STAHL 209268 Pac Carrier Installation Guide

June 3, 2024
STAHL

STAHL 209268 Pac Carrier

STAHL-209268 Pac-Carrier-FIG- \(2\)

WebCode 9195A

The 9195 series pac- Carrier is a cost- effective solution allowing Ex i field devices to be connected to common I/ O modules of distributed control systems and programmable logic controllers. The extremely robust carrier is suitable for 8 or 16 standard ISpac isolators and can process 32 signals, including a combination of Ex i and non- Ex i signals. It can be adapted to accommodate new I/ O modules at any time. The carrier can be combined with the 9192 series HART Mux

  • Prefabricated system cables for field terminal boards (FTB) make it quick and easy to install – simply snaps onto a DIN rail or mounting plate
  • Can be used with the Emerson Delta V, Schneider Foxboro/ Tricon, Honeywell C300, Siemens ET200M and ET200F, Yokogawa Centum VP and ProSafe- RS
  • All ISpac isolators 91xx can be used in the pac- Carrier

Technical Data

Explosion Protection

Application range (Zones)| 2
IECEx gas certificate| IECEx BVS 10.0042 X
IECEx gas explosion protection| Ex ec nC IIC T4 Gc
ATEX gas certificate| BVS 03 ATEX E 213 X
ATEX gas explosion protection| E II 3 G Ex ec nC IIC T4 Gc
FMus certificate| FM16US0122X
cFM certificate| FM16CA0067X
Marking cFMus| Class I, Div. 2, Groups A,B,C,D; Class I, Zone 2, Group IIC

T4 at Ta = 70°C

See Doc. 91 956 01 31 1

EAC certificate| EAES_RU_S-DEHA91B00100_20
EAC gas explosion protection| 7 2 Ex nA nC IIC T4 Gc X
Certificates| ATEX (BVS), Brazil (ULB), Canada (FM), EAC (ENDCE), IECEx (BVS), India (PESO), SIL

(exida), USA (FM)

Ship approval| CCS, EU RO MR (DNVGL)
Notes| CCC, UKCA certificate available from 2022 onward
Functional Safety
SIL| 3
Electrical Data
Type of signal| DI, DO, AI, AO
Number of channels| 32
LFD relay| Yes
I/O type| any
Redundancy| No
Connections| HART interface via HART multiplexer 9192
Electrical Data

HART-multiplexer connection| Yes
Number of channels field device interface

(HART)

| 8,16, 32
Fuse| 2 x TR5; T 2 A; exchangeable, for primary and redundant supply
Auxiliary Power
Auxiliary power| 24 V DC
Nominal voltage Vnom| 24 V DC
Redundant supply| yes, decoupled with diodes
Polarity reversal protection| Yes
Input
Line fault and loss of power signalization| Contact (30 V / 100 mA) closed to ground in case of fault

pac-Bus, floating contact (30 V / 100 mA)

Output
Fault message contact switching capacity| 30 V / 100 mA
Ambient Conditions
Ambient temperature °C| -20 °C … +70 °C
Ambient temperature °F| -4°F … +158°F
Storage temperature °C| -40 °C … +80 °C
Storage temperature °F| -40°F … +176°F
Max. relative humidity| 95%
Use at the height of| < 2000 m
Electromagnetic compatibility| Tested to the following standards and regulations: EN 61326-1 Use in industrial environ-

ment; NAMUR NE 21

Mechanical Data
Degree of protection (IP)| IP00
Number of slots| 16
Grid dimension| 17.6 mm
Width| 292 mm
Width, inches| 11.5 in
Height| 150 mm
Height, inches| 5.91 in
Length| 155 mm
Length, inches| 6.1 in
Weight| 0.843 kg
Weight| 1.86 lb
Construction drawing
 |
---|---
 | 1.          Carrier for 8 or 16 modules (32 channels)

2.          Labeling for module, slot and carrier

3.          Ejector mechanism (with screw driver)

4.          Redundant and fused supply

5.          Power supply failure and line fault signalling via relay

6.          System specific PCB

7.          System specific plugs

8.          Signal duplication and / or connection HART-Multiplexer

9.          For hat-rail or mounting plate

10.       Integrated pac-Bus for power supply and line-fault signalling

11.       Secure snap-in mechanism, without tool

12.       Single slot, any signal mixture

Mounting / Installation|
Mounting type| DIN rail or wall mounting
Mounting orientation| horizontal or vertical
Mounting orientation| Vertical

Horizontal

Connection type| Screw terminal
Min. rigid conductor cross section| 0.14 mm²
Max. rigid conductor cross section| 1.5 mm²
Min. flex conductor cross section| 0.14 mm²
Max. flex conductor cross section| 1.5 mm²
Connection cross-section AWG| 28 – 16

Technical Drawings

Subject to AlterationsSTAHL-209268 Pac-Carrier-FIG-
\(4\)

Dimensional Drawings

(All Dimensions in mm [inches]) – Subject to AlterationsSTAHL-209268 Pac-
Carrier-FIG- \(5\)

Accessories

Noni- Ex I termination module

Non-Ex i termination module Art. No.
**** The termination module is used to integrate non-Ex i field circuit into

the system integration solution pac-carrier type 9195.

In such a way it enables a flexible mixture of Ex i and non-Ex i field circuits.

| 165683

We reserve the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding

R. STAHL, INC
13259 N. Promenade Blvd.
Stafford, TX 77477
Tel. +1 800 782 4357
US Email US : sales.us@r-stahl.com
Email CAN : sales.ca@r-stahl.com
rstahl.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals