Popp Battery-Wallcontroller POPE009303 Manual

June 8, 2024
POPP

Popp

Battery-Wallcontroller

SKU: POPE009303

Quickstart

This is a
secure
Z-Wave Device
for
Europe
.

To run this device please insert fresh *1 CR2032** batteries.

Please make sure the internal battery is fully charged.

This wireless Z–Wave wall controller can act in two different modes that are activated with the first configuration action after factory default:

  1. Pushing Button 1 for one sec. (red/green blink) adds the wireless wall controller to an existing network as secondary controller.  The four buttons will send activate 4 different scenes (Central Scene Command) in the central controller The wall controller is able to control up to 4 different scenes with its four buttons. (with different configuration even more)
  2. Pushing Button 3 for one sec. (green blink) adds a new Z-Wave actuator device to the controller who becomes the primary controller of this new network. The connected new device (actuator) can be controlled using the two buttons left (Button 1 = up/on/open, Button 3 = down/off/closed).

After the first action you can further manage and configure the wall controller using the management mode. To activate this management mode push all four buttons for one second simultaneously (green blinks slowly). The buttons will have different functions then (see Installation Guidelines).

Attention: For convenience reasons some special short cut apply IF and only IF the wall controller is the primary controller of the network: The first device included into a button group will define the commands sent out by this group regardless of the default value of the configuration parameters 11-14. If the device is a door lock the button group will turn into door lock control (value=7). For dimmers and motor controls the value changes into Multilevel Switch Control (value=1). All other devices will turn the button group into Basic control (value=2). All configuration values can be changed if needed. When the wall controller is primary controller the very first device included will be automatically put into button group A and the command set will change according to the rules just mentioned. All other devices need ot be put in button groups manually.

Important safety information

Please read this manual carefully. Failure to follow the recommendations in this manual may be dangerous or may violate the law.
The manufacturer, importer, distributor and seller shall not be liable for any loss or damage resulting from failure to comply with the instructions in this manual or any other material.
Use this equipment only for its intended purpose. Follow the disposal instructions.

Do not dispose of electronic equipment or batteries in a fire or near open heat sources.

What is Z-Wave?

Z-Wave is the international wireless protocol for communication in the Smart Home. This
device is suited for use in the region mentioned in the Quickstart section.

Z-Wave ensures a reliable communication by reconfirming every message ( two- way
communication
) and every mains powered node can act as a repeater for other nodes
( meshed network ) in case the receiver is not in direct wireless range of the
transmitter.

This device and every other certified Z-Wave device can be used together with any other
certified Z-Wave device regardless of brand and origin
as long as both are suited for the
same frequency range.

If a device supports secure communication it will communicate with other devices
secure as long as this device provides the same or a higher level of security.
Otherwise it will automatically turn into a lower level of security to maintain
backward compatibility.

For more information about Z-Wave technology, devices, white papers etc. please refer
to www.z-wave.info.

Product Description

The Battery Wall Controller is a 4 button Z-Wave device capable to act both as primary or secondary controller. The four buttons  can control other Z-Wave devices such as switches, dimmer and even door locks directly. Various options – configurable by Z-Wave configuration commands – define the actions and the commands used for this control. It is possible to use two sets of buttons (one of on/open/up and one for off/closed/down) or 4 single buttons to control 4 different groups of devices.

The controller also allows  triggering scenes in a central controller. Again different modes can be configured to adapt to the various implementations of scenes in different central controllers in the market.

Control options also include special modes like “all on/off” or always controlling the Z-Wave device in proximity to the fob.

The  device supports secure communication  when included with enhanced security option and when communicating to a device also supporting enhanced security option. Otherwise the device will automatically turn into normal communication to maintain backward compatibility.

Prepare for Installation / Reset

Please read the user manual before installing the product.

In order to include (add) a Z-Wave device to a network it must be in factory default
state.
Please make sure to reset the device into factory default. You can do this by
performing an Exclusion operation as described below in the manual. Every Z-Wave
controller is able to perform this operation however it is recommended to use the primary
controller of the previous network to make sure the very device is excluded properly
from this network.

Reset to factory default

This device also allows to be reset without any involvement of a Z-Wave controller. This
procedure should only be used when the primary controller is inoperable.

Turn the device into management mode. Then click on button 3. Now Keep button 4 pushed for 5 seconds. For first 5 seconds the green LED will blink, then it turns into long-red/short-green blinking until reset is complete

Safety Warning for Batteries

The product contains batteries. Please remove the batteries when the device is not used.
Do not mix batteries of different charging level or different brands.

Installation

The device can be mounted on every flat surface either using the screws provided or the double sided tape provided as well.
To atviate the device and access hte four buttons independently for management mode operations please remove the rocker using a screw driver or simply the fingers. Push hard on one corner and lift the other corner so that the rocker will unsnap.

The device can be mounted on every dry and flat surface using either screws or double side adhesive. First the mounting base is fixed on the wall. Next step the switch frame is placed on the 2 frame and the electronic insert is used to fix the frame to the mounting base as shown on the image. Finally the switching paddle(s) are mounted on the electronic base.

For battery change, the switching paddle(s) need to be removed. The CR battery can be replaced by pushing the little nipple above the battery. The old battery will slide out and the new battery is inserted until the nipple will hold it again.

The device can be operated in two different modes:

  • Operation Mode: This is the mode where the device is controlling other Z-Wave devices or is activating scenes.
  • Management Mode: The device is turned into the management mode by pushing all four buttons for one second together. A blinking green LED indicates the management mode. In the management mode the buttons of the device have different functions. If no further action is performed, the device will turn back to the normal mode after 10 sec. Any management action terminates the management mode as well.

In management mode the following actions can be performed:

  • Button 1 – Inclusion/Exclusion: Every inclusion or exclusion attempt is confirmed by hitting this button. Single Click is used for standard inclusion and exclusion, double click is used for network wide inclusion. With this operation the device can be included into a Z-Wave Network from any physical location in the network. This requires a primary controller supporting network wide inclusion. This mode lasts for 20 seconds and stops automatically. Any button press stops the mode as well.
  • Button 2 – Sends Node Information Frame and Wake up Notification. (see explanation below)
  • Button 3 – Activates the primary controller management menu. The following sub menu items are available:
  • Button 3 followed by short click of button 1: Start Secure Inclusion
  • Button 3 followed by short click of button 2: Start Unsecure Inclusion
  • Button 3 followed by short click of button 3: Start Exclusion
  • Button 3 followed by short click of button 4: Start Primary Handover
  • Button 3 followed by pushing button 4 for 5 seconds: Factory Default Reset. After clicking on button 3 keep button 4 pushed for 4 seconds
  • Button 4 – Enters into Association mode to assign target devices to one of the four associations. Refer to the manuals section about association for more information how to set and unset association groups.

In factory default mode pushing one of the four buttons for 1 sec will start different inclusion modes:

  • Button 1: Include as secondary controller
  • Button 2: Include as secondary controller – non secure
  • Button 3: Include new device into wall controllers network
  • Button 4: Include new device into wall controllers network – non secure

The process for button 1 and 2 is indicated with fast red/green blinking, the process for button 3 and 4 shows a fast green blinking. Every button push stops the process. This fast inclusion only works when device is in factory default.

Attention: For convenience reasons some special short cut apply IF and only IF the wall controller is the primary controller of the network: The first device included into a button group will define the commands sent out by this group regardless of the default value of the configuration parameters 11-14. If the device is a door lock the button group will turn into door lock control (value=7). For dimmers and motor controls the value changes into Multilevel Switch Control (value=1). All other devices will turn the button group into Basic control (value=2). All configuration values can be changed if needed. When wall controller is primary controller the very first device included will be automatically put into button group A and the command set will change according to the rules just mentioned. All other devices need ot be put in button groups manually.

Inclusion/Exclusion

On factory default the device does not belong to any Z-Wave network. The device needs
to be added to an existing wireless network to communicate with the devices of this network.
This process is called Inclusion.

Devices can also be removed from a network. This process is called Exclusion.
Both processes are initiated by the primary controller of the Z-Wave network. This
controller is turned into exclusion respective inclusion mode. Inclusion and Exclusion is
then performed doing a special manual action right on the device.

Inclusion

In Factory Default hit upper left button  (secure) or upper right button (unsecure). After factory default you need to enter Management Mode (all four buttons for one second until green LED blinks) before using the buttons

Exclusion

Enter Management Mode (all four buttons for one second until green LED blinks), then hit the upper left button

Product Usage

Depending on the button mode and operating modes configured using the configuration parameters the key fob can be used in different ways.

Button modes:

4 Groups are controlled with single button (parameter 1/2 = 0)  The four buttons 1-4 control one single control group each: 1->A, 2->B, 3->C, 4->D. Single click turns devices in the control group on, double click turns them off. Click and hold can be used for dimming.

2 Groups are controlled with two buttons (parameter 1/2 = 1)  The buttons 1 and 3 control the control group A (button one turns on, button three turns off), the buttons 2 and 4 control the control group B (button two turns on, button four turns off). In case dimmers are controlled, holding down the larger button will dim up, holding down the smaller button will dim down the load. Releasing the button will stop the dimming function.

4 Groups are controlled with two buttons and double click (parameter 1/2 = 2)  This mode enhances the previous mode and allows to control two further control groups C and D using double clicks.

Operating modes:

The devices supports 8 different operating modes – this means the kind of command sent out when pushing a button. Operating modes either directly control other devices or they issue various scene activation commands to a central controller. Operating modes for direct device control are:

  • Direct Control of associated devices with On/Off/Dim commands (parameter 11…14 = 1). Devices are controlled using Basic Set On/Off commands and Switch-Multilevel Dim Start/Stop. This mode implements communication pattern  7.
  • Direct Control of associated devices with only On/Off commands (parameter 11…14 = 2). Devices are controlled using only Basic Set On/Off commands. On dimming Up event On is sent, on dimming Down Off is sent. This mode also implements communication pattern  7.
  • Switch All commands (parameter 11…14 = 3)  In this mode a  all neighboring devices  will receive Switch-All Set On/Off command and interpret it according to their membership in Switch-All groups. This mode implements communication pattern  7.
  • Direct Control of Devices in proximity (parameter 11…14 = 6). Basic Set and Switch-Multilevel Dim commands are sent to a device in proximity (50…100 cm) from the Fob. Attention: In case there are more than one Z-Wave devices nearby all these devices may be switched. For this reason the proximity function should be handled with care. This mode implements communication pattern 7
  • Door Lock Control (parameter 11…14 = 7)  This mode allows direct control (open/close) of electronic door locks using secure communication. The mode implements communication pattern  7.

Operating modes for scene activation are:

  • Direct Activation of preconfigured scenes (parameter 11…14 = 5)  Associated devices in an association group are controlled by individual commands defines by Z-Wave command class ?Scene Controller Configuration?. This mode enhances mode  Direct Control of associated devices with On/Off/Dim commands  and implements communication patterns  6  and  7. Please turn the button mode to “separate” to allow different a scene ID on every button.
  • Scene Activation in IP Gateway (parameter 11…14 = 4)  If configured correctly the buttons can trigger a scene in a gateway. The scene number triggered is a combination of the group number and the action performed on the button and has always two digits. The group number defines the upper digit of the scene number, the action the lower digit. The following actions are possible:
    • 1 = On
    • 2 = Off
    • 3 = Dim Up Start
    • 4 = Dim Down Start
    • 5 = Dim Up Stop
    • 6 = Dim Down Stop

Example: Clicking/double clicking the button will issue scene triggers, scene 11 (button 1 click, event on), scene 12 (button double click 1, event off, single button control is used in this example)

  • Activation of Central Scenes (parameter 11…14 = 8,Default)  Z-Wave Plus introduces a new process for scene activation – the central scene control. Pushing a button and releasing a button send a certain command to the central controller using the lifeline association group. This allows reacting both on button push and button release. This mode implements communication patterns  6  but requires a central gateway supporting Z-Wave Plus.

LED Indication

  • Confirmation – green 1 sec
  • Failure – red 1 sec
  • Button press confirmation – green 1/4 sec
  • Waiting for Network Management mode selection – slow green blinks
  • Waiting for group selection in Association Set Mode – green fast blink
  • Waiting for primary controller function selection – green fast blink
  • Waiting for NIF in Association Set Mode – green-red-off blink

Node Information Frame

The Node Information Frame (NIF) is the business card of a Z-Wave device. It contains
information about the device type and the technical capabilities. The inclusion and
exclusion of the device is confirmed by sending out a Node Information Frame.
Beside this it may be needed for certain network operations to send out a Node
Information Frame. To issue a NIF execute the following action:

Pressing Button 2 in management mode will issue a Node Information Frame.

Communication to a Sleeping device (Wakeup)

This device is battery operated and turned into deep sleep state most of the time
to save battery life time. Communication with the device is limited. In order to
communicate with the device, a static controller C is needed in the network.
This controller will maintain a mailbox for the battery operated devices and store
commands that can not be received during deep sleep state. Without such a controller,
communication may become impossible and/or the battery life time is significantly
decreased.

This device will wakeup regularly and announce the wakeup
state by sending out a so called Wakeup Notification. The controller can then
empty the mailbox. Therefore, the device needs to be configured with the desired
wakeup interval and the node ID of the controller. If the device was included by
a static controller this controller will usually perform all necessary
configurations. The wakeup interval is a tradeoff between maximal battery
life time and the desired responses of the device. To wakeup the device please perform
the following action:

(1) Turn the device into Management Mode by keeping all four buttons pushed for 5 seconds, (2) click on Button 2.

Quick trouble shooting

Here are a few hints for network installation if things dont work as expected.

  1. Make sure a device is in factory reset state before including. In doubt exclude before include.
  2. If inclusion still fails, check if both devices use the same frequency.
  3. Remove all dead devices from associations. Otherwise you will see severe delays.
  4. Never use sleeping battery devices without a central controller.
  5. Dont poll FLIRS devices.
  6. Make sure to have enough mains powered device to benefit from the meshing

Association – one device controls an other device

Z-Wave devices control other Z-Wave devices. The relationship between one device
controlling another device is called association. In order to control a different
device, the controlling device needs to maintain a list of devices that will receive
controlling commands. These lists are called association groups and they are always
related to certain events (e.g. button pressed, sensor triggers, …). In case
the event happens all devices stored in the respective association group will
receive the same wireless command wireless command, typically a ‘Basic Set’ Command.

Association Groups:

Group NumberMaximum NodesDescription

1 10 Lifeline
2 10 Control Group A
3 10 Control Group B
4 10 Control Group C
5 10 Control Group D

Special Operations as Z-Wave Controller

As long as this device is not included into a Z-Wave network of a different controller
it is able to manage its own Z-Wave network as primary controller. As a primary controller
the device can include and exclude other devices in its own network, manage associations,
and reorganize the network in case of problems. The following controller functions
are supported:

Inclusion of other devices

Communication between two Z-Wave devices only works if both belong to the same
wireless network. Joining a network is called inclusion and is initiated by a controller.
The controller needs to be turned into the inclusion mode. Once in this inclusion mode
the other device needs to confirm the inclusion – typically by pressing a button.

If current primary controller in your network is in special SIS mode this and
any other secondary controller can also include and exclude devices.

To become
primary a contoller have to be resetted and then include a device.

In Factory Default hit lower left button  (secure) or lower right button (unsecure). After factory default you need to enter Management Mode (all four buttons for one second until green LED blinks) before using the buttons.

Exclusion of other devices

The primary controller can exclude devices from the Z-Wave network. During exclusion
the relationship between the device and the network of this controller is terminated.
No communication between the device and other devices still in the network can happen
after a successful exclusion. The controller needs to be turned into the exclusion mode.
Once in this exclusion mode the other device needs to confirm the exclusion – typically
by pressing a button.

Attention: Removing a device from the network means that it is turned back
into factory default status. This process can also exclude devices from it’s previous
network.

In Factory Default hit upper left button  (secure) or upper right button (unsecure). After factory default you need to enter Management Mode (all four buttons for one second until green LED blinks) before using the buttons

Shift of Primary Controller Role

The device can hand over its primary role to another controller and become
secondary controller.

Turn into management mode by pressing all 4 buttons for 5 seconds. The green LED will start blinking slowly. Now hit button 3 to activate the primary controller functions. The green LED will blink faster. Now Hit Button 4 to turn the controller into primary shift mode. Consult the manual of the new device how to start the primary shift process for the new primary controller.

Management of Association in the controller

To control a Z-Wave device from the Key Fob the node ID of this device needs to be assigned to one of the four association groups. This is a three-step process:

  1. Turn the Key Fob into management mode and hit button 4 within 10 sec. (LED is blinking green when management mode is reached).
  2. Within 10 sec. push the button you like the Z-Wave actuator to be assigned with. After 10 sec. the device goes back to sleep.  Single click means adding to this association group, double click means removing the node selected in step (3) from this association group.
  3. Find the Z-Wave actuator you like to control by the key fob. Hit the button on the device to issue a Node Information Frame within 20 sec. A common way is hitting a control button one or three times. Please consult the manual of the device to be controlled for more information how to issue an Node Information Frame. Any button press on Key Fob at this stage will terminate the process.

Configuration Parameters

Z-Wave products are supposed to work out of the box after inclusion, however
certain configuration can adapt the function better to user needs or unlock further
enhanced features.

IMPORTANT: Controllers may only allow configuring
signed values. In order to set values in the range 128 … 255 the value sent in
the application shall be the desired value minus 256. For example: To set a
parameter to 200 it may be needed to set a value of 200 minus 256 = minus 56.
In case of a two byte value the same logic applies: Values greater than 32768 may
needed to be given as negative values too.

Parameter 1: Button 1 and 3 pair mode

In separate mode button 1 works with Group A, button 3 with Group C. Click is ON, Hold is dimming UP, Double click is OFF, Click-Hold is dimming DOWN. In pair button 1/3 are UP/DOWN correspondingly. Click is ON/OFF, Hold is dimming UP/DOWN. Single clicks works with Group A, double click with Group C.
Size: 1 Byte, Default Value: 1

SettingDescription

0 Separately
1 In pair without double clicks
2 In pair with double clicks

Parameter 2: Button 2 and 4 pair mode

In separate mode button 2 works with control group B, button 4 with control group D. Click is ON, Hold is dimming UP, Double click is OFF, Click-Hold is dimming DOWN. In pair button B/D are UP/DOWN correspondingly. Click is ON/OFF, Hold is dimming UP/DOWN. Single clicks works with Group B, double click with Group D.
Size: 1 Byte, Default Value: 1

SettingDescription

0 Separately
1 In pair without double clicks
2 In pair with double clicks

Parameter 11: Command to control Group A

This parameter defines the command to be sent to devices of control group A when the related button is pressed.
Size: 1 Byte, Default Value: 8

SettingDescription

0 Disable
1 Switch on/off and Dim (send Basic Set and Switch Multilevel)
2 Switch on/off only (send Basic Set)
3 Switch all
4 Send scenes
5 Send preconfigured scenes
6 Control devices in proximity
7 Control door lock
8 Central scene to gateway (default)

Parameter 12: Command to control Group B

This parameter defines the command to be sent to devices of control group B when the related button is pressed.
Size: 1 Byte, Default Value: 8

SettingDescription

0 Disable
1 Switch on/off and Dim (send Basic Set and Switch Multilevel)
2 Switch on/off only (send Basic Set)
3 Switch all
4 Send scenes
5 Send preconfigured scenes
6 Control devices in proximity
7 Control door lock
8 Central scene to gateway (default)

Parameter 13: Command to control Group C

This parameter defines the command to be sent to devices of control group C when the related button is pressed.
Size: 1 Byte, Default Value: 8

SettingDescription

0 Disable
1 Switch on/off and Dim (send Basic Set and Switch Multilevel)
2 Switch on/off only (send Basic Set)
3 Switch all
4 Send scenes
5 Send preconfigured scenes
6 Send preconfigured scenes
7 Control door lock
8 Central scene to gateway

Parameter 14: Command to control Group D

This parameter defines the command to be sent to devices of control group D when the related button is pressed.
Size: 1 Byte, Default Value: 8

SettingDescription

0 Disable
1 Switch on/off and Dim (send Basic Set and Switch Multilevel)
2 Switch on/off only (send Basic Set)
3 Switch all
4 Send scenes
5 Send preconfigured scenes
6 Control devices in proximity
7 Control door lock
8 Central scene to gateway (default)

Parameter 21: Send the following switch all commands

__
Size: 1 Byte, Default Value: 1

SettingDescription

1 Switch off only
2 Switch on only
255 Switch all on and off

Parameter 22: Invert buttons

__
Size: 1 Byte, Default Value: 0

SettingDescription

0 No
1 Yes

Parameter 25: Blocks wake up even when Wake Up Interval is set

If the KFOB wakes up and there is no controller nearby, several unsuccessful communication attempts will drain battery.
Size: 1 Byte, Default Value: 0

SettingDescription

0 Wake up is blocked
1 Wake up is possible if configured accordingly

Parameter 30: Send unsolicited battery report on Wake Up

__
Size: 1 Byte, Default Value: 1

SettingDescription

0 No
1 To same node as Wake Up Notification
2 Broadcast to neighbors

Technical Data

Dimensions 80x80x15mm mm
Weight 50 gr
Hardware Platform ZM5202
EAN 0019962009303
IP Class IP 20
Battery Type 1 * CR2032
Firmware Version 01.01
Z-Wave Version 04.05
Certification ID ZC10-15050016
Z-Wave Product Id 0x0154.0x0100.0x0101
Frequency Europe – 868,4 Mhz
Maximum transmission power 5 mW

Supported Command Classes

  • Scene Controller Conf
  • Association Grp Info
  • Device Reset Locally
  • Central Scene
  • Zwaveplus Info
  • Configuration
  • Manufacturer Specific
  • Powerlevel
  • Battery
  • Wake Up
  • Association
  • Version
  • Multi Channel Association
  • Multi Cmd
  • Security

Controlled Command Classes

  • Basic
  • Central Scene
  • Switch Multilevel
  • Switch All
  • Scene Activation
  • Multi Channel
  • Door Lock

Explanation of Z-Wave specific terms

  • Controller — is a Z-Wave device with capabilities to manage the network.
    Controllers are typically Gateways,Remote Controls or battery operated wall controllers.

  • Slave — is a Z-Wave device without capabilities to manage the network.
    Slaves can be sensors, actuators and even remote controls.

  • Primary Controller — is the central organizer of the network. It must be
    a controller. There can be only one primary controller in a Z-Wave network.

  • Inclusion — is the process of adding new Z-Wave devices into a network.

  • Exclusion — is the process of removing Z-Wave devices from the network.

  • Association — is a control relationship between a controlling device and
    a controlled device.

  • Wakeup Notification — is a special wireless message issued by a Z-Wave
    device to announces that is able to communicate.

  • Node Information Frame — is a special wireless message issued by a
    Z-Wave device to announce its capabilities and functions.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals