NOVUS N1500G Large Format Digital Panel Indicator Instruction Manual
- June 8, 2024
- Novus
Table of Contents
Indicator N1500G
UNIVERSAL INDICATOR – OPERATING MANUAL – V2.3x E
PRESENTATION
N1500G is a universal process indicator which accepts a large variety of input
signals and sensors. A five-digit LED display shows measured value and all
programming parameters.
Instrument configuration is achieved from the keyboard, without any hardware
change.
The user should read this manual thoroughly before using the instrument. It is
a fine electronic device and should be used accordingly for best results.
Some of the features of the basic version are:
- Universal input: Pt100, thermocouples, 4-20 mA, 0-50 mV and 0-5 Vdc
- 24 Vdc power supply for remote transmitters excitation
- Maximum and minimum memory
- Function Hold, Peak hold and Tare
Optionally may have:
- Process Variable retransmission in 0-20 mA or 4-20 mA
- RS485 MODBUS RTU serial communication
- Stabilized 10 V supply to feed load cell
- Digital input
1.1. FRONT PANEL IDENTIFICATION
Display: Shows process variable (PV) and the programming prompts.
ALM1 and ALM2: show alarm status.
INDEX key – This key is used to access the programming menu and prompts.
BACK key – This key is used to go back to the previously reached prompt in the
menu cycle.
UP / MAX key and DOWN / MIN – Used to increase and decrease parameters values,
these keys are also used to display maximum and minimum values stored in
memory.
Special FUNCTION key – This special function key is used for pre-programmed
functions as explained in the SPECIAL FUNCTION KEY section of this manual.
SPECIFICATIONS
-
Power: 100 to 240 Vac/dc ±10 %; 50/60 Hz
-
Max. Consumption: 10 VA
-
Internal resolution: 19500 levels, display: 12000 levels (-1999 a 9999)
-
Input sample rate: 5 per second
-
Accuracy: Thermocouples J, K, T and N: 0.25 % of span ±1 ºC.
Thermocouple E, R, S and B: 0.25 % of span ±3 ºC.
Pt100: 0.2 % of span
Current or linear voltage: 0.2% of the maximum range -
Minimum heating time: 15 minutes
-
Input impedance: 0-50 mV, Pt100 and thermocouples: >10 MΩ
0-5 V: >1 MΩ
0-20 mA, 4-20 mA: 22 Ω -
Pt100 measurement: 3 wire circuit. Current 0.170 mA.
PV Resolution of retransmission: 1500 levels, 550 Ω max. -
Relays: SPST-NA – 3A / 250 Vac
-
Digital Input: Dry contact or NPN open collector
-
Auxiliary Voltage Source: 24 Vdc (±10 %) / 25 mA máx.
-
Operating temperature: 0 to 55 °C, Maximum RH: 80 % up to 30 ºC.
For temperatures above 30 ºC, decrease 3 % per ºC. -
Approximate weight: 1 kg
-
Dimensions: 310 x 110 x 37 mm (C x A x P)
-
Protection: IP30 (when installed properly)
PROCESS VARIABLE INPUT – PV
The Process Variable input type should be keyboard programmed by the user according to the codes shown on Table 1 (refer to INPUT TYPE parameter “in.typ” ).
All input types are factory calibrated and no additional calibration is required. Thermocouples are calibrated to NBS standards. RTD’s are calibrated to DIN 43760 (α=0.00385).
ALARMS
The indicator features 2 alarm outputs in the basic version. Each alarm has a corresponding LED indicator in the front panel to show alarm status.
4.1. ALARM FUNCTIONS
The alarms can set to operate in six different functions: Sensor break, Low
Alarm, High Alarm, Differential Low, Differential High or Differential (Band).
These functions are shown in Table 2 and described as follows.
4.1.1. Sensor break
The alarm will go ON whenever the sensor breaks or is badly connected.
4.1.2. Low alarm
The alarm relay will go ON whenever the measured value is below the alarm set
point.
4.1.3. High alarm
The alarm relay will be ON whenever the measured value is above the alarm set
point.
4.1.4. Differential (Band)
For differential alarm 2 parameters must be set: Differential Alarm Reference
value ( ) or alarm setpoint and Alarm Deviation (Band).
For a positive deviation the alarm will switch on whenever the measured value
is out of the band defined as:
(**ALrEF**
– Deviation) and **(ALrEF**
+ Deviation)
For a negative deviation the alarm will be switched on whenever the measured
value is within the band defined above.
4.1.5. Differential Low
The alarm relay will be ON whenever the measured value is below the band
defined as:
(**ALrEF**
– Deviation)
4.1.6. Differential High
Alarm relay will be ON when the measured value is above the band defined as:
**(ALrEF**
+ Deviation)
4.2. ALARM TIMER
The alarms can be programmed to have timer functions where the user can set a
delayed alarm action, just one pulse in an alarm event, or an oscillator
function with sequential pulses. Table 3 shows these advanced functions. Times
T1 and T2 can be programmed from 0 to 6500 seconds (refer to item 8.2). Set 0
(zero) at the T1 and T2 prompt for a normal non-timer alarm operation.
Indicator N1500G
The LEDs alarm indicators will go ON whenever there is an alarm condition
regardless of the present alarm status which may be temporarily off because of
timer action.
4.3. ALARM INITIAL BLOCKING
The initial blocking option inhibits the alarm from being recognized if an
alarm condition is present when the controller is first energized. The alarm
will actuate only after the occurrence of a non alarm condition followed by a
new occurrence for the alarm. The initial blocking is disabled for the sensor
break alarm function.
SPECIAL FUNCTIONS
5.1. MAXIMUM AND MINIMUM
The indicator memorizes the measured maximum and minimum values (peak and
valley). These two values are shown by pressing either the or key. Pressing
both keys simultaneously will clear the memory for a new peak and valley
detection.
5.2. SPECIAL FUNCTION KEY AND DIGITAL INPUT
The F key and the optional digital input can execute special functions
according to the user selection.
These functions can be chosen independently to the F key or to the digital
input. A closed contact or a short circuit at terminals 12 and 13 is
recognized as activating the digital input. The special functions for the F
key and for the digital input are explained as follows.
5.2.1. Hold
The hold function freezes the measured value in the display. Each touch at the
F key or closing the digital input alternates from hold to normal mode.
Whenever the indicator is in the hold mode a “**HoLd**
” message is briefly
displayed to show the operator that the displayed value is the frozen value
and not the present reading.
5.2.2. Peak Hold
The indicator turns automatically to Peak Hold mode whenever the F key or the
digital input are programmed for “**PHoLd**
”
This operation mode makes the indicator display only the maximum reading value
from the time the key was pressed of the digital input was activated.
Each activation of the F key or digital input triggers a new Peak Hold cycle
and the display resets with a new peak value.
5.2.3. **rESEt**
(clears maximum and minimum)
This function works the same way as the and keys pressed simultaneously, as
explained in the
5.1 section. If this “**rESEt**
” function is programmed, for every touch of
the F key or activation of the digital input the memory will be cleared and a
new cycle of maximum and minimum will start.
5.2.4. **AL.oFF**
– Alarm blocking
This function allows the user to block or inhibit the alarm relays by pressing
the F key or by activating the digital input. Each touch of the key or
activation of the digital input will alternate the function from ON to OFF and
vice-versa. If an alarm situation occurs, the respective alarm status LEDs in
the front panel will light regardless of the relay alarm blocking status.
5.2.5. Tare
This function is used to zero the display. The tare residual values is
subtracted or added to the total measured value. This function is generally
used with load cells and strain gauges and applies to linear 4-20 mA, 0-50 mV
and 0-5 V inputs.
5.3. PROCESS VARIABLE RETRANSMISSION
As an option, the indicator can be supplied with an isolated 0-20 mAor 4-20 mA
analog output for Process Variable (PV) retransmission.
The PV values which define the range of the 0-20 mA or 4-20 mAretransmission
can be programmed by the user in the high and lowindication limits.
Note – PV retransmission does not take an action of the special Holdand Peak
Hold functions.
5.4. CUSTOMIZED LINEARIZATION
The indicator features three types of input signals that allow for custom
linearization, this is, the user can configure the device in order to obtain
accurate indications for electrical signals with nonlinear and ever
increasing characteristics.
The three types of input signal are: **c.0-50**
, **c.4-20**
and **c.0-5**
. When selected, the indicator creates the Custom Linearization
Cycle. The input signal must be divided in segments (maximum 19), defined
in order to minimize the error between the input signal and the corresponding
indication. In the Custom Linearization cycle the user finds the
parameterinp.01 which corresponds to the start point of the first segment and
must set the minimum value of the input signal. Then the parameter ovt.01 that
corresponds to the desired
indication for this first point. Soon afterinp.02 which is the starting point
of the second segment and ovt.02 the respective indication.
Note: The left side of the indicator is removable. It is fixed there a
label containing the connections.
6.2.1. Recommendations for Installation
-
Input signal wires should be laid out away from power lines and preferably inside grounded conduits.
-
Instrument mains (line) supply should be suitable for this purpose and should not be shared.
-
In controlling and monitoring applications, possible consequences of any system failure must be considered in advance. The internal alarm relay does not warrant total
protection. -
RC filters (47 Ω and 100 nF) are highly recommended for valve and contactor coils, etc.
6.2.2. Sensor or input signal connection
These connections should be properly done and terminals must be well
tightened. Thermocouples must be installed with proper extension or
compensation cables.
Pt100 RTDs must be 3-wire connected and the wires connected should have the
same electrical resistance (same wire gauge) for correct cable length
compensation. Four-wire RTDs can be connected by disconnecting the fourth
wire. Two-wire RTDs can be In Inp.o1 must always set the minimum value of the
selected signal type: 0.0 mV for c.0-50, 4.0mA for **c.4-20**
and **0.0 V**
for**c.0-5.**
For linearization’s that do not require all 19 segments,
simply set the maximum value of the selected input type to the last required
segment. Note: The Lower Indication Limit and Upper Indication Limit
parameters must be set before these Custom Linearization settings. In this
mode the sampling rate is 4 measurements per second.
INSTALLATION
6.1. PANEL ASSEMBLY
The indicator is composed of two parts: the fixing base and the front part
with main circuits. The base must be removed from the front and fixed onto a
wall by means of four designed holes as shown in Figure 1.
The front part is only attached to the fixing base after all electrical wire
connections are done.
6.2. ELECTRICAL CONNECTIONS
The internal electronics can be removed from the front panel without any cable
disassembly. The input signals and power connections are shown in Figure 2.
connected by shortening terminals 7 and 8 and connecting the Pt100 to
terminals 8 and 9.
OPERATION
For best results this indicator requires correct setting of parameters as
input type (T/C, Pt100, 4-20 mA, etc), alarms actuation point, alarm function,
etc.
These parameters are divided in five levels or groups of parameters which we
will refer to as CYCLES.
Cycle | Access |
---|---|
1- Work | free access |
2- Alarms | reserved access |
3- Functions
4- Configuration
5- Calibration
Table 4 – Parameters Cycles
The work cycle has free access. All other cycles require a certain combination
of key strokes to be accessed. The combination is:
and keys pressed simultaneously Within a certain cycle just press to go to the
following parameters. At the end of each cycle the display will go back to the
work cycle. At the desired prompt just press the or key to change this
parameter accordingly.
All changes are recorded in non-volatile memory as we move to next prompt.
After 25 seconds with no key pressed the indicator will return to the
measuring cycle (work cycle).
7.1. CYCLE PROTECTION
The values of parameters of a certain cycle can be protected against non-
authorized users.
The protected parameters can still be viewed but can not be changed.
To protect a cycle just press the and keys for 3 seconds at the beginning of
the referred cycle. To unlock this cycle (allow changes in parameters), press
the keys and for 3
seconds. The display will briefly blink confirming that the locking or
unlocking of the cycle.
PROGRAMMING THE INDICATOR
8.1. WORK CYCLE
This is the first and main cycle. At power up the indicator will display the
Process Variable (PV). The alarm setpoints are also displayed at this cycle.
To run through this cycle just press the key.
Whenever an alarm is set with differential function the respective alarm
setpoint is blocked (**SP.AL1, SP.AL2**
, …) and the display shows “diF” to
advise the operator that this is a configuration parameter and that the
respective deviation value must be programmed at the Alarms Cycle. The “ **AL.rEF**
” prompt will be displayed showing the reference value for the
alarm with differential function.
SCREEN | PARAMETER DESCRIPTION |
---|---|
Measure Shows the measured variable. For Pt100 or thermocouples the display |
will show the absolute temperature value.
For 4-20 mA, 0-50 mV and 0-5 V inputs the display shows the values defined in
the “in.LoL” and “in.HiL” prompts.
With the hold function programmed the display shows the frozen variable and
alternates with the message “HoLd”.
Likewise, with Peak Hold function programmed the high limit is displayed with
the “P.HoLd” prompt alternately.
Should any fault situation occur the indicator will display an error message
which can be identified at item 10 of this manual.
| Differential Alarm Reference Value – This prompt is shown only when there is
an alarm programmed with differential function.
| Set Points of Alarms 1 and 2 – Defines the operation point of each alarm
programmed with “Lo” or “Hi” function.
Note: When the alarms are programmed with differential function, the alarm
setpoint cannot be changed at this cycle and a “diF” message will be shown.
The SP differential (deviation) value is set at the Alarm Cycle.
8.2. ALARM CYCLE
| Alarm Function – Defines the alarms 1, 2, 3 and 4 function, as defined in
item 4.1
oFF : Alarm off
iErr : Broken or Shorted Sensor
Lo : Low value
Hi : High value
DiFL : Differential low
DiFH : Differential high
DiF : Differential
---|---
| Differential SP for Alarms 1 and 2 – Defines the deviation value from the
alarm setpoint in relation to the Reference Value defined in the “ALdiF”
prompt. Note: This value cannot be changed at this cycle for
alarms with non-differential function and the “AbS” is then displayed.
| Alarm Hysteresis
This is the difference from the measured value to the point where the alarm is
turned ON and OFF.
| Alarm Blocking
Should any alarm condition occur, each alarm can be disabled when energizing
the indicator. Refer to item 4.3.
| Time Alarms
The user can set delayed or sequential alarms as shown in table 3 by defining
times T1 and T2. To disable this function just set zero for T1 and T2.
8.3. FUNCTION CYCLES
| F KEY FUNCTION – Options are:
oFF – Key no used.
Hold – Hold PV
AL.oFF – Alarm disabled
rESEt – Resets Peak and Valley
PHoLd – Peak Hold
tArE – Tare zeroing
These functions are described in item 5.2.
---|---
| Digital Input Function – The same function
available for the F key:
**oFF - Hold - AL.oFF - rESEt - PHoLd - tArE**
Refer to item 5.2.
| Input Digital Filter – Adjustable from 0 to 20, this is used to reduce
instability of the measured value. 0 means the filter is off and 20 means
maximum
filtering. The higher the filter value the lower is the measured value
response.
| Display Offset – This a value which is added to the PV to offset any
measurement deviation or sensor error. The offset is shown directly in the
programmed engineering unit.
For °F measurements the null reference is at 32 °F.
| Baud Rate – Serial digital communication speed in bps.
Programmable: 1200, 2400, 4800, 9600 and 19200 bps.
| Communication Address – A number which identifies the instrument in a
multidrop network.
8.4. CONFIGURATION CYCLE
| Input Type – Selects the input signal or sensor type to be connected to the
PV terminals. Refer to Table 1.
Changing this parameter will change all other parameters related to PV and
alarms, therefore it should be the first parameter to be set.
---|---
| Decimal Point Position – Defines the decimal pointposition in the displayed
value. This applies to linearinput types 0 to 50mV, 4 to 20mA and 0 to 5V
asselected at the “in.tYP” prompt.
| Temperature Unit – Selects °C or °F indication. This prompt is not shown for
input types 0 to 50mV, 4 to 20mA and 0 to 5V as selected at the “in.tYP”
prompt.
| Square Root – This prompt is only shown for input types 0 to 50mV, 4 to 20mA
and 0 to 5V as selected at the “in.tYP” prompt.
Set “YES” and the square root will be applied to the measured value within the
limits programmed in “in.LoL” and “in.HiL”.
The display will show the low limit value should the input signal be below 1%
of the range.
| Input Low Limit – Sets the low limit for input type 0 to 50 mV, 4 to 20 mA
or 0 to 5 V. When the PV Retransmition is used this limit defines the
corresponding 4 mA (or 0 mA) in relation to the input value.
| Input High Limit – Sets the high limit for input type 0 to 50 mV, 4 to 20 mA
or 0 to 5 V. When the PV
Retransmition is used this limit defines the corresponding 20 mA in relation
to the input value.
| Scale Factor – Multiplies the displayed value by 10 to increase measured
range.
| Analog Output Type – Selects the analog output
type to either 0 to 20 mA or 4 to 20 mA.
---|---
8.5. CUSTOMIZED LINEARIZATION CYCLE
| Defines the initial and end analog input values for each custom segment
line. The values must be entered in the input signal unit: 0-50 mV, 4-20 mA or
0-5 V.
---|---
| Defines the corresponding indication that each custom segment is to show.
Values are expressed in the desired indication unit (within the Indication
Lower and Upper Limits).
8.6 CALIBRATION CYCLE
All input types are factory calibrated and field calibration is seldom
necessary. Should it be required the calibration should only be done by
experienced personnel.
If this cycle is accidentally accessed do not touch the or keys. Just press
the index key and go through all cycles until the display shows the main or
operation menu.
| Input Low Calibration – Sets the Process Variable
low calibration (offset). Several key strokes at or might be necessary to
increment one digit.
---|---
| Input Hi Calibration – Sets the Process Variable span calibration (gain).
Several key strokes at or might be necessary to increment one digit.
| Analog Output Low Calibration – Sets the analog current output low
calibration (offset).
| Analog Output Span Calibration – Sets the analog current output high
calibration (span).
| Cold Junction Calibration – Allows the user to adjust the calibration
directly in degrees for
achieving best results with thermocouples.
| Hardware Type – These parameters adapts the software to the hardware
available and should not be
changed by the user.
0 – No options
1 – With alarms 3 and 4
2 – With digital input
Figure 3 shows the sequence of levels and parameters presented in the indicator display. There are parameters that must be defined for each alarm available.
*Parameters that require definition for each available alarm.
DIGITAL COMMUNICATION
The indicator can be supplied with an asynchronous RS-485 digital
communication interface for master-slave connection to a host computer
(master).
The indicator works as a slave only and all commands are started by the
computer which sends a request to the slave address. The addressed unit
processes the command and sends back the answer.
Broadcast commands (addressed to all indicator units in a multidrop network)
are accepted but no response is generated.
9.1. CHARACTERISTICS
– RS-485 compatibility with two-wire bus from the host to up to 31 slaves in a
multidrop network topology.
– Up to 247 units can be addressed by the MODBUS RTU protocol.
– Maximum network distance: 1200 m.
– Time of indicator disconnection: Maximum of 2 ms after the delivery of the
last byte.
– Communication signals electrically isolated from the rest of the instrument.
– Baud rate: 1200, 2400, 4800, 9600, 19200, 38400 or 57600 bps.
– Number of data bits: 8, without parity or even parity – Number of stop bits:
1
– Time to start response transmission: 100 ms maximum delay after
acknowledging the command.
– Protocol: MODBUS (RTU)
9.2. RS485 INTERFACE: ELECTRICAL CONNECTION The RS-485 signals are:
D1 | D | D + | B | Bi-directional data line. | Terminal 16 |
---|---|---|---|---|---|
D0 | D – | A | Bi-directional inverted data line. | Terminal |
17
C| Optional connection that improves the performance of the
communication.| Terminal 18
GND
REDUCED REGISTERS TABLE FOR SERIAL
COMMUNICATION
Communication Protocol
The MOSBUS RTU slave is implemented. All configurable parameters can be
accessed for reading or writing through the communication port. Broadcast
commands are supported as well (address 0).
The available Modbus commands are:
01 – Read Coils
05 – Write Single Coil
03 – Read Holding Register
06 – Write Single Register
Holding register table
Follows a description of the usual communication registers. For full
documentation download the Registers Table for Serial Communication in the
N1500G section of our website –
www.novusautomation.com.
All registers are 16 bit signed integers.
Address | Parameter | Register Description |
---|---|---|
0000 | PV | Read: process variable. Write: not allowed. |
Range: the minimum value is in inlol seted and the maximum value is in inkil seted an the decimal point position depends of dppos.
0003| PV| Read: normalized Process Variable. Write: not allowed.
Maximum range: 0 to 62000.
PROBLEMS WITH THE INDICATOR
Connection errors or improper configuration will result in malfunctioning of the indicator. Carefully revise all cable connections and programming parameters before operating the unit. Some error messages will help the user identify possible problems.
Message | Possible Problem |
---|---|
Measured value is above the programmed sensor or input signal limit. | |
Measured value is below the programmed sensor or input signal limit. | |
….. | Open input. No sensor is connected or the sensor is broken. |
Pt100 cable resistance is too high or the sensor is badly connected. |
Different messages other than the ones above should be reported to the
manufacturer. Please inform the serial number if this should occur. the serial
number can be viewed at the display by pressing the BACK key for about 3
seconds.
The software version of the instrument can be viewed at the time the unit is
powered. The instrument might display false error messages when wrongly
programmed or when connected to a sensor for which it was not programmed.
WARRANTY