AcraDyne iAC4EGV-T Assignable I O Gen IV ACE iAC Controller Instructions
- June 4, 2024
- AcraDyne
Table of Contents
AcraDyne iAC4EGV-T Assignable I O Gen IV ACE iAC Controller
Assignable I/O
The Gen IV controller supports assignable I/O.
Buses: The controller is divided up into buses. Each bus has a set of inputs
and a set of outputs. Currently the controller supports the following buses.
Bus Number | Bus |
---|---|
1 | Physical I/O |
2 | Fieldbus (Anybus module) I/O |
3 | Modbus TCP |
4 | Ethernet/IP |
All assignments have a bus, element, and bit configuration to define its location in the system. The bus value needs to be set from the list above. The element and bit define the location in the bus. The first element on the bus is 0 and goes up the last legal element for the given bus. The bits in each element is referenced from 0(LSB) to 31(MSB).
Inputs
All input assignments have a Bus, Element, and Bit configuration to define its location in the system. Along with the basic configuration many also have other configuration(s) that allow its behavior to be modified to suit the application.
| | | Supported Feature| | | | Controllers|
---|---|---|---|---|---|---|---|---
Bus
|
Element
|
Bit 0-31
| Polarity N.O./N.C.|
Width
|
Offset
|
iEC
|
iAC
|
iPC
|
iBC
|
iBC-Z
Do Nothing| √| √| √| | | | √| √| √| √| √
Start| √| √| √| √| | | √| | | |
Stop| √| √| √| √| | | √| √| √| √|
Reverse| √| √| √| √| | | √| | | |
Disable| √| √| √| √| | | √| √| √| |
Reset Job| √| √| √| √| | | √| √| √| √| √
Select PSet| √| √| √| | √| √| √| √| √| √|
Select Job| √| √| √| | √| √| √| √| √| √| √
Select Job Sequence| √| √| √| | √| √| √| √| √| √| √
Disable Assembly| √| √| √| √| | | √| | | |
Set ID| √| √| √| | √| | √| √| √| √| √
Set ID (word swap)| √| √| √| | √| | √| √| √| √| √
Set Date/Time| √| √| √| | √| | √| √| √| √| √
Set Date/Time (word swap)| √| √| √| | √| | √| √| √| √| √
Verify PSet| √| √| √| | √| √| √| √| √| √| √
Clear Results| √| √| √| √| | | √| √| √| √| √
Log Change| √| √| √| | √| √| √| √| √| √| √
Decrement Batch| √| √| √| √| | | √| √| √| √| √
Increment Batch| √| √| √| √| | | √| √| √| √| √
Click Wrench| √| √| √| √| | | √| √| √| √| √
Bypass Stops| √| √| √| √| | | √| √| √| √| √
Verify Job Sequence| √| √| √| | √| √| √| √| √| √| √
ASCII ID| √| √| | | | | √| √| √| √| √
Abort Job| √| √| √| √| | | √| √| √| √|
Remote Start| √| √| √| √| | | √| | | |
Remove Lock on Reject| √| √| √| √| | | √| √| √| √|
Dual Start Interlocked| √| √| √| √| | | √| | | |
Decrement Job| √| √| √| √| | | √| √| √| √| √
Increment Job| √| √| √| √| | | √| √| √| √| √
Decrement PSet| √| √| √| √| | | √| √| √| √| √
Increment PSet| √| √| √| √| | | √| √| √| √| √
Decrement Job Sequence| √| √| √| √| | | √| √| √| √| √
Increment Job Sequence| √| √| √| √| | | √| √| √| √| √
Polarity
When the polarity is set to N.O. the input is considered active high (24vdc for physical inputs and logic 1 for all network type buses). When the polarity is set to N.C. the input is considered active low (0vdc for physical inputs and logic 0 for all network type buses).
Width and Offset
For multiple bit inputs (for example “Select PSet”) the width variable defines
the number of bits the assignment will read for its input. This allows the
input size to be restricted to a few bits saving space for other assignments.
The offset variable allows a fixed value to be added to the read value.
For example to use bits 4 & 5 of the physical inputs to select parameter sets
1-4 the assignment would look like…
Select PSet
Bus| 1| For the physical bus
Element| 0| For the first element on the bus
Bit| 4| For the starting bit location
Width| 2| To span the two bits 4 & 5
Offset| 1| Adding 1 to the read input value so we get…
Binary 00 = 1
Binary 01 = 2
Binary 10 = 3
Binary 11 = 4
Input Assignments
Do Nothing
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
---|---|---|---|---|---|---
√| √| √| | |
The “Do Nothing” assignment will run do nothing if it is active or inactive.
Start
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| √| |
The “Start” assignment will run the tool while the input is active. Start is
available for the Physical I/O bus only.
Stop
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| √| |
The “Stop” assignment will stop the tool if it is running and prevent it from
being started.
Reverse
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
---|---|---|---|---|---|---
√| √| √| √| |
The “Reverse” will put the controller in disassembly mode while the input is
active.
Disable
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| √| |
The “Disable” will disable the tool while the input is active. It will not
stop a fastening cycle that is progress.
Reset Job
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| √| |
On the transition of inactive to active the “Reset Job” assignment will reset
the active job.
Select PSet
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| | √| √
The “Select PSET” input will select the parameter set according to the input
value. Uses the width parameter limit the width of the input bits read. The
minimum width is 1 and the maximum is 8.
After the input is read the offset parameter will be added to the value do get the actual parameter set number. Selecting an invalid parameter set number will disable the tool.
Select Job
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| | √| √
The “Select Job” input will select the job number according to the input
value. Uses the width parameter limit the width of the input bits read. The
minimum width is 1 and the maximum is 8.
After the input is read the offset parameter will be added to the value do get the actual job number. Selecting an invalid job number will disable the tool.
Select Job Sequence| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| | √| √
The “Select Job Sequence” input will select the job sequence number according
to the input value. Uses the width parameter limit the width of the input bits
read. The minimum width is 1 and the maximum is 8. After the input is read the
offset parameter will be added to the value do get the actual job sequence
number. Selecting an invalid
job sequence number or a sequence that is already complete will disable the tool.
Disable Assembly| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
| | Set Date/ Time (word swap)| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
√| √| √| √| | | √| √| √| | √| |
The “Disable Assembly” assignment will disable the tool in the assembly
direction. It will not disable the tool in disassembly or tube nut homing. It
w ill not stop a fastening cycle that is progress.| The “Set Date/Time (word
swap)” assignment is the same as the “Set Date/Time” assignment except the
high and low words (16bit) are swapped prior to evaluation. This is to correct
the mixed endianness of some PLC. See the “Set Date/Time” for behavior.
|
Set ID
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| | √|
Verify PSet
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
The “Set ID” assignment will set the ID to an integer value of the input
value. The width can be set from 1 to 32 bits. The input value will read as an
integer value and an ASCII string with leading zeros will be produced and
passed to the ID recognition system.
The length of the string is based on the width of the assignment. The string will always be sized to accommodate the maximum value of the input. For example a width setting of 16 can have an integer value of 0-65535 so the produced ID would
be “00000” to “65535” (always five character long).
√| √| √| | √| √|
The “Verify PSET” input will compare the current parameter set to the input
value. Uses the width parameter limit the width of the input bits read. The
minimum width is 1 and the maximum is 8. After the input is read the offset
parameter will be added to the value do get the actual parameter set number.
If the parameter set input value does not match the current parameter of the
controller the tool will be disabled.|
| Width Length of
setting ID string ID value
Clear Results
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
| 1 – 3| 1| “0” – “n”| √| √| √| √| | |
The “Clear Results” assignment will clear the latest results outputs (Ok, Nok,
etc.) on the same bus.|
| 4 – 6| 2| “00” – “nn”
| 7 – 9| 3| “000“ – “nnn”
| 10 – 13| 4| “0000” – “nnnn”
Log Change
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
| 14 – 16| 5| “00000” – “nnnnn”
√| √| √| | √| √|
| 17 – 19| 6| “000000” – “nnnnnn”
The “Log Change” assignment will add entries to the controller event log when
the input changes.|
| 20 – 23| 7| “0000000” – “nnnnnnn”
| 24 – 26| 8| “00000000” – “nnnnnnnn”
| 27 – 29| 9| “000000000” – “nnnnnnnnn”
Decrement Batch| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
| 30 – 32| 10| “0000000000” – “nnnnnnnnnn”
√| √| √| √| | |
The “Decrement Batch” assignment will remove the latest OK rundown from the
current running JOB. This will cause the JOB count to be reduced by one.|
Set ID (word swap| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| | √|
The “Set ID (word swap)” assignment is the same as the “Set ID” assignment
except the high and low words (16bit) are swapped prior to evaluation. This is
to correct the mixed endianness of some PLC. See the “Set ID” for behavior.
Increment Batch| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
√| √| √| √| | |
The “Increment Batch” assignment will insert a manual rundown into the current
sequence of the current JOB. This will cause the JOB count to increment by
one.|
Set Date/ Time| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| | √|
The “Set Date/Time” assignment will set the date and time of the controller.
The width can be set from 1 to 32 bits but should always be set to 32 to get
the correct results. The input value will be read as the number of seconds
since 00:00:00 January 1, 1970 (POSIX time or Epoch time). If the input value
changes and it is non-zero the date and time of the controller will be set to
the new value.
Click Wrench| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
√| √| √| √| | |
The “Click Wrench” assignment is the same as “Increment Batch” with the
addition of a programmable torque value.|
Bypass Stops
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
| | Dual Start Interlocked| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
√| √| √| √| | | √| √| √| √| | |
The “Bypass Stops” assignment removes most stop conditions, allowing the tool
to be ran in an
override type condition. Hardware faults, stop and disable inputs are not removed.
|
The “Dual Start Interlocked” assignment will run the tool if the interlock
conditions are met. Dual Start Interlock is available for the Physical IO bus
only. The Dual Start Interlocked input works in combination with the Physical
input assigned to the ‘Start’ input. The Dual Start Interlocked is only
available for iEC controllers.|
Verify Job Sequence| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
√| √| √| | √| √|
Setup
• Only 1 Start Input and 1 Dual Start Interlocked Input should be assigned.
• Controller->Tool Setup –> Start Input
Configuration:
○ The Start Input Source Must be set to ‘Start From IO’.
○ Latching throttle is disabled for Dual Interlocked Start.
Dual Start Interlocked – Operation
• The tool will not run unless both inputs are activated within two seconds of each other.
• If the two second timer times out, both inputs must be deactivated to reset the timer.
• If either input is deactivated the tool stops.
• To restart the tool, both inputs must be deactivated then reactivated within two seconds of each other.
Tubenut Tool Homing Exceptions for Dual Start Interlocked functionality
• If controller’s tubenut homing configuration is
set to RELEASE:
○ Deactivating either, or both, of the inputs will initiate the homing sequence.
○ Homing will continue until sequence is complete.
• If controller’s tubenut homing configuration is
set to RELEASE AND REPRESS:
○ Deactivating either of the inputs, then activating both inputs will initiate the homing sequence.
○ Homing will continue while both inputs are active.
○ If either input is deactivated, before homing is complete, the tool will stop, and homing will pause until both inputs are reactivated.
○ To restart tool, after homing is complete, both inputs must be deactivated, then reactivated within two seconds of each other.
|
The “Verify Job Sequence” input will compare the current Job sequence to the
input value. Uses the width parameter limit the width of the input bits read.
The minimum width is 1 and the maximum
is 8. After the input is read the offset parameter will be added to the value do get the actual Job sequence number. If the Job sequence input value does not match the current Job sequence of the controller the tool will be disabled.
|
ASCII ID
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
√| √| | | | |
The “ASCII ID” assignment will set the ID to the of the input (ASCII) value.
This assignment consumes the entire element so the Bit is not used. It also
has a length parameter to set the length of the input in bytes. The input
value will be passed directly to the ID recognition system.|
Abort Job
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
√| √| √| √| | |
The “Abort Job” assignment aborts the job and disables the tool. A job reset
is required to enable the tool for the next job.|
Remote Start
| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
√| √| √| √| | |
The “Remote Start” assignment will run the tool while the input is active.
Remote Start is available for non-physical I/O buses.|
Remove Lock on Reject| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
|
√| √| √| √| | |
The “Remove Lock on Reject” assignment unlocks the tool if locked on reject,
re-enabling the tool.|
|
|
Decrement Job| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
---|---|---|---|---|---|---
√| √| √| √| |
The “Decrement Job” assignment will decrement the Job Number, selecting the
last job if decrementing past the first one.
Increment Job| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| √| |
The “Increment Job” assignment will increment the Job Number, selecting the
first job if incrementing past the last one.
Decrement PSet| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| √| |
The “Decrement PSet” assignment will decrement the PSet Number, selecting the
last PSet if decrementing past the first one.
Increment PSet| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| √| |
The “Increment PSet” assignment will increment the PSet Number, selecting the
first PSet if incrementing past the last one.
Decrement Job Sequence| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| √| |
The “Decrement Job Sequence” assignment will decrement the Job sequence,
selecting the last job sequence if decrementing past the first one.
Increment Job Sequence| ****
Bus
| ****
Element
| ****
Bit 0-32
| Polarity N.O./N.C.| ****
Width
| ****
Offset
√| √| √| √| |
The “Increment Job Sequence” assignment will increment the Job sequence,
selecting the first job if incrementing past the last one.
Outputs
All output assignments have a Bus, Element, and Bit configuration to define its location in the system. Along with the basic configuration many also have other configuration(s) that allow its behavior to be modified to suit the application.
| | | | | Supported Feature| | | | | | Controller|
---|---|---|---|---|---|---|---|---|---|---|---|---
| | | | Mode Normal, Timed, Flashed| Time| Width| Offset| Input Bus| Input
Element| Input Bit| iEC| iAC| iPC| iBC| iBC-Z
| | | Polarity N.O./
N.C.
| | | | | | | |
Bus
|
Element
| Bit 0-32| | | | | | | | | | |
Ok| √| √| √| √| √| | | | | | | √| √| √| √| √
Nok| √| √| √| √| √| | | | | | | √| √| √| √| √
Torque Ok| √| √| √| √| √| | | | | | | √| √| √| √| √
Torque Nok| √| √| √| √| √| | | | | | | √| √| √| √| √
Low Torque| √| √| √| √| √| | | | | | | √| √| √| √| √
High Torque| √| √| √| √| √| | | | | | | √| √| √| √| √
Angle Ok| √| √| √| √| √| | | | | | | √| √| √| √| √
Angle Nok| √| √| √| √| √| | | | | | | √| √| √| √| √
Low Angle| √| √| √| √| √| | | | | | | √| √| √| √| √
High Angle| √| √| √| √| √| | | | | | | √| √| √| √| √
Fastening
Complete
| √| √| √| √| √| | | | | | | √| √| √| √| √
In Cycle| √| √| √| √| √| | | | | | | √| √| √| |
Fastening Aborted| √| √| √| √| √| | | | | | | √| √| √| √| √
Fastening Stopped| √| √| √| √| √| | | | | | | √| √| √| √| √
Batch Complete| √| √| √| √| √| | | | | | | √| √| √| √| √
Job Complete| √| √| √| √| √| | | | | | | √| √| √| √| √
Error| √| √| √| √| √| | | | | | | √| √| √| √| √
Tool Start Switch| √| √| √| √| √| | | | | | | √| | | |
Tool Push to Start
Switch
| √| √| √| √| √| | | | | | | √| | | |
Tool MFB| √| √| √| √| √| | | | | | | √| | | |
Tool Enabled| √| √| √| √| √| | | | | | | √| √| √| √| √
Tool Running| √| √| √| √| √| | | | | | | √| | | |
Service Indicator| √| √| √| √| √| | | | | | | √| √| √| | √
ToolsNet
Connected
| √| √| √| √| √| | | | | | | √| √| √| √| √
Open Protocol
Connected
| √| √| √| √| √| | | | | | | √| √| √| √| √
PFCS Connected| √| √| √| √| √| | | | | | | √| √| √| √| √
Running PSet
Number
| √| √| √| | | | √| √| | | | √| √| √| √| √
Running Job
Number
| √| √| √| | | | √| √| | | | √| √| √| √| √
External Controlled| √| √| √| | | | | | √| √| √| √| √| √| √| √
Tool In CCW| √| √| √| √| √| | | | | | | √| | | |
Tool In CW| √| √| √| √| √| | | | | | | √| | | |
Torque| √| √| √| | | | √| | | | | √| √| √| √| √
Torque (x10)| √| √| √| | | | √| | | | | √| √| √| √| √
Torque (x100)| √| √| √| | | | √| | | | | √| √| √| √| √
Angle| √| √| √| | | | √| | | | | √| √| √| √| √
Rundown Saved to
FTP Server
| √| √| √| | | | √| | | | | √| √| √| √| √
Fastener Removed| √| √| √| √| √| | | | | | | √| √| √| |
Spindle Ok| √| √| √| √| √| | | | | | | √| | | |
Spindle NOk| √| √| √| √| √| | | | | | | √| | | |
Spindle Fastening
Complete
| √| √| √| √| √| | | | | | | √| | | |
Pulses| √| √| √| | | | √| | | | | | √| √| | √
Pulses High| √| √| √| √| √| | | | | | | | √| √| | √
Pulses Low| √| √| √| √| √| | | | | | | | √| √| | √
Pulses NOk| √| √| √| √| √| | | | | | | | √| √| | √
Pulses Ok| √| √| √| √| √| | | | | | | | √| √| | √
ON| √| √| √| √| √| | | | | | | √| √| √| √| √
Job Aborted| √| √| √| √| √| | | | | | | √| √| √| √|
Tool In Use| √| √| √| √| | √| | | | | | √| √| √| √| √
Barcode Scanned| √| √| √| √| | | | | | | | √| √| √| √| √
Start Trigger Active| √| √| √| √| | | | | | | | √| | | |
Polarity
When the polarity is set to N.O. the output will be high when it is active (24vdc for physical outputs and logic 1 for all network type buses). When the polarity is set to N.C. the output will be low for active (0vdc for physical inputs and logic 0 for all network type buses).
Mode
Normal
In the “Normal” mode the output will track the state of the assignment (while
still observing the polarity setting). If the polarity is set N.O. and the
assignment has an active output the output will be on and stay on till the
assignment goes to inactive.
Timed
In the “Timed” mode the output will come on when the assignments state goes
active and go off based on the time value or the assignment state going
inactive (while still observing the polarity setting). Figure 3: Timed
Mode (assignment deactivates before time expires)
Flash
In the “flash” mode the output will flash at the time rate while the
assignments state is active (while still observing the polarity setting).
Width and Offset
For multiple bit outputs (for example “Running PSet Number”) the width
variable defines the number of bits the assignment will output. This allows
the output size to be restricted to a few bits saving space for other
assignments.
The offset variable allows a fixed value to be added to the value before it is
output.
For example to use bits 4 & 5 of the physical outputs to indicate the selected
parameter set number 1-4 as binary 0-3 the assignment would look like…
Running PSet Number
Bus| 1| For the physical bus
Element| 0| For the first element on the bus
Bit| 4| For the starting bit location
Width| 2| To span the two bits 4 & 5
Offset| -1| Adding -1 to the read input value so we get…
1 = Binary 00
2 = Binary 01
3 = Binary 10
4 = Binary 11
Output Assignments
OK| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal, Timed,
Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
---|---|---|---|---|---|---|---|---|---|---|---
√| √| √| √| √| | | | | |
The “Ok” output assignment will go active at the completion of an acceptable
fastening. It will go inactive when the next fastening is started (the torque
exceeds the threshold value) or a Job reset.
Nok| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal, Timed,
Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Nok” output assignment will go active at the completion of an
unacceptable fastening. It will go inactive when the next fastening is started
(the torque exceeds the threshold value) or a Job reset.
Torque Ok| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Torque Ok” output assignment will go active at the completion of a
fastening that has an acceptable torque value. It will go inactive when the
next fastening is started (the torque exceeds the threshold value) or a Job
reset.
Torque Nok| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Torque Nok” output assignment will go active at the completion of a
fastening that has an unacceptable torque value. It will go inactive when the
next fastening is started (the torque exceeds the threshold value) or a Job
reset.
Low Torque| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Low Torque” output assignment will go active at the completion of a
fastening that has a low torque results. It will go inactive when the next
fastening is started (the torque exceeds the threshold value) or a Job reset.
High Torque| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “High Torque” output assignment will go active at the completion of a
fastening that has a high torque results. It will go inactive when the next
fastening is started (the torque exceeds the threshold value) or a Job reset.
Angle Ok| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Angle Ok” output assignment will go active at the completion of a
fastening that has an acceptable angle results. It will go inactive when the
next fastening is started (the torque exceeds the threshold value) or a Job
reset.
Angle Nok| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Angle Nok” output assignment will go active at the completion of a
fastening that has an unacceptable angle results. It will go inactive when the
next fastening is started (the torque exceeds the threshold value) or a Job
reset.
Low Angle| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Low Angle” output assignment will go active at the completion of a
fastening that has a low angle results. It will go inactive when the next
fastening is started (the torque exceeds the threshold value) or a Job reset.
High Angle| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “High Angle” output assignment will go active at the completion of a
fastening that has high angle results. It will go inactive when the next
fastening is started (the torque exceeds the threshold value) or a Job reset.
Fastening Complete| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
---|---|---|---|---|---|---|---|---|---|---|---
√| √| √| √| √| | | | | |
The “Fastening Complete” output assignment will go active at the completion of
a fastening. It will go inactive when the next fastening is started (the
torque exceeds the threshold value) or a Job reset.
In Cycle| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “In Cycle” output assignment will go active at the start of the fastening
cycle (the torque exceeds the threshold value). It will go inactive when the
fastening cycle ends.
Fastening Aborted| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Fastening Aborted” output assignment will go active at the completion of
a fastening that was aborted by the system. It will go inactive when the next
fastening is started (the torque exceeds the threshold value) or a Job reset.
Fastening Stopped| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Fastening Stopped” output assignment will go active at the completion of
a fastening that was stopped by the user. It will go inactive when the next
fastening is started (the torque exceeds the threshold value) or a Job reset.
Batch Complete| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Batch Complete” output assignment will go active at the completion of a
fastening that satisfies the bolt count of a Job sequence. It will go inactive
when the next fastening is started (the torque exceeds the threshold value) or
the job is reset.
Job Complete| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Job Complete” output assignment will go active at the completion of a
fastening that satisfies all the sequences. It will go inactive when the next
fastening is started (the torque exceeds the threshold value) or the job is
reset.
Error| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal, Timed,
Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Error” output assignment will be active while the controller has an
error.
Tool Start Switch| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Tool Start Switch” output assignment will reflect the state of the tools
start lever.
Tool Push to Start Switch| Bus| Element| Bit 0-32| Polarity N.O./N.C.|
Mode: Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element|
Input Bit
√| √| √| √| √| | | | | |
The “Tool Push to Start Switch” output assignment will reflect the state of
the tools push to start switch.
Tool MFB| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Tool MFB” output assignment will reflect the state of the tools
multifunction button.
Tool Enabled| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Tool Enabled” output assignment will be active if the tool is enabled.
Tool Running| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
---|---|---|---|---|---|---|---|---|---|---|---
√| √| √| √| √| | | | | |
The “Tool Running” output assignment will be active while the tool is running.
Service Indicator| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Service Indicator” output assignment will be active if the system is in
need of service.
ToolsNet Connected| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “ToolsNet Connected” output assignment will be active if the controller
has an active connection to a ToolsNet server.
Open Protocol Connected| Bus| Element| Bit 0-32| Polarity N.O./N.C.|
Mode: Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element|
Input Bit
√| √| √| √| √| | | | | |
The “Open Protocol Connected” output assignment will be active if the
controller has an active Open protocol connection.
PFCS
Connected
| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal, Timed, Flash|
Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “PFCS Connected” output assignment will be active if the controller has an
active PFCS connection.
Running PSet Number| Bus| Element| Bit 0-32| Polarity N.O./N.C.|
Mode: Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element|
Input Bit
√| √| √| | | | √| √| | |
The “Running PSet Number” output assignment will output the current PSet
number.
Running Job Number| Bus| Element| Bit 0-32| Polarity N.O./N.C.|
Mode: Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element|
Input Bit
√| √| √| | | | √| √| | |
The “Running Job Number” output assignment will output the current Job number.
External Controlled| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| | | | | | √| √| √
The “External Controlled” output assignment will reflect the state of an
input. Use the “Input Bus, “Input Element”, and “Input Bit” to specify the
input to reflect.
Tool in CCW| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Tool In CCW” output assignment will be active if the tool is put into
disassembly mode and inactive if the tool is in assembly mode.
Tool in CW| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Tool In CW” output assignment will be active when the is in assembly mode
and inactive if the tool is put into disassembly mode.
Torque| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal, Timed,
Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| | | | √| | | |
The “Torque” output assignment will output the final torque value of the most
recent rundown. The value will be cleared to 0 at the start of a new fastening
cycle or a Job reset. At the end of the fastening cycle the final torque will
be truncated to an integer and output.
Torque (x10)| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
---|---|---|---|---|---|---|---|---|---|---|---
√| √| √| | | | √| | | |
The “Torque (x10)” output assignment will output the final torque value of the
most recent rundown. The value will be cleared to 0 at the start of a new
fastening cycle or a Job reset. At the end of the fastening cycle the final
torque will be multiplied by 10, truncated to an integer and output.
Torque (x100)| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| | | | √| | | |
The “Torque (x100)” output assignment will output the final torque value of
the most recent rundown. The value will be cleared to 0 at the start of a new
fastening cycle or a Job reset. At the end of the fastening cycle the final
torque will be multiplied by 100, truncated to an integer and output.
Angle| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal, Timed,
Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| | | | √| | | |
The “Angle” output assignment will output the final angle value of the most
recent rundown. The value will be
cleared to 0 at the start of a new fastening cycle or a Job reset.
Rundown Saved to FTP Server| Bus| Element| Bit 0-32| Polarity
N.O./N.C.| Mode: Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input
Element| Input Bit
√| √| √| | | | √| | | |
The “Rundown Saved to FTP Server” output assignment will output the ID of the
last rundown that was saved to the FTP server.
Fastener Removed| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Fastener Removed” output assignment will go active when a fastener is
removed by the operator. The controller must be configured to report
disassembly for this output to work. It will go inactive when the next
fastening is started (the torque exceeds the threshold value) or a Job reset.
Spindle OK| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Spindle Ok” output assignment will go active at the completion of multi-
spindle fastening if all spindles have an OK. It will go inactive when the
next fastening is started (the torque exceeds the threshold value) or a Job
reset.
Spindle NOk| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Spindle NOk” output assignment will go active at the completion of multi-
spindle fastening if one or more of the spindles have an NOK. It will go
inactive when the next fastening is started (the torque exceeds the threshold
value) or a Job reset.
Spindle Fastening Complete| Bus| Element| Bit 0-32| Polarity N.O./N.C.|
Mode: Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element|
Input Bit
√| √| √| √| √| | | | | |
The “Spindle Fastening Complete” output assignment will go active at the
completion of multi-spindle fastening. It will go inactive when the next
fastening is started (the torque exceeds the threshold value) or a Job reset.
Pulses| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal, Timed,
Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| | | | √| | | |
The “Pulses” output assignment will output the pulse count value of the most
recent rundown. The value will be cleared to 0 at the start of a new fastening
cycle or a Job reset.
Pulses High| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Pulses High” output assignment will go active at the completion of a
fastening that has an pulse count that exceeds the high limit. It will go
inactive when the next fastening is started (the torque exceeds the threshold
value) or a Job reset.
Pulses Low| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
---|---|---|---|---|---|---|---|---|---|---|---
√| √| √| √| √| | | | | |
The “Pulses Low” output assignment will go active at the completion of a
fastening that has an pulse count that falls below the low limit. It will go
inactive when the next fastening is started (the torque exceeds the threshold
value) or a Job reset.
Pulses NOk| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Pulses Ok” output assignment will go active at the completion of a
fastening that has an acceptable pulse count. It will go inactive when the
next fastening is started (the torque exceeds the threshold value) or a Job
reset.
Pulses Ok| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Pulses NOk” output assignment will go active at the completion of a
fastening that has an unacceptable pulse count. It will go inactive when the
next fastening is started (the torque exceeds the threshold value) or a Job
reset.
ON| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal, Timed,
Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “ON” output assignment will be active when the controller is powered up
and remains active until power down.
Job Aborted| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| √| | | | | |
The “Job Aborted” output assignment will go active if a Job is aborted. It
will go inactive when the job is reset.
Tool In Use| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode: Normal,
Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| | √| | | | |
The “Tool In Use” output assignment will go active when the trigger is
pressed, whereupon a timer will restart. It
will go inactive when the specified time is reached without becoming active in between.
Barcode Scanned| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| | | | | | |
The “Barcode Scanned” output assignment will go active when a barcode is
scanned. The ID # (1-4) will activate the corresponding bit, if it is covered
by the number of bits configured. The maximum size is 4 bits. All bits will go
inactive when a tool reaches the InCycle threshold of a rundown or when they
are reset.
Start Trigger Active| Bus| Element| Bit 0-32| Polarity N.O./N.C.| Mode:
Normal, Timed, Flash| Time| Width| Offset| Input Bus| Input Element| Input Bit
√| √| √| √| | | | | | |
The ‘Start Trigger Active’ assignment will reflect the state of the active
Start Input configured to run the tool.
The ‘Start Trigger Active’ assignment will reflect the state of the active Start Input configured to run the tool.
Possible Start Inputs include:
- Start from IO
- Start
- Dual Start Interlocked
- Start from Tool Buttons
- Lever and/or PTS
- Dual Levers Interlocked
- Start from Master Tool
- Start from Remote Start
- Latched Throttle
Start Trigger Active is available for the iEC Controller Only.
CORPORATE HEADQUARTERS 10000 SE Pine Street Portland, Oregon 97216
Phone: (503) 254–6600
Toll Free: 1-800-852-1368
AIMCO CORPORATION DE MEXICO SA DE CV Ave. Cristobal Colon 14529
Chihuahua, Chihuahua. 31125
Mexico
Phone: (01-614) 380-1010
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>