MRCOOL MCDP3036ANPA 36000 BTU Condenser Unit Installation Guide
- June 3, 2024
- MrCOOL
Table of Contents
MRCOOL MCDP3036ANPA 36000 BTU Condenser Unit
INSTALLATION INSTRUCTIONS
This manual must be left with the homeowner for future reference.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death.
IMPORTANT
The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs,
HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarceration may be levied for
noncompliance.
CAUTION
As with any mechanical equipment, contact with sharp sheet metal edges can
result in personal injury. Take care while handling this equipment and make
sure to wear gloves and protective clothing.
Manufactured By:
MRCOOL®, LLC 48 Remington Way Hickory, KY 42051
WARNING
Improper installation, adjustment, alteration, service or maintenance can
cause personal injury, loss of life, or damage to property.
Installation and service must be performed by a licensed professional
installer (or equivalent) or a service agency.
Model Number Identification
NOTE: Special procedures are required for cleaning the aluminum coil in this unit. See Page 8 in this instruction for information.3
General
The MCV & MCH coils are only available cased and include a factory-installed
HFC-410A fixed orifice (RFC) metering device that must be replaced if the
system match
valve.
These instructions are intended as a general guide and do not supersede local or national codes in any way. Authorities who have jurisdiction should be consulted before installation.
Shipping and Packing List
Package 1 of 1 contains:
1 – Evaporator coil
Check the components for shipping damage; if found, immediately contact the
last carrier.
Releasing Air Charge
CAUTION The coil is shipped from the factory pressurized with dry air. Pierce a hole in the rubber plug that seals the vapor line to relieve the pressure before removing the plugs.
NOTE: If there is no pressure released when the vapor line rubber plug is pierced, check the coil for leaks before continuing with the installation.
The MCVP and MCHP coils are shipped with a 10 psi dry air holding charge. Puncture the suction line rubber plug to release the charge. Remove the rubber plug. Ensure that the coil is void of pressure.
Installation
WARNING
Can cause injury or death.
Recover all refrigerant to relieve pressure before opening the system.
Install the furnace or air handler and condensing unit according to the installation instructions provided with the unit.
NOTE: If the coil is to be installed on an oil furnace, it may possible
damage to the coil drain pan. See the oil furnace installation instructions
for details.
NOTE: The coil cabinet has six screw clearance holes which should be
aligned with the furnace engagement holes. Secure the coil cabinet to the
furnace or air handler
All indoor cabinets MUST be taped after installation to seal
Refrigerant Line Connections
Line Sizes
The refrigerant line sets should be sized according to the recommendations
given in the condensing unit installation instructions. Use Table 1 to
determine correct braze to match line set connections.
Model Number | Suction | Liquid |
---|---|---|
18/24 | ||
24 | ||
30 | 3/4 Inch | |
30/36 | ||
36 | 3/8 Inch | |
48 |
49
50/60
| 7/8 Inch|
60| |
Table 1. Refrigerant Line Connections
Replacement Parts
If replacement parts are necessary, order kit 69J46. The kit includes:
- 10 – Brass nuts for liquid line assemblies
- 20 – Teflon rings
- 10 – Liquid line orifice housings
- 10 – Liquid line assemblies
Figure 1. 69J46 Kit Components
Brazing Guidelines
Use a silver alloy brazing rod (5 or 6 percent silver alloy for copper-to-
copper connections or 45 percent silver alloy for copper-to-brass or copper-
to-steel connections).
Before making brazed connections, place a field-provided heat shield, such as a wet rag, against the unit cabinet bulb. The heat shield must be in place to prevent heat damage during brazing. See Figure 2.
Figure 2. Braze Refrigerant Lines
Suction Line Connection
Use the following procedure to connect the suction line to the indoor coil:
- Remove rubber plug from the stubbed connection.
- Position the properly sized refrigerant piping and make the brazed connection following the brazing guidelines.
- Do not remove the water-saturated rags from the cabinet and piping until the piping has cooled completely.
Suction Line Equalizer Fitting
Remove the copper flare seat bonnet if present from the male equalizer line
fitting (Figure 3).
Important: When removing the flare nut, ensure that the copper flare seal bonnet is removed as illustrated in Figure 3.
Figure 3. Suction Line Male Equalizer Line
Fitting Modifications
Liquid Line Connection
NOTE: The coils are shipped with a factory-installed HFC-410A fixed orifice (RFC) metering device. Some system matches with this coil require use of a check/ expansion valve.
NOTE: If the system match requires an HFC-410A check expansion valve on the liquid line connection, the fixed orifice device must be removed BEFORE a check expansion valve is installed
Fixed Orifice Removal (if necessary)
- Remove the coil access and plumbing panels.
- Remove any shipping clamps that secure the liquid line and distributor assembly.
- Using two wrenches, disconnect the liquid line stub from the orifice housing. Take care not to twist or damage the distributor tubes during this process.
- Remove and discard the existing orifice, valve stem assembly (if present) and Teflon ring as illustrated in Figure 4.
- Retain brass nut to be used later with the liquid line assembly.
Figure 4. Typical Fixed Orifice Removal
Expansion Valve/ Liquid Line Installation
Some system matches for the MCVP and MCHP coil require a check/expansion valve. The expansion valve must be installed external to the indoor coil cabinet. Refer to the instructions provided with the expansion valve kit for proper installation of the valve and sensing bulb.
See the MCVP and MCHP product specifications for approved expansion valve match-ups and application information.
- After the expansion valve, equalizer line and sensing bulb have been installed per the kit instructions, braze the properly sized refrigerant piping into place. Carefully follow brazing guidelines and use wet rags to prevent heat damage.
- Do not remove the water-saturated rags from the cabinet and piping until the piping has cooled completely.
NOTE: To prevent any possibility of water damage, properly insulate all parts of the expansion valve assembly the valve and its surrounding ambient temperatures.
Sealing Ducts
WARNING There must be an airtight seal between the bottom of the furnace and the return air plenum. Use fiberglass sealing strips, caulking, or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal. Return air must not be drawn from a room where the air handler or any gas-fueled appliance (i.e., water heater), or carbon monoxide- producing device (i.e., wood fireplace) is installed.
Ensure that the duct is secured and all joints are properly sealed to the coil cabinet flanges.
Condensate Drain Connections
Main Drain
Connect the main drain and route drain tubing downward to drain line or sump.
Do not connect drain to a closed waste system. See Figure 6 for typical drain
trap configuration.
Overflow Drain
It is recommended that the overflow drain stub be connected to an overflow
drain line for all units. If the overflow drain is not connected to a drain
line, it must be plugged with the provided cap.
IMPORTANT
After removal of drain pan plug(s), check drain hole(s) to verify that drain
opening is fully open and free of any debris. Also check to make sure that no
debris has fallen into the drain pan during installation that may plug up the
drain opening.
Condensate Drain Recommendations
The following practices are recommended to ensure better condensate removal:
- Main and overflow drain lines should NOT be smaller than both drain connections at drain pan.
- Overflow drain line should run to an area where homeowner will notice drainage.
- It is recommended that the overflow drain line be vented and a trap installed. Refer to local codes.
Figure 6. Typical Main and Overflow Drain Installations
Blower Speed Selection
Figure 7. Static Pressure Test
Cabinet | Vol: CFM | Drop: in. w.g. |
---|---|---|
Model | Width in. | Dry |
18/24ANPA | 14.5 | 600 |
14.5 | 800 | .18 |
18/24BNPA | 17.5 | 600 |
17.5 | 800 | .18 |
24ANPA | 14.5 | 800 |
24BNPA | 17.5 | 800 |
30ANPA | 14.5 | 1000 |
30BNPA | 17.5 | 1000 |
30/36ANPA | 14.5 | 1000 |
14.5 | 1200 | .27 |
30/36BNPA | 17.5 | 1000 |
17.5 | 1200 | .17 |
30/36CNPA | 21 | 1000 |
21 | 1200 | .17 |
36ANPA | 14.5 | 1200 |
36BNPA | 17.5 | 1200 |
48BNPA | 17.5 | 1400 |
17.5 | 1600 | .30 |
48CNPA | 21 | 1400 |
21 | 1600 | .16 |
49CNPA | 21 | 1600 |
50/60CNPA | 21 | 1600 |
60CNPA | 21 | 2000 |
60DNPA | 24.5 | 2000 |
Table 2 Air Volume / Static Pressure Drop Across Coil
CAUTION Take care when drilling test holes into the furnace flange and the duct. Drill holes away from refrigerant piping. Test holes should be drilled where specified in order to avoid unit damage.
Proper air volume must be provided over the evaporator coil. Select a blower motor speed tap that will provide 400 50 CFM per 12,000 Btu/h of cooling capacity (wet coil). A static pressure reading must be taken to see if the pressure drop falls within the proper range. See Table 2.
To ensure accuracy, air must be read from below the coil and above the coil. See Figure 7 for an example to obtain an accurate reading.
- Drill one 5/16″ air test hole into the delta plate between the coil slabs.
- Drill one 5/16″ air test hole into the duct above the top of the col.
- Connect the instrument for static pressure measurement hoses to the air entering side of coil. Insert the hoses so that 1/4″ extends inside the duct or end seal. Seal around holes with sealant.
- Turn on electrical power to the furnace and set the thermostat to initiate a cooling demand.
- Table 2 lists air volumes and equivalent static pressure readings for these units. Observe the static pressure reading. If the reading is below the required air
Maintenance
NOTE
Failure to follow instructions will cause damage to the unit.
This unit is equipped with an aluminum coil. Aluminum pH below 5 or above 9.
The aluminum coil should be cleaned using potable water at a moderate pressure
(less than 50 psi). If the coil cannot be cleaned using water alone, AAE
recommends use of a coil cleaner with a pH in the range of 5 to 9. The coil
must be rinsed thoroughly after cleaning.
In coastal areas, the coil should be cleaned with potable water several times
per year to avoid corrosive buildup (salt).
A trained technician or service agency must perform maintenance and service on
equipment. At the beginning of each heating or cooling season, indoor coils
should be cleaned.
on coils. These chemicals are not necessary to dissolve used to dissolve oils
and greases, which generally are not present on most installations.
Cleaning The Coil
-
Remove the coil from the cabinet or plenum, and take the coil to an appropriate place to clean it.
-
Vacuum or brush the coil to remove matted and surface debris from the fins. Use vacuum attachments and /or brushes that are non-destructive to fins.
-
If oil deposits are present, spray the coil with a mild household liquid detergent to soften deposits. Do not leave the detergent on the coil for more than 10 minutes. Flush the coil thoroughly with potable water.
NOTE: For units in coastal regions, fresh water will dissolve away any salt deposits. (Wash coils with fresh water at least every six months.) -
Spray the coil at a vertical angle of 30 to 45 degrees with a constant stream of water at moderate pressure. Apressure washer with a fan nozzle will work best. Do not spray the coil from a horizontal direction. 5 coil and base pan. For most residential units, hot water is not necessary.
-
Direct the spray so that any debris is washed out of the NOTE: Attempting to back flush from the inside of the coil will require removing parts from the unit, and it may be very difficult to flush the whole coil surface. Attempting to blow water through a coil will slow the water stream and reduce the flushing action of the outer fin surface.
-
Replace the coil into the cabinet or plenum. Ensure that you have followed the proper procedure for routing and securing the refrigerant tubing.
IMPORTANT
Ensure that the distributor lines are not rubbing together or kinked. All
tubes must have enough clearance from other metal parts. Use wire ties to
secure tubes to prevent movement that could cause the refrigerant tubing to
fail.
Please read this manual carefully before installation and keep it for future reference.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>