BLAUBERG ISO-RB Industrial Fan User Manual

June 8, 2024
BLAUBERG

ISO-RB Industrial Fan

Centrifugal duct fan in sound insulated casing

USER’S MANUAL

This user’s manual is a main operating document intended for technical, maintenance, and operating staff.

The manual contains information about purpose, technical details, operating principle, design, and installation of the ISO-RB unit and all its modifications.

Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.

SAFETY REQUIREMENTS

All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000 V are
allowed for installation. The present user’s manual should be carefully read before
beginning works.
Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorized modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing spirits, gasoline,
insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the document’s preparation.

The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.

This unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
The appliance is only to be used with the power supply unit provided with the appliance.
Connection to the mains must be made through a disconnecting device, which is integrated
into the fixed wiring system in accordance with the wiring rules for design of electrical units, and has a contact separation in all poles that allows for full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or
similarly qualified persons in order to avoid a safety hazard.
CAUTION: In order to avoid a safety hazard due to inadvertent resetting of the thermal cutout, this unit must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.
Ensure that the unit is switched off from the supply mains before removing the guard.

WARNING: If there are any unusual oscillating movements, immediately stop using the unit and contact the manufacturer, its service agent or suitably qualified persons.
The replacement of parts of the safety suspension system device shall be performed by the
manufacturer, its service agent or suitably qualified persons.
Fixing means for attachment to the ceiling such as hooks or other devices shall be fixed with a sufficient strength to withstand 4 times the weight of the appliance.
The mounting of the suspension system shall be performed by the manufacturer, its service
agent or suitably qualified persons.
The appliance is to be installed so that the blades are more than 2.3m above the floor.
Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.

THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE. DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.

PURPOSE

The unit is designed to ensure continuous mechanical air exchange in houses, offices, hotels, cafes, conference halls, and other utility and public spaces as well as to recover the heat energy contained in the air extracted from the premises to warm up the filtered stream of intake air.

The unit is not intended for organizing ventilation in swimming pools, saunas, greenhouses, summer gardens, and other spaces with high humidity.

Due to the ability to save heating energy by means of energy recovery, the unit is an important element of energy-efficient premises.
The unit is a component part and is not designed for stand-alone operation. It is rated for continuous operation.

Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favorable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).

THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE TRAINING.
THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING.
THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORISED ACCESS BY UNATTENDED CHILDREN.

DELIVERY SET

NAME NUMBER
Fan 1 pc.
User’s manual 1 pc.
Packing box 1 pc.

DESIGNATION KEY

TECHNICAL DATA

The unit is rated as a Class I electrical appliance.

|

0

0

1

B

R

O

S

I

|

5

2

1

B

R

O

S

I

|

x

a

m

5

2

1

B

R

O

S

I

|

0

5

1

B

R

O

S

I

|

0

6

1

B

R

O

S

I

|

0

0

2

B

R

O

S

I

|

0

5

2

B

R

O

S

I

|

x

a

m

5

1

3

B

R

O

S

I

|

5

5

3

B

R

O

S

I

|

0

0

4

B

R

O

S

I

|

L

0

5

4

B

R

O

S

I

|

)

(

0

0

5

B

R

O

S

I

|

)

(

0

0

5

B

R

O

S

I

---|---|---|---|---|---|---|---|---|---|---|---|---|---

Unit voltage [V/50 (60) Hz]

|

1~ 230

|

1~ 230

|

1~ 230

|

1~ 230

|

1~ 230

|

1~ 230

|

1~ 230

|

3~ 400

|

1~ 230

|

1~ 230

|

1~ 230

|

3~230

|

3~400

Power [W]

|

58

|

61

|

88

|

84

|

86

|

164

|

320

|

654

|

202

|

349

|

473

|

730

|

780

Current [A]

|

0.25

|

0.28

|

0.37

|

0.37

|

0.38

|

0.71

|

1.40

|

1.10

|

0.89

|

2.00

|

2.35

|

2.82

|

1.60

Maximum air flow [m³/h]

|

285

|

330

|

484

|

485

|

500

|

770

|

1515

|

2710

|

2235

|

2860

|

2760

|

7000

|

6720

RPM [min-¹]

|

2530

|

2560

|

2670

|

2620

|

2670

|

2580

|

2615

|

2600

|

1330

|

1380

|

1350

|

980

|

948

Sound pressure level at 3 m distance [dBA]

|

34

|

35

|

40

|

38

|

38

|

42

|

45

|

48

|

48

|

48

|

48

|

56

|

54

Transported air temperature [°C]

|

-25+55

|

-25+55

|

-25+55

|

-25+55

|

-25+55

|

-25+55

|

-25+55

|

-25+55

|

-25+55

|

-25+55

|

-25+55

|

-25+55

|

-25+55

Ingress protection rating

|

IPX4

|

IPX4

|

IPX4

|

IPX4

|

IPX4

|

IPX4

|

IPX4

|

IPX4

|

IPX4

|

IPX4

|

IPX4

|

IPX4

|

IPX4

SEC class

|

C

|

C

|

C

|

C

|

C

|

C

|

|

|

|

|

|

|

parts tools

Overall and connecting dimensions of the fan [mm]

|

D

|

H

|

L

|

A

|

A1

|

A2

|

B

|

B1

|

d

|

Weight [kg]

---|---|---|---|---|---|---|---|---|---|---

ISO-RB 100

|

99

|

258

|

517

|

414

|

458

|

507

|

420

|

228

|

14

|

13

ISO-RB 125

|

124

|

258

|

517

|

414

|

458

|

507

|

420

|

228

|

13

ISO-RB 125 max

|

124

|

280

|

630

|

525

|

568,5

|

617

|

533

|

333

|

19

ISO-RB 150

|

149

|

282

|

566

|

493

|

537

|

586

|

470

|

278

|

17

ISO-RB 160

|

159

|

282

|

566

|

493

|

537

|

586

|

470

|

278

|

17

ISO-RB 200

|

198

|

355

|

632

|

535

|

579

|

628

|

535

|

3575

|

22.6

ISO-RB 250

|

248

|

429

|

774

|

666

|

710

|

759

|

677

|

537

|

33

ISO-RB 315 max

|

313

|

460

|

857

|

666

|

719

|

747

|

760

|

560

|

9

|

48

ISO-RB 355

|

354

|

500

|

927

|

804

|

857

|

885

|

830

|

641

|

58

ISO-RB 400

|

399

|

578

|

1024

|

876

|

929

|

957

|

927

|

737

|

78.5

ISO-RB 450 L

|

449

|

607

|

1152

|

968

|

1021

|

1049

|

1049

|

858

|

84

ISO-RB 500 (∆)

ISO-RB 500 (∆)

|

499

|

744

|

1300

|

1182

|

1235

|

1263

|

1203

|

993

|

129

www.blaubergventilatoren.de

UNIT DESIGN AND OPERATING PRINCIPLE

The fan casing is made of aluzinc. For easy installation and operation, the top cover of the fan is secured with a special lock. The casing is heat- and sound-insulated with a 50 mm layer of non-flammable mineral wool. To ensure better noise absorption, the inner surface of the insulation is made of a perforated metal sheet. The round connecting spigots are rubber sealed.

The fan is equipped with an asynchronous motor with an external rotor and an impeller with backward curved blades. The motor with ball bearings with specially selected grease ensures low-noise, maintenance-free operation of the fan. The fan with a three-phase motor has an integrated overheating protection with an automatic restart.

Duct fans are intended for mounting to round air ducts. The fans are installed between the air ducts. In case the fan is mounted on flexible joints, attach the fan to a structural unit by means of supports, suspension links or brackets (purchased separately). The fan may
be installed in any position in consideration of the air flow direction (as indicated by the arrow on the fan casing).

electrical cable

INSTALLATION AND CONNECTION

WHILE INSTALLING THE UNIT ENSURE CONVENIENT ACCESS FOR SUBSEQUENT MAINTENANCE AND REPAIR.

THE UNIT MUST BE MOUNTED ON A PLANE SURFACE.
MOUNTING OF THE UNIT TO AN UNEVEN SURFACE CAN LEAD TO THE UNIT CASING DISTORTION AND OPERATION DISTURBANCE.

  • Before installing the fan, make sure the casing has no visible damages and check the integrity of power supply wires. The fan casing
    must not contain any foreign objects which can damage the impeller blades.

  • Make sure the impeller rotates freely without touching the flange and the casing.

  • Mount the fan in such a way that the arrow on the fan casing matches the air flow direction in the system.

  • The casing has mounting brackets to facilitate the fan installation.

  • The fan may be installed in any position in consideration of the air flow direction (as indicated by the arrow on the fan casing).

  • To attain the best performance of the fan and to minimize turbulence-induced air pressure losses while mounting, connect the straight air duct section to the fan spigots on both sides of the fan. The minimum straight air duct length is equal to 1 air duct
    diameter on the intake side and 3 air duct diameters on the exhaust side. No filters or any other similar devices are allowed to be installed in these sections.

Fan and remote terminal box installation sequence

  • Before installation, lay the wires and cables necessary to connect the fan to the mains.
  • Minimal distance from the fan casing to the wall is 300 mm.
  • Fasteners for fan mounting are not included in the delivery set and should be ordered separately. While choosing fasteners consider the material of the mounting surface as well as the weigh of the unit, refer to the «Technical data» section. Fasteners for unit mounting should be selected by the service technician.

1. Mark the holes for mounting the fan.

2. Drill the holes according to the markings.

3. Fix the fan to the mounting surface.

4. Connect the air ducts (purchased separately) to the fan spigots.

5. Mark the holes for mounting the terminal box.

6. Drill the holes according to the markings.

7. Fix the remote terminal box to the mounting surface.

8. Unscrew the terminal box cover.

9. Make the electrical connections in compliance with the wiring diagram. Reassemble
the terminal box in the reverse order.

CONNECTION TO POWER MAINS

POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN. THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.

  • The unit is rated for connection to 1~230 V/50(60) Hz, 3~230 V/50(60) Hz, 3~400 V/50(60) Hz power mains.
  • The unit must be connected to power mains using insulated electric conductors (cables, wires). The actual wire cross section selection must be based on the maximum load current, maximum conductor temperature depending on the wire type, insulation, length and installation method.
  • The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the electric circuit in case of overload or short-circuit. The circuit breaker installation place must provide quick access for emergency shutdown of the unit. The trip current of the automatic circuit breaker must exceed the maximum current consumption of the unit (refer to the technical data table). The recommended trip current of the circuit breaker is the next current in the standard trip current row following the maximum current of the connected unit. The automatic circuit breaker is not included in the delivery set.

Connection of the fan to power mains and to additional external control units is carried out in the remote control box. The same regulator device can be used for connecting several fans simultaneously provided that their combined capacity and working current remain within the nominal parameters of the regulator. External control units are purchased separately (shown in dotted lines in the diagram).

Wiring diagrams
The fan is connected to power mains by means of the power cord with a plug (XP) or in the remote terminal box (X1).
ISO-RB 100, ISO-RB 125, ISO-RB 125 max, ISO-RB 150, ISO-RB 160, ISO-RB 200, ISO-RB 250, ISO-RB 355

diagram

The fan is connected to power mains by means of the power cable only in a remote terminal box (X1)
ISO-RB 400, ISO-RB 450 L ISO-RB 500 (Δ) ISO-RB 315 max, ISO-RB 500 (Y)

iso

CONTROL

The fan moves the air at a constant speed without possibility of regulation.
Additional external control units (purchased separately) can be connected to the fan for speed control.

TECHNICAL MAINTENANCE

DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE
OPERATIONS! MAKE SURE THE UNIT IS DISCONNECTED FROM POWER MAINS BEFORE REMOVING THE PROTECTION

The technical maintenance includes periodic cleaning of the surfaces from accumulated dust and dirt. The impeller blades require thorough cleaning once in 6 months. Clean the blades with a soft brush or a vacuum cleaner. While cleaning the fan be careful not to
displace the impeller counter weights. Protect the electric motor against ingress of liquid.

protection

TROUBLESHOOTING

PROBLEM

|

POSSIBLE REASONS

|

TROUBLESHOOTING

---|---|---

The fan does not start.

|

No power supply.

|

Make sure that the unit is properly connected to the power  mains and make any corrections, if necessary.

Low air flow.

|

The ventilation system is soiled  or damaged.

|

Make sure the air ducts are clean and intact. Clean them if  necessary.

Noise, vibration.

|

The fan impeller is soiled.

|

Clean the impellers.

The screw connection is loose.

|

Tighten the fastening screws.

STORAGE AND TRANSPORTATION REGULATIONS

• Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 °C to + 40 °C and relative humidity up to 70 %.
• Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
• Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
• Follow the handling requirements applicable for the particular type of cargo.
• The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
• Avoid sharp blows, scratches, or rough handling during loading and unloading.
• Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least
3-4 hours.

MANUFACTURER’S WARRANTY

The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby
declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European
Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking
Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above.

The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.

The warranty repair does not include:
• routine technical maintenance
• unit installation/dismantling
• unit setup

To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment
paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty
service.

The manufacturer’s warranty does not apply to the following cases:
• User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
• Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
• User’s failure to ensure timely technical maintenance of the unit.
• External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
• Redesign or engineering changes to the unit.
• Replacement and use of any assemblies, parts and components not approved by the manufacturer.
• Unit misuse.
• Violation of the unit installation regulations by the user.
• Violation of the unit control regulations by the user.
• Unit connection to power mains with a voltage different from the one stated in the user’s manual.
• Unit breakdown due to voltage surges in power mains.
• Discretionary repair of the unit by the user.
• Unit repair by any persons without the manufacturer’s authorization.
• Expiration of the unit warranty period.
• Violation of the unit transportation regulations by the user.
• Violation of the unit storage regulations by the user.
• Wrongful actions against the unit committed by third parties.
• Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
• Missing seals if provided by the user’s manual.
• Failure to submit the user’s manual with the unit purchase date stamp.
• Missing payment paperwork certifying the unit purchase.

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT.

USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.

Unit Type

|

Centrifugal duct fan in sound insulated casing

---|---

Model

|

Serial Number

|

Manufacture Date

|

Quality Inspector’s

Stamp

|

SELLER INFORMATION

Seller

|

---|---

Address

|

Phone Number

|

E-mail

|

Purchase Date

|

This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are  acknowledged and accepted.

Customer’s Signature

|

INSTALLATION CERTIFICATE

The unit _____ is installed pursuant to the requirements stated  in the present user’s manual.


Company name

|

Address

|

Phone Number

|

Installation

Technician’s Full Name

|

Installation Date:

|

Signature:

The unit has been installed in accordance with the provisions of all the applicable local and national construction,  electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.

Signature:

|

WARRANTY CARD

Unit Type

|

Centrifugal duct fan in sound insulated casing

---|---

Model

|

Serial Number

|

Manufacture Date

|

Purchase Date

|

Warranty Period

|

Seller

|

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals