V-TAC VT-48100E LFP Lithium Rack Solar System Storage
INTRODUCTION
Thank you for selecting and buying V-TAC Product. V-TAC will serve you the best. Please read these instructions carefully & keep this user manual handy for future reference. If you have any another query, please contact our dealer or local vendor from whom you have purchased the product. They are trained and ready to serve you at the best.
Multi-Language Manual QR CODE Please scan the QR code to access the manual in multiple languages.
Overview
Overview
This operation manual mainly introduces the VT48100E ESS series product
introduction, application description, installation instructions, power-on
instructions, maintenance instructions and provides instructions for technical
support engineers, maintenance engineers and users.
Reader
This document is mainly applicable to the following engineers.
- Technical Support Engineer
- Installation Personnel
- Maintenance Engineer
Signs
The following signs may appear in this article, and their meanings are as
follows.
Sign | Meaning | Description |
---|---|---|
Danger
|
Indicates a hazard with a high level of risk that will cause death or serious injury if not avoided.
|
Warning
|
Indicates a hazard with a moderate risk that may cause death or serious injury if not avoided.
|
Notice
|
Indicates a hazard with a low level of risk that may cause minor or moderate harm if not avoided.
NOTE|
Explanation
| Supplementary explanation of key information in the main text. “Explanation” is not safety warning information, and does not involve personal, equipment and environmental
damage information.
Safety
Safety Precautions
Before carrying out battery work, you must read carefully the safety precautions and master the correct installation and connection methods of the battery.
- Prohibit to turn it upside down, tilt, or collide.
- Prohibit to short-circuit the positive and negative poles of the battery, otherwise it will cause the battery to be damaged.
- Prohibit to throw the battery pack into a fire source.
- Prohibit to modify the battery, and it is strictly prohibited to immerse the battery in water or other liquids.
- DO NOT place installation tools on the battery during battery installation.
- DO NOT disassemble, squeeze, bend, deform, puncture, or shred the battery without the authorization of supplier and authorized dealers.
- DO NOT exceed the temperature range, otherwise it will affect the battery performance and safety.
- The battery circuit must be kept disconnecting status during installation and maintenance operations.
- Check the battery connection end bolts regularly to confirm that the bolts are tight.
Abuse Operation
The battery pack needs to avoid abuse operations under the following (includ- ing but not limited to) conditions:
Abuse Operation | Protection Description |
---|---|
Reverse connection of positive and negative poles | If the positive and |
negative poles are connected reversely, the battery will be directly damaged.
External short circuit| If the battery pack is short circuited externally, the
battery will be directly damaged.
Series connection application
| The battery pack does not support the application of battery packs in series. If the battery packs are forced to be connected in series, the batteries may be directly damaged,
and may even cause fire, explosion and other dangers.
Overview
Product Description
The VT48100E ESS series products use lithium iron phosphate (LFP) as the
positive electrode material. It can be widely used in energy storage systems
such as residential energy storage, back-up power, and PV self-consumption
optimization.
The battery pack is composed of 15 cells/16 cells of LFP batteries in series
connection, with low self-discharge, high energy density, and no memory
effect. This type of battery also has excellent performance in high rate, long
cycle life, wide temperature range, and high safety.
Features
-
High energy density
Higher volume ratio energy and weight ratio energy. -
Maintenance-free
The battery pack is maintenance-free in the process of using, which can save customers’ battery operation, maintenance testing costs and reduce the frequency of on-site replacement. -
Long cycle life
The battery pack life is 3 times long than the ordinary lead-acid batteries. -
Excellent temperature characteristics
When charging, the battery working temperature can reach 0℃~+60℃
(recommended using temperature: +15~+35℃). When discharging, the battery working temperature can reach -20℃~+60℃ (recommended using temperature: +15~+35℃).
Basic Functions
-
Monitor
The battery system uses a high-performance BMS, it has protection functions such as current, voltage. -
Alarm
Support abnormal alarms such as overvoltage, under-voltage, overcurrent, short circuit, high and low temperature, battery failure, hardware failure, etc. -
Communication
Provide dual RJ45 interfaces, upload alarming and status data through the RS485/ CAN communication protocol.
Overview
-
Parallel connection application
Support multiple battery packs in parallel, RS485/CAN communication supports up to 6 groups without control unit (or max supports 15 groups with control unit). -
Balance function
Support the cells balance function. -
Extended function
Extended SNMP, LCD, anti-theft.
Application Scenario
The battery pack is used to provide backup power, load shifting, peaking
shaving and can be used for residential energy storage, solar energy storage
and other application scenarios.
The normal working operation diagram of the battery pack can be as shown in
the figure below.
Application Description
Parallel Connection Application
The battery packs support parallel connection, and synchronously increases the
backup time or backup power.
Confirm the consistency between the battery packs, check the SOC and voltage
and turn off the batteries before connecting them in parallel.
Multiple battery packs of parallel connection need to use RS485/CAN to
communicate, pay attention to the DIP switch settings.
Low-temperature Application
-
Low-temperature charging
The battery pack does not support direct charging of the battery below 0°C. When the minimum temperature of the battery is below 0°C, the BMS will cut-off the charging circuit and cannot be charged. -
Low-temperature discharging
The battery pack does not support discharge below -20°C. When the minimum temperature of battery is below -20°C, the BMS will cut-off the discharge circuit and cannot discharge.
Low Battery-capacity Storage (SOC≤5%)
After the battery pack is power off, there will be BMS static power consumption and self-discharge loss. In actual scenarios, it is necessary to avoid low-battery-power state ( SOC≤5% ) storage. If it is unavoidable, the longest storage period is 30 days@25°C, 15 days@45°C. The battery needs to be recharged in time after storage, otherwise the battery may be damaged due to over-discharge, and the entire battery pack needs to be replaced.
Application Description
The following conditions may cause the battery pack to be stored in a discharged state:
- After the utility power failure, the line/fault cannot be eliminated in time, and the power supply cannot be restored for a long time.
- After the installation and commissioning work is completed, the utility power is turned off directly, but the battery pack is not powered off, which will cause the battery to enter the low power consumption mode.
- Other reasons cause the battery pack to fail to enter low power consumption normally.
Application of Nearing the Ocean
The atmospheric corrosion environment is defined and classified according to the natural environment state, and the A/B environment is defined as follows:
- A. environment refers to the ocean or the land near the pollution source, or the environment with simple shelter (such as awning. “Near the ocean” refers to the area 0.5~3.7km away from the ocean; “Near the pollution source” refers to the area within the following radius: 3.7km from the saltwater lake, 3km from heavy pollution sources such as smelters, coal mines, and thermal power plants, chemical industry, rubber, electroplating, etc. 2km from medium pollution sources such as chemical industry, rubber and electroplating, etc. And 1km from light pollution sources such as food, leather and heating boilers, etc.
- B. environment. Refers to the environment on land or outside with simple shelter (such as awning within 500m from the coast, or the environment on the sea.
NOTE
- The battery pack can be used under other environmental conditions and cannot be used alone under A/B environment. If it is to be used in the A/B environment, it needs to be equipped with a high-protection air-conditioning cabinet, which is recommended to be IP55 or higher.
Product Introduction
Product Appearance
NOTE
- The battery packs show as above is standard product. At the same time, supplier can also provide customized products according to customer’s requirements.
- With process improvements and product upgrades, the product characteristics described are subject to change without notice.
- For the parameters of specific products, please refer to the corresponding product datasheet.
Product Introduction
Panel Introduction
Panel Function
NOTE
- VT48100E ESS series panel functions take VT48100E as an example.
The interface definition as below table:
Table 5-1 Operation Panel Interface Definition
No. | Name | Description | Remark |
---|---|---|---|
1 | SOC | State of capacity | Details shows in table5-3 |
2 | ALM | Alarm light | Details shows in table5-4 |
3 | RUN | Run state of battery | Details shows in table5-4 |
4
|
RESET
|
Reset switch
| Restart battery and recover some certain alarms status
5| ADD| Dip switch| Address range 0~15
6| RJ-11| RJ-11 interface for firmware update| Used only for professional
maintenance
7| RJ-45| 2*RJ-45 interface for RS485/CAN communication| Details shows in
table5-6
8| Battery Output| Power terminal| –
9| Switch| Power switch| –
10| LCD| Liquid Crystal Display| Display battery information
11| GND| Module ground connection| –
NOTE
- The position or terminal block of the above-mentioned panel interfaces is different for different VT48100E ESS series products. Please refer to the corresponding product datasheet.
Indicator Description
There are 6 indicators on the operation panel, divided into three categories:
4 green SOC Indicators, 1 red alarm Indicator and 1 green run indicator.
Table 5-2 Indicators Flash Mode
Flash mode | ON | OFF | Common name |
---|---|---|---|
Flash Mode 1 | 0.25 s | 3.75 s | / |
Flash Mode 2 | 0.5 s | 0.5 s | Slow Flash |
Flash Mode 3 | 0.5 s | 1.5 s | / |
Flash Mode 4 | 0.25 s | 0.25 s | Strobe |
The power indicator is used to identify the current capacity status of the battery. The number of flashing indicators corresponds to different remaining capacity. The specific meaning is shown in the following table.
Table 5-3 SOC Indicator Definition
Number of Indicator | Remaining Capacity Range |
---|---|
1 indicator on | 0%<SOC≤25% |
2 indicators on | 25%<SOC≤50% |
3 indicators on | 50%<SOC≤75% |
4 indicators on | 75%<SOC≤100% |
The corresponding relationship between battery operation status and indicator
operation status is shown in the following table.
Table 5-4 Battery Status and Indicator Operation Mode
Battery Status| Normal/ Abnormal| RUN| ALM|
SOC Indicators
|
Description
---|---|---|---|---|---
–| –| ●| ●| ●| ●| ●| ●| –
Power off/ Sleep| |
OFF
|
OFF
|
OFF
|
OFF
|
OFF
|
OFF
|
–
Standby
|
Normal
|
Flash 1
|
OFF
|
According to SOC
| Flash mode shown in Table 5-2
Charge| Normal| Flash 2| OFF| According to SOC| –
Discharge| Normal| ON| OFF| According to SOC| –
Alarm
|
Abnormal
| According to the state of charge and discharge|
Flash 2
|
According to SOC
|
Recoverable
Error| Abnormal| OFF| ON| OFF| –
DIP Address
Please assign an address to the battery BMS through the DIP switch to communicate with the battery.
The relationship between DIP address and BMS address as below:
Table 5-5 Correspondence between BMS and DIP switch
Installation
Communication Port Definition
RJ 45 definition as below:
Table 5-6 RJ 45 Definition
RJ 45Photo | Pin | Description |
---|---|---|
1/2/3 | NC | |
4 | RS485_A | |
5 | CAN _L | |
6 | CAN_H | |
7 | RS485_B | |
8 | GND |
NOTE
- The above is the definition of conventional communication, if you have special needs, please contact supplier or an authorized dealer.
Tools Preparation
ATTENTION
Use insulated tools to avoid electric shock. If you use tools without
insulation protection, you need to wrap the exposed metal parts with
insulation tape for insulation treatment.
The following table describes the tools and meters that may be used before
installation.
Table 6-1 Installation
Open-pack Inspection
- Move the battery to the nearby of site.
- Use a claw hammer to open the box and check whether the items are complete.
- Check the appearance whether there is damaged or leakage.
ATTENTION
The battery is heavy, if possible, please use tools to assist in handling.
NOTE
- Package contains VT48100E ESS series batteries, operation manual and accessories.
- If the battery is found to be damaged or leakage, please do not proceed to the next installation, and contact supplier or an authorized dealer in time.
Installation
- Make sure the Power system is in off state.
- Put the battery into cabinet or rack.
- Use 4 M6x25 bolts to fix the battery pack on the cabinet.
- Take out the ground wires and connect one end to the ground point of the battery pack and the other end to the ground point of the cabinet.
ATTENTION
The battery pack should be installed by professionally trained personnel, and
it is strictly forbidden to install it without permission.
Use insulated tools during installation to avoid electric shock. If you use
tools without insulation protection, you need to wrap the exposed metal parts
with insulation tape for insulation treatment.
The battery pack is heavy, and at least 4 manpower must be prepared during the
transportation and installation process. If possible, please use tools to
assist in handling.
Cable Connection
Power Cable Connection
Use the negative power cable to connect the negative bus bar with the battery negative (‘-’) terminal, and use the positive power cable to connect the positive bus bar with the battery positive (‘+’) terminal.
- A. The last power cable connected to the charger or inverter needs to be configured according to the actual current that may exceed 100A.
- B. If the battery total input/output current more than 100A in parallel, the wiring method should configure bus-bars to connect the power cables.
Communication Cable Connection
Use the communication cable to connect the battery packs in series through the RS485/CAN communication port, and connect the battery packs at the end to the external device BMS port. The communication cable pins refer to“Table 5-6 RJ45 Definition”.
120Ω Resistor Connection
To ensure stable CAN communication with the external device/Inverter when
batteries are used in parallel, please take out a 120Ω resistor from the
‘Battery Kit’ and insert it into the RJ45 port of the battery that
communicates farthest with the external device/Inverter.
Set Dial Address
Assign addresses to battery packs by dialing the dialing keys of the dialing
switch. DIP switch address please refer to“Table 5-5 Correspondence between
BMS and DIP switch”.
- A. When the battery and the external device use the CAN communication mode, the battery connected to the external device is set to 0, and the other packs are set to 1/2/3 in sequence.
- B. When the battery and the external device use the RS485 communication mode, the battery connected to the external device is set to 1, and the other packs are set to 2/3/4 in sequence.
ATTENTION
Before connecting cables, make sure that the bus-bars at the user end are in a power-off state.
Pay attention to the polarity of the battery pack.
Communication cables and power cables must be laid separately.
Connect the negative power cables of all battery packs first, and then connect
the positive power cables of the battery packs.
Power On
Power-on Operation
- Power on the charger/inverter at the user terminal.
- Set the lithium battery MCB/Switch to ON (if available).
- Observe Run/Alarm indicator and judge the battery operating status. If the RUN indicator of the battery is on and the ALARM indicator is off, indicating that the battery is working normally. Otherwise indicating the battery is not work, you need to reconfirm whether the cables are connected well.
Power System Parameter Setting
Table 7-1 Parameter Setting
No. | Parameters | Units | Standard Value |
---|---|---|---|
15S | 16S | ||
1 | Rated voltage | V | 48.0 |
2 | Float charge voltage | V | 54.0 |
3 | Standard charge current | A | 0.2C |
4 | Charge current limitation | A | 0.5C |
5 | Maximum charge/discharge current@25℃ | A | 1C |
6 | Condition to float charge | A | 0.05C |
7 | Charging operation temp. | ℃ | 0℃~60℃ |
8 | Discharge operation temp. | ℃ | ﹣20℃~60℃ |
9 | RH | / | 10%~95% |
NOTE
- The content in the table is just our suggestion, and actually need to refer to the customer’s design requirements.
- The setting items of different chargers will be different.
- Follow strictly the power-on procedure to power on the battery pack, otherwise it will cause damage to the device or human body.
- Make sure the charger is powered on before turning on the Battery MCB/Switch.
- Must not change the parameters optionally in the site.
Shipment & Maintenance & Storage
- Batteries will continue charge/discharge until BMS protection if there is Lead-acid mode between battery and charger / Inverter.
- After VT48100E ESS series batteries goes into the sleeping status, please turn on the Battery MCB/Switch again or press the reset button.
Shipment
It is suitable for the transportation of vehicles, ships and airplanes. During
transportation, shading, sun protection and civilized loading and unloading
should be performed. The box containing the product is allowed to be
transported by any means of transportation. In the process of loading and
unloading, the battery should be handled with care to prevent falling,
rolling, and heavy pressure. Avoid direct rain and snow and mechanical impact
during transportation.
And here is the suggestion for the initial SOC before shipment by different
transportation:
- Airplane: 30%
- Sea :50%
- Vehicle:50%
NOTE
- Whether the loading SOC status of the battery is allowed, you need to consult the relevant government transportation department.
Maintenance
Battery Maintenance Considerations
When maintaining the battery, it is required to use insulated tools or wrap the tools in insulation.
- DO NOT place any debris on the top of the battery.
- DO NOT use any organic solvents to clean the battery.
- DO NOT smoke or use naked flames near the battery.
- After the battery is discharged, the battery should be charged in time to avoid affecting the battery life.
- When not using the battery for a long time, please charge the battery to 40%~50% charged state. Long-term storage with low battery may damage the battery.
- All maintenance work must be carried out by professionals.
Routine Maintenance
The staff should perform visual inspection on VT48100E ESS series battery according to the inspection plan, please refer to the following table for maintenance.
Table 8-1 Routine Maintenance (Every three-month)
Items | Standard | Dealing |
---|
Battery Appearance
| The surface is neat and clean without stains.
The terminals are in good condition. The battery pack shell is intact, and there is no bumps, breaks, or leakage. The appearance of the battery pack does not leak.
No deformation or swelling of the shell.
| If the surface is dirty, clean the appearance of the battery pack with a cotton cloth.
The battery pack terminal is damaged, replace the cable.
If the appearance is damaged, leaking or deformed, take a photo and replace the defective battery pack.
Please contact supplier in time for other abnormal situations.
Alarm| No Alarm.| Find the solution as per alarm information.
NOTE
- Suggested routine maintenance for every three-month.
Table 8-2 Routine Maintenance (Every six-month)
Items | Standard | Action |
---|
(Suggested) Complete Cycle
|
Have a complete charge & discharge cycle under the equipment no lack of power.
| Check whether happens alarm action, and please check with the alarm list.
Please contact with supplier if the alarm still exists.
Cables
| There is no aging of the connecting wire and no cracking of the insulation layer.
The bolts at the cable connection are not loose.
|
Replace the faulty connection. Fastening bolts.
Battery Storage
- The recommended storage temperature is 15℃~35℃.
- Battery performance degradation after long-term storage, please shorten shelf time as possible as you can.
- Recharge charge before using to recover capacity loss of self-discharge during storage and transport.
- Storage battery should be at 40%-50%SOC when the battery is not used for a long time.
- Storage battery over 40°C or under 0°C will reduce battery life.
- Storage battery in dry and low temperature, well ventilated place.
If the battery is not used for a long time, the battery must be charged at regular intervals. The charging requirements are as follows:
Table 8-3 Battery Charge Requirement in Storage Status
Storage Temp. | Charge Period | Charge Process |
---|---|---|
20℃~30℃ | Each 6 months | 1.Charge by 0.2C to 100% SOC 2.Discharge by 0.2C to 0% |
SOC 3.Charge by 0.2C to 40%~50% SOC
0℃~20℃ or 30℃~40℃| Each 3 months
Trouble Shooting
Please refer to the table below to deal with common faults:
Table 9-1 FAQ
Phenomenon | Possible cause | Solution |
---|
The indicator does not flash
| The power cable of the battery pack is not properly connected. The power switch is off.
The BMS is in a sleep state. BMS is damaged.
| Reconnect the power cable of the battery pack.
Turn on the power switch. Charge the battery pack.
Replace BMS.
Unable to discharge
|
The terminal of the battery pack is damaged.
BMS communication failure. The power switch is off.
| Replace the battery pack wiring terminals. Reconnect the communication line between the BMS and the battery pack. If the communication cable is damaged, replace the communication cable.
Turn on the power switch.
Unable to charge
|
The charger is malfunctioning. The terminal of the battery pack is damaged.
BMS communication failure. The power switch is off.
| Replace the charger.
Replace the battery pack wiring terminals. Reconnect the communication line between the BMS and the battery pack. If the communication cable is damaged, replace the communication cable.
Turn on the power switch.
Communication fail
| The power switch is off.
The BMS is in a sleep status. The communication cable is
damage.
| Turn on the power switch. Charge the battery pack. Replace the network cable.
Inaccurate voltage display
| The voltage sampling line is damaged.
BMS is damaged.
| Replace the voltage sampling line. Replace BMS.
Low capacity
| The battery pack has not been maintained for a long time. The single battery is damaged.
Inaccurate voltage sampling.
| Use an equalizer to maintain the battery pack. Replace the damaged single battery.
Replace the electrical sampling line or replace
the BMS.
Low cell voltage
| The battery pack has not been maintained for a long time. The single battery is damaged.
Inaccurate voltage sampling.
| Use an equalizer to maintain the battery pack. Replace the damaged single battery.
Replace the electrical sampling line or replace
the BMS.
Warranty
Except for the following and the conditions specified in the contract, you can go to supplier and authorized dealers for reasonable warranty and maintenance.
- Failure of equipment caused by unauthorized disassembly and maintenance operations without the authorization of supplier and authorized dealers is not within the scope of the warranty.
- Equipment damage caused by negligence during storage and transportation is not covered by the warranty.
- The damage to the equipment caused by continuous overload work outside the electrical parameters of the equipment is not covered by the warranty.
- Unauthorized testing of the equipment without the authorization of supplier and authorized dealers will not be covered by the warranty.
- Non-equipment problems, adverse consequences caused by operation and matching problems are not covered by the warranty.
- Equipment damage caused by natural forces, force majeure, and uncontrol- lable factors, such as earthquakes, typhoons, tornadoes, volcanic eruptions, floods, lightning, heavy snow, and wars, is not covered by the warranty.
- If the product serial number is changed, blurred, or torn, it is not covered by the warranty.
Abbreviations
- BMS Battery Management System
- D Depth
- H Height
- LCD Liquid Crystal Display
- LFP LiFePO4
- MOSFET Metal-Oxide-Semiconductor Field-Effect Transistor
- NTC Negative Temperature Coefficient
- PC Personal Computer
- PCB Printed Circuit Board
- PCS Power Conversion System
- RTU Remote Terminal Unit
- SOC State of Charge
- W Width