MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods Instruction Manual

June 8, 2024
Mitsubishi Electric

MANUFACTURED FOR:
MITSUBISHI ELECTRIC US, INC.
LAHN-1/ LAHN-3 Low Ambient Hoods
Instruction Manual

LAHN-1 Low Ambient Hoods

For use with: CITY MULTI® N-Generation Air Cooled Outdoor Units

TECHNICAL & SERVICE MANUAL
FOR INSTALLER
For safe and effective use of these items, please read this manual thoroughly before installing these components.

Control box component identification

MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods -

Operating sequence

Outdoor unit in cooling mode
The LAHN-1/LAHN-3 low ambient hood is designed to reduce the airflow through the outdoor units as the ambient temperature drops. This maintains the head pressure at a level that will allow the system to perform at full capacity down to -10°F outdoor temperature.

NOTE
For R2 Systems: *Full cooling capacity down to -10°F. **In cooling mode or cooling main, to guarantee full cooling capacity, the system must operate with a constant heat load in the zones requiring cooling when ambient temperatures fall below 5°F.

A thermistor mounted on the side of the unit senses the outdoor temperature. As the outdoor temperature drops, the resistance of the thermistor increases. The thermistor is connected to the specially designed circuit board and the resistance value from the thermistor is converted to a DC voltage output within the circuit board. This DC voltage output drives the damper actuator to a predetermined position based on the outdoor temperature. The inverter-driven fan motor will adjust the discharge pressure based on system capacity demand. The motor will speed up and force more air through the damper if there is a higher system capacity demand, or slow down if system capacity demand decreases.
Outdoor unit in heating mode
Heating mode requires the damper to be in a fully open position to allow full airflow and maximum heating capacity. Heating mode automatically deactivates the kit through an interlock relay. The coil for this relay is tied into the reversing valve connection on the outdoor unit. When the unit switches to heating mode, the reversing valve is energized. This in turn energizes the interlock relay. When the relay is energized, the normally closed contact opens. By opening this contact, the power to the transformer and control board is interrupted, this allows the damper to spring to the fully open position.
Outdoor unit in defrost mode
If the outdoor unit will be running in heating mode, a defrost period is inevitable. During defrost, the low ambient controls see this as the unit operating in cooling mode. If the outdoor temperature is below 40°F, the damper will close to a position equal to that required during the cooling cycle. Once the unit comes back out of defrosting and into heating mode, the damper will again spring wide open for full airflow.
Operation test
Outdoor unit must be in cooling mode.
All hoods and damper controls are tested at the factory before shipping. To perform an operational test once the installation is complete, follow the steps below. Please refer to the following chart and table for detailed control logic.

Operation testing when the outdoor ambient is ABOVE 40°F

  1. Turn on power to the outdoor unit.

  2. Make sure the outdoor unit is in cooling mode.

  3. Locate the outdoor temperature sensing thermistor at the end of the short conduit coming out the side of the control panel; it can be seen inside the plastic shield.

  4. Using an aerosol dusting sprayer, invert the can and spray the thermistor with very short bursts of the cold liquid.
    Caution: Do Not overspray the thermistor as it could be damaged. It may take 10 – 20 seconds for the internal thermistor temperature to drop.
    The damper will start to move toward the closed position after the thermistor drops below 35°F.

  5. Once the thermistor warms above 40°F, it will move back to the fully open position indicating the low ambient kit is working as designed.

Ambient temp [ °F ]| Hood angle [ 0 ]| Output voltage [VDC]| Resistance [0]
---|---|---|---
-10| 80| 9.| 117960
-5| 80| 9.| 100184
0| 70| 8.| 85340
5| 70| 8.| 72906
10| 70| 8.| 62460
15| 70| 8.| 53658
20| 60| 7.| 46220
25| 60| 7.| 39917
30| 60| 7.| 34562
35| 60| 7.| 30000
40| OPEN| 2| 26104
45| OPEN| 2| 22767

Operation testing when the outdoor ambient is BELOW 35°F

  1. Turn on power to the outdoor unit.
  2. Make sure the outdoor unit is in cooling mode.
  3. The damper will move toward the closed position to a predetermined position based on the outdoor ambient temperature, indicating the low ambient kit is working as designed.

LAHN Damper Hysteresis Control

MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods - Hysteresis
Control

If neither of these tests work, proceed with the component troubleshooting instructions.
Component troubleshooting Thermistor
The thermistor is a 10,000 Ω, NTC Type. The circuit board has a blinking indicator light built in to reference what the thermistor is sensing. The following chart shows what the blinking light sequence means.

MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods -
Temperature

If the light is on constantly, the thermistor is open or shorted and needs to be replaced. If the blinking light sequence doesn’t fall within the range given in the chart, the thermistor needs to be replaced. If it’s suspected that the thermistor is operating inaccurately, check the tolerance in the following instructions.
Disconnect the thermistor from the control board. Measure the resistance across the two leads. Measure the temperature of the thermistor. (Accuracy on the temperature reading is important to prevent a good thermistor from being replaced). Compare the ohm reading with the temperature on the chart below. Based on the thermistor temperature the ohm reading should be within 3% of the number shown below. If not, and the thermistor connections are not corroded, the thermistor should be replaced.

°F Ohms °F Ohms °F Ohms °F Ohms
86 8,056 59 15,714 32 32,650 5 72,906
84 8,448 57 16,551 30 34,562 3 77,620
82 8,682 55 17,438 28 36,601 1 82,676
81 9,077 54 17,902 27 37,671 0 85,340
79 9,526 52 18,873 26 38,776 -2 90,962
77 10,0000 50 19,903 23 42,315 -4 96,999
75 10,501 48 20,997 21 44,875 -6 103,486
73 11,301 46 22,159 19 47,610 -8 110,460
72 11,307 45 22,767 18 49,047 -9 114,141
70 11,884 43 24,040 16 52,069 -11 121,921
68 12,493 41 25,394 14 55,301 -13 130,295
66 13,139 39 26,835 12 58,759 -15 139,313
64 13,822 37 28,368 10 62,460 -17 149,030
63 14,179 36 29,171 9 64,408 -18 154,169
61 14,924 34 30,856 7 68,510 -20 165,048

Circuit board
Confirm the thermistor is operating properly before troubleshooting the circuit board. Make sure the control board has 24 Volts AC when measured at the 24 VAC and the com terminals. If not, find the cause of voltage failure. The circuit board is designed to convert the thermistor ohm input to a 2 – 9.16 VDC output to control the position of the damper actuator. Above 2 VDC output, the actuator will start to move the damper toward the closed position. At 9.16 VDC, the actuator will have moved 85 degrees and the damper will be approximately 95% closed. The damper should never be 100% closed. The chart below includes the various damper angles based on the different outdoor temperatures. Measure the DC voltage output on the circuit board at com (-) and the out (+) terminals. If the output doesn’t match the thermistor input ohms as shown below, replace the circuit board.

Ambient temp [ °F ] Hood angle [ ° ] Output voltage [VOC] Resistance [0]
-10 80 8.78 117960
-5 80 8.78 100184
0 70 7.9 85340
5 70 7.9 72906
10 70 7.9 62460
15 70 7.9 53658
20 60 7.04 46220
25 60 7.04 39917
30 60 7.04 34562
35 60 7.04 30000
40 OPEN 2 26104
45 OPEN 2 22767

Transformer
The transformer is 208/230 -24volt AC. For proper connections to the outdoor unit, refer to the following diagram and instructions.

MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods -
Transformer

208/230 volt and also 460-volt outdoor units. On 208 volt units, the CNAC2 connector will provide 208 volts to the control transformer. On 230 volt units, the CNAC2 connector will provide 230 volts to the control transformer. The 460-volt units include a transformer that reduces the outdoor unit internal voltage to 230 volts. Because of this, on the 460-volt units, the CNAC2 connector will also provide 230 volts to the control transformer. Once the proper connection is confirmed, measure the voltage on the primary side of the transformer. It should be 208 or 230 +- 10% depending on the supply voltage at the outdoor unit. If there is no voltage on the primary side of the transformer check the fuse that is located in the fuse holder inside the outdoor unit. See wiring diagram for fuse location. Once power has been confirmed at the primary side of the transformer.

Interlock relay
The interlock relay uses a normally closed contact to allow power to flow to the transformer energizing the low ambient kit control circuitry. Any time the outdoor unit is in cooling mode, this contact will be closed.
When the outdoor unit reversing valves energizes (switches to heating mode) the coil of the relay is energized, opening this contact. This in turn de- energizes the transformer, disconnecting power to the low ambient kit control circuitry. This allows the damper to spring return to the fully open position during heating mode. To check, make sure the contact is closed when the outdoor unit is in cooling mode (coil deenergized) and the contact is open when the outdoor unit is in the heating mode (coil energized).
Damper actuator Before troubleshooting the damper motor, verify the two factory switches are in the position shown below.MITSUBISHI ELECTRIC LAHN-1
Low Ambient Hoods - Damper actuator

Make sure the motor has 24 volts on the (1) Common and (2) +Hot connections. If not, find the cause of the voltage failure and correct it. The damper actuator receives a DC voltage signal from the circuit board.
This voltage can be measured between (1) Common and (3) 2-10VDC connections. The damper actuator has an angle indicator where it clamps onto the damper shaft linkage. Compare the DC voltage supply to the damper angle indicator position in the chart below. The angle should be within 2% of the chart shown below. If not, check to make sure the damper started off in the correct position, 0 Degrees.

IMPORTANT
It’s possible that during shipping, the damper shaft may have moved in the actuator shaft clamp assembly. See Section 3. Damper Blade Adjustment.

If the damper actuator angle doesn’t match within 2%, with the corresponding control board voltage supplied as shown below, the damper actuator should be replaced.

Ambient temp [ °F ] Hood angle [ 0 ] Output voltage [VDC] Resistance [0]
-10 80 8.78 117960
-5 80 8.78 100184
0 70 7.9 85340
5 70 7.9 72906
10 70 7.9 62460
15 70 7.9 53658
20 60 7.04 46220
25 60 7.04 39917
30 60 7.4 34562
35 60 7.4 30000
40 OPEN 2 26104
45 OPEN 2 22767

Damper blade adjustment

IMPORTANT
Its possible that during shipping, the damper shaft may have moved in the actuator shaft clamp assembly. In some cases due to manufacturing tolerances the LAHN blades could close 100%.

The damper should never be 100% closed during operation. When working properly, the damper will be approximately 90% closed at -5 F and below for S, L, and XL units. FOR EXL ODUs ONLY, an additional adjustment is required which limits closure to 65% at 15 F and below. This additional step MUST BE followed for proper unit operation. The following procedure will allow proper adjustment.
The Belimo damper motor within the LAHN control box has a built in mechanical stop to adjust the maximum angle of rotation. This must be adjusted to 85 degrees and the damper blade position verified or re set to the proper position (1/4″ open) to ensure the unit functions properly. After this “calibration” step, FOR EXL ODUs ONLY an additional step MUST BE followed in which the built in mechanical stop is adjusted to ~65 degrees.

Belimo motor angle indicating scale shown below| The factory setting for the mechanical stop is shown below at 85 degree hood angle.
---|---
|

IMPORTANT
ENSURE POWER IS OFF BEFORE STARTING!!

Basic Service Overview

  1. Set damper motor stop to 85 degrees.
  2. Loosen “U” bolts on damper shaft.
  3. Crank the motor against the 85-degree stop then lock into position.
  4. Set damper to approx. ¼” open. (Use damper crank handle as spacer.)
  5. Re-tighten “U” bolts on damper shaft.
  6. Release motor by slightly cranking with handle. Check operation manually.
  7. The goal is to have ¼” opening on damper assembly in the 85-degree position.

Step 1. Loosen the Philips head screw for the mechanical stop.MITSUBISHI
ELECTRIC LAHN-1 Low Ambient Hoods - mechanical stopStep 2. Slide the mechanical stop to 85 (halfway between 8 and 9) and tighten the screw, making sure the locating teeth on the stop are engaged into the actuator motor teeth.MITSUBISHI ELECTRIC LAHN-1 Low Ambient
Hoods - motor teeth

Step 3. Loosen the (2) nuts on the damper shaft “U” clamp.MITSUBISHI
ELECTRIC LAHN-1 Low Ambient Hoods - damper shaftStep 4. Using the crank handle turn the motor counterclockwise until the indicator snugs against the stop at 85 degrees.MITSUBISHI ELECTRIC
LAHN-1 Low Ambient Hoods - counterclockwiseStep 5. Lock the motor in the 85 degree position.MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods - degree
position

Step 6. Close the blades by hand and insert the crank handle under the damper blade near the screws as shown to ensure it is open approximately 1/4 inch at 85 degrees.MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods - open
approximatelyStep 7. Holding the blades against the handle re-tighten the (2) nuts on the damper shaft “U” clamp. Step 8. Ensure that the end of the shaft is flush to the edge of the clamp black surface as shown. Step 9. Slightly crank the handle to release the motor. The damper will return to the open position.MITSUBISHI ELECTRIC
LAHN-1 Low Ambient Hoods - open position

Review and Manual Test
To ensure the LAHN-1/LAHN-3 unit is functioning as designed, crank the Belimo motor back to the 85degree position and visually check that the damper does not close completely.
Your goal is approximately ¼” opening between the blades at the 85-degree position.

Additional louver adjustment: EXL ODUs ONLY

IMPORTANT
This section is only to be followed for EXL ODUs. For clarification on which ODUs are EXL, refer to the Applications Guide.

The previous instructions must be followed to ensure the louver calibration is correct. For EXL LAK hood installation, the following steps MUST be taken to limit the maximum closure of the hood louvers and allow for intended ODU operation.

Step 1. Loosen the Phillips head screw for the mechanical stop. Step 2. Slide the mechanical stop to approximately 65 degrees (between the “6” and “7” marks) and tighten the screw, making sure the locating teeth on the stop are engaged into the actuator motor teeth.

NOTE
The 65 degree position is likely the correct position for this mechanical stop, however this may need to be corrected. Final judgement of the correct mechanical stop position will be determined in step 4.

Step 3. Using the included crank handle, turn the motor counter-clockwise until the indicator stops against the mechanical stop. Lock the indicator against the mechanical stop using the locking switch, circled below.MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods - locking
switchStep 4. Check the louver angle alignment in this position using a tape measure or other device. The gap between louvers should be 2.0″. If the gap between louvers differs by more than 1/8″, repeat steps 2 and 3 using a differing mechanical stop angle until acceptable louver spacing is achieved. See image below for measurement example.MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods - mechanism on the
actuator

Step 5. Once the louver spacing is adjusted properly, release the locking mechanism on the actuator. The louvers should return to their default open position.

Damper actuator manual override

IMPORTANT
Never manually override the damper position if the outdoor unit could switch to heating mode during the override period. Heating mode requires the damper to be fully open for full capacity.
It may be desirable to manually override the damper position and lock it into position until repairs can be completed. If so, select an average temperature, typical for the outside environment during the override period, and then use that average temperature to find the desired damper angle in the chart below.

Ambient temp [ °F ] Hood angle [ ° ] Output voltage VDC Resistance Ω
-10 80 9. 117960
-5 80 9. 100184
0 70 8. 85340
5 70 8. 72906
10 70 8. 62460
15 70 8. 53658
20 60 7. 46220
25 60 7. 39917
30 60 7. 34562
35 60 7. 30000
40 OPEN 2 26104
45 OPEN 2 22767

Follow the instructions below for manually positioning and locking the damper in place.

IMPORTANT
Disconnect power to the damper motor before locking in place.

The damper actuator comes with a crank handle attached, to manually move the damper position. The crank handle is removable and if it’s missing, a 3/16” allen wrench will work just as well.
Use the following diagrams and instructions for this procedure.

Winding the damper actuator
-Insert Crank handle
-Turn the handle in the direction of the arrow.| Locking the damper actuator
-Flip the lock switch to the position pointing to the “locked” symbol.| Unlocking the damper actuator (2 options)
-Flip the lock switch to the position pointing to the “unlocked” symbol.
-Remote control by supplying power to the unit for > than 3 seconds
---|---|---
| |

MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods - Unlocking the
damper1

Parts list

MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods - Damper Control
Box

Note:
Damper linkage parts can be purchased locally.
If damper blades or complete assembly needs replacing, order new LAHN-2/LAHN-4 hood and damper assembly.

Wiring diagram

MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods - Wiring
diagram

This product is designed and intended for use in the commercial and light- industrial environment.
Please be sure to put the contact address/telephone number on this manual before handing it to the customer.

Manufactured for:
MITSUBISHI ELECTRIC US, INC.
www.mitsubishielectric-usa.com
Toll Free: 800-433-4822
MEUS DOC# MD-1922-K002, Ver.4. January 2022
Specifications are subject to change without notice.
© 2022 Mitsubishi Electric US, Inc.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Mitsubishi Electric User Manuals

Related Manuals