QUBINO Flush On/Off Thermostat 2 ZMNKID3 Manual
- June 8, 2024
- QUBINO
Table of Contents
- QUBINO
- Flush On/Off Thermostat 2
- SKU: ZMNKID3
- Quickstart
- Important safety information
- What is Z-Wave?
- Product Description
- Prepare for Installation / Reset
- Inclusion/Exclusion
- Quick trouble shooting
- Association – one device controls an other device
- Configuration Parameters
- Parameter 1: Parameter no. 1Input I1 switch type
- Parameter 110: Parameter no. 110Temperature Sensor Offset Settings
- Parameter 120: Parameter no. 120Temperature Sensor Reporting Threshold
- Parameter 2: Parameter no. 110Temperature Sensor Offset Settings
- Parameter 4: Parameter no. 4Input 1 contact type
- Parameter 40: Parameter no. 40Watt Power Consumption Reporting Threshold
- Parameter 42: Parameter no. 42Watt Power Consumption Reporting Time
- Parameter 43: Parameter no. 43Hysteresis Upper temperature offset
- Parameter 44: Parameter no. 44Hysteresis Lower temperature offset
- Parameter 45: Parameter no. 45Antifreeze
- Parameter 59: Parameter no. 59 – Thermostat mode
- Parameter 60: Parameter no. 60Too low temperature limit
- Parameter 61: Parameter no. 61Too high temperature limit
- Parameter 63: Parameter no. 63Output switch selection
- Parameter 78: Parameter no. 78Scale Selection
- Technical Data
- Supported Command Classes
- Controlled Command Classes
- Explanation of Z-Wave specific terms
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
QUBINO
Flush On/Off Thermostat 2
SKU: ZMNKID3
Quickstart
This is a
secure
HVAC-Thermostat
for
.
To run this device please connect it to your mains power supply.
Important safety information
Please read this manual carefully. Failure to follow the recommendations in
this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any
loss or damage resulting from failure to comply with the instructions in this
manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal
instructions.
Do not dispose of electronic equipment or batteries in a fire or near open heat sources.
What is Z-Wave?
Z-Wave is the international wireless protocol for communication in the Smart
Home. This
device is suited for use in the region mentioned in the Quickstart section.
Z-Wave ensures a reliable communication by reconfirming every message ( two-
way
communication) and every mains powered node can act as a repeater for other
nodes
( meshed network ) in case the receiver is not in direct wireless range of
the
transmitter.
This device and every other certified Z-Wave device can be used together
with any other
certified Z-Wave device regardless of brand and origin as long as both are
suited for the
same frequency range.
If a device supports secure communication it will communicate with other
devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to
maintain
backward compatibility.
For more information about Z-Wave technology, devices, white papers etc.
please refer
to www.z-wave.info.
Product Description
The Qubino On/Off Thermostat 2 is a wireless heating and hot water controller that also measures the power consumption. It’s ideal for wireless control of electric or water-based underfloor heating systems, electric water heaters, hot water pumps, and electric radiators. It allows:Scheduling the temperature of your home to your lifestyle. Automatically turn the smart heating system off after leaving the home in the morning and turn it back on remotely before returning.The temperature sensors can trigger the heating system to turn on occasionally and prevent the temperature to drop.On/Off Thermostat 2 can significantly reduce the energy needs and save moneywhile keeping the house at an optimal temperature. Heating every room separately offers a maximum level of well-being while making your home more energy-efficient. The Qubino Smart Thermostat 2 enables smart zoning, which means you can turn the heating off in isolated rooms and save energy without compromising your comfort.
Prepare for Installation / Reset
Please read the user manual before installing the product.
In order to include (add) a Z-Wave device to a network it must be in factory
default
state. Please make sure to reset the device into factory default. You can do
this by
performing an Exclusion operation as described below in the manual. Every
Z-Wave
controller is able to perform this operation however it is recommended to use
the primary
controller of the previous network to make sure the very device is excluded
properly
from this network.
Safety Warning for Mains Powered Devices
ATTENTION: only authorized technicians under consideration of the country-
specific
installation guidelines/norms may do works with mains power. Prior to the
assembly of
the product, the voltage network has to be switched off and ensured against
re-switching.
Inclusion/Exclusion
On factory default the device does not belong to any Z-Wave network. The
device needs
to be added to an existing wireless network to communicate with the
devices of this network.
This process is called Inclusion.
Devices can also be removed from a network. This process is called
Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network.
This
controller is turned into exclusion respective inclusion mode. Inclusion and
Exclusion is
then performed doing a special manual action right on the device.
Quick trouble shooting
Here are a few hints for network installation if things dont work as expected.
- Make sure a device is in factory reset state before including. In doubt exclude before include.
- If inclusion still fails, check if both devices use the same frequency.
- Remove all dead devices from associations. Otherwise you will see severe delays.
- Never use sleeping battery devices without a central controller.
- Dont poll FLIRS devices.
- Make sure to have enough mains powered device to benefit from the meshing
Association – one device controls an other device
Z-Wave devices control other Z-Wave devices. The relationship between one
device
controlling another device is called association. In order to control a
different
device, the controlling device needs to maintain a list of devices that will
receive
controlling commands. These lists are called association groups and they are
always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’
Command.
Association Groups:
Group NumberMaximum NodesDescription
1| 5| Supports the following commands: Device Reset Locally: triggered upon
request, Sensor multilevel report: triggered upon temperature change, Meter
report: triggered upon energy consumption change according to configuration
parameters 40, 42, Notification report: triggered upon current overload
detection, Thermostat mode: triggered upon thermostat mode change Thermostat
operating state: triggered upon thermostat operating state (Idle, Heating,
Cooling)
---|---|---
2| 5| Supports the following command: Basic set: triggered by change of output
Q
3| 5| Supports the following command: Basic set: triggered when actual
temperature reaches Too High or Too Low temperature limit; Heat mode: when
temperature reaches Too High Temperature Limit reports OFF (0x00), when
temperature reaches Too Low Temperature Limit reports ON (0xFF). Cool mode:
when temperature reaches Too High Temperature Limit reports ON (0xFF), when
temperature reaches Too Low Temperature Limit reports OFF (0x00). Thermostat
off mode reports OFF (0x00) on both limits reached.Hysteresis is 1C.
4| 5| Supports the following command: Sensor multilevel report: triggered by
change of temperature for threshold defined in configuration parameter 120
Configuration Parameters
Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock
further
enhanced features.
IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200âit may be needed to set a value of 200 minus 256 = minus
56.
In case of a two byte value the same logic applies: Values greater than 32768
may
needed to be given as negative values too.
Parameter 1: Parameter no. 1Input I1 switch type
With this parameter, you can select between push-button (momentary) and
on/off toggle switch types.Values (size is 1 byte dec): default value 1 0 –
push-button (momentary) 1 – on/off toggle switch
Size: 1 Byte, Default Value: 1
SettingDescription
0 – 1| With this parameter, you can select between push-button (momentary) and
on/off toggle switch types.
---|---
Parameter 110: Parameter no. 110Temperature Sensor Offset Settings
Set value is added to or subtracted from the actually measured value to
adjust the temperature report sent by an external sensor.NOTE1: If
configuration parameter 78 (Scale selection) is set to Celsius, then valid
interval is -150150 (-15.0 C15.0 C, resolution 0.1 C)NOTE2: If configuration
parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is
-270 – 270 (-27.0 F27.0 F, resolution 0.1 F)NOTE3: If configuration parameter
78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be
converted to Celsius degrees. Due to conversion algorithm please be advised
that configuration value could drift when converting values back and forth.
Size: 2 Byte, Default Value: 0
SettingDescription
-270 – 270 | Values (size is 2 byte dec):default value 0-270 – 270 NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -150150 (-15.0 C15.0 C, resolution 0.1 C) NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is -270 – 270 (-27.0 F27.0 F, resolution 0.1 F) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. |
---|
Parameter 120: Parameter no. 120Temperature Sensor Reporting Threshold
This configuration parameters sets reporting threshold between reported
temperature and actual temperature for reporting temperature at association
group 4.
Size: 2 Byte, Default Value: 5
SettingDescription
0 – 270| Values (size is 2 byte dec): Default value 5 = 0.5C 0Reporting
disabled 0270 NOTE1: If configuration parameter 78 (Scale selection) is set to
Celsius, then valid interval is0150 (0 C15.0 C, resolution 0.1 C) NOTE2: If
configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid
interval is 0 – 270 (0 F27.0 F, resolution 0.1 F) NOTE3: If configuration
parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit
values will be converted to Celsius degrees. Due to conversion algorithm
please be advised that configuration value could drift when converting values
back and forth.
---|---
Parameter 2: Parameter no. 110Temperature Sensor Offset Settings
Set value is added to or subtracted from the actually measured value to
adjust the temperature report sent by an external sensor.NOTE1: If
configuration parameter 78 (Scale selection) is set to Celsius, then valid
interval is -150150 (-15.0 C15.0 C, resolution 0.1 C)NOTE2: If configuration
parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is
-270 – 270 (-27.0 F27.0 F, resolution 0.1 F)NOTE3: If configuration parameter
78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be
converted to Celsius degrees. Due to conversion algorithm please be advised
that configuration value could drift when converting values back and forth.
Size: 2 Byte, Default Value: 0
SettingDescription
-270 – 270 | Values (size is 2 byte dec):default value 0-270 – 270 |
---|
Parameter 4: Parameter no. 4Input 1 contact type
This parameter determines how the switch or push-button is connected.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Values (size is 1 byte dec):default value 00 – NO (normally open) input
type1 – NC (normally close) input type
---|---
Parameter 40: Parameter no. 40Watt Power Consumption Reporting Threshold
for Q Load
Choose by how much power consumption needs to increase or decrease to be
reported. Values correspond to percentages so if 10 is set, for example, the
device will report any power consumption changes of 10% or more compared to
the last reading.
Size: 1 Byte, Default Value: 10
SettingDescription
1 – 100| Values (size is 1 byte dec):default value 100 – Power consumption
reporting disabled1 – 100 = 1% – 100% Power consumption reporting enabled. New
value is reported only when Wattage in real time changes by more than the
percentage value set in this parameter compared to the previous Wattage
reading, starting at 1% (the lowest value possible). NOTE: Power consumption
needs to increase or decrease by at least 1 Watt to be reported, REGARDLESS of
percentage set in this parameter.
---|---
Parameter 42: Parameter no. 42Watt Power Consumption Reporting Time
Threshold for Q
Set value refers to the time interval with which power consumption in Watts
is reported (3032767 seconds) starting from time of last Watts reported. If
for example 300 is entered, energy consumption reports will be sent to the
gateway (hub) every 300 seconds (or 5 minutes).EXAMPLE: If we set value to 30
seconds and the device reports Watts because of percent change of power
(parameter 40 – Watt Power Consumption Reporting Threshold) at time = 5
seconds, then the device will send next meter report at time = 35 seconds
(assuming the device has not sent report within interval 5 to 35 seconds).
Size: 2 Byte, Default Value: 600
SettingDescription
0 – 32767| Values (size is 2 byte dec): default value 600 (600 seconds = 10
minutes) 0 – Power consumption reporting disabled 30 – 32767 = 30 – 32767
seconds. Power consumption reporting enabled. Report is sent according to time
interval (value) set here.EXAMPLE: If we set value to 30 s and the device
reports Watts because of percent change of power (parameter 40 – Watt Power
Consumption Reporting Threshold) at time = 5 seconds, then the device will
send next meter report at time = 35 s (assuming the device has not sent report
within interval 5 to 35 seconds).
---|---
Parameter 43: Parameter no. 43Hysteresis Upper temperature offset
This parameter defines minimum temperature difference between real measured
temperature and set-point temperature to turn device on in heat mode or turn
device off in cool mode.
Size: 2 Byte, Default Value: 5
SettingDescription
0 – 450| Values (size is 2 byte dec): default value 5 (0.5 C) 0450 NOTE1: If
configuration parameter 78 (Scale selection) is set to Celsius, then valid
interval is 0250 (0.0 C25.0 C, resolution 0.1 C) NOTE2: If configuration
parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is
0450 (0.0 F45.0 F, resolution 0.1 F) NOTE3: If configuration parameter 78
(Scale selection) is set to Fahrenheit, note that Fahrenheit values will be
converted to Celsius degrees. Due to conversion algorithm please be advised
that configuration value could drift when converting values back and forth.
---|---
Parameter 44: Parameter no. 44Hysteresis Lower temperature offset
This parameter defines minimum temperature difference between real measured
temperature and set-point temperature to turn device off in heat mode or turn
device on in cool mode.NOTE1: If configuration parameter 78 (Scale selection)
is set to Celsius, then valid interval is 0250 (0.0 C25.0 C, resolution 0.1
C)NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit,
then valid interval is 0450 (0.0 F45.0 F, resolution 0.1 F)NOTE3: If
configuration parameter 78 (Scale selection) is set to Fahrenheit, note that
Fahrenheit values will be converted to Celsius degrees. Due to conversion
algorithm please be advised that configuration value could drift when
converting values back and forth.
Size: 2 Byte, Default Value: 5
SettingDescription
0 – 450| Values (size is 2 byte dec): default value 5 (0.5 C) 0 – 450 NOTE1:
If configuration parameter 78 (Scale selection) is set to Celsius, then valid
interval is 0250 (0.0 C25.0 C, resolution 0.1 C) NOTE2: If configuration
parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is
0450 (0.0 F45.0 F, resolution 0.1 F) NOTE3: If configuration parameter 78
(Scale selection) is set to Fahrenheit, note that Fahrenheit values will be
converted to Celsius degrees. Due to conversion algorithm please be advised
that configuration value could drift when converting values back and forth.
---|---
Parameter 45: Parameter no. 45Antifreeze
Set value determines at which temperature the device will be turned on even
(if the thermostat was manually set to off).
Size: 2 Byte, Default Value: 50
SettingDescription
-125 – 1000 | Values (size is 2 byte dec): default value 50 (5.0 C) -125545 1000 – Antifreeze functionality disabled NOTE1: Antifreeze is activated only in heating mode and it uses hysteresis of 0.5 C.NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -125125 (-12.5 C12.5 C, resolution 0.1 C) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 95545 (9.5 F54.5 F, resolution 0.1 F) NOTE4: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. |
---|
Parameter 59: Parameter no. 59 – Thermostat mode
This parameter determines how the device will operate if it will operate in
the heating mode or in the cooling mode. The range of the hysteresis will
remain the same, only operation will change from heating to cooling and vice
versaNOTE1: After parameter change, first exclude device (without setting
parameters to default value) and then re include the device!
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Values (size is 1 byte dec): default value 0 0 – Heat mode 1 – Cool
mode NOTE1: After parameter change, first exclude device (without setting
parameters to default value) and then re include the device!
---|---
Parameter 60: Parameter no. 60Too low temperature limit
This parameter determines the temperature at which the device sends a
command to the associated device – to turn ON device or to turn OFF
device.NOTE1: Too low temperature limit is used with Association Group
3.NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius,
then valid interval is -1501000 (-15.0 C100.0 C, resolution 0.1 C)NOTE3: If
configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid
interval is 502120 (5.0 F212.0 F, resolution 0.1 F)NOTE4: If configuration
parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit
values will be converted to Celsius degrees. Due to conversion algorithm
please be advised that configuration value could drift when converting values
back and forth.
Size: 2 Byte, Default Value: 50
SettingDescription
-150 – 2120 | Values (size is 2 byte dec): Default value 50 (Too low temperature limit is 5.0 C) -1502120 NOTE1: Too low temperature limit is used with Association Group 3. NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -1501000 (-15.0 C100.0 C, resolution 0.1 C) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 502120 (5.0 F212.0 F, resolution 0.1 F) NOTE4: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. |
---|
Parameter 61: Parameter no. 61Too high temperature limit
This parameter determines the temperature at which the device sends a
command to the associated device, to turn ON device or to turn OFF
device.NOTE1: Too high temperature limit is used with Association Group
3.NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius,
then valid interval is 11000 (0.1 C100.0 C, resolution 0.1 C)NOTE3: If
configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid
interval is 3222120 (32.2 F212.0 F, resolution 0.1 F)NOTE4: If configuration
parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit
values will be converted to Celsius degrees. Due to conversion algorithm
please be advised that configuration value could drift when converting values
back and forth.
Size: 2 Byte, Default Value: 700
SettingDescription
1 – 2120| Values (size is 2 byte dec): default value 700 (too high temperature
limit is 70.0 C) 12120 NOTE1: Too high temperature limit is used with
Association Group 3. NOTE2: If configuration parameter 78 (Scale selection) is
set to Celsius, then valid interval is 11000 (0.1 C100.0 C, resolution 0.1 C)
NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit,
then valid interval is 3222120 (32.2 F212.0 F, resolution 0.1 F) NOTE4: If
configuration parameter 78 (Scale selection) is set to Fahrenheit, note that
Fahrenheit values will be converted to Celsius degrees. Due to conversion
algorithm please be advised that configuration value could drift when
converting values back and forth.
---|---
Parameter 63: Parameter no. 63Output switch selection
Set value determines the type of the device connected to the on/off output.
The output type can be normally open (NO) or normally closed (NC).
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Values (size is 1 byte dec): default value 00 – When switch/device is
off the output is 0 V (NC). 1 – When switch/device is off the output is 240
Vac or 24 Vdc (NO).
---|---
Parameter 78: Parameter no. 78Scale Selection
This parameter determines in which measurement unit the device will report
temperature (Fahrenheit or Celsius) and determines the scale the configuration
parameters (43, 44, 44, 45, 60, 61, 110, 120) are interpreted as.NOTE1: This
scale has influence on Temperature reporting. The device is capable of
receiving a Set point in all supported scales.NOTE2: This configuration
parameter has impact on configuration parameters 43, 44, 44, 45, 60, 61, 110,
120. If scale is set to degrees Fahrenheit configuration values at parameters
43, 44, 44, 45, 60, 61, 110, 120 will be converted to degrees Celsius. Please
note that converted values could drift when converting values back and forth.
Size: 1 Byte, Default Value: 0
SettingDescription
0 – 1| Values (size is 1 byte dec):Default value 0 = degrees Celsius0 =
degrees Celsius1 = degrees Fahrenheit
---|---
Technical Data
Hardware Platform | ZM5202 |
---|---|
Device Type | Thermostat – HVAC |
Network Operation | Always On Slave |
Firmware Version | HW: 1 FW: 10.00:10.00 |
Z-Wave Version | 6.81.03 |
Certification ID | ZC10-20036879 |
Z-Wave Product Id | 0x0159.0x0005.0x0054 |
Thermostat Modes | CoolHeat |
Electric Load Type | Inductive (e.g. Motor) |
Switch Type | Toggle |
Thermostat HVAC Systems Supported | Cool OnlyHeat OnlySimple Relay |
Thermostat Power Source | Mains powered (120V/240V)Power Stealing (hard-wired |
24V)
Color| Light Blue
Security V2| S2_UNAUTHENTICATED ,S2_AUTHENTICATED
Frequency| XXfrequency
Maximum transmission power| XXantenna
Supported Command Classes
- Association Grp Info V3
- Association V2
- Basic V2
- Configuration
- Device Reset Locally
- Manufacturer Specific V2
- Meter V4
- Notification V8
- Powerlevel
- Security
- Security 2
- Sensor Multilevel V7
- Supervision
- Thermostat Mode V3
- Thermostat Operating State
- Thermostat Setpoint V3
- Transport Service V2
- Version V2
- Zwaveplus Info V2
Controlled Command Classes
- Basic V2
Explanation of Z-Wave specific terms
-
Controller — is a Z-Wave device with capabilities to manage the network.
Controllers are typically Gateways,Remote Controls or battery operated wall controllers. -
Slave — is a Z-Wave device without capabilities to manage the network.
Slaves can be sensors, actuators and even remote controls. -
Primary Controller — is the central organizer of the network. It must be
a controller. There can be only one primary controller in a Z-Wave network. -
Inclusion — is the process of adding new Z-Wave devices into a network.
-
Exclusion — is the process of removing Z-Wave devices from the network.
-
Association — is a control relationship between a controlling device and
a controlled device. -
Wakeup Notification — is a special wireless message issued by a Z-Wave
device to announces that is able to communicate. -
Node Information Frame — is a special wireless message issued by a
Z-Wave device to announce its capabilities and functions.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>