Monolith 50700 Series Pure Sine Wave Uninterruptible Power Supply UPS User Manual

June 9, 2024
MONOLITH

Monolith logo 50700 Series Pure Sine Wave Uninterruptible Power Supply UPS
User Manual USER MANUAL

50700 Series Pure Sine Wave Uninterruptible Power Supply UPS

Pure Sine Wave Uninterruptible Power Supply (UPS)
Model: 50716, 50717, 50718, 50719, 50720, 50721
www.oltec.com
PLEASE READ AND KEEP THIS MANUAL
Thank you for your trust and for choosing this Pure Sine Wave Qoltec Uninterruptible Power Supply (UPS). We are convinced that the product will meet your expectations. This manual will guide you through the installation and use of the device and contains important safety instructions for the operation and proper installation of the UPS. If you have any problems with the machine, please read this manual carefully before calling Customer Service.

IMPORTANT SAFETY INSTRUCTIONS

The UPS has been designed to provideall the necessary safety conditions to protect home appliances and electronic office equipment If you have any questions, please contact theTechnicalSenrice of NTECsp. zo.o..

  • In order to avoid any damage to the device, it is recommended to ship it in its original packaging.
  • Steam may form inside the UPS in case of sudden changes in temperature. Wait at least 2 hours before starting it. It is imperative to dry the device before turning it on.
  • After drying, all specified conditions must be adhered toin the technical specification, before connecting to the electric network.
  • Please put all cables in a proper place so that they will not be damaged by users. Before connecting to the mains, carefully read all instructions and wamings in the “BEFORE INSTALLATION’ section of this manual. Do not throw any objects into the device. In emergency situations (damage to the housing, front panel, mains connections, flooding with liquid), please turn off the power supply, remove the plug and inform the Technical Service of NTEC sp. zo.o..
  • Do not connectloads to thedevice that exceed its power range.
  • When the input distortion is too great, the power supply may not function properly.
  • Thecable insulation must beaktight to prevent oxidation of the cable.

INTRODUCTION

50716 and 50719 – 500VA/ 50778and 50720- 800VAI 50717and 50721 – 1000VA are Uninterruptible Power Supplies designed specifically to maintain the power supply of all home and office electrical appliances in the event of a mains power failure.They feature the latest line interactive technology, CPU- controlled PM technology and a fully protected modular circuit It is a reliable source of backup power forall types of receivers.
This symbol gives information on points of importance toyour own health and safety, the operation of the UPS and the safety of your data
This symbol contains information, warnings, and other suggestions.

FEATURES:

– 365x 24 hours of operation (Long backup period) High charging current up to 13A, charging large batteries such as 100Ah or 200Ah in ashorttime.
– Puresinewave output Applicableto all types of loads, especially suited to engine loads.
– Modular CPU controlled circuit Provides accurate output signal and protection.
– Big colorful display The largecolourdisplay shows basic information.
– AVR(automatic voltage regulator) function The best solution for places where the mains voltage is very unstable.
– Heavy duty transformer and circuit, strong loading ability With the high efficiency heavy-duty transformer, and specially designed circuit with strong loading ability.
– 3-Stage charging current selector It allows the user to connect different batteries depending on the backup time required.
– Full protection Overload, overheat, battery over charge/discharge, short circuit protection.

SPECIFICATIONS

Model number Capacity Battery voltage Device size (DxWxH)
50716 and 50719 500VA/350W 12VDC 310x148x164mm
50718 arid 50720 800VAINOW 12VDC 310x160x180mm
50717 and 50721 1000VA/700W 12VDC 310x160x180mm

The grounding conductor should be selected in terms of current carrying capacity. Use a grounding cable for all ground connections of devices that are connected to the UPS. There is a risk of damage to electrical circuits without proper grounding or grounding without approval.
When installing the UPS, if the wrong specification cable is used, it may be dangerous to the health of the user and the device itself.

Input voltage range 147-275V AC
Input frequency range 45-65Hz
Znamionowe napiqcie wyjSclowe 230U AC
Rated output voltage Battery mode: /3%; mains mode: +10%.* -13%
Output frequency Battery Mode 50/60 Hz 2 1%: Mains mode

synchronized with input frequency
Wave form| Pure sine wave
Efficiency| Battery mode: >75%; Mains mode: >95%
Transfer time| gams
Display| LED
Charging current| 500VA-7A max
NOVA-10A max
1000VA-13A max
Protection| Low voltage. High voltage, Overheat Short
circuit Overload, Low battery
Buzzer Alarm| Battery mode, battery low yokes overload, cverheat, other errors
Safety standard| CE
Operating temperatures| -10°C – +40°C
Relative humidity| 10%-90%, non-condensing
Storage temperature| -20°- + 40°C
Poziorn halasu| <56013. at 1 m distance with full load
Noise level| IP20
Protection class| I
Mains conversion efficiency: ri| 500VA71000VA- 95%: BOOVA – 94%
Battery conversion conversion efficiency: ri| AVA – 7 – 800VA – 81% 1000UA – 80%
PEC| 0.7

The UPS may only be repaired by an Authorized Service Center. Any attempt by the user to open and repair it may be dangerous.
Attaching magnetic data carriers to the power adapter may damage your data.

INSTALLATION

4.1 UNPACK AND CHECK
The package includes: UPS, operating instructions, warranty card and 2 wires for connecting the battery.
** Please check the rating label/plate to ensure that the UPS is as ordered. Make sure that the housing of the unit is not damaged! If you notice any damage, please contact the seller immediately! Keep the packaging for possible transport.
4.2 PLACEMENT**
This power supply is intended for indoor use only!

  • Install the UPS in acool, dry and clean place.
  • Install the UPS in a well-ventilated area, keep a minimum distance of 50 cm between the UPS and the wall.
  • Keepaway from unstable ground or sources of excessive vibration.
  • Keep away from windows, dust, moisture and cold places.
  • Keepaway from fire and heat sources.
  • Keepawayfromcorrosive gas or fluid.
  • Operating temperature: -10*C-+40.C.
  • Operating humidity: 10%-90%(non-condensing).

The expected operating altitude of this UPS is less than 1000m. If the installation site is above 1000m above sea level, the load capacity will be correspondingly lower, as shown in the table below.

Altitude
(m)| 1000| 1500| WOO| 2500| 3000| 3500| 4000| 4500| 5000
---|---|---|---|---|---|---|---|---|---
% of Load| 100%| 95%| 91%| 86%| 82%| 78%| 74%| 70%| 67%

** Special Precautions:
When the UPS input comes from a generator:
a. Output power capacity must be higher than the UPS rating, otherwise the UPS and generator may not work properly.
b. Output frequency of generator must be in range from 45 to 65Hz, and wave form must be sine wave, otherwise the UPS and generator may not work properly.
4.3 EXTERNAL DESCRIPTION**
A. Front view
Monolith 50700 Series Pure Sine Wave Uninterruptible Power Supply UPS - fig
1

  1. Power switch
  2. LED display
  3. Battery
  4. Mains
  5. Warnings
  6. Overload

EXPLANATION OF SYMBOLS IN LED DISPLAYMonolith 50700 Series Pure Sine
Wave Uninterruptible Power Supply UPS - fig 2

B. Back view (Model: 50716 and 50719 – 500VA)
Monolith 50700 Series Pure Sine Wave Uninterruptible Power Supply UPS -
fig 3

  1. Cooling fan
  2. Battery terminal “-“
  3. Battery terminal….”
  4. AC input
  5. Input circuit breaker (press to reset)
  6. Outlet socket

**B. Back view (Model:50718 and 50720 – 800VA. 50717 and 50721 – 1000VAI![Monolith 50700 Series Pure Sine Wave Uninterruptible Power Supply UPS

4.4 INSTALLATION OF BATTERY
A. Make sure using the correct battery cable. The over current ability of the battery cable should not be less than the maximum discharging current. Please refer to the below table.

Model number Specification of battery cable
50716 and 50719 – 500VA 10AWG/5.26mm2
50718 and 50720- 800VA 8AWG/8.37mm2
50717 and 50721 – 1000VA 6AWG/13.3mm2

B.Pleasemakesure that the battery voltage *correct asspecified on the case.
C. Disconnect the UPS from mains power completely.
D. Connect the negative I-) of battery to the EtATTERY TERMINAL ‘-‘ of UPS, and positivel+Ito the BATTERY TERMINAL”.
E. Before replacing battery, turn off the UPS and disconnect it from mains power.
**
This UPS is designed for longtime backup, the connected battery should be at least 20AH because the initial charging current is at least 3A. Smaller battery could be damaged easily.
4.5 CONNECTION TO MAINS POWER AND TO LOAD
A. Plug the UPS into the wall socket
B. Make sure the loads/appliances are turned off before connection.
C. Connect the loads/appliances to the UPS one by one. Make sure the total capacity of connected appliances does not exceed the rated capacity of UPS.

OPERATION

5.1 TURN ON THE UPS
Press the POWER SWITCH, The UPS is switched on and deliver output till the UPS gives one beeping sound.
Then switch on the connected appliances one by one. If there are 2 or many appliances, please turn on the biggest appliance at the first, the smallest appliance at the last, according to their rated power.
5.2 TURN OFFTHE UPS
Turn off the devices one by one, and then press the “SWITCH” button, when you hear one beep, it means that theUPS will turn off.
Even if the output of UPS is turned off, the UPS is still working to charge the battery, the UPS is not totally switched off.
To switch it off completely, disconnect the UPS from the mains power.

5.3CHARGINGCURRENTSELECTOR
Its recommended toselect the charging current as below:

Battery capacity Charging current
20AH to 50AH low (3A-5A)
60N-I to 100AH Medium (7A-9AI
100AH to 200AH High (9A-13A)

** Wrong selection of the charging current may lead to the damage of battery in charging process!
5.4 WORK AS AVR (AUTOMATIC VOLTAGE REGULATOR)**
Even if the battery is not connected, the UPS can work as an AVR when the input range is 147-275V. offering regulated output and overload protection to the onnecteddevices.

MAINTENANCE OF BATTERY

With correct using and maintenance, the life of the battery can last for three to six years, depending on the times of discharging and temperature. So regular check and maintenance are very necessary.
A. Charge the battery every three months if you don’t use the UPS fora long time. The charging time should beat least 12 hours.
B. If the UPS works continuously in mains mode for more than fours months, please discharge the battery to 50% of rated load, so as to keep the battery be active.
C. More details, please refer to the specification of the battery.

ALARM AND PROTECTION

7.1 BATTERY MODE ALARM
TheUPS will beep 4 sounds when working from mains mode tobattery mode.
7.2 BATTERY LOW VOLTAGEALARM ANDSHUTDOWN
The UPS will beep once every second when battery is in low level. When the battery is near empty, it will beep rapidly andshut down automatically.
7.3 OVERHEAT PROTECTION
When the temperature of transformer winding is exceeding the limitation:
– At MainsMode. the UPS will go to bypass mode automatically.
– At Battery Mode, the UPS will beep rapid ly,than shutdown automatically.

7.40VERLOAD PROTECTION
– At Mains Mode, the UPS wi II beep continually until the overload is removed. At Battery Mode, the UPS will beep 60 seconds, thenshut down automatically.
7.5 SHORTCIRCUIT
– At Mains Mode, the circuit breaker will cut off the input power automatically once a short circuit happens.
– At Battery Mode, the UPS will beep 3 sounds rapidly for around 10 seconds, then shut downautomatically.
7.6 BATTERY REVERSECONNECTION PROTECTION
Once the batteries are reverse connected (battery polarity wrong), the internal DC fuse will be burnt to prevent inverter from being. Please contact Technical Service of NTEC sp.z o.o. to replace it.

MAINTENANCES

This UPS is basically maintenance free! while regular maintenance can extend the lif e of the UPS by the f °Vowing steps:
8.1 REGULAR INSPECTION
– Disconnect the UPS f rom themainspowerandbattery completely
– Use cotton cloth and detergent to clean the body and ventilation holes.
8.2 EXTRAORDINARY INSPECTION
– When malfunction occurs, or the UPS is abnormal, please measure and check the parameters, refer to theauthorized dealer if needed.
– During storms or the rainy season, a detailed inspection should be carried out to prevent failure.
– Maintenance must not be operated when UPS is working.

 OTHERS

This UPS has been designed and manufactured in accordance with strict standards and a quality control system for general use, but if it causes danger to the lives of people orothers, pleasecontactthedealer.
– Apply to traffic system;
– Apply to medical purpose;
– Apply tonuclear. powersystem;
– Apply to aviation and aerospace;
– Apply toall kinds of safety devices; -Otherspecial usages.

DISPLAY &AUDIBLE ALARM

Mode Item LED Display & Audible Alarm
Mains  mode Normal (output on) Input voltage, output voltage, frequency,

load capacity, battery capacity,
‘Mains Mode” symbol appears.
Normal (output off)| Input voltage, battery capacity,
“Mains Mode” symbol appears.
Charging Battery| Bar of “Battery Capacity”
is running
Battery is full, or disconnected| Bar of “Battery Capacity” is full
and still.
Overload| “Overload’symbol appears.
Buzzer beeps continually.
Overheat| Ups goes to bypass mode automatically.
Short Circuit| Input circuit breaker trips off.
Battery mode| Normal| Output voltage, frequency, load capacity, battery capacity,
‘Battery Mode” symbol appears.
Buzzer don’t beep any.
Mode| Item| LED Display & Audible Alarm
---|---|---
Battery mode| Battery Low Voltage| Buzzer beeps continually.
Battery Empty| Buzzer keeps beeping 5 mins,
then UPS shuts down.
Overload (<120%)| “Overload” symbol appears.
Buzzer beeps continually.
Overload (>120%)| „E06″ appears. Buzzer keeps beeping,
then UPS shuts down immediately.
Overheat| „E04″ appears. Buzzer keeps beeping, then UPS shuts down immediately.
Short Circuit| ,,E06″ appears. Buzzer keeps beeping,
then UPS shuts down immediately.

PROBLEM SOLVING

Malfunction Cause Solution
CUPS goes into battery mode, but there is mains power The input voltage or
input frequency is out Of range Wait till the input voltage or Input

frequencywill be normal
2.Can not turn on UPS when there
is mains power.| Press tine is too short| Press and hold the power switch till the UPS give a beeping sound
Others| Contact the seller
3.can not turn on UPS at battery mode.| Press time is too shon| Press and had the power switch till the UPS give a beeping sound
Battery is empty| Charge the battery
Battery connection is Nose / disconnected| Tighten/ connect the battery
Others| Contact the seller
4.Can not charge the battery| Battery is faulty| Replace the battery
Charger is faulty| Contact the seller
5. Short backup time| Short charging time| Charge battery at least 10 hours
---|---|---
Battery is faulty| Replace the battery
6.”Overload” symbol appears, or ” Overload” LED is ON, and UPS
is beeping| UPS is overloaded| Removed the non-critical load
7.”Error” symbol appears, or “Overload” LED is ON (not due to overload, and UPS is beeping).| UPS is overheating| Remove the non-critical load
Ventilation hole are blocked| Clean the ventilation holes
Ambient temperature is too high| Cut off the output and input, and wait at least 30 minutes, then restart it
Load is short circuit| Remove load and restart the UPS, if it is still not ok.,
contact the seller
8.Input circuit breaker trips off| UPS is short circuit| Contact the dealer /manufacturer
9.Other| Other| Contact the dealer Manufacturer

ECOLOGICAL INFORMATION

Waste electrical and electronic equipment are a special waste category, collection, storage, transport, treatment and recycling are important because they can avoid environmental pollution and are harmful to heath submitting waste electrical and electronic equipment to special collection centers makes the waste to be recycled property and protecting the environment.

Producer: NTEC sp. z o.o. ul.
Chorzowska 44B 44-100
Gliwice, Poland
www.b2b.ntec.eu
WEEE/BDO: 000137497
Made in China
Designed in Europe www.qoltec.com Monolith 50700
Series Pure Sine Wave Uninterruptible Power Supply UPS -