AMETEK 910 Ultrasonic Level Switch Instruction Manual
- June 5, 2024
- AMETEK
Table of Contents
AMETEK 910 Ultrasonic Level Switch Instruction Manual
Model 910
Read this Manual Before Installing
This manual provides information on the Echotel®
Model 910 Ultrasonic Liquid Level Switches. It is important that all
instructions are read carefully and followed in sequence. Detailed
instructions are included in the Installation section of this manual.
Conventions Used in this Manual
Certain conventions are used in this manual to convey specific types of
information. General technical material, support data, and safety information
are presented in narrative form. The following styles are used for notes,
cautions, and warnings.
NOTES
Notes contain information that augments or clarifies an operating step. Notes
do not normally contain actions. They follow the procedural steps to which
they refer.
Cautions
Cautions alert the technician to special conditions that could injure
personnel, damage equipment, or reduce a component’s mechanical integrity.
Cautions are also used to alert the technician to unsafe practices or the need
for special protective equipment or specific materials. In this manual, a
caution box indicates a potentially hazardous situation which, if not avoided,
may result in minor or moderate injury.
WARNINGS
Warnings identify potentially dangerous situations or serious hazards. In this
manual, a warning indicates an imminently hazardous situation which, if not
avoided, could result in serious injury or death.
Safety Messages
The EchotelModel 910 is designed for use in Category II, Pollution Degree 2
installations. Follow all standard industry procedures for servicing
electrical and computer equipment when working with or around high voltage.
Always shut off the power supply before touching any components. Although high
voltage is not present in this system, it may be present in other systems.
Electrical components are sensitive to electrostatic discharge. To prevent equipment damage, observe safety procedures when working with electrostatic sensitive components.
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and (2) This device must
accept any interference received, including interference that may cause
undesired operation.
WARNING! Explosion hazard. Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Low Voltage Directive
For use in Category II installations. If equipment is used in a manner not
specified by manufacturer, protection provided by equipment may be impaired.
Warranty
All Magnetrol Model 910 Level Switches are warranted free of defects in
materials or workmanship for eighteen months from the date of original factory
shipment.
If returned within the warranty period; and, upon factory inspection of the control, the cause of the claim is determined to be covered under the warranty; then, Magnetrol will repair or replace the control at no cost to the purchaser (or owner) other than transportation.
Magnetrol shall not be liable for misapplication, labor claims, direct or consequential damage or expense arising from the installation or use of equipment.
There are no other warranties expressed or implied, except special written warranties covering some Magnetrol products.
Quality Assurance
The quality assurance system in place at Magnetrol guarantees the highest
level of quality throughout the company. Magnetrol is committed to providing
full customer satisfaction both in quality products and quality service.
The Magnetrol quality assurance system is registered to ISO 9001 affirming its commitment to known international quality standards providing the strongest assurance of product/service quality available.
Copyright © 2022 AMETEK Magnetrol USA, LLC.
All rights reserved.
Performance specifications are effective with date of issue and are subject to change without notice. Magnetrol® reserves the right to make changes to the product described in this manual at any time without notice. Magnetrol makes no warranty with respect to the accuracy of the information in this manual.
1.0 Introduction
Echotel® Model 910 Level Switches utilize ultrasonic contact technology for measuring level in clean liquid applications.
1.1 Principle of Operation
The Model 910 Level Switch uses ultrasonic energy to detect the presence or
absence of liquid in a transducer gap. The basic principle behind ultrasonic
contact technology is that high-frequency sound waves are easily transmitted
across a transducer gap in the presence of a liquid medium, but are severely
attenuated when the gap is dry. The Model 910 uses an ultrasonic frequency of
3 MHz to perform this liquid level measurement in a wide variety of process
media and application conditions.
The transducer uses a pair of piezoelectric crystals that are encapsulated in epoxy at the tip of the 316 stainless steel transducer. The crystals are made of a ceramic material, that vibrates at a given frequency when subjected to an applied voltage. The transmit crystal converts an electrical signal from the Model 910 electronics into an ultrasonic signal. When liquid is present in the gap, the receive crystal is able to sense the ultrasonic signal from the transmit crystal and convert it back to an electrical signal. This signal is sent to the electronics to indicate the presence of liquid in the transducer gap. When there is no liquid present, the ultrasonic signal is attenuated, and is not detected by the receive crystal.
2.0 Installation
2.1 Unpacking
Unpack the instrument carefully. Inspect all units for damage. Report any
concealed damage to carrier within 24 hours. Check the contents of the packing
slip and purchase order. Check and record the serial number for future
reference when ordering parts.
Model #
Serial #
2.2 Electrostatic Discharge (ESD)
Handling Procedure
Magnetrol electronic instruments are manufactured to the highest quality
standards. These instruments use electronic components that may be damaged by
static electricity present in most work environments.
The following steps are recommended to reduce the risk of component failure due to electrostatic discharge.
- Ship and store circuit boards in anti-static bags. If an antistatic bag is not available, wrap the board in aluminum foil. Do not place boards on foam packing materials.
- Use a grounding wrist strap when installing and removing circuit boards. A grounded workstation is recommended.
- Handle circuit boards only by the edges. Do not touch components or connector pins.
- Make sure that all electrical connections are completely made and none are partial or floating. Ground all equipment to a good, earth ground.
2.3 Preliminary Operational Check
After unpacking and before installation, perform the
following operational check on the unit in a nonhazardous
area:
- Apply proper operating voltage to terminals L1 and L2/N. Power supply ground should be connected to the green ground screw in housing base.
- Fill a suitable container with liquid.
- Place transducer gap in the liquid. The relay output should actuate.
- Remove transducer from the liquid. The relay output should de-actuate. In case of malfunction, consult Section 3.1, Troubleshooting on page 7.
Caution: This unit contains CMOS electronics which may become damaged by static electricity. Do not touch any semiconductor devices unless you are properly grounded.
2.4 Mounting
Figure 2
Typical Mounting Orientations
Model 910 level switches are shipped as integral units with the electronics assembled to the transducer. They may be mounted in a variety of positions as shown in Figures 2 through 5.
Figure 4
Horizontal Mounting
Proper orientation of the transducer gap will provide maximum performance in difficult applications. When the switch is mounted horizontally, the transducer gap must be turned vertical to allow proper drainage of the liquid media. See Figures 2 and 4.
Screw transducer into the opening using pipe compound or thread tape. If flanged, bolt unit to mating flange with proper gasket.
Caution: Never tighten unit on the tank connection by turning the housing. Use a wrench on the transducer mounting nut flats. Use thread tape or suitable pipe compound on the threads. Do not overtighten.
When installed in a nozzle or pipe, the transducer gap must extend into the tank at least one inch beyond the inside tank wall. Refer to Figure 5.
2.5 Wiring
2.5.1 Power
Power connections are made at the two-position terminal block labeled TB1
within the electronics enclosure. Use of 14–22 AWG wire is recommended.
NOTE: Observe all applicable electrical codes and proper wiring procedures.
- Make sure the power is turned off.
- Unscrew and remove the housing cover.
- Prevent moisture seepage into housing by installing an approved seal-drain fitting in the conduit run leading to the unit.
- Route wires into housing.
- Connect ground wire to green ground screw located in the base of the housing. DO NOT proceed until ground connection is made.
- After grounding is complete, connect the power leads to proper terminals as follows:
Caution: In hazardous areas, do not power the unit until the conduit is
sealed and the enclosure cover is screwed down securely.
7. Dress wiring to ensure no interference or contact with cover or circuit
board components.
2.5.2 Relay
Model 910 switches have a number of possible relay wiring options. The table
below lists the relay contact positions for all possible combinations of power
failure, condition of the transducer gap, and fail-safe jumper position. The
user must decide which combinations constitute fail-safe and alarm conditions,
and then select the appropriate relay wiring and fail-safe position.
1. Run relay output wiring to the terminal blocks labeled TB2 and TB3. Ensure that the load to be controlled is within the relay’s rated capacity as shown in Section 3.3.2, Electrical on page 10.
2. Select high or low fail-safe using the P1 jumper.
P1 Fail-safe Jumper
3. Replace housing cover. Installation is complete.
Caution: Never tighten unit to the tank connection by turning the
housing. Use a wrench on the transducer mounting nut flats. Use thread tape or
suitable pipe compound on threads. Do not overtighten.
3.0 Reference Information
3.1 Troubleshooting
Caution: In hazardous areas, do not remove housing cover until power is disconnected and atmosphere is determined to be safe.
3.1.1 No signal with level change
a. Verify power and control circuit wiring.
b. Make sure liquid is filling the transducer gap.
c. Check for dense foam on surface or dried product in the gap. Unit will not
function properly if either condition exists.
d. Check probe wiring for proper connection into PC board at J1 & J2 (phono
jack models) or TB4 & TB5 (terminal block models).
e. If control circuit does not actuate, consult factory.
3.1.2 Calibration
Model 910 switches do not require field calibration. The set point is not
adjustable.
3.1.3 Switch chatter
a. Check voltage to make sure it is within tolerances shown in Section 3.3.2.
b. Check for turbulence. Relocate control or isolate from turbulence.
c. Check for excessive aeration.
d. Consult factory.
3.1.4 Control output will not de-actuate
a. Check transducer for plugged gap.
b. Check for dense foam or liquid in gap.
c. If control circuit does not de-actuate, consult factory.
3.2 Agency Approvals
These units are in compliance with the EMC-directive 2014/30/EU, the PED- directive 2014/68/EU and the ATEX directive 2014/34/EU.
Explosion Proof / Dust Ignition Proof
US/Canada: FM19US0170X/FM20CA0034X
Class I, Div 1, Groups B, C, D T6
Class II, III, Div. 1 Groups E, F, G T6
SINGLE SEAL
Type 4X
US: Class I, Zone 1 AEx db IIC T6 Gb
Canada: Ex db IIC T6 Gb
SINGLE SEAL
-40ºC ≤ Ta ≤+70ºC
Probes > 60 inches Ta = -20°C ≤ Ta ≤ 70°C
IP66
Flame Proof
ATEX – FM20ATEX0005X
Integral:
II 2 G Ex db IIC T6 Gb
-40ºC ≤ Ta ≤+70ºC
Probes > 60 inches Ta = -20°C ≤ Ta ≤ 70°C
IP66
IEC IECEx FMG20.0004X
Ex db IIC T6 Gb
-40ºC ≤ Ta ≤+70ºC
Probes > 60 inches Ta = -20°C ≤ Ta ≤ 70°C
IP66
Non-Incendive
US/Canada:
US: Class I Div. 2, Groups A, B, C D T5
Class II, III, Div. 2 Groups F and G T5
SINGLE SEAL
-40ºC ≤ Ta ≤+70ºC
Probes > 60 inches Ta = -20°C ≤ Ta ≤ 70°C
IP66
The following approval standards are applicable:
FM3600:2018, FM3611:2004, FM3615:2018, FM3810:2005, ANSI/NEMA 250:1991, EN
60079-0:2012+A11:2013, EN 60079-1:2014, CSA C22.2 No. 25:2014, CSA C22.2 No.
30:2020, CSA C22.2 No. 94:R2011, CSA C22.2 No. 60079-0:2019, CSA C22.2 No.
60079-1:2016, CSA C22.2 No. 60529:2005, ANSI/UL60079-0:2019,
ANSI/UL60079-1:2015 and EN 60529:1991 + A1:2000+A2:2013, CSA C22.2 No. 0.4
2017, CSA C22.2 No. 0.5 2016, IEC 60079-0:2017, IEC 60079-1:2014, IEC
60529:2013, ANSI/IEC 60529:2004
3.2.1 Special Conditions of Use
- The Echotel 910 Level Transmitter is only for use with the Echotel 910 probe.
- To maintain the T6 temperature code care shall be taken to ensure the “Enclosure Temperature” does not exceed 70°C.
- The risk of electrostatic discharge shall be minimized at installation, following the direction given in the instructions.
- For Installation with ambient temperature of 70°C, refer to the manufacturer’s instructions for guidance on proper selection of conductors.
- The flamepaths of the equipment are not intended to be repaired. Consult the manufacturer if repair of the flamepath joints is necessary.
3.3 Specifications
3.3.1 Physical
inches (mm)
Aluminum sand cast housing (Dual 3⁄4″ NPT conduits)
Aluminum sand cast housing (Dual 3⁄4″ NPT conduit with 1″ BSP process connection)
3.3.2 Electrical
3.4 Replacement Parts
3.5 Model Numbers
- 1″ (code 001) minimum with NPT process connections, 2″ (code 002) minimum with hygienic or ASME flanged process connections.
- 3 cm (code 003) minimum with NPT process connections, 5 cm (code 005) minimum with 1″ BSP, or hygienic or ASME flanged process connections.
- Consult factory for longer lengths.
ASSURED QUALITY & SERVICE COST LESS
Service Policy
Owners of Magnetrol may request the return of a control or any part of a
control for complete rebuilding or replacement. They will be rebuilt or
replaced promptly. Controls returned under our service policy must be returned
by Prepaid transportation. Magnetrol will repair or replace the control at no
cost to the purchaser (or owner) other than transportation if:
1. Returned within the warranty period; and
2. The factory inspection finds the cause of the claim to be covered under
the warranty.
If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be charges for labor and the parts required to rebuild or replace the equipment.
In some cases it may be expedient to ship replacement parts; or, in extreme cases a complete new control, to replace the original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the control to be replaced. In such cases, credit for the materials returned will be determined on the basis of the applicability of our warranty.
No claims for misapplication, labor, direct or consequential damage will be allowed.
Return Material Procedure
So that we may efficiently process any materials that are returned, it is
essential that a “Return Material Authorization” (RMA) number be obtained from
the factory, prior to the material’s return. This is available through a
Magnetrol local representative or by contacting the factory. Please supply the
following information:
- Company Name
- Description of Material
- Serial Number
- Reason for Return
- Application
Any unit that was used in a process must be properly cleaned in accordance with OSHA standards, before it is returned to the factory.
A Material Safety Data Sheet (MSDS) must accompany material that was used in any media.
All shipments returned to the factory must be by prepaid transportation. All replacements will be shipped F.O.B. factory.
NOTE: See Electrostatic Discharge Handling Procedure on page 4.
Caution:
WARNING:
DO NOT OPEN WHEN ENERGIZED
WARNING:
POTENTIAL ELECTROSTATIC CHARGING HAZARD– SEE INSTRUCTIONS
WARNING:
DO NOT OPEN WHEN AN EXPLOSIVE GAS ATMOSPHERE IS PRESENT. KEEP ASSEMBLY TIGHTLY
CLOSED WHEN IN OPERATION. COVER JOINTS MUST BE CLEANED BEFORE REPLACING COVER.
705 Enterprise Street • Aurora, Illinois 60504-8149 USA
630.969.4000 • info.magnetrol@ametek.com •
magnetrol.com
Copyright © 2022 AMETEK Magnetrol USA, LLC