EATON C22-PVT45P-K02 Kill Switch Instruction Manual

June 9, 2024
EATON

EATON C22-PVT45P-K02 Kill Switch

EATON C22-PVT45P-K02 Kill Switch

Electric current! Danger to life!
Only skilled or instructed persons may carry out the following operations.

C22-PV…

M22-XPV
M22-X(Z)(A)(B)K…

mm   in
  a ≧ b ≧
C22-PV…45… 55 55
C22-PV…60… 70 70
M22-XPV60-Y-… 70 70

M22-XPV…

M22-XPV…

M22-XPV60-Y-24

M22-XPV60-Y-24

M22-XPV60-Y-120

M22-XPV60-Y-230

![M22-XPV60-Y-120

M22-XPV60-Y-230](https://manuals.plus/wp- content/uploads/2023/02/EATON-C22-PVT45P-K02-Kill-Switch-Instruction- Manual-12.png)

 |  | M22 -( C ) K . . .| M22 -( C ) K…| C22 PV. . .| M22 PV…
---|---|---|---|---|---
Ie
AC-15| 24 V| –| –| 4A| –
115V| 6A| 6A| 2A| –
220 V 230 V 240 V| 6A| 6A| 1.5 A| –
380 V 400 V 415 V| 4A| –| –| –
500V| 2A| –| –| –
Ie
DC-13| 24 V| 3A| 3A| 3A| –
42V| 1.7 A| –| –| –
60V| 1.2 A| 1 A| 1 A| –
110 V| 0.6 A| 0.6 A| 0.6 A| –
220V| 0.3A| 0.3A| 0.3 A| –
Ue AC|  | 500 V| 230V| 230 V| –
Ue DC|  | 220 V| 220 V| 220 V| –
U·I|  | 500 V| 250 V| 250V| –
Uimn|  | 6000 V AC| 4000 V AC| 4000 V AC| –
In|  | 1 kA| 1 kA| 1 kA| –
IP|  | 20| 20| 67,69| 66, 67,69

Safety and application notes

  • Can be installed in any position.
  • Install the emergency stop unit in such a way that the operator is protected against penetrating foreign particles, e.g., swarf, sand, etc.
  • If emergency stop devices are connected in series, the performance level as defined in EN ISO 13849-1 may become lower due to reduced fault detection capabilities.
  • When using emergency stop applications, it is required for the overall system to be validated as specified in EN ISO 13849-2.

Regular maintenance activities

  • Check the emergency stop unit to ensure that it has a secure mechanical fit.
  • Check the cable connections to make sure they are in good condition.

Max. short-circuit protective devi ce| M22- ( C ) K . . .| M22- ( C ) K | C22-PV | M22-PV .. .
---|---|---|---|---
Fuseless| PKZM0-10/

FAZ-86/1

| –| –| –
| 10 A| 10 A| 10 A| –

CAUTION

The devices can be used for the emergency-stop/ emergency-off functions. The definition of the functions/symbols to be used is specified in the following standards:
– IEC 60204-1 – DIN EN 60204-1
– ISO 13850 – DIN EN ISO 13850 or in the relevant national standards

Declaration of Conformity
Declaration of Conformity
Declaration of Conformity Declaration of Conformity

EATON  Logo

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals