CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer Instructions

June 3, 2024
CARLO GAVAZZI

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer

CARLO GAVAZZI EM111 AV5 Energy Management Energy
Analyzer

Installation and use instructions

5 A CT connection single-phase energy analyzer with Modbus interface Code 8022144

The analyzer measures active and reactive energy, summing (easy connection mode on) or separating imported energy from exported energy. It manages two energy tariffs using a digital input or Modbus command. It is equipped with an output to communicate measurements: RS485 Modbus port. It measures one DIN module, with backlit LCD display with sensitive touch screen areas for page scrolling and parameters setting.

Features

Electrical specifications
Power Self-powered (via measured voltage)
Consumption ≤ 1 W, ≤ 8 VA
Rated current 5 A
Maximum current (continuing) 6 A
Minimum current 0.25 A
Start up current 5mA
Rated voltage 230 V LN, from -30% to +20%
Frequency 45-65 Hz
Accuracy class Active energy: Class 1 (EN62053-21)

Reactive energy: Class 2 (EN62053-23)

Environmental specifications
Working temperature From –25 to +65 °C/from –13 to +149 °F

Storage temperature

R.H.:

| From –30 to +80 °C/from –22 to +176 °F

From 0 to 90% non-condensing @ 40°C

Output specifications
Modbus RS485 port output Modbus RTU protocol

NOTE: for further details, see relevant protocol available on request. To set output parameters, see Parameters menu (Fig. 12).

LED specifications
Pulse weight Proportional to the current transformer ratio:
  Weight (pulses/kWh)
  100
  1000

Duration   max 90 ms
Color    Red and orange

General features

Terminals| 1, 2, N, L : section 2.5–6 mm2, torque 1.1 Nm

3-8 : section 1.5 mm2, torque 0.4 Nm

---|---
Protection grade| Front: IP51, terminals: IP20
Dimensions| See Fig. 14.

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
9

Cleaning
Use a slightly dampened cloth to clean the instrument display; do not use abrasives or solvents.

SERVICE AND WARRANTY
In the event of malfunction, fault or for information on the warranty, contact the CARLO GAVAZZI branch or distributor in your country.

GENERAL WARNINGS

DANGER : Live parts. Heart attack, burns and other injuries. Disconnect the power supply and load before installing the analyzer.
The energy analyzer should only be installed by qualified/authorized personnel.

These instructions are an integral part of the product. They should be consulted for all situations tied to installation and use. They should be kept within easy reach of operators, in a clean place and in good conditions.

Code key (analyzer side) EM111-DIN

AV5 . 1 . X . S1 . X

230 V L-N ac, 5(6) A,

CT connection

| Single-phase current system, two-wire| Self-powered (via measured voltage)| Output type: Modbus RS485 port| No option included

Product (Fig. 1)

Produ

Area

| ct (Fig. 1)

Description

---|---
A| Current, voltage and communication connection terminals.
B| Backlit LCD display with sensitive touch screen areas.
C| Model, feature summary and serial number.
D| LED:

• blinking red: depending on CT ratio

• orange on: current connected in opposite direction. Control only run if the imported and exported energies are measured separately ( Measure = b).

E| Sealable terminal caps.

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
1

In case you want to mount the sealing terminal caps (Fig.1 E) remember to lock them with the appropriate cable sealing.

Connection diagrams

Diagram Description
Fig. 2 Single-phase system 315 mA fuse ( F ), if required by local

law.
Fig. 3| Digital input. Open contact = tariff 1, closed contact = tariff 2.
Fig. 4| RS485 Modbus with Master

Note: additional instruments with RS485 are connected in parallel. The serial output must only be terminated on the last network device connecting terminals A- and T . For connections longer than 1000 m use a signal repeater. Maximum 247 transceivers on the same bus.

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
2

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
3

Area Function
A Measurement menu. Measurements displayed by default when turned on.

Pages are characterized by the reference unit of measure.
B| Parameter menu. Parameter settings pages. Require login password.
C| Information menu. The pages display information and set parameters without having to enter a password.

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
4

Commands

Navigation

Operation                             Command
View the next page                   Fig. 6
View the previous page             Fig. 7
Open the parameter menu        Fig. 8
Exit the parameter menu          Fig. 8 (page End)
Open the information menu     Fig. 9
Exit the information menu        Fig. 9

NOTE: after 120s of disuse, the measurement home page is displayed and the command only works if touched twice. Upon first touch of the touch command area, the display back light turns on.

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
5

Parameter settings
Operation Command
Increase a parameter value Fig. 6
View the next value option Fig. 6
Decrease a parameter value Fig. 7
View the previous value option Fig. 7
Confirm a value Fig. 8
Open the parameter settings page Fig. 8
Quickly confirm the 0000 default password Fig. 9

Setting a parameter (Fig. 10)

Procedure example: how to set P int=24.
NOTE: the first displayed value is the current one. Settings are applied when the value is confirmed. The set value is out of range if Error appears. After 120 s of disuse on a value being set, the title page is displayed (P int in the figure). After another 120 s, the initial measurement page is displayed.

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
6

Measurement menu (Fig. 11)

**NOTE *** : only displayed if full display mode is set (Mode = Full).

Page Description
00 Home page. Total imported active energy. If easy connection is on

( Measure = A), it indicates total active energy without considering the direction.
01| Only if imported and exported energy are measured separately ( Measure = b). Total exported active energy.
02| Active power
03| Voltage
04| Current
05| Power factor ( L = inductive, C = capacitive)
06| Frequency
07| Total imported reactive energy. If easy connection is on ( Measure = A), it indicates total reactive energy without considering the direction.
08| Only if imported and exported energy are measured separately ( Measure = b). Total exported reactive energy.
09| Reactive power
10| Requested average power ( d = demand) calculated for the set interval. The value remains the same for the entire interval. It is = 0 during the first start up interval.
11| Maximum requested power ( Pd = Peak demand) reached since last reset
12| Active energy imported with tariff 1. tar 1 appears after 5 s and remains displayed for 2 s. Displayed if tariff management is on (Tariff = on).
13| Active energy imported with tariff 2. tar 2 appears after 5 s and remains displayed for 2 s. Displayed if tariff management is on (Tariff = on).

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
7

Measurement faults
If the measured signal exceeds the admitted analyzer limits, a specific message appears:

  • EEE blinking: the measured value is out of limits
  • EEE on: the measurement depends on a value that is out of limits

NOTE: active and reactive energy measurements are displayed but do not change.

Parameter menu (Fig. 12)

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
8

NOTE *: the value settings page automatically opens after 3 s.

CARLO GAVAZZI EM111 AV5 Energy Management Energy Analyzer
10

Information menu (Fig. 13)

NOTE: the value automatically alternates every 2 s with the page title.

Page Description
YEAr Year of manufacture
SErIAL Serial number, corresponds to the one indicated on the front

print
rEv.| Firmware revision
Ct rAtIo| Current transformer ratio
MEASurE| Measurement type
P int| Requested average power calculation interval
ModE| Display mode
tArIFF| Enabling tariff management and any current tariff
AddrESS| Modbus address, 01 by default.
bAUd| Baud rate
Parity

CHECK_S

| Parity and any stop bit

Checksum