Carrier R32 Air-to-water Monobloc Wired controller User Manual
- June 9, 2024
- Carrier
Table of Contents
Carrier R32 Air-to-water Monobloc Wired controller User Manual
Acronyms
IDU| Indoor unit
ODU| Outdoor unit
DHW| Domestic hot water
EH| Electrical heater
IAT| Indoor ambient temperature
OAT| Outdoor ambient temperature
LWT| Leaving water temperature
EWT| Entering water temperature
Tw-in| Entering water temperature of BPHE
Tw-out| Leaving water temperature of BPHE
BPHE| Brazed Plate Heat Exchanger
|
Presentation
This wired controller is used to control the operation of the unit and
configuration of the system. It can also be used to check the system running
parameter and display the status of system via the LCD screen. The wired
controller communicates with the IDU (Indoor unit) board with certain
protocols and detect the communication status in real time. The IDU board will
activate the communication fault alarm once it loses communication. However,
it will not send the alarm if you do not connect the wired controller to the
IDU board with the system power on. Hence, if the wired controller is not
necessary, please do not connect it before the system is powered on. The wired
controller will shut down its screen for saving energy without needing to
press for 35s (except the technical parameter configuration), and will wake up
if you press any button.
Application of the wired controller:
- Power supply: Take power supply from IDU board (12V power supply);
- Working temperature range: -300 ~500
- Working humidity range: RH10%~95%
Wired controller can be installed inside your home or on the unit itself for split types. This manual provides guidelines on how to use this interface effectively. If you have any questions regarding the display and its configuration, please contact your installer for more information.
Caution:
- Do not press the button of wired controller for 5s after power on.
If you have any questions regarding the display and its configuration, please contact your installer for more information
Interface introduction
Button Overview
Definition | Description |
---|
- Mode button
- Electric heater button
- Up button
- Down button
- Setting button
- Confirm button
- ON/OFF button
- Query button
| Used to change the running mode
Used to manually switch on/off the DHW EHs
Used to change the value of the parameter or turn the page during system
configuration or commissioning
Used to change the value of the parameter or turn the page during system
configuration or commissioning
Used to set user / technical parameter configuration
Used to confirm the current setting
Used to turn on/off the unit
Used to query the operation parameter or configuration parameter
Overview of Icons
| Non-operating cooling mode|
| Non-operating heating mode| **| Non-operating DHW mode
| Operating cooling mode|
**| Operating heating mode| | Operating DHW mode
| Anti-frozen protection|
| Main water loop EHs| | DHW EHs
| External heat source (boiler)| | Weekly timer| |
Clock
| Timer on| | ** Timer off|
| ** Alarm
| ** Air purge mode|
| OTA (water setpoint control)| **| IAT (air setpoint control)
LED display (Left)| LWT/time display (hour)/alarm|
**** LED display (Middle)| ** DHW temp./time display (minute)|
LED display (Right)| ** IAT/OAT(OAT is reserved)
| Days of week| | Constant light: Eco
modeFlash: Away mode| |
Button introduction
This wired controller has 8 buttons for the setpoint control, configuration, parameter check, etc. Details of each button are given in the table below:
ON/OFF | 1. Press this button to turn the unit on and off. |
---|
Confirm| 1. Press this button to confirm the setting to exit the interface of
parameter setting or query.
Mode| 1. Press this button to change the mode: cooling-heating-cooling.2.
Press and hold this button to activate the anti-legionella mode manually.
Query| 1. Press this button to check the configuration and running
parameters.2. Refer to section 3, parameter and status check, for details.
EHs| 1. While operating in heating mode, press this button to
activate/deactivate the main water loop EHs manually.2. While operating in
DHW mode, press this button to activate/deactivate the DHW EHs manually.3.
Press and hold this button to start force-defrosting, and the wired controller
will display “dF” for 5s.
Up| | 1. Temperature setting①
While in standby mode, for the first time, press this button to change the
settingvalue of LWT; press the confirm button or wait for 5s without pressing
any button for DHWtemperature setting.② While operating in cooling/heating
mode, for the first time, press this button to change the setting value of
LWT; press the confirm button or wait for 5s without pressing any button for
DHW temperature setting.③ While operating DHW mode, for first time, press this
button to change the setting temperature of DHW; press the confirm button or
wait for 5s without pressing any button for setting the value of LWT.2. Time
correction and timer setting① Refer to details for configuration.
Down|
Setting| 1. User parameter configuration: please refer to the configuration section.2. Technical parameter configuration: please refer to the configuration section.
User operation
Clock setting
Before usage, it is necessary to set the time and date of the wired controller. Please follow the steps below to set the clock accurately:
-
Press the “setting” button, then press “confirm” button to enter day settings; the date will flash at this moment.
-
Next, press the “up” or “down” button to change the date, if necessar
-
. After setting the date, press the “confirm” button to enter time settings. The hour will flash at this moment
-
Next, press the “up” or “down” button to set the correct time in hours;
-
After setting the hour, press the “confirm” button to enter the “minutes” setting; the minutes will flash at this moment.
-
Next, press the “up” or “down” button to set the correct time in minutes;
-
Press the “confirm” button to confirm and exit clock settings. You can also press the “settings” button to go to the next parameter. (Refer to the user parameter configuration for the full details on parameters setting)
Example: Friday, 3:05:31
ON-OFF setting
Mode setting
1. Press this button to chang
Mode setting
- Press this button to change the mode: cooling-heating-cooling.
Example
Mode | Cooling | Mode | Heating |
---|---|---|---|
Occupancy | Home | Occupancy | Home |
Temp. control | Water setpoint control | Temp. control | Water setpoint control |
Setpoint of LWT | 170C | Setpoint of LWT | 180C |
Setpoint of DHW | 250C | 250C |
Current setpoint setting
Here are two setpoint controls: (Refer to the technical parameter configuration, item 1 for detailed settings)
- Water setpoint control; the unit is controlled by water setpoint;
- Air setpoint control: the unit is controlled by the air setpoint, and it requests to install the wired controller in the room.
There is an IAT sensor built inside the wired controller to detect the room temperature. Here are the steps to change the water setpoint control:
-
While in standby mode or operating cooling/heating mode: First press “up” or “down” button to change the setting of LWT;
Then press the confirm button or wait for 5s without pressing any button to DHW temperature setting. Next, press the “up” or “down” button to change the setting of DHW.
-
While operating in DHW mode:
First press the “up” or “down” button to change the temperature of DHW;
Press the confirm button or wait for 5s without pressing any button to enter
the setting value of LWT. Next, press the “up” or “down” button to change the
setting of LWT
Here are the steps to change the air setpoint control:
Here are the steps to change the air setpoint control:
-
While in standby mode or operating in cooling/heating mode:
First press the “up” or “down” button to change the air setpoint;
Next, press the confirm button or wait for 5s without pressing any button to change the DHW temperature setting. Next, press the “up” or “down” button to change the DHW.
-
While operating in DHW mode:
First press the “up” or “down” button to change the temperature of DHW ;
-
Press the confirm button or wait for 5s without pressing any button to enter the setting value of LWT. Next, press the “up” or “down” button to change the air setpoint.
Home/away/eco setting
To optimize the energy efficiency of the building, you can select the occupancy mode manually according to the following steps. Each occupancy mode is associated with a pre-defined temperature range.
-
Press the “setting” button to item 5: Select Occupancy mode
-
Press the “up” or “down” button to change the value. (0-Home; 1-Eco; 2-Away)
-
Next, press “confirm” to confirm and exit user setting or you can also press the “setting” button to go to the next item. (Refer to the user parameter configuration for the full parameter setting details)
Example: Eco mode
This icon lights up on selecting eco mode.
DHW schedule setting
This schedule is used to set the operating of DHW mode automatically according to the timed schedule. Please follow the steps below to set the DHW schedule
-
Press the “setting” button to item 1: DHW schedule setting.
-
Press and hold the “confirm” button; the icon “on” will flash, then press the “confirm” button to confirm, the icon “on” will light up constantly;
-
Press and hold the “down” button to enter the date settings, then press “up” or “down” to select the day, press “confirm” to confirm day settings, after that, the icon of that day will light up constantly;
-
Press and hold the “down” button to enter the hour settings, then press “up” or “down” to select the time in hours; press “confirm”.
-
Press and hold the “down” button to enter minute settings, then press “up” or “down” button to select the time in minutes and press “confirm”.
-
Press and hold the “down” button to set the timer off, then press the “down” button to enter hour settings. Press the “up” or “down” button to select the time in hours and press “confirm”.
-
Press and hold “down” button to enter minute settings, then press “up” or “down” to select the time in minutes and press “confirm”.
-
Press and hold “confirm” button to confirm and exit user settings. You can also press “settings” button to go to the next item.
Refer to the user parameter configuration for all parameter settings)
Example
The unit will operate the DHW mode at 22:00 from Monday to Friday and will exit the DHW mode automatically at 6:00 from Tuesday to Saturday.
Schedule of DHW mode
Day| Monday| Tuesday| Wednesday| Thursday| Friday| Saturday| Sunday
√| √| √| √| √| ×| ×
Time on| 22:00| 22:00| 22:00| 22:00| 22:00| 22:00| 22:00
Time off| 6:00| 6:00| 6:00| 6:00| 6:00| 6:00| 6:00
Button lock settings
Used to lock the button of wired controller in case of touching by mistake; double press the “settings” button to unlock.
-
Press the “setting” button to go to item 9: wired controller button lock.
-
Press the “up” or “down” button to set the value (0-unlock; 1-lock)
-
Next, press “confirm” button to confirm and exit user setting or you can also press “settings” button to go to next item. (Refer to the user parameter configuration for all parameter settings)
Configuration
This wired controller can be used to configure the system setting during installation and operation. Here follow two configuration sections: user parameters configuration and technical parameters configuration, please check the details in 3.1 & 3.2.
User parameter configuration
Press the “settings” button to enter the user parameters configuration interface and press this button to page down the setting items from 0-9 as circuit. Use the “up” or “down” button to change the value of each item.
Details of the user parameters configuration table are given below: (The No. in the table below will be displayed in the left LED tube except “0”)
No. | Item | Description |
---|---|---|
0 | Clock settings | ① |
②
③
④| Press the “settings” button and then press “confirm” to enter date settings
andthen press “up” or “down” button to change the date if necessary;Next,
press “confirm” to enter hour settings, press “up” or “down” to set the
correcttime in hours;Next, press “confirm” to enter minute settings and press
“up” or “down” button toset the correct time in minutes.Press “confirm” to
confirm and exit clock settings.You can also press “settings” button to go to
the next parameter.
1| Schedule of DHW| ①
②
③
④
⑤
⑥
⑦
| Press and hold the “confirm” button, the icon “on” will flash, then press
“confirm”,and the “on” icon will light up constantly;Press and hold the “down”
button to enter day settings, then press “up” or “down”button to select the
day, press “confirm”, and the icon will remain lit up;Press and hold the
“down” button to enter hour settings, then press “up” or “down”to select the
time in hours, press “confirm”.Press and hold the “down” button to enter
minute settings, then press “up” or“down” to select the time in minutes and
press “confirm”.Press and hold the “down” button to set the timer off, then
press the “down” button to enter hour settings, then press “up” or “down”
button to select the time in hours, and press “confirm”.Press and hold “down”
button to enter minute settings, then press “up” or “down”to select the time
in minutes, press the “confirm” button to confirm;Press and hold “confirm” to
confirm and exit user settings. You can also press the“settings” button to go
to the next item.
2| Power memory setting| This is used to record the settings if power is
shutdown, and the system will recover the previous status once power is back.①
Press “up” or “down” button to set the value; 0- With power memory
(default);1- Without power memory
3| WIFI Status| Reserved
4| Air purge mode| ①0-1-| Press the “up” or “down” button to set the value; Do
not start air purge modeStart air purge modeIf choosing 0, then press the
“settings” button to go to the next item;
| | If choosing 1, then press the “confirm” button to exit the settings and
unit will startthe air purge mode; during the air purge mode, wired controller
will be displayed “PA”, and only the “ON/OFF” button are valid to exit this
mode.
---|---|---
5| Occupancy mode setting| ① Press “up” or “down” button to set the value;②
Then press “confirm” button to confirm and exit user settings or you can
alsopress “settings” button to go to the next item.0- Home; 1- Eco; 2- Away
6| Night mode setting| This is used to set up night mode for low noise during
the night-time. Press “up” or “down” button to set the value:0- Without night
mode 1- With night modeIf choosing 0, press “confirm” and exit user settings
or you can also press “settings”button to go to the next item;If choosing 1,
then follow the steps below:① Press “confirm” button to set the start timer
setting, then press “up” or “down”button to set the time in hours;② Press
“confirm” to enter minute setting, then press “up” or “down” button to setthe
time in minutes;③ Press the “confirm” button to enter the stop timer setting,
then press “up” or“down” button to set the time in hours;④ Press “confirm”
button to enter minute settings, then press “up” or “down” buttonto set the
time in minutes;⑤ Next, press “confirm” to confirm and exit user settings or
you can also press the“settings” button to go to the next item.
7| Anti-legionella temperature setting| Press the “up” or “down” button to set
the value; Temperature range: 60-700C, default as 600C.
8| Anti-legionella timer starts| ① Press and hold “confirm” button to enter
day settings, press “down” button to set the day, then press the “confirm”
button to confirm, after which the icon of the day will remain lit up.② Press
and hold the “down” button to enter hour settings, then press “up” or
“down”button to select the time in hour, press the “confirm” button to
confirm.③ Press and hold the “down” button to enter minute settings, then
press “up” or“down” button to select the time in minutes and press “confirm”.④
Press and hold the “confirm” button to confirm and exit user settings or you
canalso press “settings” button to go to the next item.
9| Lock of wired controller| Used to lock the button of wired controller in
case children touch by mistake; double press the “settings” button to unlock.①
Press the “up” or “down” button to set the value;② Next, press the “confirm”
button to confirm and exit user settings or you can alsopress the “settings”
button to go to the next item.0- Without lock1- With lock
Technical parameter configuration
Press and hold the “setting” button to enter the technical parameter configuration interface and press the “setting” button to turn down the setting items from 0-25. You can use “up” or “down” button to change the value of each item.
Details of the user parameter configuration are given below:
No. | Item | Description |
---|---|---|
0 | Control setpoint type | 0- Water setpoint control 1- Air setpoint control |
1 | Controller selection | 0- Wired controller1- Dry contact |
2 | Back up function | 0- Main water loop EHs + DHW EHs + boiler 1- Main water |
loop EHs + DHW EHs2- DHW EHs + boiler3- Main water loop EHs + boiler 4-
DHW EHs only5- Boiler only6- Main water loop EHs only 7- Non back up
3| Climate curve selection| 0- Non climate curve 1- Climate curveAfter
setting 1 with climate curve, please follow the below steps:① After choosing
1, enter heating climate setting, press “up” or “down” to choose fromclimate
curves 1-13, if choosing between 1-12, press “confirm” and then go to step③;
if choosing 13, press “confirm” and then go to step ②;.② Customized heating
curve value input:a. Press “up” or “down” to set the value of MinOAT;b. Press
“confirm” button to set MaxOAT, press “up” or “down” to setthe value of
MaxOAT;.c. Press “confirm” to set MinWSP, press “up” or “down” to set thevalue
of MinWSP;d. Press “confirm” to set MaxWSP, press “up” or “down” to set
thevalue of MaxWSP;e. Press “confirm” to go to step ③.③ Press the “up” or
“down” button to set the heating climate offset from -5~50 C , default as
00 C ; then press “confirm” to go to step p ⑥④ Enter cooling climate
settings; press the “up” or “down” button to choose between climate curves
1-3, if choosing 1-2, press “confirm”, then go to step ⑥ ; if choosing 3,
press “confirm” to go to step ⑤.⑤ Customized heating curve value input:a.
Press “up” or “down” to set the value of Min OAT;. b. Press “confirm” to set
Max OAT, press “up” or “down” to set the value ofMax OAT;
|
| c. Press “confirm” to set Min WSP, press “up” or “down” to set the value
ofMin WSP;d. Press “confirm” \to set Max WSP, and press “up” or “down” to
set the value ofMax WSP;e. Press “confirm” to go to step ⑥.⑥ Press the “up”
or “down” button to set the heating climate offset from -5~50C, default as
00C; then press “confirm” to confirm and exit or “setting” button to go to the
next item.
---|---|---
4| Capacity test setting| Reserved
5| 3-way valve type select| 0- Normal open1- Normal closed
6| DI1| 0- Disable1- Power limitation (night mode) 2- Load-shed3- DHW
request4- Anti-legionella request5- HDW priority
7| DI2
8| DI3
9| DI4
10| DO1| 0- Disable1- Unit in alarm2- Unit in standby 3- Unit running4-
Unit in cooling 5- Unit in heating 6- Unit in DHW7- Unit in defrost8- Unit
controlled by Modbus
11| DO2
12| DO3
13| Eco mode cooling setpoint offset| If air setpoint is chosen, it is air
setpoint offset, otherwise, it is water setpoint offset 0~100 C , default
as 20 C
14| Away mode cooling setpoint offset| If air setpoint is chosen, it is air
setpoint offset, otherwise, it is water setpoint offset 0~100 C ,, default
as 40 C 15
15| Eco mode heating setpoint offset| If air setpoint is chosen, it is air
setpoint offset, otherwise it is water setpoint offset-20~00 C , default
as -20 C
16| Away mode heating setpoint offset| If air setpoint is chosen, it is air
setpoint offset, otherwise, it is water setpoint offset-20~00 C , default
as -40 C
17| Eco mode DHWsetpoint offset| -10~00 C , default as -50 C
18| Minimum OAT for heating| -26~100 C , default as -260 C
19| Booster OAT Threshold| -10~00 C , default as -50 C
20| Heat pumpwarmup time| 0~120min, default 60min
21| Booster Deltatemperature| 1~200 C , default 100 C
22| Second zone setting| 0 – No bi-zone function1- Bi-zone function for
heating mode only2- Bi zone function for both cooling and heating modes
No.| Item| Description
---|---|---
23| Water pump ΔT control setting| ΔT default as 50 C , can be adjusted
from 3.50 C ~80 C , with precision 0.50 C
24| Water pump controltype setting| 0- ΔT control 1-Force to on 2- Force to
off
25| Water pump speed setting| If the item 24 (last setting item) is set to 1 –
force to on, then you can set this item 25, in this case you can choose the
value from 0-99, which means the water pump speed is from 1%-100%0- 1%
speed1- 2% speed…99 – 100% speed
NOTE:
DI: Customized input, dry contact;
DO: Customized output, 230V contact;
All the settings will be changed only by resetting and never by repowering.
Parameter and status checking
Parameter and status checking
This wired controller can be used to check the system status and running
parameters. Press the “query” button to enter the parameter query interface,
and press “confirm” or don’t press any button for more than 10s to exit the
parameter query interface.
After going into query interface, press “up” or “down” to check the parameters or status as given in the table below:
No. | Definition | Description |
---|---|---|
1 | Setting temp.: Ts1 | Display Ts1 during standby/cool/heat mode |
2 | Setting temp.: Ts2 | Display Ts2 during DHW mode |
3 | Setting temp.: Ts3 | Display Ts3 when it chooses the air setpoint control |
4 | Capacity of unit | HP*10, example: 10 means that unit is at 1HP capacity |
5 | Target frequency | |
6 | Running frequency | |
7 | Water flow rate | m3/h, feedback from inverter water pump |
8 | Capacity output | =1.163 (water flow rate) [Tw_out – Tw_in] (kW) |
9 | T3 value | ODU coil temp. |
10 | T4 value | OAT |
11 | TP value | Discharged temp. |
12 | T7 value | Temp. of refrigerant for PCB cool |
13 | EVX opening degree | Actual value |
14 | ODU fan motor speed | |
15 | AC current | |
16 | AC voltage | |
17 | IPM temp. (T9) | Compressor module temp. |
0: no limitation; | ||
1: T3B temp. limitation (reserved); | ||
2: OAT limitation; | ||
4: Discharged temp. limitation; | ||
18 | Limitation reason of compressor frequency | 8: Voltage limitation16: |
Current limitation
| | 32: IPM temp’ limitation
| | 64: Night mode limitation
| | 128: LWT limitation
| | If multi limitation occurs, display value=sum of all limitation values
19| Limitation reason for compressor frequency| 0: no limitation;1: Limitation
of different values between EWT & LWT
20| Tw_in value| EWT
21| Tw_out value| LWT of BPHE
22| T1 value| LWT of unit (after the EHs inside the unit)
23| T6 value| IAT, the sensor built inside the wired controller
24| T5 value| DHW value
---|---|---
25| Tw-2 value| Second zone EWT value when this function is set (reserved)
26| T1B value| External heat source (boiler) LWT value
27| Capacity demand|
28| Inv. Pump speed|
29| Last alarm|
30| Penultimate alarm|
31| Antepenultimate alarm|
32| Current protection| P0-P3: check the details in the alarm table
33
|
Detail of P6 alarm in function board
| L-: no alarm;L0: IPM or IGBT over current; L1: lack of phaseL2: Compressor
losing speed fault; L3: DC voltage is too low to protect L4: Fan motor over
current protection L5: Fan motor lack of phase;L6: Fan motor zero speed fault
L7: PFC faultL8: DC voltage is too high to protect L9: Compressor zero speed
fault LA: PWM synchronization faultLb: MCE faultLc: Compressor over current
protection Ld: EEPROM data is wrongLE: Compressor fails to start; LF: fan
motor losing speed fault
34| SV2 statue of water loop| This is a 2-way valve which is used to cut off
the heating terminal waterloop once the unit is running cooling mode (OFF- 0;
ON- 1)
35| SV3 statue of water loop| DHW 3-way valve
36| Main water loop EHs statue| Standard equipment with one EH; the other two
are field supplies(OFF-0; ON-1)
37| DHW EHs| OFF-0; ON-1
38| External heat source statue| OFF-0; ON-1
39| P_m| External main water loop pump (OFF-0; ON-1)
40| P_p| Second zone water loop pump (OFF-0; ON-1)
41| P_o| First zone water loop pump (OFF-0; ON-1)
42| Anti-frozen heater statue| OFF-0; ON-1
43| Chassis heater statue| OFF-0; ON-1
44| Crank heater statue| OFF-0; ON-1
45| SV2 statue of refrigerant system| FCU water loop valve, to cut off water
supply to radiator/spaceheater coil in cool mode (OFF-0; ON-1)
Error code
This wired controller also functions as the detector to display the unit alarm as outlined in the following table: Example: E1
This icon will light up once the alarm sounds.
Alarm code | Description |
---|---|
E0 | Water flow switch fault |
E1 | Communication fault between IDU board and ODU board |
E2 | LWT of unit sensor (T1 sensor) fault |
E3 | Gas refrigerant temp sensor (T2 sensor) fault (reserved) |
E4 | Liquid refrigerant temp sensor (T2B sensor) fault (reserved) |
E5 | ODU (module part) alarm |
E6 | DHW sensor (T7 sensor) fault |
E7 | LWT sensor (T_in sensor) fault |
E8 | LWT of BPHE sensor (T_out sensor) fault |
E9 | Communication fault between wired controller and function board |
EA | Second zone LWT sensor (Tw_2 sensor) fault (Only valid after setting |
second zone function, reserved)
Eb| External heat source LWT sensor (T1B sensor) fault (Only valid after
setting the external heat source – boiler)
Ec| Water pump fault
Ed| Reserved
EE| Reserved
EF| Mode conflict (reserved)
P0| EEPROM fault
P1| Protection from huge different values between EWT and LWT
P2| Protection from lack of water
P3| Protection from abnormal different values between EWT and LWT
P6| Protection from standard electrical heater overheat
802058000056
CR-SA-XKQENG12-2
Manufacturer: Guangdong Carrier Heating, Ventilation & Air Conditioning Company Limited Address: N0.1, Helangsha, Shengli Village, Lishui Town, Nanhai District, Foshan, Guangdong Province, China Order No: 10192, 12.2019 – Supersedes order No: 10192, 01.2019. Manufacturer reserves the right to change any product specifications without notice