SUNFIRE SF-150 Radiant Heater User Manual
- June 8, 2024
- Sunfire
Table of Contents
SF-150 Radiant Heater
User Manual
SF-150 Radiant Heater
Symptom | Possible Cause | Corrective Action |
---|---|---|
1.Will not start. | Main electrical power circuit breaker tripped | Reset |
breaker
Optional thermostat turned down or improperly installed/defective| Turn
thermostat up, check for loose wires and test components and replace if
needed.
Primary control safety tripped/defective| Reset/test components, replace if
needed
Too much light showing on CAD cell/defective| Eliminate light to CAD cell/test
component
Tip switch contacts are closed| If plugged in, verify amber light is on. If
not, it is a tip switch issue. Make sure SunFire unit is level. If level, tip
switch may be defective and need replacement.
2.Attempts to fire but does not establish a flame| Low fuel| Add fuel to tank
Contaminated fuel| Drain fuel by removing plug on bottom of fuel tank, clean,
retighten plug, and fill with clean fuel.
Clogged nozzle/Dirty fuel filter| Repalce nozzle/fuel filter
Air bubble in fuel line| Can sometimes be cleared by starting 3-4 times. Or
fix using the following process. Step 1: Open burner control housing. Step 2:
Loosen nut that holds copper fuel line to the ignitor box See Fig. 7-1. Step
3: Hold a rag around loosened nut to catch fuel. Step 4: Turn unit “on”. At 15
seconds the solenoid will open from the pump and fuel will pour out. Catch
fuel in rage and immediately turn unit off. Step 5: Re-tighten copper fuel
line and re-test heater. Also Inspect fuel filter assembly and hose
connections for air gaps if not tight or stripped or for possible cracks in
the hose.
Symptom| Possible Cause| Corrective Action
---|---|---
2.Attempts to fire but does not establish a flame – cont’d| Electrodes not
sparking| Through front heat dome, look for sparking when turning unit on.
Clean or replace electrodes.
Clogged nozzle
or defective fuel pump.| Replace nozzle by removing burner from cone assembly.
Or replace defective fuel pump.
3.Fires and then fails Only if fails contintually within| CAD cell is dirty|
Clean CAD cell with cloth. If issue still pursists see below.
30 seconds
CAD Cell is misaligned| Test CAD cell by slightly adjusting position a few
times. If issue pursists, see below.
CAD cell is defective| Test by using a jump wire from terminal Fl to terminal
F2 on the primary control with the following process. Step 1: Hook jumper to
Fl. Step 2: Start unit and wait until flame is present. Step 3: Then
immediately hook jump wire to F2. If unit continues to run after 1 minute, CAD
cell is defective and needs to be repalced. WARNING: THIS IS FOR TESTING
PURPOSES ONLY. FOR SAFETY, DO NOT CONTINTUE TO OPERATE USING JUMP WIRES.
Burner settings may need adjustment.| Test burner. Remove burner housing panel
to access the burner. Start the SunFire and view the LED lights to the right
of the burner primary control. If green light continues to blink, an
adjustment may be needed. Adjust the top fuel pressure screw along with very
slight adjustements to the air band until a correct adjustment is achieved and
the green light stays solid green.
Symptom| Possible Cause| Corrective Action
---|---|---
4.Fires and then fails Only if fails after at least 30| Contaminated fuel
supply| Drain tank from side plug, clean, and fill with clean fuel.
seconds with a flame
Dirty fuel filter| Clean and replace filter
Improper air flow causing a poor flame. The CAD cell may shut unit off with a
poor flame.| Adjust air band setting to 1.50 and test flame. See air band
adjustement on Figure 3-1.
Plugged nozzle or pre-heater assembly| Clean or replace nozzle
Improper power supply| If using agenerator, run for 20 minutes and retry. Try
a clean or different power supply.
Slight haze or dust build up on CAD cell.| Wipe off CAD cell eye with a rag
and restart. you may need to click reset button.
5.Black smoke or whisking Whisking – flames protrude| Nozzle is dirty or
clogged| Replace nozzle
Improper Air flow| Adjust air band to 1.5 position
through holes in dome face
Improper fuel flow rate| Adjust fuel flow rate
Only after replacing nozzle
6.Runs briefly on a generator and shuts off| Generator is low on charge| Run
generator for 20 minutes, then plug in SunFire unit and restart.
7.Amber lamp does not light| Loose wires| Check all power and tip-switch wires
for cut or loose wires and secure or fix if needed.
Tip switch is closed| Level SunFire or replace tip switch.
Bad Light| Replace light
Defective primary control circuit board| Replace primary control
8.Won’t fire If using a thermostat| Check temperature setting.| Set thermostat
to a higher temperature if desired.
Check for loose wires| Tighten wires for improved connection to thermostat.
Defective thermostat| Replace thermostat.
Note: Thermostat must not
require an external 24V power
source – if used it will damage
the primary.
Symptom| Possible Cause| Corrective Action
---|---|---
9.No green light calling for heat when unit is turned on| Check the reset
button| Push and hold the reset button
If using thermostat| See #8 above
Defective Primary| Replace primary
10.Bad flame| Clogged Nozzle| Soak Nozzle in parts cleaner/degreaser and blow
it out. Or replace nozzle.
Dirty/poor fuel| drain fuel and add new clean fuel.
Clogged/dirty filter| Replace filter
11.Smoky flame| Open transformer lid| Make sure lid is closed
Diesel treatment was used| Add clean fuel to decrease treatment ratio, or
drain all fuel and replace with new fuel and clean diesel treatment.
Air flow is restricted| Check air band and increase the air flow until smoke
is no longer visible.
Improper seal between fuel fliter and filter assembly.| Check the seal on the
fuel filter to make sure there are no obstructions between the filter and the
filter assembly that could allow air to become mixed in the fuel, causing an
improper fuel mixture.
Bad fuel| Drain fuel from tank and add new clean fuel.
12.No flame| No fuel| Add fuel
fuel is not spraying| There are multiple possibilities. Call your distributor
or the manufcturer at 855-251-1649 for
instructions.
Vaccum leak| Check hoses for leaks and tighten or replace.
Other issues| We are here to assist you.| Call us at
855-251-1649
HELPFUL SERVICE MANUAL IMAGES
FIGURE 1-1 Burner Housing/Control Box
FIGURE 1-2 Burner Pressure Valves
Note: Turn right for more fuel flow and left for less fuel.
FIGURE 1-3 Igniter Assembly
Note: Loosen screws and turn clamps to open igniter assembly.
FIGURE 2-1 CAD Cell
FIGURE 2-2 Inside igniter box
Note: If there is excessive dust while running the SunFire, the inside
area of the igniter box should be inspected and cleaned periodically.
Dust can build and causing the unit to turn of prematurely from dust build up
on the CAD cell, which will shut the unit off for safety as the flame will not
be visible and the electrodes may not receive a proper spark If igniters are
dirty. If dirty, simply clean with cloth.
FIGURE 3-1 Air Band
Note: The Air band should be set to approximately 1.25 – 1.5. Reducing
the air band to a lower level will reduce the amount of airflow to the flame
giving a higher concentration level of fuel that will raise the temperature
of the SunFire. However, if reduced too low, it can cause whisking – see
Figures 4-1&2 for examples. Reducing too low can become dangerous. This can
easily be solved by increasing the amount of air within the flame by
increasing the level of the air band.
If the air band level is set too low, upon start up, you may notice some smoke
and a more noticeable smell of diesel.
FIGURE 4-1 Primary Control
Note: Will blink for a second before the green flame sense light turns no. This simply let’s you know the unit has been turned on and will be calling for heat to produce a flame.
FIGURE 4-2 Primary Control
Note: A green light that blinks indicates potential issues with the flame not running efficiently. Check symptoms and causes on previous pages. If green light remains solid, the flame is running correctly. If flame gets just a little worse, it will shut the heater off. It will auto-restart one more time and if it happens again,it will go into lockout and you will need to hit the reset button to restart.
FIGURE 4-3 Primary Control
Note: If red “locked out” light is on, the control has failed to sense a flame after two attempts to fire and the reset button must be pressed before attempting to start again. When unit is turned on and does not fire on first attempts, this light will blink for 45 seconds. A 2nd attempt will be made and if no flame is sensed, the light will turn solid until the reset button is pushed.
FIGURE 5-1 Minor Whisking
Note: It is recommended to increase the air band setting to approximately 1.50 and reduce the fuel flow on the high pressure valve if necessary.
FIGURE 5-2 Severe Whisking
Warning: This is can be dangerous at these levels. It is recommended to immediately increase the air band setting to approximately 1.50 and reduce the fuel flow on the high pressure valve.
FIGURE: 6-1 View Inside Cone of Nozzle/Flame Assembly
Note: It is important that the nozzle and electrodes remain free from excessive build-up. Clean if necessary or replace nozzle. It is critical to never run the unit without the burner cone in place to produce a proper flame.
FIGURE: 7-1 Copper fuel line in Burner Assembly
ITEM NO. | PART NUMBER | DESCRIPTION | QTY. |
---|---|---|---|
1 | 29462 | SUNFIRE DOME ASSEMBLY | 1 |
2 | 34099 | NUT 5/16-18 SERR FLANGE | 4 |
3 | 29468 | SUNFIRE RIGHT LOWER STRAP | 1 |
4 | 34502 | SCREW 3/8-16X1″ HEX | 9 |
5 | 34009 | NUT 3/8-16 FLANGE | 4 |
6 | 29463 | SF-150 BURNER | 1 |
7 | 34505 | 5/8 PUSH ON WHEEL RETAINER | 2 |
8 | 29518 | WHEEL 10X2.75 HUB2.25 | 2 |
9 | 29467 | SUNFIRE TANK ASSEMBLY | 1 |
10 | 7202 | NUT 3/8-16 HEX | 4 |
11 | 29465 | SUNFIRE LIFTING HANDLE ASSEMBL | 2 |
12 | 34514 | SCREW 3/8-16 X 1-1/2 HH ZN | 4 |
13 | 29492 | HINGE HANDLE | 1 |
14 | 34516 | BUMPER SELF ADHESIVE SF-150 | 2 |
15 | 29469 | SUNFIRE LEFT LOWER STRAP | 1 |
16 | 34515 | PIN QUICK RELEASE 6MM DIA 40M | 2 |
ITEM NO.| PART NUMBER| DESCRIPTION| BOTTOM
HALF/QTY.
---|---|---|---
1| 29506| CAP GAUGE COMBO RAD HEAT 8″| 1
2| 29411| FING.J1C.ST.H.90ELO6MJ-06MJ| 1
3| 29402| HEATER BAND FOR FUEL FILTER| 1
4| 29407| FING.J1C.ST.H.90ELO6M1-08MP| 2
5| 34447| 1/4-20 x 3/8′| 2
6| 29401| FUEL FILTER ASSEMBLY| 1
7| 29511| SUCTION LINE HOSE e| 1
8| 29484| RAD HEAT TUBE DRAW ASSEMBLY| 1
9| 29467| SUNFIRE TANK ASSEMBLY| 1
10| 37500| FUEL FILTER REPLACEMENT| 1
ITEM NO. | PART NUMBER | DESCRIPTION | QTY. |
---|---|---|---|
1 | 13154 | NOZZLE W/CHECK VALVE | 1 |
2 | 26669 | RADIANT HEATER BURNER CONE | 1 |
3 | 29418 | SPINNER RAD HTR VERSION 2 | 1 |
4 | 29459 | FLANGE GASKET RAD HTR | 1 |
5 | 81010390 | ELECTRIC IGNITER | 1 |
6 | 33404 | SF-ISO PRIMARY | 1 |
7 | 29544 | SUNFIRE BURNER BLOWER WHEEL | 1 |
8 | 9502 | MOTOR 1/6HP | 1 |
9 | 29505 | ELECTRODES | 2 |
10 | 29450 | SWITCH TIP RAD HEATER | 1 |
11 | 29437 | CORD POWER RAD HTR | 1 |
12 | 33168 | LED AMBER LIGHT | 1 |
13 | 35408 | PLUG RUBBER RESET RADIANT HEAT | 1 |
14 | 33169 | LED GREEN LIGHT | 1 |
15 | 29449 | SWITCH ON/OFF HI/LOW RAD HTR | 2 |
16 | 29513 | FILTER TO BURNER HOSE 10.5′ | 1 |
17 | 29512 | RETURN FROM BURNER TO TANK | |
13.5′ | I | ||
18 | 29460 | PUMP HEAD RADIANT HEATER | 1 |
19 | 29523 | COUPLER BURNER RAIDANT | |
HEATER | I | ||
20 | 8981 | CAD CELL | 1 |
ITEM NO. | PART NUMBER | DESCRIPTION | QTY. |
---|---|---|---|
1 | 34457 | SCREW 3/8-16 X 1-1/2 HH | 8 |
2 | 34400 | 3/8 FLAT WASHER – SS | 8 |
3 | 29472 | FLAME GUARD | 1 |
4 | 29487 | ROLLED SHROUD ASSEMBLY | 1 |
5 | 29471 | DOME PUNCHED FACE | 1 |
6 | 29542 | RADIANT HEATER TOP GASKET | 1 |
7 | 29508 | SUNFIRE DOME INSULATION | 1 |
8 | 29499 | INSULATION DOME GASKET | 1 |
9 | 29507 | SUNFIRE SPUN DOME | |
WITH BRACKET SUPPORTS | 1 | ||
10 | 29495 | SF HEAT SHEILD | 1 |
11 | 34116 | 10 X 5/8 HEX WASHER HEAD TEK Z | 4 |
12 | 34399 | 3/8 SPLIT LOCK WASHER – SS | 8 |
13 | 34010 | 3/8-16 BRASS HEX NUT | 8 |
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>