EATON C22-PVT45P-K02 Kill Switch
Electric current! Danger to life!
Only skilled or instructed persons may carry out the following operations.
C22-PV…
M22-XPV
M22-X(Z)(A)(B)K…
mm | in | |
---|---|---|
a ≧ | b ≧ | |
C22-PV…45… | 55 | 55 |
C22-PV…60… | 70 | 70 |
M22-XPV60-Y-… | 70 | 70 |
M22-XPV…
M22-XPV60-Y-24
M22-XPV60-Y-120
M22-XPV60-Y-230
![M22-XPV60-Y-120
M22-XPV60-Y-230](https://manuals.plus/wp- content/uploads/2023/02/EATON-C22-PVT45P-K02-Kill-Switch-Instruction- Manual-12.png)
| | M22 -( C ) K . . .| M22 -(
C ) K…| C22 – PV. . .| M22 – PV…
---|---|---|---|---|---
Ie
AC-15| 24 V| –| –| 4A| –
115V| 6A| 6A| 2A| –
220 V 230 V 240 V| 6A| 6A| 1.5 A| –
380 V 400 V 415 V| 4A| –| –| –
500V| 2A| –| –| –
Ie
DC-13| 24 V| 3A| 3A| 3A| –
42V| 1.7 A| –| –| –
60V| 1.2 A| 1 A| 1 A| –
110 V| 0.6 A| 0.6 A| 0.6 A| –
220V| 0.3A| 0.3A| 0.3 A| –
Ue AC| | 500 V| 230V| 230 V| –
Ue DC| | 220 V| 220 V| 220 V| –
U·I| | 500 V| 250 V| 250V| –
Uimn| | 6000 V AC| 4000 V AC| 4000 V AC| –
In| | 1 kA| 1 kA| 1 kA| –
IP| | 20| 20| 67,69| 66, 67,69
Safety and application notes
- Can be installed in any position.
- Install the emergency stop unit in such a way that the operator is protected against penetrating foreign particles, e.g., swarf, sand, etc.
- If emergency stop devices are connected in series, the performance level as defined in EN ISO 13849-1 may become lower due to reduced fault detection capabilities.
- When using emergency stop applications, it is required for the overall system to be validated as specified in EN ISO 13849-2.
Regular maintenance activities
- Check the emergency stop unit to ensure that it has a secure mechanical fit.
- Check the cable connections to make sure they are in good condition.
Max. short-circuit protective devi ce| M22- ( C ) K .
. .| M22- ( C ) K …| C22-PV …|
M22-PV .. .
---|---|---|---|---
Fuseless| PKZM0-10/
FAZ-86/1
| –| –| –
| 10 A| 10 A| 10 A| –
CAUTION
The devices can be used for the emergency-stop/ emergency-off functions. The
definition of the functions/symbols to be used is specified in the following
standards:
– IEC 60204-1 – DIN EN 60204-1
– ISO 13850 – DIN EN ISO 13850 or in the relevant national standards