Schneider Electric 56165 Residual Current Protection Relay Instruction Manual

June 9, 2024
Schneider Electric

56165 Residual Current Protection Relay
Instruction Manual

56165 Residual Current Protection Relay

Protection or monitoring relay

Schneider Electric 56165 Residual Current Protection
Relay

Safety instructions

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

  • This device is designed to protect personnel and equipment.
  • This equipment must only be installed and serviced by qualified electrical personnel.
  • Turn off all power supplying this equipment before working on or inside equipment. Lock the switchgear in the isolated position.
  • Always use a properly rated voltage sensing device to confirm power is off.
  • Put back all devices, doors, and covers before turning on power to this device.

Failure to follow these instructions will result in death or serious injury.

Unpacking

Schneider Electric 56165 Residual Current Protection Relay -
1

The product’s manufacture date is coded PP-YYYY-Www-D, where:

  • PP: plant code
  • YYYY: year of manufacture
  • Www: week of manufacture
  • D: weekday of manufacture (Monday = 1)

Eg: 7Q-2014-W19-3 = product manufactured at plant 7Q on Wednesday 7 May 2014.

Description

Schneider Electric 56165 Residual Current Protection Relay -
2

A Power supply terminals
B Green power LED
C Red fault LED
D Set point and time delay settings
E Test and Reset buttons
F Sealing cover

Installation

Schneider Electric 56165 Residual Current Protection Relay -
3

Schneider Electric 56165 Residual Current Protection Relay -
4

Connection

Relay supply

Schneider Electric 56165 Residual Current Protection Relay -
5

Cabling with MN

Schneider Electric 56165 Residual Current Protection Relay -
6

All the diagrams are shown with the circuits “de-energised”, all the devices “open” and the relays in the “released” position.

MIN| Undervoltage release
MX| Shunt release
Q1| Main circuit protection circuit-breaker
Q2| DPN circuit breaker
Q3| 1A circuit-breaker C or D curve
T| Class 2 insulation transformer compulsory for VA, A2 24 V AC
T1 -T2, S1-S2, M1 -M2| A or OA type toroid or rectangular sensor (if lAn 500 mA)
Z| The DC supply must be galvanically insulated from the network
RH••M
Al -A2| Auxiliary supply
T1-T2| Sensor
11-14| “Supply voltage presence” relay
26-25| Device Test
27-25| “Fault” status Reset
31-32-34| “Fault” changeover relay

Terminal capacity

| Cable max. length| **| | | |
---|---|---|---|---|---|---
RH10M, RH21M, RH86M, RH99M
11, 14| –| 0.2…4 mm²
AWG 24-12| 0.2. 2.5 mm²
|AWG 24-14| 8 mm
(0.31 in)| 0.6 N.m.
(5.3 Ib-in)
31,32,34| –
A1, A2| –| 0.2. 2.5 mm²
AWG 24-14| 0.25. 2.5 mm²
AWG 24-14| 7 mm
(0.27 in)| 0.6 N.m.
(5.3 Ib-in)
T1, T2
(1)**| –| 0.14. 1.5 mm²
AWG 26-16| 0.14…1 mm²
AWG 26-18| 0.2. 0.5 mm²
AWG 24-20| 5 mm

(0.19 in)

| 0.25 N.m.
(2.2 Ib-in)
25, 26, 27 (2)| < 10 m ( 30 ft )
Rectangular sensors
L1: 280 x 115
L2: 470 x 160| 10 m ( 30 ft )| 0.5. 2.5 mm²
AWG 20-14| 8…9 mm
(0.33 in)| –
Toroids **
TA30, PA50, IA80, MA120, SA200, GA300, POA, GOA TOA80, TOA120| 18 m ( 60 ft )| 0.22 mm2 ( AWG 22 )
(3)| ** 6…7 mm
(0.25 in)| ** –
60 m ( 197 ft )| 0.75 mm2 ( AWG 18 )
(3)
80 m ( 262 ft )| 1 mm2 ( AWG 18 )
(3)
100 m ( 328 ft )| 1.5 mm2 ( AWG 16 )
(3)**

  1. Twisted pair
  2. 3 twisted wires
  3. Wire cross-section for a resistance Rmax. = 3 Ω

Test cabling and remote Reset
Use pushbuttons with “low level” contacts adapted to load of 1 mA at 4 V.

Schneider Electric 56165 Residual Current Protection Relay -
7

Compatibility of the various sensors

Toroids Vigi PacT RH●●M
TA30, PA50, IA80, MA120, SA200, GA300, POA, GOA , TOA80, TOA120 OK
Rectangular sensors Vigi PacT RH●●M
L1: 280 x 115 **** I∆n u 0.3 A

L2: 470 x 160

Setting

Schneider Electric 56165 Residual Current Protection Relay -
8

If I∆n is set to 30 mA tripping is instantaneous (∆t = 0s).

Test with tripping

PLEASE NOTE
A test with tripping is compulsory on installation startup.

OFF
ON

  1.  RH99M signalling: resetting is automatic

Test without tripping
PLEASE NOTE

A test with tripping is compulsory on installation startup.

OFF
ON

  1. RH99M signalling: resetting is automatic

Commissioning

Dielectric test Sealing

Schneider Electric 56165 Residual Current Protection Relay -
11

NOTICE
HAZARD OF PRODUCT DAMAGE

The power supply A1-A2 must be disconnected before dielectric test. Failure to follow these instructions can result in equipment damage.
Status LEDs

On Fault Meaning ****
Normal operation
Fault current detected
Faulty sensor-relay link
No power or device not working
Anomaly detected
__ ****
--- --- ---
OFF ON flashing

Characteristics

  • Type of network to monitor: < 1000 V AC; 50 Hz, 60 Hz, 400 Hz
  • Overvoltage category: 4
  • Storage temperature: -55…+85° C(-67 … +185° F)
  • Operating temperature: -35…+70° C (-31 … +158° F)
  • Measurement accuracy: 7 %
  • Maximum consumption: 4 VA
  • Degree of protection: IP 20

Schneider Electric Industries SAS
35 rue Joseph Monier
CS 30323
F – 92506 Rueil Malmaison Cedex
www.se.com
Schneider Electric Limited
Stafford Park 5
Telford, TF3 3BL
United Kingdom
www.se.com/uk
51005191AA-09
© 2022 Schneider Electric. All rights reserved.
Printed on recycled paper.

Documents / Resources

| Schneider Electric 56165 Residual Current Protection Relay [pdf] Instruction Manual
56165, Residual Current Protection Relay, Protection Relay, Residual Current Relay, Current Relay, Relay
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Schneider Electric User Manuals

Related Manuals