flex7 Lighting Connection & Control App User Guide
- June 4, 2024
- flex7
Table of Contents
- flex7 Lighting Connection & Control App
- ABOUT
- Wiring Connection when using flex7 control
- Wiring Connection when using hard-wired control
- Mains (230V) Switching
- Protected Extra Low Voltage (PELV) Switching
- Protected Extra Low Voltage (PELV) 2-Way Switching
- Protected Extra Low Voltage (PELV) Switching & Manual Dimming
- Protected Extra Low Voltage (PELV) Occupancy Control
- Protected Extra Low Voltage (PELV) Occupany Control (2 x Heads)
- Protected Extra Low Voltage (PELV) Occupancy & Daylight Linking To Window
- Protected Extra Low Voltage (PELV) Absence Control
- Protected Extra Low Voltage (PELV) Occupancy Control + Expansion Unit For
- Protected Extra Low Voltage (PELV) Absence Control + Tap-Off Unit With
- 2 x Protected Extra Low Voltage (PELV) Occupancy Control + Global
- 3 x Protected Extra Low Voltage (PELV) Occupancy Control + Corridor Hold
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
flex7 Lighting Connection & Control App
ABOUT
When you choose products from flex7 you can be certain that you’ve opted for a
system that offers unrivaled flexibility combined with the simplest of
installation methods.
The following pages detail a number of common lighting control applications
ranging from traditional mains rated (on/off) switching through to daylight
linking, along with a list of the flex7 products required to achieve each. The
scenarios may be diverse, but the only on-site termination required in all
cases is LNE to the Distribution Box, so standardizing the installation
process regardless of complexity. This is possible because at the heart of
every flex7 product is the fundamental of plug-in modularity which, as well as
reducing installation time, also offers a trouble-free upgrade path should
requirements change in the future; unplug the old device(s) and plug in the
new.
Wiring Connection when using flex7 control
Wiring Connection when using hard-wired control
If the application you’re looking for doesn’t appear in the following pages please contact us on 020 8580 1066. Our Technical team will be able to advise as to the most appropriate products to use in order to achieve the result you need.
Mains (230V) Switching
Control of the luminaires is from 1 location via a traditionally hard-wired
230V, 1-way switch; a small range of 230V plug-in switch drops are available
if preferred. On-site termination of the supply and 230V control wiring is
made as detailed, at the Distribution Box.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box | FSU08 |
4 X Standard (on/off)Luminaire Lead | FL3100LSHF5/W |
2 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
Protected Extra Low Voltage (PELV) Switching
Control of the luminaires is from 1 location via a flex7 plug-in switch
operating at PELV. The luminaires are manually switched on or off with a short
pulse of the switch. The use of flex7 control modules negate the need for RCD
and/or earthed mechanical protection of the switch drop. Additionally,
installation time is dramatically reduced as everything plugs-in, meaning only
the 4 conductors at the Distribution Box require on-site termination.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box | FSU08 |
1 X Switch Kit | FNS1000/U |
1 X Switch | FWS01/K/AT/W/WP |
1 X Switch Adaptor | FWSY/13/AT |
4 X Standard (on/off) Luminaire Lead | FL3100LSHF5/W |
2 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
Protected Extra Low Voltage (PELV) 2-Way Switching
Control of the luminaires is from 2 locations via flex7 plug-in switches
operating at PELV. The luminaires are manually switched on or off with a short
pulse of either of the switches. The use of flex7 control modules negates the
need for RCD and/or earthed mechanical protection of the switch drop. The
installation of strappers, usually required for 2-way / intermediate
switching, is not necessary. Both switches simply plug into the control
module. Additionally, installation time is dramatically reduced as everything
plugs in meaning only the 4 conductors at the Distribution Box require on-site
termination.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box | FSU08 |
1 X Switch Kit | FNS1000/U |
2 X Switch | FWS01/K/AT/W/WP |
1 X Switch Adaptor | FWSY/13/AT |
1 X Switch Drop Lead | FSL10/BL |
4 X Standard (on/off) Luminaire Lead | FL3100LSHF5/W |
2 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
Protected Extra Low Voltage (PELV) Switching & Manual Dimming
Control of the luminaires, both switching and manual dimming, is from 1
location via a flex7 plug-in switch operating at PELV. The luminaires are
manually switched on or off with a short pulse of the switch. Once on, the
luminaires can be dimmed or brightened by holding the switch until the desired
light level is reached. The use of flex7 control modules negate the need for
RCD and/or earthed mechanical protection of the switch drop. Additionally,
installation time is dramatically reduced as everything plugs in meaning only
the 4 conductors at the Distribution Box require on-site termination.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box | FSU08 |
1 X Switch Kit | FNS3000X/U |
1 X Switch | FWS01/K/AB/W/WP |
1 X Switch Adaptor | FWSY3/AB |
4 X Dimming Luminaire Lead | FL5100LSHF5/B |
2 X Dimming Maintained Emergency Luminaire Lead | FL6100LSHF5/R |
Protected Extra Low Voltage (PELV) Occupancy Control
Control of the luminaires is via a flex7 plug-in sensor head operating at
PELV. The luminaires are automatically switched on when movement is sensed.
After the room is vacated the luminaires switch off when the timeout period
has elapsed. Installation time is dramatically reduced as everything plugs-in,
meaning only the 4 conductors at the Distribution Box require on-site
termination.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box | FSU08 |
1 X Sensor Kit | FNS1200 |
4 X Standard (on/off) Luminaire Lead | FL3100LSHF5/W |
2 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
Protected Extra Low Voltage (PELV) Occupany Control (2 x Heads)
Control of the luminaires is via 2 flex7 plug-in sensor heads operating at PELV. The luminaires are automatically switched on when movement is sensed. After the room is vacated the luminaires switch off when the timeout period has elapsed. The decision to install 2 (or more) sensor heads as opposed to 1 may be made simply because the room is too large to be covered effectively by
- Alternatively, day to day use of the room may be such that occupants will
be desk based for long periods meaning fine movements need to be detected to
avoid luminaires switching off whilst the room is still occupied. Installation
time is dramatically reduced as everything plugs-in, meaning only the 4
conductors at the Distribution Box require on-site termination.
Note: emergency luminaires are tested via a hard-wired 230V key switch, often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION PART NO.
| 1 X Starter Box
FSU08
| 1 X Sensor Kit
FNS1200
| 1 X AUX Sensor Head
FNH/AUX
| 1 X Sensor Lead
FSL05
| 4 X Standard (on/off) Luminaire FL3100LSHF5/W Lead
| 2 X Maintained Emergency FL4100LSHF5/R
Luminaire Lead
Protected Extra Low Voltage (PELV) Occupancy & Daylight Linking To Window
Luminaires
Control of the luminaires is via a flex7 plug-in sensor head operating at
PELV. The 2 luminaires adjacent to the window are dimmable. The luminaires are
automatically switched on when movement is sensed. After the room is vacated
the luminaires switch off when the timeout period has elapsed. A second layer
of control, in the form of daylight linking, is applied to the dimmable
luminaires adjacent to the window. As the available natural light
increases/decreases during the day, the window luminaires’ light output will
also increase/decrease in order to maintain the optimum light level in that
area of the room. Installation time is dramatically reduced as everything
plugs-in, meaning only the 4 conductors at the Distribution Box require on-
site termination.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box | FSU08 |
1 X Sensor Kit | FNS3400X |
3 X Standard (on/off) Luminaire Lead | FL3100LSHF5/W |
1 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
1 X Dimming Luminaire Lead | FL5100LSHF5/B |
1 X Dimming Maintained Emergency Luminaire Lead | FL6100LSHF5/R |
Protected Extra Low Voltage (PELV) Absence Control
Control of the luminaires is via a flex7 plug-in sensor head and switch, both
operating at PELV. The luminaires are manually switched on with a short pulse
of the switch, after which they remain on whilst movement is sensed. After the
room is vacated the luminaires switch off when the timeout period has elapsed.
The use of flex7 control modules negate the need for RCD and/or earthed
mechanical protection of the switch drop. Additionally, installation time is
dramatically reduced as everything plugs-in, meaning only the 4 conductors at
the Distribution Box require on-site termination.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box | FSU08 |
1 X Sensor Kit | FNS1200/U |
1 X Switch | FWS01/K/AT/W/WP |
1 X Switch Adaptor | FWSY3/AB |
4 X Standard (on/off) Luminaire Lead | FL3100LSHF5/W |
2 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
Protected Extra Low Voltage (PELV) Occupancy Control + Expansion Unit For
Extra Luminaires
2 of the luminaires have been added at a later date to the original 6,
resulting in the Distribution Box being too small for the new layout. A flex7
Expansion Box is plugged directly into the end-cap socket of the original box,
instantly increasing the number of available outlets. The 2 boxes now operate
as 1. A range of expansion leads are available if the installation would
benefit from the 2 boxes being remote from each other. Control of the
luminaires is via a flex7 plug-in sensor head operating at PELV. The
luminaires are automatically switched on when movement is sensed. After the
room is vacated the luminaires switch off when the timeout period has elapsed.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box | FSU08 |
1 X Expansion Unit | FXU04 |
1 X Sensor Kit | FNS1200/U |
1 X Switch | FWS01/K/AT/W/WP |
1 X Switch Adaptor | FWSY/13/AT |
6 X Standard (on/off) Luminaire Lead | FL3100LSHF5/W |
2 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
Protected Extra Low Voltage (PELV) Absence Control + Tap-Off Unit With
Protected Extra Low Voltage (PELV) Occupancy Control For Next Room
Originally 1 large office. Reconfigured to create 2 separate spaces, requiring
individual control; absence for the Office; occupancy for the Store Cupboard.
A flex7 tap-off box is plugged into the original box via a tap-off lead. The
boxes now share the same supply, but require separate flex7 control modules.
Control of Office luminaires is via a flex7 plug-in sensor head and switches,
all operating at PELV. The luminaires are manually switched on with a short
pulse of either switch. They remain on whilst movement is sensed. After the
room is vacated the luminaires switch off when the timeout period has elapsed.
Control of Store Cupboard luminaires is via a flex7 plug-in sensor head
operating at PELV. The luminaires are automatically switched on when movement
is sensed. After the room is vacated the luminaires switch off when the
timeout period, has elapsed.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box | FSU08 |
1 X Tap-Off Unit | FTU04 |
1 X Tap-Off Lead | FT4150LSHF5/B |
1 X Sensor Kit | FNS1200 |
1 X Switch Lead | FWSY3/AB |
1 x Switch Drop Lead | FSL10/BL |
1 X Sensor Kit | FNS1200/U |
2 X Switch | FWS01/K/AT/W/WP |
1 X Switch Adaptor | FWSY/13/AT |
5 X Standard (On/Off) Luminaire Lead | FL3100LSHF5/W |
3 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
2 x Protected Extra Low Voltage (PELV) Occupancy Control + Global
Emergency Test
An Office and adjoining Store Cupboard, each protected by different devices at
the distribution board (could be different phases), requiring individual
occupancy control, but a single key switch to facilitate emergency test across
both circuits. Each space has its own flex7 starter Distribution Box with a
separate 3-core supply (LNE) back to the distribution board; no separate
emergency live is required. Control of the Office and the Store Cupboard
luminaires is via separate flex7 plug-in sensor heads operating at PELV. The
luminaires are automatically switched on when movement is sensed. After the
room is vacated the luminaires in that room switch off when the timeout period
has elapsed. The plug-in switch drop is connected to a latching key switch
located next to the office door and operates at PELV. The switch affects the
separate emergency relay in both networked control modules, simultaneously
initiating the emergency test across both separate circuits.
Note: emergency control modules can be configured so that during a test
all connected luminaires are isolated from the supply or only emergency
luminaires are isolated leaving non-emergencies fully operational.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box (8-way) | FSU08 |
1 X Starter Box (4 way) | FSU04 |
2 X Control Module | FNC2000/E |
2 X Sensor Head | FNH200 |
2 X Link Lead | FSL05 |
1 X Switch Drop Lead | FSW10 |
1 X Netwok Lead | FNL05 |
2 X Network Adaptor | FNY/Y |
5 X Standard (On/Off) Luminaire Lead | FL3100LSHF5/W |
3 X Maintained Emergency Luminaire Lead | FL4100LSHF5/R |
3 x Protected Extra Low Voltage (PELV) Occupancy Control + Corridor Hold
Two Offices, either side of a central Corridor, all protected by different
devices at the distribution board (could be different phases); all three
requiring individual occupancy control. Control of both Offices and Corridor
luminaires is via separate flex7 plug-in sensor heads operating at PELV. The
luminaires are automatically switched on when movement is sensed. After the
room is vacated the luminaires in that room switch off when the time-out
period has elapsed. The addition of a plug-in Corridor Hold facility means
that the corridor luminaires are held on whilst either of the Offices are
occupied. Crucially, movement detected in the corridor has no effect on the
Office luminaires.
Note: emergency luminaires are tested via a hard-wired 230V key switch,
often located in close proximity to the distribution board.
Wiring Connection
DESCRIPTION | PART NO. |
---|---|
1 X Starter Box (6-way) | FSU06 |
2 X Starter Box (4-way) | FSU04 |
3 X Control Module | FNC2000 |
3 X Sensor Head | FNH200 |
3 X Link Lead | FSL05 |
3 X Network Lead | FNL05 |
1 X Corridor Hold Unit | FCH8/2 |
7 X Standard (On/Off)
Luminaire Lead
| FL3100LSHF5/W
1 X Maintained Emergency Luminaire Lead| FL4100LSHF5/R
flex7 Ltd
Ruscombe Business Park Ruscombe Lane
Twyford RG10 9LR
www.flex7.co.uk |
info@flex7.co.uk
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>