value from Line no. 1010
°C
4
Value from Line no. 1012
–
0.10
4.00
°C
-4.5
4.5
°C
Off, On
°C
—/8
30
°C
—/-10
10
–
No, Yes
°C
8
Value from Line no. 1041
°C
Value from Line no. 1040
80
°C
Value from Line no. 1040 Value from Line no. 1041
s
0
600
%
—/0
100
°C
—/0.5
4
°C
—/0
20
–
Off, Down to Reduced setpoint, Down to Frost protection
setpoint
min
0
360
min
0
360
°C
—/30
10
°C
-30
Value from Line no. 1100
Off, On
–
Off, On
°C
0
50
–
2-position, 3-position
°C
0
20
s
30
873
°C
1
100
s
10
873
–
Off, Functional heating, Curing heating, Manual
°C
0
95
°C
–
–
–
0
32
–
Off, Heating mode, Always
–
No, Yes
–
No, Yes
–
No, Yes
–
Frost protection, Reduced, Comfort
–
None, Protection, Reduced,
Comfort, Automatic
Factory setting Protection 20.0 16.0 10.0 0.8 0.0 Off 20 -3 Yes 8 50 50 10 20
1 2
Down to Reduced setpoint
0 0 -5 -15 Off On 5 3-position 2 135 24 90 Off 25 Indication only 0 Off Yes
Yes No Reduced Protection
Installation & Servicing Instructions ATAG QR-Series
47
Parameters technician
Menu HC 3 (when activated)
Line no. 1300 1310 1312 1014 1320 1321 1326 1330 1332 1333 1340 1341 1342 1346
1350 1360 1370 1380
1390 1391 1400 1401 1409 1420 1430 1432 1433 1434 1435 1436 1450 1451 1455
1456 1461 1470 1472 1490 1498 1500
Selection possibilities Operating mode HC2 Comfort setpoint Reduced setpoint
Frost protection setpoint Heating curve slope Heating curve parallel
disHeating curve adaption Summer/winter heating limit 24-hour heating limit
Ext’n 24-hour heating limit Flow temp setpoint min Flow temp setpoint max Flow
temp setpoint room stat Room influence Room temp limitation Boost heating
Summer/winter heating limit Quick setback
Optimum start control max Optimum Stop control max Reduced setp increase start
Reduced setp increase end Continuous pump operation HC3 Overtemp prot pump
circuit Mixing valve boost Actuator type Switching differential 2-pos Actuator
running time P-Band (Xp) HC1 Integral action time (Tn) HC1 Floor curing
function Floor curing setp manually Floor curing setp current Floor curing day
current Excess heat draw With buffer With prim contr/system pump Flow setp
readj speed ctrl Operating level change over Optg mode changeover
- see page 52
Unit
Min.
Max
–
Protection, Automatic mode, Reduced
°C
Value from Line no. 1312
35
°C
Value from Line no. 1314 Value from Line no. 1310
°C
4
Value from Line no. 1312
–
0.10
4.00
°C
-4.5
4.5
°C
Off, On
°C
—/8
30
°C
—/-10
10
–
No, Yes
°C
8
Value from Line no. 1341
°C
Value from Line no. 1340
80
°C
Value from Line no. 1340 Value from Line no. 1341
s
0
600
%
—/0
100
°C
—/0.5
4
°C
—/0
20
–
Off, Down to Reduced setpoint, Down to Frost protection
setpoint
min
0
360
min
0
360
°C
—/30
10
°C
-30
Value from Line no. 1400
Off, On
–
Off, On
°C
0
50
–
2-position, 3-position
°C
0
20
s
30
873
°C
1
100
s
10
873
–
Off, Functional heating, Curing heating, Manual
°C
0
95
°C
–
–
–
0
32
–
Off, Heating mode, Always
–
No, Yes
–
No, Yes
–
No, Yes
–
Frost protection, Reduced, Comfort
–
None, Protection, Reduced,
Comfort, Automatic
Factory setting Protection 20.0 16.0 10.0 0.8 0.0 Off 20 -3 Yes 8 50 50 10 20
1 2
Down to Reduced setpoint
0 0 -5 -15 Off On 5 3-position 2 135 24 90 Off 25 Indication only 0 Off Yes
Yes No Reduced Protection
Installation & Servicing Instructions ATAG QR-Series
48
Parameters technician
Menu Domestic hot water
Consumer circuit 1 Consumer circuit 2 Consumer circuit 3 Swimming pool Primary
control/ System pump
Line no. 1600 1610 1612 1614 1620
1630
1640 1641 1642 1644 1645 1646 1647 1660
1661 1663 1680 1859 1874 1875 1878 1880 1909 1924 1925 1928 1930 1959 1974
1975 1978 1980 2055 2056 2065 2070 2080 2110 2111 2121 2130 2132 2133 2134
2135 2136 2150
Selection possibilities Operating mode Nominal setpoint Reduced setpoint
Nominal setpoint max Release
Charging priority
Legionella function Legionella function periodically Legionella funct Day
Legionella funct time Legionella funct setpoint Legionella funct duration
Legionella funct circ pump Circulating pump release
Circulating pump cycling Circulation setpoint Optg mode changeover Flow temp
setp cons request DHW charging priority Excess heat draw With buffer With prim
contr/system pump Flow temp setp cons request DHW charging priority Excess
heat draw With buffer With prim contr/system pump Flow temp setpoint DHW
charging priority Excess heat draw With buffer With prim contr/system pump
Pool setpoint solar heating Pool setpoint producer heating Pool charging
priority solar Pool temperature maximum Pool with solar Flow temp min
limitation Flow temp max limitation Syst pump on heat gen lock Mixing valve
boost Actuator type Switching differential 2-pos Actuator running time P-Band
(Xp Integral action time (Tn) HC1 Primary control/System pump
Unit °C °C °C –
–
uu:mm °C min –
°C
°C °C
°C °C °C °C °C °C °C °C s °C s –
Min.
Max
Off, On, Eco
8
80
8
80
8
80
24h/Day, Time programs HCs, Time program 4/DHW
Absolute, Shifting, None, MC shifting PC absolute
Off, Periodically, Fixed weekday
1
7
Mo,Tu,We,Th,Fr,Sa,Su
00:00
23:50
55
95
10
360
Off, On
Time program 3/HCP, DHW release, Time program 4/DHW, Time program 5
Off, On
8
80
None, Off, On
8
120
No, Yes
No, Yes No, Yes
No, Yes
8
120
No, Yes
No, Yes
No, Yes
No, Yes
8
No, Yes
No, Yes
No, Yes
No, Yes
8
80
8
80
Priority 1, Priority 2, Priority 3
8
95
No, Yes
8
95
8
95
Off, On
0
50
2-position, 3-position
0
20
30
873
1
100
10
873
Upstream of buffer, Downstream of buffer
Factory setting Off 60 40 65
combi: 24h/Day solo: Time programs HCs
Absolute
Fixed weekday 7
Montag –65 30 On
DHW release
Off 45 None 70 Yes No Yes Yes 70 Yes No Yes Yes 45 Yes No Yes Yes 26 22
Priority 3 30 Yes 8 80 Off 5 3-position 2 120 32 120 Downstream of buffer
Installation & Servicing Instructions ATAG QR-Series
49
Parameters technician
Menu Boiler
Line no. 2210 2212 2214 2236 2237 2243 2245 2250 2253 2270 2301 2305
2316 2317 2320
2321 2322
Selection possibilities Setpoint min Setpoint max Setpoint manual control
P-band Xp DHW Integral action time (Tn) dhw Burner off time min SD burner off
time Pump overrun time Pump overr time after DHW Return setpoint min Boiler
pump on heat gen lock Impact heat generation lock
Temp differential max Temp differential nominal Pump modulation
Starting speed Pump speed min
2323
Pump speed max
Unit
Min.
Max
°C
8
95
°C
8
120
°C
8
120
°C
1
200
s
4
873
min
0
60
°C
0
80
min
0
240
min
0
20
°C
8
95
–
Off, On
–
Heating mode only, Heating and DHW
mode
°C
0
80
°C
0
80
–
None, Demand, Boiler setpoint,
Temp differential nominal, Burner output
%
0
100
%
0
100
%
0
100
2330
Output nominal
kW
0
2000
2331
Output basic stage
kW
0
2000
2334 2335
Output at pump speed min Output at pump speed max
%
0
%
0
2441
Max. speed at maximum output in heating mode
rpm
0
2442
Fan speed full charging max
rpm
0
100 100
1000
1000
2444
Fan speed DHW max
rpm
0
1000
2445 2446 2450
2452 2453 2454 2455 2456 2457 2460 2461 2462 2463
Fan shutdown heating mode Fan shutdown delay Controller delay
Controller delay speed Controller delay duration Switching diff on HCs
Switching diff off min HCs Switching diff off max HCs Settling time HCs
Switching diff on DHW Switching diff off min DHW Switching diff off max DHW
Settling time DHW
–
Uit, Aan
s
0
200
–
Off, Heating mode only, DHW mode only,
Heating and DHW mode
rpm
0
10000
s
0
255
°C
0
20
°C
0
20
°C
0
20
min
0
240
°C
0
20
°C
0
20
°C
0
20
min
0
240
Factory setting
20
85
50
35
75
5
40
3
1
8
Off
Heating and DHW mode
25
20
Temp differential nominal
100
Q25SR: 60 Q38SR: 60 Q51SR: 55 Q60SR: 55 Q25CR: 60 Q38CR: 60 Q51CR: 55
Q25SR: 70 Q38SR: 100 Q51SR: 100 Q60SR: 100 Q25CR: 75 Q38CR: 100 Q51CR: 100
Q25SR: 25 Q38SR: 38 Q51SR: 51 Q60SR: 60 Q25CR: 25 Q38CR: 38 Q51CR: 51 Q25SR:
5.0 Q38SR: 6.9 Q51SR: 10.0 Q60SR: 10.0 Q25CR: 6.9 Q38CR: 6.9 Q51CR: 10.0
0
100
Q25SR: 5390 Q38SR: 5450 Q51SR: 4750 Q60SR: 5400 Q25CR: 3590 Q38CR: 5450 Q51CR:
4750 See Line no. 2444
Q25SR: 5390 Q38SR: 5450 Q51SR: 4750 Q60SR: 5400 Q25CR: 5020 Q38CR: 5450 Q51CR:
4750
Uit
3
Heating mode only
1500
30
3
5
10
1
1
6
8
1
Installation & Servicing Instructions ATAG QR-Series
50
Parameters technician
Installation & Servicing Instructions ATAG QR-Series
Menu Boiler Cascade (when activated) Solar
51
Line no. 2470 2628
2630 2655 2656 2657 2662 2663 3510
3511 3512 3530 3531 3532 3533 3534 3540 3541 3544 3560 3810 3811 3812 3813
3814 3815 3816 3817 3818 3822 3825 3826 3827 3828 3830 3831 3840 3850 3860
3865 3867 3868 3869 3870 3871 3880
3881 3884 3887
Selection possibilities Delay heat req special op Deaeration function release
Auto deaeration procedure ON time deaeration OFF time deaeration Number of
repetititions Deaeration time heat circuit Deaeration time DHW Lead strategy
Output band min Output band max Release integral source seq Reset integral
source seq Restart lock Switch on delay Forced time basic stage Auto source
seq ch’over Auto source seq exclusion Leading source Return setpoint min Temp
diff on Temp diff off Min charging temperature DHW storage tank Temperature
differential ON buffer Temperature differential OFF buffer Min charging
temperature buffer Temperature differential swimming pool ON Temperature
differential swimming pool OFF Min charging temperature swimming pool Charging
priority storage Charging time relative priority Wait time relative priority
Wait time parallel operation Start delay secondary pump Collector Start
function Min collector pump running time Collector frost protection temp
Collector overtemperature protection Evaporation temperature of heat carrier
Starting speed coll pump 1 Starting speed exch pump Starting speed buffer pump
Starting speed swi pool pump Pump speed min solar Pump speed max solar Type of
antifreeze added
Antifreeze concentration Volumetric flow solar pump Pulse unit yield
Unit s –
s s min min –
% % °Cmin °Cmin s min s h °C °C °C °C °C °C °C °C °C °C min min min s min s
°C °C °C % % % % % %
% l/h l
Min.
Max
0
600
0: None 1: Water pressure too low 2: Water pressure too high 3: Water pressure
too low or too high 4: Power-On 5: Power-On or water pressure too low 6:
Power-On or water pressure too high 7: Power-On or water pressure too low/too
high
Off, On
0
240
0
240
0
100
0
255
0
255
Late on early off, Late on late off, Early on late off
0
100
0
100
0
500
0
500
0
1800
0
120
0
1200
10
990
None, First, Last, First and Last
1
16
8
95
0
40
0
40
8
95
0
40
0
40
8
95
0
40
0
40
8
95
None, DHW storage tank, Buffer
2
60
1
40
0
40
0
600
5
60
5
120
-20
5
30
350
60
350
0
100
0
100
0
100
0
100
0
100
0
100
1: None (water), 2: Ethylenglycol, 3: Proplylenglykol, 4: Mixture Ethylen- and Propylenglycol
1
100
10
1500
0
100
Factory setting 0
5: Power-On or water pressure too low
Off 20 10 3 3 2 Late on early off,
40 90 100 8 300 5 60 500 None Source 1 8 8 4 30 – – – – 30 – – – – – – DHW
storage tank – – – – – – 60 – – 30 –80 110 100 100 100 100 40 100 1: None
(water)
30 200 10
Parameters technician
Menu DHW Storage tank
Line no. 5010 5020 5021 5022
5024 5030 5040 5050 5055 5056 5057 5060 5061 5062 5070 5085
5090 5092 5093 5101 5102 5130 5131 5140 5141 5142 5146 5148 5151
Selection possibilities Charging Flow setpoint boost Transfer boost Type of
charging
Switching diff Charging time limitation Discharging protection Charging temp
max Recooling temp Recooling heat gen/HCs Recooling collector El imm heater
optg mode El immersion heater release El immersion heater control Automatic
push Excess heat draw
With buffer With prim contr/system pump With solar integration Pump speed min
Pump speed max Transfer strategy Comparison temp transfer DHW charging circuit
boost DHW charging circuit boost max Delay flow set point contr Full charge
with B36 Min start temp diff Q33 Charg’ cir excess superv delay
Unit
Min.
Max
–
Once/day, Several times/day
°C
0
30
°C
0
30
–
Recharging, Full charging, Full charging legio, Full
charg 1st time day, Full charg 1st time day legio
°C
0
20
min
10
600
–
Off, Always, Automatic
°C
8
95
°C
8
95
–
Off, On
–
Off, Summer, Always
–
Substitute, Summer, Always
–
24h/day, DHW release, Time program 4/DHW
–
External thermostat, DHW sensor
–
Off, On
–
Off, On
–
No, Yes
–
No, Yes
–
No, Yes
%
0
100
%
0
100
–
Off, Always, DHW release
–
DHW sensor B3, DHW sensor B31
°C
0
10
°C
2
20
s
0
60
–
No, Yes
°C
-20
20
s
0
255
Factory setting Several times/day
16 8 Full charging
5 60 Automatic 70 70 Off Always Substitute DHW release DHW sensor On On
No No Yes 100 100 Always DHW sensor B3 2 2 30 Yes 4 30
Installation & Servicing Instructions ATAG QR-Series
52
Parameters technician
Menu Configuration
Line no. 5710 5715 5721 5730
5731
5734 5736 5737 5774 5775 5840 5841 5870 5890
Selection possibilities Heating circuit 1 Heating circuit 2 Heating circuit 3
DHW sensor
DHW controlling element
Basic pos DHW div valve DHW separate circuit Optg action DHW div valve Ctrl
boiler pump/DHW valve Boiler pump with DHW Solar controlling element External
solar exchanger Combi storage tank Relay output QX1
5891 5892 5930
Relay output QX2 Relay output QX3 Sensor input BX1
5931
Sensor input BX2
Unit
Min.
Max
Factory setting
–
Off, On
On
–
Off, On
Off
–
Off, On
Off
–
DHW sensor B3, Thermostat,
DHW outlet sensor B38
–
No charging request, Charging pump,
Diverting valve
–
Last request, Heating circuit, DHW
DHW sensor B3 Charging pump
Last request
–
Off, On
Off
–
Position On DHW, Position On HC
Position On DHW
–
All requests, Request HC1/DHW only
All requests
Off, On
On
–
Charging pump, Diverting valve
Charging pump
–
Jointly, DHW storage tank, Buffer storage tank
Jointly
–
No, Yes
No
–
0: None
1:Circulating pump Q4
2:El imm heater DHW K6
3:Collector pump Q5
4:Cons circuit pump VK1 Q15
5:Boiler pump Q1
6:Bypass pump Q12
7:Alarm output K10
8:2nd pump speed HC1 Q21
9:2nd pump speed HC2 Q22
10:2nd pump speed HC3 Q23
11:Heat circuit pump HC3 Q20
12:Cons circuit pump VK2 Q18
13:System pump Q14
14:Heat gen shutoff valve Y4
15:Solid fuel boiler pump Q10
16:Time program 5 K13
17:Buffer return valve Y15
18:Solar pump ext exch K9
19:Solar ctrl elem buffer K8
20:Solar ctrl elem swi pool K18
22: Swimming pool pump Q19
25:Cascade pump Q25
26:St tank transfer pump Q11
27:DHW mixing pump Q35
28:DHW interm circ pump Q33
29:Heat request K27
30:Refrigeration request K28
33:Heat circuit pump HC1 Q2
34:Heat circuit pump HC2 Q6
35:DHW ctrl elem Q3
36:Instant heater ctrl elem Q34
38:Water filling K34
39:2nd boiler pump speed Q27
40:Status output K35
–
41:Status information K36
42:Flue gas damper K37
–
43:Fan shutdown K38
–
0: None
1:DHW sensor B31
2:Collector sensor B6
4:DHW circulating sensor B39
5:Buffer sensor B4
6:Buffer sensor B41
7:Flue gas temp sensor B8
8:Segment flow sensor B10
9:Solid fuel boiler sensor B22
10:DHW charging sensor B36
11:Buffer sensor B42
12:Segment return sensor B73
13:Cascade return sensor B70
14:Pool sensor B13
–
16:Solar flow sensor B63
17:Solar return sensor B64
19: Primary exch sensor B26
33:Heat circuit pump HC1 Q2
None DHW ctrl elem Q3
None 7:Flue gas temp sensor B8
Installation & Servicing Instructions ATAG QR-Series
53
Parameters technician
Menu Configuration
Line no. 5950
Selection possibilities Function input H1
5960
5951 5961 5953 5954 5955 5956 5970
Function input H3
Contact type H1 Contact type H3 Voltage value 1 H1 Function value 1 H1 Voltage
value 2 H1 Function value 2 H1 Function input H4
5971 5973 5974 5975 5976
Contact type H4 Frequency value 1 H4 Function value 1 H4 Frequency 2 H4 Function value 2 H4
Unit
Min.
Max
–
0: None
1:Optg mode change HCs+DHW
2:Optg mode changeover DHW
3:Optg mode changeover HCs
4:Optg mode changeover HC1
5:Optg mode changeover HC2
6:Optg mode changeover HC3
7:Heat generation lock
8:Error/alarm message
9:Consumer request VK1
10:Consumer request VK2
11:Release swi pool source heat
12:Excess heat discharge
13:Release swi pool solar
14:Operating level DHW
15:Operating level HC1
16:Operating level HC2
17:Operating level HC3
18:Room thermostat HC1
19:Room thermostat HC2
20:Room thermostat HC3
21:DHW flow switch
22:DHW thermostat 24: Pulse count
28:Checkb sign flue gas damper
29:Start prevention
31:Boiler flow switch
32:Boiler pressure switch
51:Consumer request VK1 10V
52:Consumer request VK2 10V
54: Pressure measurement 10V
58: Preselected output 10V
–
NC, NO
–
V
0
10
–
-1000
5000
V
0
10
–
-1000
5000
–
0: None
1:Optg mode change HCs+DHW
2:Optg mode changeover DHW
3:Optg mode changeover HCs
4:Optg mode changeover HC1
5:Optg mode changeover HC2
6:Optg mode changeover HC3
7:Heat generation lock
8:Error/alarm message
9:Consumer request VK1
10:Consumer request VK2
11:Release swi pool source heat
12:Excess heat discharge
13:Release swi pool solar
14:Operating level DHW
15:Operating level HC1
16:Operating level HC2
17:Operating level HC3
18:Room thermostat HC1
19:Room thermostat HC2
20:Room thermostat HC3
21:DHW flow switch
22:DHW thermostat 24: Pulse count
28:Checkb sign flue gas damper
29:Start prevention
31:Boiler flow switch
32:Boiler pressure switch
50: Flow measurement Hz
–
NC, NO
–
0
1000
–
-1000
5000
–
0
1000
–
-1000
Factory setting None
Consumer request VK1 10V NO NO 2 200 10 850
Start prevention
NC 0 0 0 0
Installation & Servicing Instructions ATAG QR-Series
54
Parameters technician
Menu Configuration
Line no. 6016
Selection possibilities Function input H8
6017 6018
Type of contact H8 Function input H9
6019 6020 6021 6022
Type of contact H9 Function extension module 1 Function extension module 2 Function extension module 3
6024 6026 6028 6030 6031 6032 6033 6034 6035 6036 6037 6038
Funct input EX21 module 1 Funct input EX21 module 2 Funct input EX21 module 3 Relay output QX21 module 1 Relay output QX22 module 1 Relay output QX23 module 1 Relay output QX21 module 2 Relay output QX22 module 2 Relay output QX23 module 2 Relay output QX21 module 3 Relay output QX22 module 3 Relay output QX23 module 3
Unit
Min.
Max
–
0: None
18 Room thermostat HC1
19 Room thermostat HC2
20 Room thermostat HC1
–
0: Normal closed, 1: Normal opened
–
0: None
18 Room thermostat HC1
19 Room thermostat HC2
20 Room thermostat HC1
–
0: Normal closed, 1: Normal opened
–
0: None
1:Multifunctional
–
2:Heating circuit 1
–
3:Heating circuit 2
4:Heating circuit 3
5:Return temp controller
6:Solar DHW
7:Primary contr/system pump
–
0: None
25: Limit thermostat HC –
–
–
0: None
1:Circulating pump Q4
–
2:El imm heater DHW K6
–
3:Collector pump Q5 4:Cons circuit pump VK1 Q15
–
5:Boiler pump Q1
6:Bypass pump Q12
–
7:Alarm output K10
–
8:2nd pump speed HC1 Q21 9:2nd pump speed HC2 Q22
–
10:2nd pump speed HC3 Q23
11:Heat circuit pump HC3 Q20
–
12:Cons circuit pump VK2 Q18
13:System pump Q14
–
14:Heat gen shutoff valve Y4
15:Solid fuel boiler pump Q10
16:Time program 5 K13
17:Buffer return valve Y15
18:Solar pump ext exch K9
19:Solar ctrl elem buffer K8
20: Solar ctrl elem swi pool K18
22: Swimming pool pump Q19
25:Cascade pump Q25
26:St tank transfer pump Q11
27:DHW mixing pump Q35
28:DHW interm circ pump Q33
29:Heat request K27
30:Refrigeration request K28
33:Heat circuit pump HC1 Q2
34:Heat circuit pump HC2 Q6
35:DHW ctrl elem Q3
36:Instant heater ctrl elem Q34
38:Water filling K34
39:2nd boiler pump speed Q27
40:Status output K35
41:Status information K36
43: Fan shutdown K38
Factory setting 0: None
0: Normal closed 0: None
0: Normal closed No function No function No function
None None None None None None None None None None None None
Installation & Servicing Instructions ATAG QR-Series
55
Parameters technician
Menu Configuration
Line no. 6040 6041 6042 6043 6044 6045
Selection possibilities Sensor input BX21 module 1 Sensor input BX22 module 1 Sensor input BX21 module 2 Sensor input BX22 module 2 Sensor input BX21 module 3 Sensor input BX22 module 3
6046 6054 6062
Function input H2 module 1 Function input H2 module 2 Function input H2 module 3
6047 6055 6063 6049 6057 6065 6050 6058 6066
Contact type H2 module 1 Contact type H2 module 2 Contact type H2 module 3 Voltage value 1 H2 module 1 Voltage value 1 H2 module 2 Voltage value 1 H2 module 3 Function value 1 H2 module 1 Function value 1 H2 module 2 Function value 1 H2 module 3
Unit
Min.
Max
–
0: None
–
1: DHW sensor B31 2: Collector sensor B6
–
4: DHW circulation sensor B39
5: Buffer sensor B4
–
6: Buffer sensor B41
7: Flue gas temp sensor B8
–
8: Common flow sensor B10
–
9: Solid fuel boiler sensor B22 10: DHW charging sensor B36
11: Buffer sensor B42
12: Common return sensor B73
13: Cascade return sensor B70
14: Swimming pool sensor B13
16: Solar flow sensor B63
17: Solar return sensor B64
19: Primary exch sensor B26
–
0: None
1: Optg mode change HCs+DHW
–
2: Optg mode changeover DHW
–
3: Optg mode changeover HCs 4: Optg mode changeover HC1
5: Optg mode changeover HC2
6: Optg mode changeover HC3
7: Heat generation lock
8: Error/alarm message
9: Consumer request VK1
10: Consumer request VK2
11: Consumer request VK3
12: Excess heat discharge
13: Release swi pool solar
14: Operating level DHW
15: Operating level HC1
16: Operating level HC2
17: Operating level HC3
18: Room thermostat HC1
19: Room thermostat HC2
20: Room thermostat HC3
21: DHW flow switch
22: DHW thermostat
25: Limit thermostat HC
29: Start prevention
31: Boiler flow switch
–
–
NC, NO
–
V
V
0
10
V
–
–
-1000
5000
–
Factory setting None None None None None None
None None None
NO NO NO 0 0 0 0 0 0
Installation & Servicing Instructions ATAG QR-Series
56
Parameters technician
Installation & Servicing Instructions ATAG QR-Series
Menu Configuration
LPB
57
Line no. 6051 6059 6067 6052 6060 6068 6085 6086 6097 6098 6100 6110 6117 6118 6120 6200 6205 6212 6213 6215 6217 6220 6234 6236 6351
Selection possibilities Voltage value 2 H2 module 1 Voltage value 2 H2 module 2 Voltage value 2 H2 module 3 Function value 2 H2 module 1 Function value 2 H2 module 2 Function value 2 H2 module 3 Output P1 function selection Signal logic output P1 Sensor type collector Readjustm collector sensor Readjustm outside sensor Time constant building Central setpoint shift Setpoint reduction delay Frost protection plant Save sensors Reset to default parameters Control number heat generation 1 Control number heat generation 2 Control number storage tank Control number heating circuits Device SW version Boiler type number OEM Parameter set number OEM Function OT channel 1
6352
Function OT channel 2
6355 6356 6357 6359
6600 6601 6604 6610 6612 6620 6621 6623 6624 6625
6630 6631 6632 6640
Room controller HC1 Room controller HC2 Room controller HC3 Extern handling
DHW
LPB-Adress Segment address LPB power supply function selection Display system
message Alarm delay Central switch-over working area Summer/winter changeover
automatic Operating mode changeover Manuall producer lock Dhw allocation
Cascade master Ext source with eco mode Outside temp limit external source
accept Clock time source
Unit V V V °C °C h °C
K/min –
–
–
min –
–
Min.
Max
0
10
-1000
5000
0: None, 1: Boiler pump Q1
0: Standard, 1: Inverted
NTC, PT 1000
-20
20
-3
3
0
50
1
100
Off , 1 – 200
Off, On No, Yes No, Yes
0
199999
0
199999
0
199999
0
199999
0
99
0
65535
0
65535
1: By ext. room controller 1 2: By ext. room controller 2
References
- Boilers | Boilers Combi | Boilers electric | ATAG Commercial | ATAG Commercial a division of Elco Heating Solutions Limited
- Installers First
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>