BLAUBERG VENTO Argo A50-1 Pro V.3 Single-Room Reversible Energy Recovery Ventilator User Manual
- June 8, 2024
- BLAUBERG
Table of Contents
- INTRODUCTION
- SAFETY REQUIREMENTS
- PURPOSE
- DELIVERY SET
- DESIGNATION KEY
- TECHNICAL DATA
- DESIGN AND OPERATING PRINCIPLE
- MOUNTING AND SET-UP
- CONNECTION TO POWER MAINS
- CONTROL
- REMOTE CONTROL
- TECHNICAL MAINTENANCE
- TROUBLESHOOTING
- STORAGE AND TRANSPORTATION REGULATIONS
- MANUFACTURER’S WARRANTY
- CERTIFICATE OF ACCEPTANCE
- SELLER INFORMATION
- INSTALLATION CERTIFICATE
- WARRANTY CARD
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
BLAUBERG VENTO Argo A50-1 Pro V.3 Single-Room Reversible Energy Recovery
Ventilator
INTRODUCTION
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the VENTO Ergo A50/85-1 Pro V.3 unit
and all its modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
SAFETY REQUIREMENTS
All user’s manual requirements as well as the provisions of all the applicable
local and national construction, electrical, and technical norms and standards
must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000
V are allowed for installation. The present user’s manual should be carefully
read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the
grille before starting installation. The casing internals must be free of any
foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing! Deformation of the
casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky
substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to incorporate
the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
Connection to the mains must be made through a disconnecting device, which is
integrated into the fixed wiring system in accordance with the wiring rules
for design of electrical units, and has a contact separation in all poles that
allows for full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent, or similarly qualified persons in order to avoid a safety
hazard.
Ensure that the unit is switched off from the supply mains before removing the
guard.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
PURPOSE
The ventilator is designed to ensure continuous mechanical air exchange in
flats, cottages, hotels, cafés and other domestic and public premises. The
ventilator is equipped with a regenerator that enables supply of fresh
filtered air heated by means of extract air heat energy recovery.
The ventilator is designed for installation on external walls.
The unit is rated for continuous operation.
DELIVERY SET
Name | Number |
---|---|
Indoor assembly unit of the ventilator | 1 pc. |
Telescopic air duct | 1 pc. |
Regenerator with filters, assembled | 1 pc. |
Outer ventilation hood | 1 pc. |
Remote control | 1 pc. |
Cardboard mounting plate | 1 pc. |
Sealing gasket | 1 pc. |
Mounting kit | 1 pc. |
Mounting wedges | 1 kit |
User’s manual | 1 pc. |
Mounting hood installation instruction | 1 pc. |
Packing box | 1 pc. |
DESIGNATION KEY
TECHNICAL DATA
The temperature in the room where the indoor unit of the ventilator is installed must be in the range from +1 ˚C to +40 ˚C with relative humidity up to 65% (no condensation buildup). If the conditions for using the ventilator are beyond the specified limits, turn off the ventilator. Provide fresh air supply through windows.
The temperature of the transported air should be in the range from -20 ˚C to
+40˚C.
The unit is rated as a class II electric appliance.
Ingress protection rating against access to hazardous parts and water ingress
is IP22.
The ventilator design is constantly being improved, thus some models may be
slightly different from those described in this manual.
The telescopic design of the air duct allows its length to be adjusted without mechanical cutting. The thickness of the wall, in which the ventilator can be installed, depending on the used outer hood, is shown in the table below:
Ventilator model | Allowable wall thickness [mm] |
---|---|
VENTO Ergo A50/85-1 Pro V.3 | 240 – 425 |
VENTO Ergo A50/85-1 S Pro V.3 | 120 – 300 |
The technical specifications of the particular model are indicated on the unit
casing.
The overall and connecting dimensions of the outer ventilation hood, the
outside protrusion length of the air duct A and the mounting sequence of the
hood are stated in its installation instruction.
The overall dimensions of the front panel are stated in the figure below.
DESIGN AND OPERATING PRINCIPLE
The ventilator consists of an indoor unit with a decorative front panel, a
telescopic air duct and an outer ventilation hood. Two filters, two air flow
rectifiers and a ceramic regenerator are installed in the inner duct of the
telescopic air duct. The air filters are designed to purify supply air and
prevent foreign object ingress into the heat exchanger and the fan.
The ceramic regenerator utilities extract air heat energy to warm up supply
air flow. The cord laid inside the regenerator is designed to pull the
regenerator from the air duct. The heat exchanger is heat insulated with a
special insulating material.
The outer ventilation hood is used to prevent direct ingress of water and
other objects to the ventilator.
VENTILATOR DESIGN
-
Ventilation unit
Generates air flow by means of the fan rotation. The ventilation unit is covered with a ventilation grille on the inner wall side to prevent ingress of foreign objects into the fan.
The ventilation unit is equipped with automatic shutters to prevent air backflow. The air shutters open during operation of the ventilator and close when the unit is turned of -
Inner air duct
Inner part of the telescopic air duct. -
Ceramic regenerator
Utilises extract air heat energy to warm up supply air flow. -
Outer air duct
Outer part of the telescopic air duct. -
Mounting plate
A mounting box for installing the ventilation unit on the wall and connecting the ventilator to power supply -
Air flow rectifier
Prevents air turbulences in the ventilator -
Filter
Cleans the air flowing through the ventilator of dust and foreign objects and prevents contamination of the regenerator.
The indoor unit is equipped with automatic shutters. During the ventilator
operation the automatic shutters are opened and let the air flow freely
through the ventilator. The automatic shutters are closed for 2 minutes at the
ventilator shut down.
The ventilator has four ventilation modes:
- Natural air supply. The automatic shutters are opened, the fan is idle.
- Air supply. The ventilator supplies fresh air to the premise.
- Ventilation. The ventilator operates in permanent supply or extract mode at a set speed depending on the CN7 jumper position.
- Regeneration. The ventilator operates in reversible mode with heat and humidity recovery.
In the Regeneration mode the ventilator operates in two cycles, 70 seconds
each.
Cycle I. Warm stale air is extracted from the room. As it flows through the
ceramic regenerator, it heats and moisturizes the regenerator, transferring up
to 90 % of heat energy. In 70 seconds as the ceramic regenerator gets warmed
the ventilator is switched to the supply mode.
Cycle II. Fresh intake air from outside flows through the ceramic regenerator, absorbs accumulated moisture and is heated up to the room temperature. In 70 seconds as the ceramic regenerator gets cooled down, the ventilator is switched to the exhaust mode and the cycle is renewed.
MOUNTING AND SET-UP
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
DO NOT BLOCK THE AIR DUCT OF THE INSTALLED VENTILATOR WITH DUST ACCUMULATING
MATERIALS, SUCH AS CURTAINS, CLOTH SHUTTERS, ETC.
AS IT PREVENTS AIR CIRCULATION IN THE ROOM.
-
Prepare a round core hole in the outer wall. The hole size is shown in the figure below.
While preparing core holes it is recommended to make preparations for layout of the power cable and other required cables. Use the supplied cardboard template to mark the relative position of the duct opening and cable exit points.
-
Insert the air duct in the wall. For ease of installation use the mounting wedges included in the delivery set. The air duct end must protrude for the distance A that enables installation of an outer ventilation hood. The distance A is stated in the installation instruction for the ventilation hood.
Insert the air duct into the wall as shown in the picture on the left.
Install the air duct with the minimum slope of 3 mm down towards the street.
On the outer wall side the air duct end must protrude to a distance that enables installation of the outer ventilation hood. Distance A is stated in the installation instruction for the ventilation hood.
The air duct length can be changed before and after its fixation in the wall. In the former case, calculate the required length before mounting and in the second case, be sure to have enough access to cut the air duct length after its installation. -
Remove the mounting plate to access the control board. It is necessary for connection of the ventilator to power supply and connection of other ventilators as stated in the “Connection to power mains” section.
To remove the mounting plate, unscrew the four self-tapping screws as shown in the figure below. Then disconnect the mounting plate from the unit with care and push it aside to enable access to the control board. While doing that avoid abrupt movements not to damage the connecting cables between the control board and the mounting plate. Disconnect the mounting plate from the ventilation unit by disconnecting the two connectors. Assemble the mounting plate unit in the reverse order. Install the cables with care.
-
Using the cardboard template supplied, mark the holes for attaching the ventilator as shown in the figure below. Drill the holes and insert the dowels. Install the mounting plate unit on the wall, while laying a sealing gasket under it, fix the unit with self-tapping screws from the mounting kit. Install the mounting plate back with the connectors in place and secure it with four screws.
-
Install the air flow rectifier, filter, ceramic regenerator, one more filter and one more air flow rectifier inside the telescopic air duct. Then install the ventilation unit on the mounting plate unit.
CONNECTION TO POWER MAINS
DISCONNECT THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
CONNECTION OF THE UNIT TO POWER MAINS IS ALLOWED BY A QUALIFIED ELECTRICIAN
WITH A WORK PERMIT FOR THE ELECTRIC UNITS UP TO 1000 V AFTER CAREFUL READING
OF THE PRESENT USER’S MANUAL.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S
LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
The ventilator is rated for connection to single-phase AC 1~100-230 V 50/60 Hz
power mains.
Connect the ventilator to power mains through the external automatic circuit
breaker with a magnetic trip integrated into the fixed wiring system.
The power cable is connected to the upper terminal block.
Ventilation mode setting
Air direction in the Ventilation mode is determined by position of the jumper
on the control board.
The circuit board of the controller is located inside the ventilation unit.
Connection of several ventilators in series
When the ventilators are connected in series, all the connected ventilators
are controlled with the first ventilator and a remote control. To connect the
ventilators in series, connect the control terminals with a cable as shown in
the diagram below. Connect the second ventilator with the third ventilator in
the same way, etc.
For connection, use a screened cable with a wire cross-section of at least
0.25 mm2 (not included in the delivery set).
When the ventilators are connected in series, power must be supplied
separately to each of them.
CONTROL
The ventilator is operated with a remote control or the buttons on the ventilator casing, see the figure below.
The operation buttons on the ventilator casing have limited functionality and
include activating the second and third speed and setting three of four
ventilation modes. The remote control has wider control capabilities. The
guaranteed minimum reach distance of the remote control is 3 m. The IR
receiver is located at the bottom of the fan assembly. Please consider the
location of the port while using the remote control.
In case of power failure, the ventilator reverts to the previous operation
mode after power supply resumption.
| Third speed
---|---
| The fan is off
The ventilator does not operate. The shutters are closed.
| Second speed
| Ventilation mode
The ventilator operates either in the exhaust or supply mode with no reference to the CN7 jumper position.
| Regeneration mode
In this mode, the ventilator switches from the supply mode to the exhaust mode every 70 seconds. Heat recovery is performed in this mode.
| Supply mode
All the connected in series ventilators operate in the supply mode with no reference to the CN7 jumper position.
REMOTE CONTROL
-
Turning the ventilator on/off
-
Speed selection
-
Passive air supply
The shutters are open, the fan does not run. -
Ventilation*
The ventilator operates either in the exhaust or supply mode at the selected speed depending on the CN7 jumper position. -
Humidity set point setting
-
Night mode
The ventilator switches to the first speed in the darkness. -
Air supply
The ventilator continually supplies fresh air to the room no matter of CN7 jumper position) -
Heat recovery
The ventilator switches between the supply and exhaust mode each 70 seconds with heat regeneration.
Heat recovery is performed in this mode.
*When connected in series, the ventilators operate depending on the position of the jumper for setting the Ventilation mode on the control board. Setting of the Ventilation mode is described on page 10.
REMOTE CONTROL OF THE VENTILATION UNIT
Set the speed switch to position and the operation mode switch to position to enable remote control of the ventilation unit.
-
Turning the ventilator on/off
ON/OFF -
Night mode
ON/OFF
If the Night mode is activated, the ventilator switches to the first speed in the dark time of the day when the light is turned off.
Activation of the night mode is confirmed by a long sound signal. Exiting the night mode is confirmed by a short sound signal. -
Speed changeover
First speed
Second speed
Third speed -
Operation mode
Natural air supply mode. The room is ventilated in the natural way, the fan is off
Air supply mode. Air is supplied to the room at a set speed. All the connected in series ventilators operate in supply mode with no reference to the CN7 jumper position
Ventilation mode. Air is extracted (factory setting) or supplied at a selected speed. All the ventilators connected in series operate depending on the position of the CN7 jumper
Regeneration mode. The ventilator operates 70 seconds in the supply mode and 70 seconds in the exhaust mode.
Heat recovery is also performed in this mode -
Humidity Control mode.
The humidity control may be activated in the Regeneration mode only by pressing one of the humidity control buttons.
In the Humidity Control mode the ventilator humidity sensor monitors the extract air humidity and controls the fan speed depending on difference between the set humidity point and actual indoor humidity. If indoor humidity is about the set range or has slight deviations, the ventilator operates at the second speed. If indoor humidity is above the set humidity point, the ventilator changes to the third speed. If indoor humidity is below the set humidity point, the ventilator changes to the first speed.
Humidity threshold – 45 %
Humidity threshold – 55 %
Humidity threshold – 65 %
HUMIDITY CONTROL FUNCTION MAY BE ACTIVATED WITH THE REMOTE CONTROL ONLY!
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
MAKE SURE THE UNIT IS DISCONNECTED FROM POWER MAINS BEFORE REMOVING THE
PROTECTION
Maintenance of the ventilator means regular cleaning of the ventilator surfaces of dust and cleaning and replacement of the filters.
Heat exchanger and filter maintenance (3-4 times per year).
- Remove the ventilation unit.
- Remove the air flow rectifier.
- Remove the filter upstream of the regenerator.
- Pull the regenerator cord to remove the regenerator from the air duct.
- Be careful while pulling the regenerator to avoid its damage.
- Remove the filter downstream of the regenerator.
Clean the filters as often as required, but at least 3 times a year.
- After completion of the period set for the motor hour meter (factory setting 90 days) the filter replacement indicator in the bottom of the mounting plate glows to indicate the need of the filter cleaning of replacement.
- Wash the filters, let those dry out and install the dry filters inside the air duct.
- Vacuum cleaning is allowed.
- The filter rated service life is 3 years.
- For new filters contact the Seller.
Some dust may accumulate on the regenerator block even in case of regular maintenance of the filters.
- Clean the heat exchanger regularly to ensure its high heat recovery efficiency.
- Vacuum clean the regenerator not less than once a year.
Fan inspection (once per year).
Take off the ventilation unit and clean the fan blades.
Remove dust using a soft brush, cloth or a vacuum cleaner.
Do not use water, abrasive detergents, solvents, sharp objects for cleaning.
The impeller blades must be cleaned once a year.
To reset the operating hours counter after installing filters and a regenerator in the ventilator, press and hold for 10 seconds. The red indicator, indicating that the filter is dirty, should go out.
Replacement of the remote control battery (if necessary).
Replace the battery of the remote control after prolonged use. No response of
the ventilator for pressing the remote control buttons indicates the need to
replace the battery.
The battery type is CR2025.
To replace the battery of the remote control, remove the battery holder with a
battery.
Replace the battery and install the holder with a new battery back to the
remote control.
TROUBLESHOOTING
POSSIBLE MALFUNCTIONS AND TROUBLESHOOTING
Problem | Possible reasons | Troubleshooting |
---|---|---|
When switching on the ventilator, the fan does not start. | No power supply. |
Make sure the power supply line is connected correctly, otherwise troubleshoot
a connection error.
The motor is jammed, the impeller blades are soiled.| Turn the ventilator off.
Troubleshoot the motor jam and impeller clogging. Clean the blades. Turn the
ventilator on.
Circuit breaker tripping during the ventilation unit start-up.| Overcurrent as
a result of short circuit in the electric line.| Turn the ventilator off.
Contact the Seller for further information.
Low air flow.
| Low set fan speed.| Set higher speed of the fan.
The filters, the fan or the regenerator are clogged.| Clean or replace the
filter. Clean the fan and the heat exchanger.
Noise, vibration.| The impeller is clogged.| Clean the impeller.
Loose screw connection of the unit casing or the outer ventilation hood.|
Tighten the screws of the ventilator or the outer ventilation hood.
STORAGE AND TRANSPORTATION REGULATIONS
-
• Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range
from +5 °C to + 40 °C and relative humidity up to 70 %. -
Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
-
Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
-
Follow the handling requirements applicable for the particular type of cargo.
-
The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
-
Avoid sharp blows, scratches, or rough handling during loading and unloading.
-
Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above. The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP.
CERTIFICATE OF ACCEPTANCE
Unit Type | Single-room reversible energy recovery ventilator |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Quality Inspector’s Stamp |
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
INSTALLATION CERTIFICATE
The unit __ is installed pursuant to the requirements stated in the present user’s manual.
Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards. The unit operates normally as intended by the manufacturer.
Signature:|
WARRANTY CARD
Unit Type | Single-room reversible energy recovery ventilator |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>