SELTRON AVC + 3 W Surface Mounted Heating Controller Instructions
- June 9, 2024
- SELTRON
Table of Contents
AVC + 3 W Surface Mounted Heating Controller
Instructions
AVC + 3 W Surface Mounted Heating Controller
Actuator AVC For Mixing Valve
For the connection of the actuator to the electric power supply, a circuit
breaker with an open contact gap of at least 3 mm shall be implemented for
each of the line conductors.
Prior to starting to connect the actuator, please check whether the mains
power supply, or the main circuit breaker, has been turned off.
Mounting Instructions
-
Take the button, lever or indicator (depending on the actuator model) off, remove the scale and loosen the screws. Remove the actuator cover (cf. Picture 1), too.
-
Insert the electrical supply cable through the cable gland and connect the electrical conductors (cf. Fig. 2-I). Fasten the cables (cf. Fig. 2-II) and adjust the ring (depending
on the actuator model) for the additional switch (cf. Fig. 2-III). -
Return the motor cover to its original position and fasten both screws (cf. Fig. 3).
-
Put the adapter “b” onto the motor shaft “a” and turn it to the centre of the valve scale. Fasten the locking screw “c” to the valve. Position the actuator “d” onto the adapter “b”.
The possible actuator mounting positions are indicated in Figure 4-I.
As per factory default, the actuator is set to the central position (45 °).Đ
Insert the scale “f”; while adjusting it, pay attention to the open and closed
positions of the valve. Finally, insert the button “h”, handle “g”, or
indicator “i”, ensuring that the position of the accessory applied complies
with the scale.
Insert and fasten the screw “l”. Cover the button with the lid “j” or “k”. *
Valid for actuators supplied without cable.
Instructions For Use
Automatic operation
When the button “e” (Fig. 4) is in the position , the actuator, operates
automatically.
Manual operation
When the button “e” (Fig. 4) is in the position the actuator operation is
turned off.
The valve position can be set manually by the button or handle.
Indication Lamps
The actuator has 3 indication lamps. The left and right lamps indicate the
actuator rotation direction (Fig. 2-III). The central lamp indicates the state
of the additional switch (depending on the actuator model).
Technical data
| AVCO5 AVC10| AVC15
---|---|---
Maximum load| 5 Nm 10 Nm| 15 Nm
Rotation angle| 90 °
Running time| 15 s, 30 s, 1min, 2 min, 4 min, 8 min
Supply voltage| 230 (24) V —, 50 Hz
Consumption| 2,5 VA – 4 VA
Protection degree| IP42
Protection class| II
Dimensions (WxHxD)| M x 101 x 85 (72)
Weight| 390 g – 630 g I 600 g – 860 g
Disposal of Old Electrical & Electronic Equipment
(Applicable in the European Union and other European countries with separate
collection systems)
This symbol on the product or on its packaging indicates that this product
shall not be treated as household waste. Instead it shall be handed over to
the applicable collection point for the recycling of electrical and electronic
equipment.
By ensuring this product is disposed of correctly, you will help prevent
potential negative consequences for the environment and human health, which
could otherwise be caused by inappropriate waste handling of this product.
The recycling of materials will help to conserve natural resources. For more
detailed information about recycling of this product, please contact your
local city office, your household waste disposal service or the shop where you
purchased the product.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>