Schneider Electric SpaceLogic SE8000 Room Controllers Instruction Manual
- June 3, 2024
- Schneider Electric
Table of Contents
Schneider Electric SpaceLogic SE8000 Room Controllers Instruction Manual
Safety Information
Important Information
Read these instructions carefully and inspect the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
⚠ This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
⚠ DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
⚠ WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in
death or serious injury.
⚠ CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this signal word.
Please Note
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
Lua4RC Programming for SE8000
SE8000 Room Controllers can run custom applications designed to meet specific
customer requirements. These scripts, referred to as Lua4RC scripts, can be
developed for Integrators, or by qualified Integrators. Lua4RC adds a layer of
programming on top of the embedded control logic of a SE8000 Room Controller.
The script running on the Room Controller has the ability to override
parameters set by the embedded application. With this added flexibility, you
can adapt the control logic of the SE8000 Room Controllers to meet the
specific requirements of your projects.
This section gives an overview of the basic functions of the Lua language. It
is not an exhaustive and complete tutorial on the Lua language.
Accessing SE8000 Room Controller Database
When writing a Lua4RC script, the keyword “ME” is used to access the objects
in the local database. For example, a line that reads “ME.AV25 = 10” in a Lua
script would set the value of the AV25 object as 10.
The following object types are available:
- AI (Analog Input)
- AO (Analog Output)
- AV (Analog Value)
- BI (Binary Input)
- BO (Binary Output)
- BV (Binary Value)
- MSI (Multi-state Input)
- MV (Multi-state Value)
- CSV (Character String Value)
Notes:
- A list of each point available, along with the description and possible values can be found in the SE8000 Room Controllers BACnet Integration Guide.
- When accessing Binary Objects (BI, BO, BV), the return values are limited to 0 and 1, and not
true’ or
false’.
Lua4RC Scripts
There are 2 distinct locations to store custom Lua scripts in a SE8000 Room Controller, each having different characteristics and limitations:
Standard Lua Library
The SE8000 Lua environment uses LUA 5.1. Refer to the following for additional information: http://www.lua.org/manual/5.1/manual.html#5 for an introduction to the basics of Lua programming. http://www.lua.org/manual/5.1/ provides more general details on the Lua language. Only basic functions and mathematical functions are implemented. Other libraries (advanced string manipulation, table manipulation, input and output facilities, operating system facilities, and debug libraries) are not available.
Lua Functions and Tools
These functions offer basic control over common Room Controller applications frequently used in most installations.
tools.switch()
Switch function (on-off with deadband). Simulates the operation of a
conventional ON-OFF thermostat. It also provides a deadband function, so an
Object does not continuously switch ON and OFF based on a specific value.
output (0 or 1) =tools. switch( output, input-expr, off-expr, on-expr).
ME.BO28 = tools.switch(ME.BO28, ME.AO21, 0, 15) –W1(BO28) will go (ON at 15%
PI_Heat) then (OFF at 0% PI_Heat)
The “switch” function is the equivalent of:
tools.scale()
tools.scale(variable,offset,x1,y1,x2,y2). This function returns the linear
interpolation between two points. The function can also add the offset value
to the final result if desired.
ME.AO123 = tools.scale(ME.AO21, 0, 0, 2, 100, 10) –UO11(AO123) 2-10Vdc will follow the 0-100% PI_Heat (AO21)
Scripting Best Practices
This section provides an overview of best practices when writing Lua4RC scripts.
Variable Declaration
Variable declarations should always be made at the beginning of a script and contained within an “init” statement. This is done to optimize CPU usage, processing time, proper initialization of values and is a general scripting good practice. The below shows an example.
Priority Management
Lua4RC accesses various points of the Room Controller using BACnet naming
convention and priorities. The default priority of the Room Controller’s
internal control sequence is 17. When writing a Lua4RC script, the default
write priority is priority 16. As a result, the internal control is overridden
by LUA commands such as “ME.AV25 = 10”. Apply caution when using priorities
other than the default value as this could result in some values being
permanently overridden. To write to another priority, an array is used. The
example below would write a value of 20 to AV25, using priority 8:
ME.AV25_PV[8] = 20
To release this specific priority, you can set it to nil:
ME.AV25_PV[8] = nil
To access the relinquish default (the Room Controller’s internal logic
application priority), priority 17 can be used.
ME.AV25_PV[17] = 30
NOTICE
PRIORITY LEVELS Priority levels 1, 2, 3 and 17 (Relinquish Default) are
stored in the non-volatile (EEPROM) memory of the Room Controller.
- This means the stored values will remain in the memory after a power cycle. It is necessary to perform a factory reset of the Room Controller to reset these values.
- Each location in the EEPROM memory is limited to 1 million (1,000,000) writes, so care must be taken to minimize changes written to priorities stored in EEPROM. Failure to do so will damage the device.
-
* Do not write values that change regularly to priority levels stored in EEPROM. Use other priority levels that are stored in RAM only and support infinite read/write cycles.
- Do not write to EEPROM locations on every cycle of the script (every 1 second). If you must write data in priority levels stored in EEPROM, do so less frequently (e.g. every 15 minutes).
- Do not “NIL” a value before writing to it. This is unnecessary and causes two writes to the EEPROM location. For example, avoid the following:
- ME.MV16_PV[17] = nil
- ME.MV16_PV[17] = 2
Failure to follow these instructions can result in equipment damage.
-
Script / BACnet Variables
To interface between the Lua engine of the Room Controller and the BACnet
integration, 12 variables are made available: AV25 to AV30 and AV225 to AV230.
These can be read and written from the Lua engine and BACnet. Since these
variables are also visible and configurable from the Room Controller’s HMI,
they can be exposed to the User for quick customization or parametrization of
points. To change the name of one or more of these variables, the _Desc
property of each point can be modified from a Lua script. This will be visible
both in the HMI and BACnet. To change the name of AV25 (for example) to Time
delay (s) the following script can be used:
ME.AV25_Desc = “Time delay (s)”
Minimum / Maximum and Increment Values
To restrict the values of AV25-AV30 to a certain range, the minimum and maximum acceptable values can be adjusted by modifying the _Min and _Max properties of each object.
Note : For Firmware version 1.4.2, AV30 has a known issue where _Min,
_Max and _Inc will not function. It is also possible to modify the increment
property of a point. This will be used when adjusting the point on the Room
Controller. An increment of 10 means the Room Controller will cycle between
0,10,20, etc. when using the up/down arrows, while an increment of 5 will
cycle between 0,5,10,15, etc.
Note: If the increment is set to 0, the parameter is read-only. If the
parameter is set to nil, the present value is not displayed.
User Interface
This section describes using the Lua screens on the SE8000 Room Controllers.
Access Lua Configuration Menu
- Press and hold the top-center area of the Room Controller screen for 2 seconds.
- Navigate to the Setup page 2/2 by pressing the arrow button and select Lua.
Lua Screen 1/4
Lua page 1/4 presents the first 10 lines of the script.
Lua Screen 2/4
This screen gives the option to run or stop the Lua script. When the Room
Controller is started up and a script is loaded, the script is automatically
in Running status, shown in the Program status field.
If the script is not in Running status, the Program error field shows if there is an error in the script. If the field shows anything other than No error, there are errors in the loaded script and it does not run. If there are errors, a message explaining the error(s) is shown in the Debug log.
The most frequent error is, for example: “Unable to write to AV39_Present_Value[16]” and most of the time it is because the value is out of range. Writing a temperature in °F like Heating Setpoint = 73 when the Network units are set to default degree Celcius results in 73°C being out of range. To resolve this issue, set Network Units to °F (MV6=2) in the INIT section before writing to any temperature points.
The Debug log can also be used for printing values from the script. The Debug log window can hold a maximum of 78 characters on 3 lines. The Debug log is refreshed every time the script loops back on itself.
Lua Screens 3/4 and 4/4
The SE8000 Lua environment offers 12 AV objects that can be used in the
scripts. These objects are regular BACnet AV objects and are accessible
directly from the screen. The values can be set in the user interface, and the
user interface sets the value at the lowest level of priority (relinquish
default level 17).
Any value gets overridden by a value set in a script or via BACnet. When the
value is overridden, the value’s text shows red and it is not possible to
change it in the interface. To release the override, the script or the BACnet
client must set the value priority to nil.
IMPORTANT: Even if the script is not currently running, the AV25 to AV30 and AV225 to AV230 variables, if used by the script, get overridden and cannot be changed by the user.
Lua4RC Applied Examples
The section shows some common applied examples using Lua4RC.
Pre-commission Points and Parameters
This allows to quickly set all the necessary configuration points without
having to use the HMI of the Room Controller at the time of installation. In
this example, the points that are likely to be modified by the installer (or
end-user) are set at priority 17 (relinquish default), while others are left
at the default priority of 16.
Note: The script will set the included values each time the room
controller starts.
Custom Button Action
The section shows how the icon and functionality of the 5th button of the Room Controller’s home screen (bottom right) can be changed via MV115. This specific example will change the logo of the 5th button to Lighting and set the function to No Function. It will then toggle physical point Binary Output 8 (BACnet point BO98) when the button is pressed.
Note: The last button press variable (AV92) must be reset to 0 in the script.
The below tables show the various buttons along with descriptions.
For reference purposes, the below shows the possible values for the last button pressed value (AV92):
- 1: Button 1 (lower-left)
- 2: Button 2
- 3: Button 3
- 4: Button 4
- 5: Button 5 (lower-right)
- 6: setpoint down-arrow
- 7: up-arrow
- 8: config (upper middle)
- 9: schedule (upper left or right corner)
- 10: another spot on the home screen
- 25 to 30: AV25..30 on the custom page
- 35: home button in custom page(s)
Configure Lua Parameter Page Title
This script will change the title of the Lua parameter page to “Humidification”. The name will appear when the custom button is pressed and requires the button function to be set to “custom”.
Remote Wired Humidity Sensor
All SE8000 Room Controllers have an internal Relative Humidity sensor. They can also use a remote wireless Zigbee sensor instead, but they do not have a dedicated input for a wired remote Relative Humidity sensor. This LUA will configure UI24 Universal Input as 0-10 Vdc. Monitor the input to see if there is at least 0.5 Vdc (5% RH) on UI24. If that is the case, the LUA will automatically use this reading instead of the internal sensor (the LUA will update the value only if it is different from the previous value (COV)). If the reading is less than 0.2 Vdc (2% RH), the LUA will release the reading to the internal value as if the remote sensor is absent or defective.
SE8650 Active Dehumidification
This LUA will do “active” dehumidification on a call for dehumidification, The Fan will be forced On as well as the Y1 and Y2 Cooling stages and W1 Heating stage. Dehumidification is also conditional to Occupancy, System Mode and Room Temperature.
Miscellaneous Examples
Reverse 0-100% input to 10-0 Vdc output
ME.AO123 = 10 – (ME.AO21/10)) — Modulating based on Heating Demand
Convert a 0-100% input to 10-2 Vdc output
ME.AO123 = 10 – (0.8 * (ME.AO21/ 10)) — Modulating based on Heating Demand
Reverse Y1 output
ME.BO26_PV[16] = (1 – ME.BO26_PV[17])
Average Room_Temp and Remote (use UI20 (RS) for the remote sensor)
if init == nil then
ME.MV145 = 2 init = true
end –Set Room_Temp sensor = Local (this line goes in the “init” section)
ME.AV100_PV[16] = (ME.AV100_PV[17] + ME.AV105) / 2
www.schneider-electric.com/buildings