Nortek GoControl Plug-In Switch Series 500 PD300EMZ5-1 Manual

June 8, 2024
NORTEK

Nortek

GoControl Plug-In Switch Series 500

SKU: PD300EMZ5-1

Quickstart

This is a ****

Light Dimmer
for
U.S. / Canada / Mexico
.

To run this device please connect it to your mains power supply.

To add this device to your network execute the following action:
With your Controller in Discovery or Add Mode, tap the button on the face of the outlet. The LED will blink slowly when in ADD Mode.You should see an indication on your Controller that the device was added to the network and the LED will stop blinking.The device will appear in the list of Switches. It should display as a switch.

Please refer to the
Manufacturers Manual
for more information.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The PD300EMZ5-1 is a plug in the wall device designed to control dimmable lamps providing the ideal mood for every situation.Supporting Energy Monitoring the PD300EMZ5-1 will provide both a visual indication of the amount of energy the connected device is using, and also transmit this information to the Z-Wave hub for tracking purposes.Dual long life LEDs will also act as a night light when the load is off.The integrated button can be used to turn the connected device on / off, but it can also be temporarily disabled to eliminate the inadvertent operation of the device.With Over The Air upgrading supported, this device can be seamlessly updated to the most recent firmware and software features.Finally, as a Z-Wave plus product, its 30% longer range is ideal for easily creating a strong Z-Wave mesh network for an easier installation and more reliable operation.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

In the event that your primary Controller is lost or otherwise inoperable, to reset the PD300EMZ5-1 and clear all network information, follow these steps:1. Tap the button on the face of the outlet five (5) times.2. Press and hold the button for 15 seconds. The LED will increasingly blink faster to indicate that a Reset is taking place.

Safety Warning for Mains Powered Devices

ATTENTION: only authorized technicians under consideration of the country- specific
installation guidelines/norms may do works with mains power. Prior to the assembly of
the product, the voltage network has to be switched off and ensured against re-switching.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

With your Controller in Discovery or Add Mode, tap the button on the face of the outlet. The LED will blink slowly when in ADD Mode.You should see an indication on your Controller that the device was added to the network and the LED will stop blinking.The device will appear in the list of Switches. It should display as a switch.

Exclusion

Set the Controller into Removal Mode and follow its instruction to delete the PD300EMZ5-1 from the Controller.Remove the switch by tapping the button on the face of the outlet 2 times. The LED will begin blinking slowly for 10 seconds indicating that it has been removed.You should see an indication on your Controller that the device was removed from the network.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1 5 Z-Wave Plus Lifeline

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 11: Power Monitoring

Turns Power Monitoring ON or OFF
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 1 0 – Power Monitoring OFF.1 – Power Monitoring ON

Parameter 12: Local Power Use Reporting

Sets the duration the LED will change color to indicate the amount of energy being used.
Size: 2 Byte, Default Value: 60

SettingDescription

1 – 255| 1 – 254 – Number of seconds LED displays power level usage.255 – Power Level usage continuous ON.
---|---

Parameter 13: Energy monitoring

Reports the total accumulated Kilowatt Hours (kWh) and the instantaneous Wattsbeing consumed by the load.
Size: 2 Byte, Default Value: 6

SettingDescription

0 – 255| 0 – Automatic reporting OFF.11-255 Number of minutes between automatic reporting (Default = 6)
---|---

Parameter 16: Local Dim Time

Defines the timing between the steps for local attached dimmers.
Size: 2 Byte, Default Value: 1

SettingDescription

1 – 255 # – Local Dim Time in mS

Parameter 17: All Switch Dim Step

Defines the number of steps switches takes from full ON to OFF or OFF to ON for all devices when an All Switch command is received.
Size: 1 Byte, Default Value: 3

SettingDescription

1 – 99 # – Number of All switch steps

Parameter 18: All Switch Dim Time

Defines the timing between the steps for all switcheswhen an All Switch command is received.
Size: 2 Byte, Default Value: 1

SettingDescription

1 – 255 # – Local Dim Time in mS

Parameter 2: LED Intnesity

Set the intensity of the LED.
Size: 1 Byte, Default Value: 100

SettingDescription

0 – 100 0 = OFF.1 = Very Dim.100 = Full Brightness.

Parameter 3: Night Light

Configures the function of the integrated night light
Size: 1 Byte, Default Value: 1

SettingDescription

0 – 3| 0 – LED ON when the load is on and OFF when the load is off.1 – LED OFF when the load is on, and ON when the load is off.2 – LED is always on.3 – LED is always off.
---|---

Parameter 7: Remote Dim Step

Defines the number of steps the dimmer takes from full ON to OFF or OFF to ON for Remote devices.
Size: 1 Byte, Default Value: 3

SettingDescription

1 – 99 # – Number of remote dimmer steps

Parameter 8: Remote Dim Time

Defines the timing between the steps for remote dimmers.
Size: 2 Byte, Default Value: 1

SettingDescription

1 – 255 # – Remote Dim Time in mS

Parameter 9: Local Dim Step

Defines the number of steps the dimmer takes from full ON to OFF or OFF to ON for attached devices.
Size: 1 Byte, Default Value: 3

SettingDescription

1 – 99 # – Number of attached dimmer steps

Technical Data

Hardware Platform ZM5101
Device Type Light Dimmer Switch
Network Operation Always On Slave
Firmware Version HW: 4 FW: 1.43
Z-Wave Version 6.51.08
Certification ID ZC10-18106267
Z-Wave Product Id 0x014F.0x5044.0x3533
Color White
Supported Meter Type Electric Energy
Firmware Updatable Updatable by Consumer via Internet
Z-Wave Scene Type Scene
Frequency XXfrequency
Maximum transmission power XXantenna

Supported Command Classes

  • Association Grp Info
  • Association V2
  • Basic
  • Configuration V2
  • Device Reset Locally
  • Firmware Update Md V2
  • Manufacturer Specific V2
  • Meter V4
  • Powerlevel
  • Protection
  • Scene Activation
  • Scene Actuator Conf
  • Switch All
  • Switch Multilevel V3
  • Version V2
  • Zwaveplus Info V2

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

NORTEK User Manuals

Related Manuals