QwikSwap® X1 & X3 Troubleshooting Steps
QT6100 OEM Constant Torque ECM w PSC Board
PROBLEM| SOLUTION| |
---|---|---|---
I don’t know if I need to use the R terminal on the QwikSwap Board (X1 or
X3).| Use of the R terminal on the QwikSwap (X1 or X3) in most installations
is optional (some installations will require the use of the R terminal if the
air handler fan control board outputs a DC voltage or if there is a resistor
in the control wiring). Connecting the R terminal activates a delay that keeps
the fan running for 3 minutes after the thermostat tells it to shut off. If
you want this delay connect the R terminal to the 24 VAC terminal
on the low voltage transformer (typically the red wire that also goes to the
thermostat R terminal) and remove the jumper next to the R terminal.
I connected the R
terminal but now the QwikSwap (X1 or X3) will not turn off.| Connecting the R
terminal activates the 3 minute delay after break feature. Sometimes the
blower control board in the air handler has an additional delay that adds to
the
3 minute delay of the QwikSwap. If you wish to disable the 3 minute delay on
the QwikSwap, install the jumper on the two pin header next to the R terminal.
I have read all of the troubleshooting steps but I still cannot solve the
problem I am having.| Using insulated test leads carefully measure and record
the voltage across the terminals listed below (measure for both AC and DC) and
call:
Mainstream Engineering for technical support
(321-631-3550).
Measure Across
These Terminals| Normal
Measured Voltage “Expected”Voltage
C and 1
(if there is a wire on 1)| | 20-30 AC or DC
C and 2
(if there is a wire on 2)| | 20-30 AC or DC
C and 3
(if there is a wire on 3)| | 20-30 AC or DC
C and 4
(if there is a wire on 4)| | 20-30 AC or DC
C and 5
(if there is a wire on 5)| | 20-30 AC or DC
C and R
(if there is a wire on R)| | 20-30 AC
L and N| | 120-240 VAC
Speed and COM| | 120-240 VAC
For more details or information about QwikSwap
visitwww.qwik.com
QwikProducts® and QwikSwap® are registered trademarks of Mainstream
Engineering Corporation, Rockledge, Florida 32955,
321-631-3550
• © 2022 Mainstream Engineering Corporation
• All QwikProducts® are made in the USA. Patents Pending
Mainstream Engineering Corporation
1-800-866-3550
www.qwik.com
5010162_REV-B / 1201820002
Documents / Resources
|
QwikProducts QT6100 OEM Constant Torque ECM w PSC
Board
[pdf] Instructions
QT6100 OEM Constant Torque ECM w PSC Board, QT6100, OEM Constant Torque ECM w
PSC Board, Constant Torque ECM w PSC Board, Torque ECM w PSC Board, ECM w PSC
Board, PSC Board, Board
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>