MRCOOL MCDP3036ANPA 36000 BTU Condenser Unit Installation Guide

June 3, 2024
MrCOOL

MRCOOL-LOGO

MRCOOL MCDP3036ANPA 36000 BTU Condenser Unit

INSTALLATION INSTRUCTIONS

This manual must be left with the homeowner for future reference.

This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.

IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.

CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and make sure to wear gloves and protective clothing.

Manufactured By:
MRCOOL®, LLC 48 Remington Way Hickory, KY 42051

WARNING
Improper installation, adjustment, alteration, service or maintenance can cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional installer (or equivalent) or a service agency.

Model Number Identification

MRCOOL-MCDP3036ANPA-36000-BTU-Condenser-Unit-02 NOTE: Special procedures are required for cleaning the aluminum coil in this unit. See Page 8 in this instruction for information.3

General

The MCV & MCH coils are only available cased and include a factory-installed HFC-410A fixed orifice (RFC) metering device that must be replaced if the system match
valve.

These instructions are intended as a general guide and do not supersede local or national codes in any way. Authorities who have jurisdiction should be consulted before installation.

Shipping and Packing List

Package 1 of 1 contains:
1 – Evaporator coil
Check the components for shipping damage; if found, immediately contact the last carrier.

Releasing Air Charge

CAUTION The coil is shipped from the factory pressurized with dry air. Pierce a hole in the rubber plug that seals the vapor line to relieve the pressure before removing the plugs.

NOTE: If there is no pressure released when the vapor line rubber plug is pierced, check the coil for leaks before continuing with the installation.

The MCVP and MCHP coils are shipped with a 10 psi dry air holding charge. Puncture the suction line rubber plug to release the charge. Remove the rubber plug. Ensure that the coil is void of pressure.

Installation

WARNING
Can cause injury or death.
Recover all refrigerant to relieve pressure before opening the system.

Install the furnace or air handler and condensing unit according to the installation instructions provided with the unit.

NOTE: If the coil is to be installed on an oil furnace, it may possible damage to the coil drain pan. See the oil furnace installation instructions for details.
NOTE: The coil cabinet has six screw clearance holes which should be aligned with the furnace engagement holes. Secure the coil cabinet to the furnace or air handler

All indoor cabinets MUST be taped after installation to seal

Refrigerant Line Connections

Line Sizes
The refrigerant line sets should be sized according to the recommendations given in the condensing unit installation instructions. Use Table 1 to determine correct braze to match line set connections.

Model Number Suction Liquid
18/24
24
30 3/4 Inch
30/36
36 3/8 Inch
48

49

50/60

| 7/8 Inch|
60| |

Table 1. Refrigerant Line Connections
Replacement Parts
If replacement parts are necessary, order kit 69J46. The kit includes:

  • 10 – Brass nuts for liquid line assemblies
  • 20 – Teflon rings
  • 10 – Liquid line orifice housings
  • 10 – Liquid line assemblies

MRCOOL-MCDP3036ANPA-36000-BTU-Condenser-Unit-03Figure 1. 69J46 Kit Components

Brazing Guidelines
Use a silver alloy brazing rod (5 or 6 percent silver alloy for copper-to- copper connections or 45 percent silver alloy for copper-to-brass or copper- to-steel connections).

Before making brazed connections, place a field-provided heat shield, such as a wet rag, against the unit cabinet bulb. The heat shield must be in place to prevent heat damage during brazing. See Figure 2.

MRCOOL-MCDP3036ANPA-36000-BTU-Condenser-Unit-04

Figure 2. Braze Refrigerant Lines

Suction Line Connection
Use the following procedure to connect the suction line to the indoor coil:

  1. Remove rubber plug from the stubbed connection.
  2. Position the properly sized refrigerant piping and make the brazed connection following the brazing guidelines.
  3. Do not remove the water-saturated rags from the cabinet and piping until the piping has cooled completely.

Suction Line Equalizer Fitting
Remove the copper flare seat bonnet if present from the male equalizer line fitting (Figure 3).

Important: When removing the flare nut, ensure that the copper flare seal bonnet is removed as illustrated in Figure 3.

MRCOOL-MCDP3036ANPA-36000-BTU-Condenser-Unit-05Figure 3. Suction Line Male Equalizer Line
Fitting Modifications

Liquid Line Connection

NOTE: The coils are shipped with a factory-installed HFC-410A fixed orifice (RFC) metering device. Some system matches with this coil require use of a check/ expansion valve.

NOTE: If the system match requires an HFC-410A check expansion valve on the liquid line connection, the fixed orifice device must be removed BEFORE a check expansion valve is installed

Fixed Orifice Removal (if necessary)
  1. Remove the coil access and plumbing panels.
  2. Remove any shipping clamps that secure the liquid line and distributor assembly.
  3. Using two wrenches, disconnect the liquid line stub from the orifice housing. Take care not to twist or damage the distributor tubes during this process.
  4. Remove and discard the existing orifice, valve stem assembly (if present) and Teflon ring as illustrated in Figure 4.
  5. Retain brass nut to be used later with the liquid line assembly.

MRCOOL-MCDP3036ANPA-36000-BTU-Condenser-Unit-06

Figure 4. Typical Fixed Orifice Removal

Expansion Valve/ Liquid Line Installation

Some system matches for the MCVP and MCHP coil require a check/expansion valve. The expansion valve must be installed external to the indoor coil cabinet. Refer to the instructions provided with the expansion valve kit for proper installation of the valve and sensing bulb.

See the MCVP and MCHP product specifications for approved expansion valve match-ups and application information.

  1. After the expansion valve, equalizer line and sensing bulb have been installed per the kit instructions, braze the properly sized refrigerant piping into place. Carefully follow brazing guidelines and use wet rags to prevent heat damage.
  2. Do not remove the water-saturated rags from the cabinet and piping until the piping has cooled completely.

NOTE: To prevent any possibility of water damage, properly insulate all parts of the expansion valve assembly the valve and its surrounding ambient temperatures.

Sealing Ducts

WARNING There must be an airtight seal between the bottom of the furnace and the return air plenum. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where the air handler or any gas-fueled appliance (i.e., water heater), or carbon monoxide- producing device (i.e., wood fireplace) is installed.

Ensure that the duct is secured and all joints are properly sealed to the coil cabinet flanges.

Condensate Drain Connections

Main Drain
Connect the main drain and route drain tubing downward to drain line or sump. Do not connect drain to a closed waste system. See Figure 6 for typical drain trap configuration.

Overflow Drain
It is recommended that the overflow drain stub be connected to an overflow drain line for all units. If the overflow drain is not connected to a drain line, it must be plugged with the provided cap.

IMPORTANT
After removal of drain pan plug(s), check drain hole(s) to verify that drain opening is fully open and free of any debris. Also check to make sure that no debris has fallen into the drain pan during installation that may plug up the drain opening.

Condensate Drain Recommendations
The following practices are recommended to ensure better condensate removal:

  • Main and overflow drain lines should NOT be smaller than both drain connections at drain pan.
  • Overflow drain line should run to an area where homeowner will notice drainage.
  • It is recommended that the overflow drain line be vented and a trap installed. Refer to local codes.

MRCOOL-MCDP3036ANPA-36000-BTU-Condenser-Unit-07 Figure 6. Typical Main and Overflow Drain Installations

Blower Speed Selection

Figure 7. Static Pressure Test

Cabinet Vol: CFM Drop: in. w.g.
Model Width in. Dry
18/24ANPA 14.5 600
14.5 800 .18
18/24BNPA 17.5 600
17.5 800 .18
24ANPA 14.5 800
24BNPA 17.5 800
30ANPA 14.5 1000
30BNPA 17.5 1000
30/36ANPA 14.5 1000
14.5 1200 .27
30/36BNPA 17.5 1000
17.5 1200 .17
30/36CNPA 21 1000
21 1200 .17
36ANPA 14.5 1200
36BNPA 17.5 1200
48BNPA 17.5 1400
17.5 1600 .30
48CNPA 21 1400
21 1600 .16
49CNPA 21 1600
50/60CNPA 21 1600
60CNPA 21 2000
60DNPA 24.5 2000

Table 2 Air Volume / Static Pressure Drop Across Coil

CAUTION Take care when drilling test holes into the furnace flange and the duct. Drill holes away from refrigerant piping. Test holes should be drilled where specified in order to avoid unit damage.

Proper air volume must be provided over the evaporator coil. Select a blower motor speed tap that will provide 400 50 CFM per 12,000 Btu/h of cooling capacity (wet coil). A static pressure reading must be taken to see if the pressure drop falls within the proper range. See Table 2.

To ensure accuracy, air must be read from below the coil and above the coil. See Figure 7 for an example to obtain an accurate reading.

  1. Drill one 5/16″ air test hole into the delta plate between the coil slabs.
  2. Drill one 5/16″ air test hole into the duct above the top of the col.
  3. Connect the instrument for static pressure measurement hoses to the air entering side of coil. Insert the hoses so that 1/4″ extends inside the duct or end seal. Seal around holes with sealant.
  4. Turn on electrical power to the furnace and set the thermostat to initiate a cooling demand.
  5. Table 2 lists air volumes and equivalent static pressure readings for these units. Observe the static pressure reading. If the reading is below the required air

Maintenance

NOTE
Failure to follow instructions will cause damage to the unit.
This unit is equipped with an aluminum coil. Aluminum pH below 5 or above 9. The aluminum coil should be cleaned using potable water at a moderate pressure (less than 50 psi). If the coil cannot be cleaned using water alone, AAE recommends use of a coil cleaner with a pH in the range of 5 to 9. The coil must be rinsed thoroughly after cleaning.
In coastal areas, the coil should be cleaned with potable water several times per year to avoid corrosive buildup (salt).

A trained technician or service agency must perform maintenance and service on equipment. At the beginning of each heating or cooling season, indoor coils should be cleaned.
on coils. These chemicals are not necessary to dissolve used to dissolve oils and greases, which generally are not present on most installations.

Cleaning The Coil
  1. Remove the coil from the cabinet or plenum, and take the coil to an appropriate place to clean it.

  2. Vacuum or brush the coil to remove matted and surface debris from the fins. Use vacuum attachments and /or brushes that are non-destructive to fins.

  3. If oil deposits are present, spray the coil with a mild household liquid detergent to soften deposits. Do not leave the detergent on the coil for more than 10 minutes. Flush the coil thoroughly with potable water.
    NOTE: For units in coastal regions, fresh water will dissolve away any salt deposits. (Wash coils with fresh water at least every six months.)

  4. Spray the coil at a vertical angle of 30 to 45 degrees with a constant stream of water at moderate pressure. Apressure washer with a fan nozzle will work best. Do not spray the coil from a horizontal direction. 5 coil and base pan. For most residential units, hot water is not necessary.

  5. Direct the spray so that any debris is washed out of the NOTE: Attempting to back flush from the inside of the coil will require removing parts from the unit, and it may be very difficult to flush the whole coil surface. Attempting to blow water through a coil will slow the water stream and reduce the flushing action of the outer fin surface.

  6. Replace the coil into the cabinet or plenum. Ensure that you have followed the proper procedure for routing and securing the refrigerant tubing.

IMPORTANT
Ensure that the distributor lines are not rubbing together or kinked. All tubes must have enough clearance from other metal parts. Use wire ties to secure tubes to prevent movement that could cause the refrigerant tubing to fail.

Please read this manual carefully before installation and keep it for future reference.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MrCOOL User Manuals

Related Manuals