Altronix OLS250220 power supply/charger converts 220VAC (working range 198VAC- 256VAC), 50/60Hz input into 24VDC at 10A of continuous supply current (see specifications). This general purpose power supply has a wide range of applications for access control and security system accessories that require additional power.
Specifications
Input
- 220VAC (working range 198VAC-256VAC), 50/60Hz, 0.95A.
Output
- 24VDC output.
- 10A continuous supply current.
- Filtered and electronically regulated output.
- Short circuit and thermal overload protection.
Supervision
- AC fail supervision (form “C” contacts).
- Low battery supervision (form “C” contacts).
Visual Indicators
- AC input and DC output LED indicators.
Battery Backup
- Built-in charger for sealed lead acid or gel type batteries.
- Automatic switch over to stand-by battery when AC fails.
- Maximum charge current 0.7A.
Features:
- Power ON/OFF switch.
- Includes battery leads.
Board Dimensions (L x W x H approx.)
- 7.25” x 4.5” x 1.75”
- (184.1mm x 114.3mm x 44.5mm).
Installation Instructions
OLS250220 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
-
Mount the OLS250220 in the desired location/enclosure (mounting hardware included).
-
Slide [Power ON/OFF] switch to OFF position (Fig. 1, pg. 2).
-
Connect AC power to the terminals marked [L & N], connect ground to the terminal marked [G]. Use 18 AWG or larger for all power connections (Battery, DC output, AC input).
Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts.
Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside.
Refer installation and servicing to qualified service personnel. -
Slide [Power ON/OFF] switch to ON position (Fig. 1, pg. 2).
-
Measure output voltage before connecting devices. This helps avoiding potential damage.
-
Slide [Power ON/OFF] switch to OFF position (Fig. 1, pg. 2).
-
Connect devices to be powered to the terminals marked [– DC +].
When the use of stand-by batteries is desired, they must be lead acid or gel type. -
Connect battery to the terminals marked [– BAT +] (battery leads included).
Note: When batteries are not used, a loss of AC will result in the loss of output voltage. -
Connect appropriate signaling notification devices to AC Fail & Low battery supervisory relay outputs marked [NC, C, NO].
-
Slide [Power ON/OFF] switch to ON position (Fig. 1, pg. 2).
LED Diagnostics
Terminal Identification
Altronix is not responsible for any typographical errors.140 58th Street,
Brooklyn, New York 11220 USA | phone:
718-567-8181 | fax:
718-567-9056
website: www.altronix.com | e-mail:
info@altronix.com | Lifetime Warranty
IIOLS250220 – Rev. 080609 H31U
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>