MITSUBISHI ELECTRIC LAHN-1 Low Ambient Hoods Instruction Manual
- June 8, 2024
- Mitsubishi Electric
Table of Contents
MANUFACTURED FOR:
MITSUBISHI ELECTRIC US, INC.
LAHN-1/ LAHN-3 Low Ambient Hoods
Instruction Manual
LAHN-1 Low Ambient Hoods
For use with: CITY MULTI® N-Generation Air Cooled Outdoor Units
TECHNICAL & SERVICE MANUAL
FOR INSTALLER
For safe and effective use of these items, please read this manual thoroughly
before installing these components.
Control box component identification
Operating sequence
Outdoor unit in cooling mode
The LAHN-1/LAHN-3 low ambient hood is designed to reduce the airflow through
the outdoor units as the ambient temperature drops. This maintains the head
pressure at a level that will allow the system to perform at full capacity
down to -10°F outdoor temperature.
NOTE
For R2 Systems: *Full cooling capacity down to -10°F. **In cooling mode or
cooling main, to guarantee full cooling capacity, the system must operate with
a constant heat load in the zones requiring cooling when ambient temperatures
fall below 5°F.
A thermistor mounted on the side of the unit senses the outdoor temperature.
As the outdoor temperature drops, the resistance of the thermistor increases.
The thermistor is connected to the specially designed circuit board and the
resistance value from the thermistor is converted to a DC voltage output
within the circuit board. This DC voltage output drives the damper actuator to
a predetermined position based on the outdoor temperature. The inverter-driven
fan motor will adjust the discharge pressure based on system capacity demand.
The motor will speed up and force more air through the damper if there is a
higher system capacity demand, or slow down if system capacity demand
decreases.
Outdoor unit in heating mode
Heating mode requires the damper to be in a fully open position to allow full
airflow and maximum heating capacity. Heating mode automatically deactivates
the kit through an interlock relay. The coil for this relay is tied into the
reversing valve connection on the outdoor unit. When the unit switches to
heating mode, the reversing valve is energized. This in turn energizes the
interlock relay. When the relay is energized, the normally closed contact
opens. By opening this contact, the power to the transformer and control board
is interrupted, this allows the damper to spring to the fully open position.
Outdoor unit in defrost mode
If the outdoor unit will be running in heating mode, a defrost period is
inevitable. During defrost, the low ambient controls see this as the unit
operating in cooling mode. If the outdoor temperature is below 40°F, the
damper will close to a position equal to that required during the cooling
cycle. Once the unit comes back out of defrosting and into heating mode, the
damper will again spring wide open for full airflow.
Operation test
Outdoor unit must be in cooling mode.
All hoods and damper controls are tested at the factory before shipping. To
perform an operational test once the installation is complete, follow the
steps below. Please refer to the following chart and table for detailed
control logic.
Operation testing when the outdoor ambient is ABOVE 40°F
-
Turn on power to the outdoor unit.
-
Make sure the outdoor unit is in cooling mode.
-
Locate the outdoor temperature sensing thermistor at the end of the short conduit coming out the side of the control panel; it can be seen inside the plastic shield.
-
Using an aerosol dusting sprayer, invert the can and spray the thermistor with very short bursts of the cold liquid.
Caution: Do Not overspray the thermistor as it could be damaged. It may take 10 – 20 seconds for the internal thermistor temperature to drop.
The damper will start to move toward the closed position after the thermistor drops below 35°F. -
Once the thermistor warms above 40°F, it will move back to the fully open position indicating the low ambient kit is working as designed.
Ambient temp [ °F ]| Hood angle [ 0 ]| Output voltage [VDC]|
Resistance [0]
---|---|---|---
-10| 80| 9.| 117960
-5| 80| 9.| 100184
0| 70| 8.| 85340
5| 70| 8.| 72906
10| 70| 8.| 62460
15| 70| 8.| 53658
20| 60| 7.| 46220
25| 60| 7.| 39917
30| 60| 7.| 34562
35| 60| 7.| 30000
40| OPEN| 2| 26104
45| OPEN| 2| 22767
Operation testing when the outdoor ambient is BELOW 35°F
- Turn on power to the outdoor unit.
- Make sure the outdoor unit is in cooling mode.
- The damper will move toward the closed position to a predetermined position based on the outdoor ambient temperature, indicating the low ambient kit is working as designed.
LAHN Damper Hysteresis Control
If neither of these tests work, proceed with the component troubleshooting
instructions.
Component troubleshooting Thermistor
The thermistor is a 10,000 Ω, NTC Type. The circuit board has a blinking
indicator light built in to reference what the thermistor is sensing. The
following chart shows what the blinking light sequence means.
If the light is on constantly, the thermistor is open or shorted and needs to
be replaced. If the blinking light sequence doesn’t fall within the range
given in the chart, the thermistor needs to be replaced. If it’s suspected
that the thermistor is operating inaccurately, check the tolerance in the
following instructions.
Disconnect the thermistor from the control board. Measure the resistance
across the two leads. Measure the temperature of the thermistor. (Accuracy on
the temperature reading is important to prevent a good thermistor from being
replaced). Compare the ohm reading with the temperature on the chart below.
Based on the thermistor temperature the ohm reading should be within 3% of the
number shown below. If not, and the thermistor connections are not corroded,
the thermistor should be replaced.
°F | Ohms | °F | Ohms | °F | Ohms | °F | Ohms |
---|---|---|---|---|---|---|---|
86 | 8,056 | 59 | 15,714 | 32 | 32,650 | 5 | 72,906 |
84 | 8,448 | 57 | 16,551 | 30 | 34,562 | 3 | 77,620 |
82 | 8,682 | 55 | 17,438 | 28 | 36,601 | 1 | 82,676 |
81 | 9,077 | 54 | 17,902 | 27 | 37,671 | 0 | 85,340 |
79 | 9,526 | 52 | 18,873 | 26 | 38,776 | -2 | 90,962 |
77 | 10,0000 | 50 | 19,903 | 23 | 42,315 | -4 | 96,999 |
75 | 10,501 | 48 | 20,997 | 21 | 44,875 | -6 | 103,486 |
73 | 11,301 | 46 | 22,159 | 19 | 47,610 | -8 | 110,460 |
72 | 11,307 | 45 | 22,767 | 18 | 49,047 | -9 | 114,141 |
70 | 11,884 | 43 | 24,040 | 16 | 52,069 | -11 | 121,921 |
68 | 12,493 | 41 | 25,394 | 14 | 55,301 | -13 | 130,295 |
66 | 13,139 | 39 | 26,835 | 12 | 58,759 | -15 | 139,313 |
64 | 13,822 | 37 | 28,368 | 10 | 62,460 | -17 | 149,030 |
63 | 14,179 | 36 | 29,171 | 9 | 64,408 | -18 | 154,169 |
61 | 14,924 | 34 | 30,856 | 7 | 68,510 | -20 | 165,048 |
Circuit board
Confirm the thermistor is operating properly before troubleshooting the
circuit board. Make sure the control board has 24 Volts AC when measured at
the 24 VAC and the com terminals. If not, find the cause of voltage failure.
The circuit board is designed to convert the thermistor ohm input to a 2 –
9.16 VDC output to control the position of the damper actuator. Above 2 VDC
output, the actuator will start to move the damper toward the closed position.
At 9.16 VDC, the actuator will have moved 85 degrees and the damper will be
approximately 95% closed. The damper should never be 100% closed. The chart
below includes the various damper angles based on the different outdoor
temperatures. Measure the DC voltage output on the circuit board at com (-)
and the out (+) terminals. If the output doesn’t match the thermistor input
ohms as shown below, replace the circuit board.
Ambient temp [ °F ] | Hood angle [ ° ] | Output voltage [VOC] | Resistance [0] |
---|---|---|---|
-10 | 80 | 8.78 | 117960 |
-5 | 80 | 8.78 | 100184 |
0 | 70 | 7.9 | 85340 |
5 | 70 | 7.9 | 72906 |
10 | 70 | 7.9 | 62460 |
15 | 70 | 7.9 | 53658 |
20 | 60 | 7.04 | 46220 |
25 | 60 | 7.04 | 39917 |
30 | 60 | 7.04 | 34562 |
35 | 60 | 7.04 | 30000 |
40 | OPEN | 2 | 26104 |
45 | OPEN | 2 | 22767 |
Transformer
The transformer is 208/230 -24volt AC. For proper connections to the outdoor
unit, refer to the following diagram and instructions.
208/230 volt and also 460-volt outdoor units. On 208 volt units, the CNAC2 connector will provide 208 volts to the control transformer. On 230 volt units, the CNAC2 connector will provide 230 volts to the control transformer. The 460-volt units include a transformer that reduces the outdoor unit internal voltage to 230 volts. Because of this, on the 460-volt units, the CNAC2 connector will also provide 230 volts to the control transformer. Once the proper connection is confirmed, measure the voltage on the primary side of the transformer. It should be 208 or 230 +- 10% depending on the supply voltage at the outdoor unit. If there is no voltage on the primary side of the transformer check the fuse that is located in the fuse holder inside the outdoor unit. See wiring diagram for fuse location. Once power has been confirmed at the primary side of the transformer.
Interlock relay
The interlock relay uses a normally closed contact to allow power to flow to
the transformer energizing the low ambient kit control circuitry. Any time the
outdoor unit is in cooling mode, this contact will be closed.
When the outdoor unit reversing valves energizes (switches to heating mode)
the coil of the relay is energized, opening this contact. This in turn de-
energizes the transformer, disconnecting power to the low ambient kit control
circuitry. This allows the damper to spring return to the fully open position
during heating mode. To check, make sure the contact is closed when the
outdoor unit is in cooling mode (coil deenergized) and the contact is open
when the outdoor unit is in the heating mode (coil energized).
Damper actuator Before troubleshooting the damper motor, verify the two
factory switches are in the position shown below.
Make sure the motor has 24 volts on the (1) Common and (2) +Hot connections.
If not, find the cause of the voltage failure and correct it. The damper
actuator receives a DC voltage signal from the circuit board.
This voltage can be measured between (1) Common and (3) 2-10VDC connections.
The damper actuator has an angle indicator where it clamps onto the damper
shaft linkage. Compare the DC voltage supply to the damper angle indicator
position in the chart below. The angle should be within 2% of the chart shown
below. If not, check to make sure the damper started off in the correct
position, 0 Degrees.
IMPORTANT
It’s possible that during shipping, the damper shaft may have moved in the
actuator shaft clamp assembly. See Section 3. Damper Blade Adjustment.
If the damper actuator angle doesn’t match within 2%, with the corresponding control board voltage supplied as shown below, the damper actuator should be replaced.
Ambient temp [ °F ] | Hood angle [ 0 ] | Output voltage [VDC] | Resistance [0] |
---|---|---|---|
-10 | 80 | 8.78 | 117960 |
-5 | 80 | 8.78 | 100184 |
0 | 70 | 7.9 | 85340 |
5 | 70 | 7.9 | 72906 |
10 | 70 | 7.9 | 62460 |
15 | 70 | 7.9 | 53658 |
20 | 60 | 7.04 | 46220 |
25 | 60 | 7.04 | 39917 |
30 | 60 | 7.4 | 34562 |
35 | 60 | 7.4 | 30000 |
40 | OPEN | 2 | 26104 |
45 | OPEN | 2 | 22767 |
Damper blade adjustment
IMPORTANT
Its possible that during shipping, the damper shaft may have moved in the
actuator shaft clamp assembly. In some cases due to manufacturing tolerances
the LAHN blades could close 100%.
The damper should never be 100% closed during operation. When working
properly, the damper will be approximately 90% closed at -5 F and below for S,
L, and XL units. FOR EXL ODUs ONLY, an additional adjustment is required which
limits closure to 65% at 15 F and below. This additional step MUST BE followed
for proper unit operation. The following procedure will allow proper
adjustment.
The Belimo damper motor within the LAHN control box has a built in mechanical
stop to adjust the maximum angle of rotation. This must be adjusted to 85
degrees and the damper blade position verified or re set to the proper
position (1/4″ open) to ensure the unit functions properly. After this
“calibration” step, FOR EXL ODUs ONLY an additional step MUST BE followed in
which the built in mechanical stop is adjusted to ~65 degrees.
Belimo motor angle indicating scale shown below| The factory setting for the
mechanical stop is shown below at 85 degree hood angle.
---|---
|
IMPORTANT
ENSURE POWER IS OFF BEFORE STARTING!!
Basic Service Overview
- Set damper motor stop to 85 degrees.
- Loosen “U” bolts on damper shaft.
- Crank the motor against the 85-degree stop then lock into position.
- Set damper to approx. ¼” open. (Use damper crank handle as spacer.)
- Re-tighten “U” bolts on damper shaft.
- Release motor by slightly cranking with handle. Check operation manually.
- The goal is to have ¼” opening on damper assembly in the 85-degree position.
Step 1. Loosen the Philips head screw for the mechanical stop.Step 2. Slide the mechanical stop to 85 (halfway between 8 and 9) and tighten the screw, making sure the locating teeth on the stop are engaged into the actuator motor teeth.
Step 3. Loosen the (2) nuts on the damper shaft “U” clamp.Step 4. Using the crank handle turn the motor counterclockwise until the indicator snugs against the stop at 85 degrees.Step 5. Lock the motor in the 85 degree position.
Step 6. Close the blades by hand and insert the crank handle under the damper blade near the screws as shown to ensure it is open approximately 1/4 inch at 85 degrees.Step 7. Holding the blades against the handle re-tighten the (2) nuts on the damper shaft “U” clamp. Step 8. Ensure that the end of the shaft is flush to the edge of the clamp black surface as shown. Step 9. Slightly crank the handle to release the motor. The damper will return to the open position.
Review and Manual Test
To ensure the LAHN-1/LAHN-3 unit is functioning as designed, crank the Belimo
motor back to the 85degree position and visually check that the damper does
not close completely.
Your goal is approximately ¼” opening between the blades at the 85-degree
position.
Additional louver adjustment: EXL ODUs ONLY
IMPORTANT
This section is only to be followed for EXL ODUs. For clarification on which
ODUs are EXL, refer to the Applications Guide.
The previous instructions must be followed to ensure the louver calibration is correct. For EXL LAK hood installation, the following steps MUST be taken to limit the maximum closure of the hood louvers and allow for intended ODU operation.
Step 1. Loosen the Phillips head screw for the mechanical stop. Step 2. Slide the mechanical stop to approximately 65 degrees (between the “6” and “7” marks) and tighten the screw, making sure the locating teeth on the stop are engaged into the actuator motor teeth.
NOTE
The 65 degree position is likely the correct position for this mechanical
stop, however this may need to be corrected. Final judgement of the correct
mechanical stop position will be determined in step 4.
Step 3. Using the included crank handle, turn the motor counter-clockwise until the indicator stops against the mechanical stop. Lock the indicator against the mechanical stop using the locking switch, circled below.Step 4. Check the louver angle alignment in this position using a tape measure or other device. The gap between louvers should be 2.0″. If the gap between louvers differs by more than 1/8″, repeat steps 2 and 3 using a differing mechanical stop angle until acceptable louver spacing is achieved. See image below for measurement example.
Step 5. Once the louver spacing is adjusted properly, release the locking mechanism on the actuator. The louvers should return to their default open position.
Damper actuator manual override
IMPORTANT
Never manually override the damper position if the outdoor unit could switch
to heating mode during the override period. Heating mode requires the damper
to be fully open for full capacity.
It may be desirable to manually override the damper position and lock it into
position until repairs can be completed. If so, select an average temperature,
typical for the outside environment during the override period, and then use
that average temperature to find the desired damper angle in the chart below.
Ambient temp [ °F ] | Hood angle [ ° ] | Output voltage VDC | Resistance Ω |
---|---|---|---|
-10 | 80 | 9. | 117960 |
-5 | 80 | 9. | 100184 |
0 | 70 | 8. | 85340 |
5 | 70 | 8. | 72906 |
10 | 70 | 8. | 62460 |
15 | 70 | 8. | 53658 |
20 | 60 | 7. | 46220 |
25 | 60 | 7. | 39917 |
30 | 60 | 7. | 34562 |
35 | 60 | 7. | 30000 |
40 | OPEN | 2 | 26104 |
45 | OPEN | 2 | 22767 |
Follow the instructions below for manually positioning and locking the damper in place.
IMPORTANT
Disconnect power to the damper motor before locking in place.
The damper actuator comes with a crank handle attached, to manually move the
damper position. The crank handle is removable and if it’s missing, a 3/16”
allen wrench will work just as well.
Use the following diagrams and instructions for this procedure.
Winding the damper actuator
-Insert Crank handle
-Turn the handle in the direction of the arrow.| Locking the damper actuator
-Flip the lock switch to the position pointing to the “locked” symbol.| Unlocking the damper actuator (2 options)
-Flip the lock switch to the position pointing to the “unlocked” symbol.
-Remote control by supplying power to the unit for > than 3 seconds
---|---|---
| |
Parts list
Note:
Damper linkage parts can be purchased locally.
If damper blades or complete assembly needs replacing, order new LAHN-2/LAHN-4
hood and damper assembly.
Wiring diagram
This product is designed and intended for use in the commercial and light-
industrial environment.
Please be sure to put the contact address/telephone number on this manual
before handing it to the customer.
Manufactured for:
MITSUBISHI ELECTRIC US, INC.
www.mitsubishielectric-usa.com
Toll Free: 800-433-4822
MEUS DOC# MD-1922-K002, Ver.4. January 2022
Specifications are subject to change without notice.
© 2022 Mitsubishi Electric US, Inc.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>