Philio Technology AC Master Lite PAR01 Manual

June 8, 2024
Philio Technology

Philio Technology

AC Master Lite

SKU: PAR01

Quickstart

This is a
secure
HVAC-Thermostat
for
CEPT (Europe)
.

Please make sure the internal battery is fully charged.

To add this device to your network execute the following action:
1, Refer to your primary controller to enter into the Inclusion Mode or Exclusion Mode2,When it is prompted to enter it, please triple click the PROG button within 1 second.3,Green Indicator flashes TWICE then stay off

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

PAR01, AC Master Lite, is a Z-Wave plus compliant Z-Wave-to-IR Bridge to control split air conditioner by receiving Z-Wave command and translating to Infrared command. With its comprehensive built-In and cloud-stored IR database (library). PAR01 can control different brands and models of air conditioners worldwide.PAR01 is a security enabled Z-Wave plus device. A security Enabled Z-Wave Plus Controller must be used in order to fully utilize the product.PAR01 is a Z-Wave slave device, it depends on gateway to setup particular AC brand with correct IR code. Different gateway has different user interface for setup.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Press and Hold PROG button for 3 seconds on AC Master Lite, the Green Indicator will light up. DO NOT Release the PROG Button until Green Indicator flashes TWICE.Remark : Please use this procedure only when the network primary controller is missing or otherwise incoperable.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

1, Refer to your primary controller to enter into the Inclusion Mode or Exclusion Mode2,When it is prompted to enter it, please triple click the PROG button within 1 second.3,Green Indicator flashes TWICE then stay off

Exclusion

1, Refer to your primary controller to enter into the Inclusion Mode or Exclusion Mode2,When it is prompted to enter it, please triple click the PROG button within 1 second.3,Green Indicator flashes TWICE then stay off

Communication to a Sleeping device (Wakeup)

This device is battery operated and turned into deep sleep state most of the time
to save battery life time. Communication with the device is limited. In order to
communicate with the device, a static controller C is needed in the network.
This controller will maintain a mailbox for the battery operated devices and store
commands that can not be received during deep sleep state. Without such a controller,
communication may become impossible and/or the battery life time is significantly
decreased.

This device will wakeup regularly and announce the wakeup
state by sending out a so called Wakeup Notification. The controller can then
empty the mailbox. Therefore, the device needs to be configured with the desired
wakeup interval and the node ID of the controller. If the device was included by
a static controller this controller will usually perform all necessary
configurations. The wakeup interval is a tradeoff between maximal battery
life time and the desired responses of the device. To wakeup the device please perform
the following action:

Press the “PROG” button to Wakeup the unit

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1 1 Z-Wave Plus Lifeline

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 25: Learn IR Code

Default: 0x0000range: (0x0000 to 0x01B6)refer to learning mapping table
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 32 Storage Location

Parameter 26: Check IR Code Learning Status

Default: 0x00range: 0 to 4 (0x00 to 0x04)0(0x00) : Idle – IR Channel is idle1(0x01) : OK – the last learning operation was completed successfully2(0x02) : Learning – PAR01- is busy processing previous learning request3(0x03) : FullAll locations are being used.4(0x04) : The last learning request was failedNote:The status value 0x01 and 0x04 will be reset to 0x00 after PAR01 receives a get command to this parameter.
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 4 Read Only

Parameter 27: Set IR Code Number From built-in code library

Refer to Code Finder Webpage
Size: 2 Byte, Default Value: 0

SettingDescription

0 – 65535 IR Code Number

Parameter 30: Set Auto Report condition Trigger by Room Temperature

change

0(0x00) = Disable (Default)(for saving battery life)Auto report if room temperature is different from last report.1(0x01) = 1F (0.5C)2(0x02) = 2F (1C) 3(0x03) = 3F (1.5C)4(0x04) = 4F (2C)5(0x05) = 5F (2.5C)6(0x06) = 6F (3C)7(0x07) = 7F (3.5C)8(0x08) = 8F (4C)
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 8 Temp change

Parameter 32: Set built-in IR Emitter Control

Default: 0xFF0 or 255(0x00 or 0xFF)0(0x00): Disable255(0xFF): Enable (Default)
Size: 1 Byte, Default Value: 255

SettingDescription

0 Disable
255 Enable

Parameter 33: Control Air Conditioner SWING function

Default: 0x01Range 0 to 1 (0x00 or 0x01)0(0x00) : Swing OFF1(0x01) : Swing Auto (Default)
Size: 1 Byte, Default Value: 1

SettingDescription

0 Swing OFF
1 Swing Auto

Parameter 34: Set Auto Report Condition by Time Interval

Auto report by the following time interval.1(0x01) = 1 Hr2(0x02) = 2 Hrs3(0x03) = 3 Hrs4(0x04) = 4 Hrs5(0x05) = 5 Hrs6(0x06) = 6 Hrs7(0x07) = 7 Hrs8(0x08) = 8 Hrs (Default)
Size: 1 Byte, Default Value: 8

SettingDescription

1 – 8 Hours

Parameter 37: Calibrate Temperature reading

Temperature offset value.0(0x00) = 0C (Default)1(0x01) = 1C2(0x02) = 2C3(0x03) = 3C4(0x04) = 4C5(0x05) = 5C255(0xFF) = -1C254(0xFE) = -2C253(0xFD) = -3C252(0xFC) = -4C251(0xFB) = -5C
Size: 1 Byte, Default Value: 0

SettingDescription

0 – 5 Positive range
251 – 255 Negative range

Technical Data

Hardware Platform SD3502
Device Type Thermostat – HVAC
Network Operation Listening Sleeping Slave
Firmware Version HW: 0 FW: 1.04:01.07:182.03
Z-Wave Version 6.61.00
Certification ID ZC10-19016349
Z-Wave Product Id 0x013C.0x0102.0x8290
Thermostat Modes AutoAwayCoolDry AirFan OnlyHeatResume
Firmware Updatable Updatable by Consumer by RF
Color White
Thermostat HVAC Systems Supported
Sensors Air Temperature
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Application Status
  • Association Grp Info V3
  • Association V2
  • Basic
  • Battery
  • Configuration V2
  • Device Reset Locally
  • Firmware Update Md V3
  • Manufacturer Specific V2
  • Powerlevel
  • Security
  • Sensor Multilevel V7
  • Thermostat Fan Mode V4
  • Thermostat Mode V3
  • Thermostat Setpoint V3
  • Version V2
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals