Altronix OLS250220 Off-Line Power Supply Charger Installation Guide

June 4, 2024
Altronix

Altronix OLS250220 Off-Line Power Supply Charger

Overview

Altronix OLS250220 power supply/charger converts 220VAC (working range 198VAC- 256VAC), 50/60Hz input into 24VDC at 10A of continuous supply current (see specifications). This general purpose power supply has a wide range of applications for access control and security system accessories that require additional power.

Specifications

Input

  • 220VAC (working range 198VAC-256VAC), 50/60Hz, 0.95A.

Output

  • 24VDC output.
  • 10A continuous supply current.
  • Filtered and electronically regulated output.
  •  Short circuit and thermal overload protection.

Supervision

  • AC fail supervision (form “C” contacts).
  • Low battery supervision (form “C” contacts).

Visual Indicators

  • AC input and DC output LED indicators.

Battery Backup

  • Built-in charger for sealed lead acid or gel type batteries.
  • Automatic switch over to stand-by battery when AC fails.
  • Maximum charge current 0.7A.

Features:

  • Power ON/OFF switch.
  • Includes battery leads.

Board Dimensions (L x W x H approx.)

  • 7.25” x 4.5” x 1.75”
  • (184.1mm x 114.3mm x 44.5mm).

Installation Instructions

OLS250220 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.

  1. Mount the OLS250220 in the desired location/enclosure (mounting hardware included).

  2. Slide [Power ON/OFF] switch to OFF position (Fig. 1, pg. 2).

  3. Connect AC power to the terminals marked [L & N], connect ground to the terminal marked [G]. Use 18 AWG or larger for all power connections (Battery, DC output, AC input).
    Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).
    Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, Battery Wires). Minimum 0.25” spacing must be provided.
    CAUTION: Do not touch exposed metal parts.
    Shut branch circuit power before installing or servicing equipment.
    There are no user serviceable parts inside.
    Refer installation and servicing to qualified service personnel.

  4. Slide [Power ON/OFF] switch to ON position (Fig. 1, pg. 2).

  5. Measure output voltage before connecting devices. This helps avoiding potential damage.

  6. Slide [Power ON/OFF] switch to OFF position (Fig. 1, pg. 2).

  7. Connect devices to be powered to the terminals marked [– DC +].
    When the use of stand-by batteries is desired, they must be lead acid or gel type.

  8. Connect battery to the terminals marked [– BAT +] (battery leads included).
    Note: When batteries are not used, a loss of AC will result in the loss of output voltage.

  9. Connect appropriate signaling notification devices to AC Fail & Low battery supervisory relay outputs marked [NC, C, NO].

  10. Slide [Power ON/OFF] switch to ON position (Fig. 1, pg. 2).Altronix OLS250220 Off-Line Power Supply Charger FIG 1

LED Diagnostics

Altronix OLS250220 Off-Line Power Supply Charger FIG
3

Terminal Identification

Altronix OLS250220 Off-Line Power Supply Charger
FIG 2

Altronix is not responsible for any typographical errors.140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty