STAHL 261410 9270 Series Switching Repeater Instruction Manual
- June 3, 2024
- STAHL
Table of Contents
**STAHL 261410 9270 Series Switching Repeater Instruction Manual
**
Safety notes
Installation notes
- The device is an associated apparatus (category 1) which belongs to the “Intrinsic Safety” ignition protection class and can be installed in Ex zone 2 as a category 3 device. It meets the requirements of EN 60079- 0:2012+A11:2013, EN 60079-11:2012, EN 60079-15:2010 or IEC 60079-0 ed. 6.0, IEC 60079-11 ed. 6.0, and IEC 60079-15 ed. 4.0.
- Installation, operation, and maintenance may only be carried out by qualified electricians. Follow the installation instructions as described. When installing and operating the device, the applicable regulations and safety directives (including national safety directives), as well as general technical regulations, must be observed. For the safety data, refer to this document and the certificates (EU examination certificate and other approvals if appropriate).
- The device must not be opened or modified. Do not repair the device yourself, replace it with an equivalent device. Repairs may only be carried out by the manufacturer. The manufacturer is not liable for damage resulting from violation.
- The IP20 degree of protection (IEC/EN 60529) of the device is intended for use in a clean and dry environment (degree of pollution 2, IEC/EN 60664-1). Do not subject the device to mechanical and/or thermal loads that exceed the specified limits.
- The device complies with the EMC regulations for industrial areas (EMC class A). When using the device in residential areas, it may cause radio interference.
Intrinsic safety
- The device is approved for intrinsically safe (Ex i) circuits up to zone 0 (gas) and zone 20 (dust) in the Ex area. The safety technology values for intrinsically safe equipment and the connecting lines must be observed for the hook-up process (IEC/EC 60079-14) and the values specified in this installation note and/or the EU examination certificate must be observed.
- When carrying out measurements on the intrinsically safe side, observe the relevant regulations regarding the connection of intrinsically safe equipment. Use only these approved measuring devices in intrinsically safe circuits.
- If the device was used in circuits which are not intrinsically safe, it is forbidden to use it again in intrinsically safe circuits. Label the device clearly as being not intrinsically safe
Installation in the Ex area (zone 2)
- Observe the specified conditions for use in potentially explosive areas! Install the device in a suitable, approved housing that meets the requirements of IEC/EN 60079-15 and has at least IP54 protection. Also observe the requirements of IEC/EN 60079-14.
- In zone 2 only connect or disconnect cables and adjust the DIP switch when the power is disconnected.
- In potentially explosive areas, only snap the device onto or off the pac-Bus 9294 or connect and disconnect the cables when the power is disconnected.
- The device must be stopped and immediately removed from the Ex area if it is damaged, was subject to an impermissible load, stored incorrectly or if it malfunctions.
Potentially dust-explosive areas
- The device is not suitable for installation in zone 22.
- If you nevertheless intend to use the device in zone 22, you must install it in a housing according to IEC/ EN 60079-31. Observe the maximum surface temperatures in this case. Adhere to the requirements of IEC/ EN 60079-14.
- Connection to the intrinsically safe circuit in areas with a danger of dust explosions (zone 20, 21 or 22) is only permitted if the equipment connected to this circuit is approved for this zone (e.g., category 1D, 2D or 3D).
Safety-related applications (SIL)
NOTE
When using the device in safety-related applications, observe the instructions
in the safety manual available at r-stahl.com, as the requirements may differ
for safety-related functions.
Short description
The switching repeater has been designed for intrinsically safe operation of proximity sensors (as per IEC/ EN 60947-5-6 NAMUR) and switch contacts with open circuit or resistance circuits, as well as switches, installed in hazardous zones. The output side has two NO contact relays. Both can be operated as signal outputs. Output 2 can also be used as an error message output (set via the DIP switch).
Operating and indicating elements
- Yellow “OUT2” LED, status of relay 2
- Yellow “OUT1” LED, status of relay 1
- Red “LF” LED, line fault of the sensor cable
- Green “PWR” LED, power supply
- Connection terminal blocks for the safe area (black/green)
- Switch DIP 1 … DIP 4
- Connection terminal blocks for the Ex area (intrinsically safe Ex i, blue)
Installation
NOTE: Electrostatic discharge
Take protective measures against electrostatic discharge before opening the
front cover!
Connection notes
EN / UL 61010-1:
WARNING
- Provide for a switch/circuit-breaker in the vicinity of a device that is marked as disconnect device for this device.
- Provide overcurrent protection (I ≤ 16 A) within the installation.
- To protect the device against mechanical or electrical damage, install it in suitable housing with an appropriate degree of protection according to IEC/EN 60529.
- During maintenance work, disconnect the device from all effective power sources.
- Before configuring settings using DIP switch, make sure the device has been de energized.
- If the device is not used as described in the documentation, the intended protection can be negatively affected.
- Thanks to its housing, the device has basic insulation to the neighboring devices, for 300 Veff. If several devices are installed next to each other, this has to be taken into account, and additional insulation has to be installed if necessary! If the neighboring device is equipped with basic insulation, no additional insulation is necessary.
- The voltages present on the input and supply are extra-low voltages (ELVs). The switching voltage on the relay output may, depending on application, be a hazardous voltage (> 30V). For this event, safe electrical isolation from the other connections has been implemented.
The device can be snapped onto all 35 mm DIN rails according to IEC/EN 60715.
When using the 9294/31-12, first insert it to bridge the power supply. 3
NOTE
Please also observe the direction of the module and pac-Bus 9294 when snapping
into position: snap-on foot at the top and connector on the left.
Power supply
The supply voltage can be supplied via terminal points 5 and 6 or via the pac- Bus 9294.
Supply via terminal set 9194/50-01
You can connect the supply voltage directly with the bus connector by way
of the terminal set. Adhere to the maximum feed-in of 4 A.
Feed-in via supply module type 9193
Supply module type 9193 is used to feed in the supply voltage to the DIN rail
bus connector.
WIRING
Configuration
By default upon delivery, all DIP switches are in the “I” position. Position “I” = OFF, position “II” =
Direction of action (switch DIP 1)
I = Normal phase (operating current behavior) II = Inverse phase (closed
circuit current behavior)
Line fault detection (switch DIP 2)
I = Line fault detection disabled – (not permitted for safety-related
applications) II = Line fault detection enabled If a line fault occurs, the
relay trips and the red LED “LF” flashes (NE 44). The DIN rail bus connector
is used to transmit an error message to the type 9193 supply module and to
forward it as a group error message.
NOTE
For switch contacts with an open circuit, line fault detection (LF) must be
disabled or the corresponding resistance circuit must be provided directly at
the contact. 6
Configuration of output 2 (switch DIP 3/4)
DIP 3 | DIP 4 | OUT 2 |
---|---|---|
I | I | Deactivated |
I | II | Signal duplicator |
II | I | Fault indicator |
II | II | Signal duplicator |
Truth table 7
Key:
S: Switch without resistance circuit; N: NAMUR sensor; SR: Switch with
resistance circuit; E: State of input circuit; SD: Signal duplicator; LFD:
Fault indicator; D: Disconnected; O: Open/blocking; C: Closed/conducting; OK;
LB: Open circuit; LS: Short circuit
Connection method
Connection method|
---|---
Hardware version| Screw connection
Input data| CAT II (250 V against 6)
Input signal
NAMUR proximity sensors (IEC/EN 60947-5-6) Floating switch contacts Switch
contacts with resistance circuit| Intrinsically safe
Switching points| Blocking conductive
Short-circuit current|
Switching hysteresis|
Non-load voltage|
Line fault detection Break 0.05 mA < IIN < 0.35 mA Short circuit 100 Ω <
RSensor < 360 Ω|
Output data| Relay output
Contact type| 2 N/O contacts
Maximum switching capacity|
Recommended minimum load|
Mechanical service life| 107 cycles
Switching frequency| without load
General data|
Nominal voltage UN|
Voltage range| 24 V DC -20%…+25%
Nominal current| 24 V DC
Ambient temperature Storage temperature| (Any mounting position)
Relative humidity| non-condensing
Use at altitude|
Fire resistance (UL 94)|
Electrical isolation|
Input/output Peak value in accordance with IEC/EN 60079-11|
Input/supply, DIN rail connector Peak value in accordance with IEC/EN 60079-11
Rated insulation voltage (overvoltage category II; pollution degree 2, safe
isolation in accordance with IEC/EN 61010-1)|
Output 1/output 2/input, power supply, T connector Rated insulation voltage
(overvoltage category III; degree of pollution 2, safe isolation as per IEC/EN
61010-1)|
Output 1/output 2/input/power supply, DIN rail connector 50 Hz, 1 min., test
voltage|
Safety data as per ATEX|
Max. output voltage Uo|
Max. output current Io|
Max. output power Po| Max. external inductivity Lo/Max. external capacitance
Co
Max. internal inductance Li| negligible
Max. internal capacitance Ci|
Safety-related maximum voltage Um|
Conformance/Approvals| CE-compliant, additionally IEC/EN 61326
ATEX| IBExU17ATEX1151X
IECEx| IBExU17ATEX1151X
NEC| See final page
SIL in accordance with IEC 61508| to
Noise immunity|
References
- R. STAHL | Explosion Hazard Systems | Industrial Explosion Protection
- You will find a little bit of Stahl chemistry everywhere | Stahl | Stahl
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>