Vokera PINNACLE High Efficiency System Boiler User Manual
- September 28, 2024
- Vokera
Table of Contents
PINNACLE High Efficiency System Boiler
“`html
Specifications
- Product: PINNACLE High efficiency system boiler
- Dimensions:
- Height: 740 mm
- Width: 420 mm
- Depth: 275 mm
- Clearances Required:
- Above: 25mm*
- Below: 200mm^
- Left Side: 5mm
- Right Side: 5mm**
- Front: 4mm***
Product Usage Instructions
1. Things You Should Know
-
Gas Appliances: Ensure installation and
maintenance are done by a competent person and in accordance with
regulations. -
Electrical Supply: Connect to a double pole
isolator with a 3 AMP fuse. Must be earthed. -
Warranty Registration: Register warranty on
Vokera websites.
2. Getting Started
2.1 Before Switching On
Familiarize yourself with isolating the appliance from gas,
water, and electricity pressure, external thermostats, and
appliance controls.
2.2 Appliance Controls
Refer to page 2 for details on appliance controls.
2.3 Lighting the Boiler
Ensure gas and electrical supply are on. Follow commissioning
preparation steps to start the boiler.
2.4 Start Screen
After connecting to electrical supply, set time and date. The
boiler will enter ‘pre-purge’ mode. Press the center of the display
to activate desired selection (OFF, WINTER).
FAQ
Q: How do I register the warranty for the appliance?
A: You can register the warranty on the Vokera websites by
following the instructions provided and having your appliance
warranty card ready.
Q: What should I do if I need to dispose of the product?
A: Do not dispose of the product as solid urban waste. Instead,
hand it over to a differentiated waste collection centre for proper
disposal.
“`
PINNACLE
High efficiency system boiler
Users Instructions Installation & Servicing Instructions
PINNACLE 20S NG G.C. N° 47-364-25 PINNACLE 25S NG G.C. N° 47-364-26 PINNACLE
32S NG G.C. N° 47-364-27
THESE INSTRUCTIONS TO BE RETAINED BY USER
Vokèra is a licensed member of the Benchmark scheme which aims to improve the
standards of installation and commissioning of domestic hot water systems in
the UK.
1. THINGS YOU SHOULD KNOW…………………………………………… 3 2. GETTING
STARTED………………………………………………………….. 3 3. CONTROL PANEL…………………………………………………………….. 4
4. HOW TO…………………………………………………………………………… 8 5. WHAT
IF…………………………………………………………………………… 8 SECTION 1 – DESIGN PRINCIPLES AND OPERATING
SEQUENCE ……………………………………………………………………….. 10 SECTION 2 – TECHNICAL DATA
………………………………………….. 11 SECTION 3 – GENERAL REQUIREMENTS (UK) ……………………. 14
SECTION 3A – GENERAL REQUIREMENTS (EIRE)……………….. 16
SECTION 4 – INSTALLATION ………………………………………………. 17
SECTION 5 – COMMISSIONING & OPERATION…………………….. 23
SECTION 6 – MAINTENANCE AND CLEANING …………………….. 30 SECTION 7 – PASSWORD
SETTING FOR ACCESSING AND CHANGING PARAMETERS IN THE TECHNICAL MENU ……. 32
SECTION 8 – USER INSTRUCTIONS ……………………………………. 36 SECTION 9 – GUIDED TOUR
……………………………………………….. 39 SECTION 10 – SERVICING INSTRUCTIONS …………………………….. 40
SECTION 11 – CHECKS, ADJUSTMENTS AND FAULT FINDING .. 41 SECTION 12 – LPG
INSTRUCTIONS …………………………………….. 44 Commissioning checklist ……………………………………………………
45
Benchmark …………………………………………………………………….46-49
USERS INSTRUCTIONS
INTRODUCTION
Dear Customer Your Vokèra PINNACLE boiler has been designed to meet and exceed
the very latest standards in gas central heating technology, and if cared for,
will give years of reliable use and efficiency. Please therefore take some
time to read these instructions carefully. Do’s and Don’t’s – Do ensure that
the system pressure is periodically checked – Do ensure that the boiler should
not be used by children or unassisted disabled people – Do ensure that you
know how to isolate the appliance in an emergency – Do ensure that you are
familiar with the appliance controls – Do ensure that your installer has
completed the appliance log book section – Do not attempt to remove the
appliance casing or gain internal access – Do not hang clothes etc. over the
appliance – Do not forget to have the appliance serviced annually.
This booklet is an integral part of the appliance. It is therefore necessary
to ensure that the booklet is handed to the person responsible for the
property in which the appliance is located/installed. A replacement copy can
be obtained from the Vokera website
For the warranty terms and conditions please refer to www.vokera.co.uk (UK) or
www.vokera.ie (ROI).
At the end of its life, the product should be not be disposed of as solid
urban waste, but rather it should be handed over to a differentiated waste
collection centre.
2
1. THINGS YOU SHOULD KNOW
1.1 GAS APPLIANCES
Gas Safety (Installation and Use) Regulation (UK). In the interests of your
safety and that of others it is a legal requirement that all gas appliances
are installed and correctly maintained by a competent person and in accordance
with the latest regulations.
1.2 ELECTRICAL SUPPLY
Please ensure that this appliance has been properly connected to the
electrical supply by means of a double pole isolator, and that the correct
size of fuse (3 AMP) has been fitted. Warning: this appliance must be earthed!
1.3 WARRANTY REGISTRATION
Please take the time to register the appliance warranty which can be done via
the Vokera websites – Vokera.co.uk (UK) & Vokera.ie (Ireland) (please have
your appliance warranty card to hand).
1.4 APPLIANCE COMMISSIONING
CHECKLIST (UK only)
The Benchmark checklist section can be found at the rear of the appliance
installation booklet. This important document must be completed during the
installation/commissioning of your boiler. All GAS SAFE registered installers
carry a GAS SAFE ID card, and have a registration number. These details should
be recorded in the Benchmark commissioning checklist section within the
installation booklet. You can check your installers details by calling GAS
SAFE direct on 08004085500. Failure to install and commission the appliance in
accordance with the manufacturers instructions will invalidate the warranty.
This does not affect your statutory rights.
1.5 HOW DOES IT WORK?
Your PINNACLE boiler supplies heated water to your radiators and hot water
cylinder. The central heating is controlled via a time clock and any
thermostats that your installer may have fitted. The boiler will light when it
receives a request from the time clock via any thermostat that may be
installed. Your PINNACLE boiler lights electronically and does not have a
pilot light. In the unlikely event of a fault developing with your boiler, the
supply of gas to the burner will be terminated automatically.
150 25
200
1.6 DIMENSIONS
HEIGHT 20S-25S-32S 740 mm
WIDTH 420 mm
DEPTH 275 mm
1.7 CLEARANCES REQUIRED
ABOVE BELOW LEFT SIDE RIGHT SIDE FRONT
25mm 200mm^ 5mm 5mm 4mm
- 25mm above flue bend
5
5
if top flue outlet is used. Consideration should
be given to providing
reasonable clearance
for the insertion of a FGA
probe.
** Disconnection
of
adjacent components
may be required in
order to facilitate syphon
removal.
*** Provided that a door or
removal panel enables
420mm access for
maintenance.
^ Can be reduced to
5mm if a removal panel
enables 200mm for
maintenance.
2. GETTING STARTED
2.1 BEFORE SWITCHING ON
Before switching the appliance on, please familiarise yourself with: – how to
isolate the appliance from the gas, water, and electricity
supplies; – how to check and top-up if necessary the system water
pressure; – any external thermostats and their functions; – the appliance
controls.
2.2 APPLIANCE CONTROLS (see page 2)
NOTE: the appliance frost protection is active in all the boiler modes. The
control panel functions can be used to vary the temperature of the water that
circulates around your radiators and the water that flows from your hot water
cylinder. The heating temperature range can be adjusted between 20C – 40C (low
temperature) or 40C – 80C (high temperature) this range is configured by your
installer and the default is the high temperature range. Refer to the main
appliance status table for fault indicator and boiler status.
2.3 LIGHTING THE BOILER
Ensure the gas and electrical supply to the boiler are turned on. After
completing all operations required to prepare commissioning, proceed as
follows to start the boiler.
2.4 START SCREEN
When the appliance is first connected to the electrical supply, the UI may
require you to set the time and date (see page 4), and the appliance will
enter its pre-purge’ mode that will last for several minutes. On completion of the
pre-purge’ phase, the appliance will enter its `standby’ mode unless a
heating request has been made. By pressing in the centre of the display it is
possible to activate the desired selection (OFF, WINTER).
2.5 HOW TO RESET THE APPLIANCE
Reset function In order to reset the boiler’s operation in the event of a
fault, refer to the adjacent pages for information on the meaning of the
various alarm or fault codes; and how to carry out a reset.
3
3. CONTROL PANEL
The PINNACLE touchscreen display allows the user to interact quickly and
easily with the interface, which, depending on the level of use, is presented
with graphic symbols or descriptive text. When the display is not being used,
the stand-by screen is shown, simply press in the centre of the display to
activate the operating mode.
Key : allows a reset of an ongoing fault.
Key : ENABLE/DISABLE winter operation.
The touchscreen has colours that help the user take even more advantage of the SMART features of our interface:
grey
white
green
red
orange
The colour ‘grey’ is The colour ‘white’ is Indicates correct oper- When associated with the Indicates the presence
usually associated with usually associated with ation of the appliance. a parameter or function a parameter or function
symbol it indicates the of a transient fault.
that cannot be changed. that can be changed.
presence of a fault that sends
the boiler into a lockout con-
ditions.
EXAMPLE: WINTER SCREEN – EXAMPLES OF COLORS ON TOUCH SCREEN
12 39
Gio
1.2 bar
1.2
bar WHITE
45 52 12 1.2 bar
°C
°C
39
.5
.5
45 52 14
°C
°C
JUL
.5
.5
Heating
Hot water
GREY
GIO 14 LUG
12°C
42.5 °C
49.5 °C
12°C
42.5°C
49.5°C
Heating
Domestic Hot Water
RED
b Some icons may be active depending on which set-
tings are currently active.
12 Time and date
1.2
39
bar
Gio 14 Automatically sets
JUL Modify time 12:39
Modify date 30 Settembre 2022
12°C
SETTINGS MENU
12 Menu
1.2
39
bar
Gio 14
Domestic water 52°C
JUL Heating circuit
45°C
Boiler mode Winter
System info
12°C
12 Menu
1.2
39 Comfort functions
bar
Gio 14 JUL
Preheat
Biberon Off
Guided tour On/active
Hourly scheduling
12°C On
12 Menu
1.2
39 Time and date
bar
Gio 12:39 thu 14 jul
14
JUL Screen lock
Off
Buzzer On/active
12°C
Language English
12 Menu
1.2
39 Technical menu
bar
Gio Blocked
14
JUL
TIME & DATE
FAULT RESET
SCREEN
12 39
1.2
bar
Gio
14
JUL
12 39
1.2 bar
1.2
bar
E010 Maximum number of
ignition attempts
Gio
45 14
°C
JUL
.5
Heating
52 °C .5
Hot water
12°C
COMFORT
12 39 Comfort functions
1.2
bar
12°C
42.5°C
49.5°C
FUNCTIONS
Gio 14 Comfort functions JUL
Preheat
SETTINGS HEATING DELIVERY
TEMPERATURE
12 Temperature heating
1.2
39 circuit
bar
Gio
14
JUL
45 °C .5
SETTINGS
12°C
DHW
TEMPERATURE
12 DHW temperature
1.2
39
bar
Gio
14
JUL
52 °C .5
Smart preheating Touch&go
12°C
OK
12°C
OK
MENU GESTIONE PRESSIONE PRESSURE MANAGEMENT MENU
12 Boiler pressure
1.2
39
bar
Gio
1.2 bar
14
JUL
1.0
1.5
The boiler pressure is correct
12 Boiler pressure
1.2
39
bar
Gio
0.7 bar
14
JUL
1.0
1.5
The system is not working optimally, proceed to automatic filling?
PRESSURE MANAGEMENT
12 39
Boiler pressure
1.2
bar
Gio
0.2 bar
14
JUL
1.0
1.5
The system is not working optimally, proceed to automatic filling?
12°C
12°C
OK
12°C
OK
12°C
12 39
Boiler pressure
1.2
bar
12 39
Boiler pressure
1.2
bar
Gio
0.7 bar
14
Gio 14
0.2 bar
JUL
1.0
1.5
JUL
1.0
1.5
Automatic system filling in progress…
Automatic system filling in progress…
12°C
12°C
4
USER MENU
12 Menu
1.2
39
bar
Gio 14
Domestic water 52°C
JUL Heating circuit
45°C
Boiler mode Winter
System info
12°C
12 Menu
1.2
39 Comfort functions
bar
Gio Preheat
14 JUL
Biberon Off
Guided tour On/active
Hourly scheduling
12°C On
12 Menu
1.2
39 Time and date
bar
Gio 12:39 thu 14 jul
14
JUL Screen lock
Off
Buzzer On/active
12°C
Language English
12 Menu
1.2
39 Technical menu
bar
Gio Blocked
14
JUL
12°C
TECHNICAL MENU
12 Security password
1.2
39
bar
Gio 14
JUL 0 0 0 0
12°C
OK
12 Service menu
39
Gio
Chimney sweep
14
Ipd
JUL
Alarm history
Call service
Call service
12°C
High efficiency enable Not active
Contact service
12 Technical menu 39
Gio Guided tour 14 JUL Combustion
Configuration
Heating
12°C
Dhw
12 Technical menu 39
Gio Service 14 JUL Connectivity
12°C
1.2
bar
12 Connectivity
39
Gio Bus 485 config 14 Wi-Fi key
JUL Ot config
1.2
Activate
bar
12°C
1.2
bar
1.2
bar
12 Combustion
39
Gio 14
Gas – gas type Methane
JUL D52 – p1 GAS VALVE
45
Gac
Apl – power
12°C 25 kW
1.2
bar
12 39
Configuration
Gio Hydraulic configuration 14 Inst flowmeter
JUL Min rpm 1000 RPM
Max rpm 7900 RPM
12°C
Max ch rpm 6300 RPM
12 39
Configuration
Gio Range rated 14 6300 RPM JUL Config aux 1
Not set
Exhaust probe reset
12°C
12 39
Gio 14 JUL
12°C
Configuration
Hydraulic configuration Inst flowmeter Water pressure transducer Water
transducer Auto-fill enable Not active Air purging cycle
12 39
Gio 14 JUL
12°C
Configuration
Min rpm 1000 RPM Max rpm 7900RPM Max ch rpm 6300 RPM Range rated 6300 RPM
12 39
Configuration
Gio Config aux 1 14 Not set
JUL Exhaust probe reset
12°C
1.2
12 Heating
bar
39 Pump control type
Gio 85
14
Ot cascade control
JUL Activate
Screed function
Anti cycle function
12°C 3Min
Reset ch timers Activate
1.2
12 Heating
bar
39 Type of heating
Gio High temperature
14
Max temp
JUL 80.5°C
Min temp 40°C
Thermoregulation
12°C Activate
Hourly scheduling Activate
1.2
12 Heating
bar
39 Hyst on high temp
Gio 5°C
14
Hyst off high temp
JUL 5°C
Hyst on low temp 3°C
Hyst off low temp
12°C 3°C
Pump control type 85
1.2
12 Heating
bar
39 Ot cascade control
Gio Activate
14
Screed function
JUL
Anti cycle function 3Min
Reset ch timers
12°C Activate
Type of heating High temperature
1.2
12 Heating
bar
39 Max temp
Gio 80.5°C
14
Min temp
JUL 40°C
Thermoregulation Activate
Hourly scheduling
12°C Activate
1.2 12 Dhw
1.2
bar
39
bar
Gio 14
Anti legionella function Not active
JUL Tank hysteresis on
5°C
Tank hysteresis off
5°C
Tank flow temp
12°C 80°C
1.2 12 Dhw
1.2
bar
39
bar
Gio Min temp
14
37°C
JUL Max temp
60°C
Special functions
None
12°C
1.2 12 Dhw
1.2
bar
39
bar
Gio Anti legionella function
14
Not active
JUL Tank hysteresis on
5°C
Tank hysteresis off
5°C
Tank flow temp
12°C 80°C
1.2 12 Dhw
1.2
bar
39
bar
Gio Min temp
14
37°C
JUL Max temp
60°C
Special functions
None
Post circulation
12°C Not active
1.2
bar
5
3.1 Signalling and faults
GREEN
DISPLAY WITH REGULAR OPERATION
ORANGE
RED
DISPLAY WITH
A FAULT
PRESENT
12
1.2 12
1.2
39
bar
39
bar
Gio 14 JUL
E077
Absence of communication with low temperature thermostat
Gio
14
JUL E011
Parasitic flame
12°C
12°C
The presence of a fault is indicated with two different colours: – orange:
indicates that a self-resetting transient error is present
which could limit the correct operation of the boiler
– red (together with the symbol ) indicates the presence of an error which will put the boiler into a lockout condition.
Reset function To restore operation of the boiler in the event of a fault, press
. At this point, if the correct operating conditions have been
restored, the boiler will restart automatically. A maximum of 5
consecutive unlocking attempts can be made from the inter-
face, after which the interface displays
12
1.2
39
bar
Gio
14
JUL
E099 reset attempts exhausted
12°C
In this case, the boiler must be disconnected from the electric-
ity supply and then reconnected again, to reactivate operation.
b If the attempts to reset the boiler do not work, contact the
Technical Assistance Centre.
PRESSURE fault When the pressure value falls below 0.5 bar, the following situations can occur:
warning signal FIL
12
0.5
39
bar
Gio
FIL
14
JUL
FIL LOW WATER PRESSURE
CHECK THE HTG SYSTEM
12 °C
The boiler is operating normally, but it is still recommended to fill
the system in the following way:
– attach the temporary flexi-pipe and open both filling taps A&B – close the
filling valve, access the Info menu (section 7.2, item
I018) to check that the pressure value reaches 1-1.5 bar
– close both A&B taps and remove the flexi-pipe (see also “4.1 HOW TO TOP-UP
THE SYSTEM PRESSURE” page 8).
temporary fault – E041
12
0.2
39
bar
Gio
14
JUL
E041
Low water pressure
12°C
The boiler is not working properly. Fill the system as described in the previous point; operation required within 10 minutes of the message appearing otherwise the anomaly becomes definitive (E040).
definitive fault – E040
12
0.2
39
bar
Gio 14 JUL
E040
Low water pressure
12°C
In the event of a permanent lockout, fill the system and then release the alarm.
Press to restore operation.
Once operation is restored, the boiler performs an automatic vent cycle.
b If the drop in pressure is very frequent, request the inter-
vention of the Technical Assistance Centre.
DHW PROBE fault (E060)
Indicates a possible configuration error; please contact Vokera Technical or
the Service Centre for assistance.
PRIMARY HEAT-EXCHANGER CLEANING fault (E091) The boiler has an auto-diagnostic system which, based on the total number of hours in certain operating conditions, can signal the need to clean the primary heat exchanger. Once the cleaning operation has been completed with the cleaning kit supplied as an accessory, it is necessary to reset the total hours meter as follows:
12 39
Configuration
Gio Config aux 1 14 Not set
JUL Exhaust probe reset
1.2 12 Exhaust probe reset
1.2
bar 39
bar
Gio
14
JUL Proceed with reset of the hour counter of the flue gas probe?
12°C
12°C
OK
NOTE: The meter resetting procedure should be carried out after each in-depth cleaning of the primary exchanger or if this latter is replaced.
The fault occurs when the hour meter exceeds 2500 hours; this value can be
verified as follows: access the “System Info” menu to display the value of the
flue
gas probe meter (display/100, example 2500h = 25).
12 System info
39
Gio
Screed heating hours
14 JUL
Flow probe
Return probe
1.2
bar 0 21°C 22°C
Dhw probe
20°C
12°C Dhw set
Exhaust probe
44°C 33°C
6
ERROR CODE E010 E011 E012 E013 E014 E015 E020 E021 E030 E031 E032 E033 E034
E035 E036 E037 E038 E039 E040 E042 E071 E075 E081 E088 E090 E092 E093 E094
E097 E098 E099 E041 E050 E051 E052 E055 E056 E060 E070 E071 E072 E077 E080
E081 E082 E090 E091 E095 E096 FIL
pressure value
COM
E065
FWER
CFS SFS
OBCD
LLL CFG
ERROR MESSAGE MAXIMUM NUMBER OF IGNITION ATTEMPTS
PARASITIC FLAME MAXIMUM NUMBER OF FLAME LOSSES
SERIAL PROTOCOL FLAME DETECT TEST FAILED VOLTAGE DETECT FLAME TEST FAILED
LIMIT THERMOSTAT GAS VALVE CONTROL MALFUNCTION
FAN ERROR FAN FAILURE MECHANICAL BLOCKAGE
ROTOR FAN FAILURE BLOCKED ROTOR FAN FAILURE DAMAGED CHIMNEY OBSTRUCTION IN
PREVENTILATION BLOCKAGE OBSTRUCTION FLUE GAS LOW POWER BLOCKAGE OBSTRUCTION
FLUE GAS HIGH POWER FAILED COMBUSTION CHECK LOW POWER COMBUSTION CHECK FAILED
HIGH POWER
ABNORMAL FLAME VALUE LOW WATER PRESSURE WATER TRANSDUCER – LWCO ERROR HEATING
TEMPERATURE OVER LIMIT VALVE OPENING LIMIT REACHED RETURN TEMPERATURE OVER
LIMIT
CAC FAILED EXHAUST PROBE ERROR
CALIBRATION FAILED TOO MANY CALIBRATION ATTEMPTS
LAMBDA OVER LIMIT Check FAILED GAC FAILED
RESET ATTEMPTS EXHAUSTED LOW WATER PRESSURE
SMOKE OBSTRUCTION ERROR LOW POWER SMOKE OBSTRUCTION ERROR HIGH POWER
HARDWARE ERROR OUT OF THRESHOLD NO CARD FAN COMMUNICATION
NO COMMUNICATION MICROPROCESSOR CARD CONFIGURATION ERROR CH PROBE ERROR
HEATING TEMPERATURE OVER LIMIT DELTA T RETURN OUT OF LIMIT
ABSENCE OF COMMUNICATION WITH LOW TEMPERATURE THERMOSTAT RETURN PROBE ERROR
RETURN TEMPERATURE OVER LIMIT WARNING DELTA TEMPERATURE EXHAUST PROBE ERROR
CLEAN PRIMARY HT EXCHANGER CALIBRATION FAILED LAMBDA OVER LIMIT
LOW WATER PRESSURE CHECK THE HTG SYSTEM HIGH WATER PRESSURE CHECK THE HTG
SYSTEM
APPLIANCE PCB COMMUNICATION LOST (more than 30 seconds)
IMOD ERROR
WARNING FIRMWARE VERSIONS NOT COMPATIBLE
CALL FOR SERVICE STOP FOR SERVICE
ON BOARD CLOCK DAMAGED
GENERIC FIRMWARE BLOCK GAC NOT EXECUTED
ERROR TYPE DESCRIPTION
DEFINITIVE
TRANSITORY
SIGNAL SIGNAL: (the boiler continues to operate
but with no display or keys) SIGNAL
SIGNAL: (the boiler continues to operate but with no display or keys) SIGNAL
DEFINITIVE
SIGNAL: (the boiler continues to operate but with no display or keys) SIGNAL
SIGNAL
7
4. HOW TO…
5. WHAT IF…
4.1 HOW TO TOP-UP THE SYSTEM
PRESSURE
The system pressure must be checked periodically to ensure the correct
operation of the boiler. The system pressure is shown at the top of the LCD
display or can be read on the gauge located on the underside of the appliance.
When the boiler is at room temperature, the system pressure should be
approximately 1.0 bar. If the pressure requires `topping-up’ use the following
instructions as a guide. – Locate the filling valve connections (usually
beneath the
boiler, see fig. 1). – Attach the filling loop to both connections. – Open the
filling valve slowly until you hear water entering the
system. – Close the filling valve when the pressure gauge (on the boiler)
reads between 1 and 1.5 BAR. – Remove the filling loop from the connections.
control valve (A)
Fig.1
temporary connection
control valve (B)
flow/return pipe
double check valve supply pipe
4.2 HOW TO CARE FOR THE APPLIANCE
To clean the outer casing use only a clean damp cloth. Do not use any scourers
or abrasive cleaners.
5.1 WHAT IF I SUSPECT A GAS LEAK
If you suspect a gas leak, turn off the gas supply at the gas meter and
contact your installer or local gas supplier. If you require further advice
please contact your nearest Vokèra office.
5.2 WHAT IF I HAVE FREQUENTLY TO TOPUP THE SYSTEM
If the system regularly requires topping-up, it may be indicative of a leak.
Please contact your installer and ask him to inspect the system.
5.3 WHAT IF THE APPLIANCE IS DUE ITS ANNUAL SERVICE
Advice for tenants only Your landlord should arrange for servicing. Advice for
homeowners Please contact Vokèra Customer Service (0330 236 8630 (UK) or 056
7755055 (ROI) if you would prefer a Vokèra service engineer or agent to
service your appliance. Alternatively your local GAS SAFE registered engineer
may be able to service the appliance for you.
5.4 WHAT IF I NEED TO CALL AN ENGINEER
If you think your boiler may have developed a fault, please contact your
installer or Vokèra Customer Services (0330 236 8630 (UK) or 056 7755055 (ROI)
have all your details to hand including full address and postcode, relevant
contact numbers, and your appliance log book. It is a requirement of your
warranty terms & conditions that your Benchmark logbook has been filled out
correctly and is fully up to date.
8
INSTALLATION AND SERVICING INSTRUCTIONS
INTRODUCTION
All installers are asked to follow the Benchmark Scheme by adhering to the
Code of Practise, details of which can be obtained from www.benchmark.org.uk.
The PINNACLE has a ACC (Active Combustion Control) system. This control system
ensures functionality, efficiency and low emissions under any conditions. The
ACC system uses an ionisation sensor immersed in the burner flame, whose
information allows the control board to operate the gas valve that regulates
the fuel. This sophisticated control system provides the auto-regulation of
the combustion, so there is no need for an initial calibration. The ACC system
is able to adapt the boiler to operate with different gas compositions,
different outlet pipes lengths and different altitudes (within the specified
design limits). The ACC system can also perform an auto-diagnostic operation
that locks out the burner before the permitted upper emission limit is
exceeded. The PINNACLE product family comprises a range of highefficiency
system boilers. These appliances by design incorporate electronic
ignition, circulating pump, expansion vessel, safety valve, pressure gauge and
automatic by-pass. The range is produced as room sealed, category
II2H3PII2HY203P appliances, suitable for internal wall mounting applications
only. Each appliance is provided with a fan powered flue outlet with an
annular co-axial combustion air intake that can be rotated horizontally
through 360 degrees for various horizontal or vertical applications.
b Before connecting the “Hi, Comfort T300 or K100″ de-
vices, the Connectivity Menu must be set up correctly to avoid communication
failure problems (see section section 8.10).
These appliances are designed for use with a sealed system only; consequently
they are not intended for use on open vented systems.
The boiler is suitable for use with combustible gases group H and/or group E
and natural gas mixtures and hydrogen up to 20% by volume.
This booklet is an integral part of the appliance. It is therefore necessary
to ensure that the booklet is handed to the person responsible for the
property in which the appliance is located/ installed. A replacement copy can
be downloaded from the Vokèra website – www.vokera.co.uk.
The boiler complies with basic requirements of the following Directives: –
Regulation (EU) 2016/426; – Yield directive: Article 7(2) and Annex III of
directive 92/42/
EEC; – Electromagnetic compatibility directive 2014/30/EU; – Low-voltage
directive 2014/35/EU; – Directive 2009/125/EC Ecodesign for energy-using
appliances; – Regulation (EU) 2017/1369 Energy labeling; – Delegated
Regulation (EU) No. 811/2013; – Delegated Regulation (EU) No. 813/2013; –
Regulation UNI/TS 11854.
At the end of its life, the product should be not be disposed of as solid
urban waste, but rather it should be handed over to a differentiated waste
collection and/or recycling centre.
Fig.2
F
G
R
General layout
1 Safety valve 2 Pressure transducer 3 Siphon 4 Fan 5 Air filter 6 Mixer 7 NTC
delivery probe 8 Limit thermostat 9 Flame detection electrode/ionisation
sensor 10 Burner 11 Combustion analysis socket plug 12 Flue gas exhaust 13
Flue gas probe 14 Flame ignition electrode 15 Exchanger 16 Expansion vessel 17
NTC return probe 18 Degassing pipe 19 Gas valve 20 Air vent valve 21
Circulator 22 Drain tap 23 Hydrometer
R Heating return connection
F Heating flow connection G Gas connection
9
1. SECTION – DESIGN PRINCIPLES AND OPERATING SEQUENCE
1.1 PRINCIPLE COMPONENTS
· A fully integrated electronic control board featuring electronic temperature
control, anti-cycle control, pump over-run, selfdiagnostic fault indicator,
full air/gas modulation
· Stainless-steel heat exchanger · Electronic ignition with flame supervision
· Integral high-head pump · Fan · Expansion vessel · Flue sensor · Pressure
transducer · Safety valve
1.2 MODE OF OPERATION (AT REST)
When the appliance is at rest and there are no requests for heating or hot
water, the following functions are active: · frost-protection system: the
frost-protection system protects
the appliance against the risk of frost damage, if the main temperature falls
to 5°C, the appliance will function on minimum power until the temperature on
main reaches 35°C. · anti-block function: the anti-block function enables the
pump to be energised for short periods, when the appliance has been inactive
for more than 24-hours.
1.3 MODE OF OPERATION (HEATING AND/
OR HOT WATER)
When there is a request for heat via the onboard clock and/ or any external
control, the pump and fan are started, the fan speed will modulate until the
correct signal voltage is received at the control PCB. At this point an
ignition sequence is enabled. Ignition is sensed by the electronic circuit to
ensure flame stability at the burner. Once successful ignition has been
achieved, the electronic circuitry increases the gas rate to 75% for a period
of 15 minutes. Thereafter, the boiler’s output will either be increase to
maximum or modulate to suit the set requirement. When the appliance reaches
the desired temperature the burner will shut down and the boiler will perform
a three-minute anti-cycle (timer delay). When the request for heat has been
satisfied the appliance pump and fan may continue to operate to dissipate any
residual heat within the appliance.
1.4 SAFETY DEVICES
When the appliance is in use, safe operation is ensured by: · a pressure
transducer that monitors system water pressure
and will de-activate the pump, fan, and burner should the system water
pressure drop below the required minimum value; · fan speed sensor to ensure
safe operation of the burner; · a high limit thermostat that over-rides the
temperature control circuit to prevent or interrupt the operation of the
burner; · flame sensor that will shut down the burner when no flame signal is
detected and/or when incomplete combustion or high emissions are detected; ·
flue sensor that will shut down the burner if the flue threshold temperature
is exceeded; · a safety valve which releases excess pressure from the primary
circuit.
NOTE: when the appliance is first switched ON or when the electrical supply is
interrupted then restored, the appliance will enter a short purge’ cycle whereby the pump cycles ON & OFF for approximately 2-minutes. Only when the
purge’ cycle has been completed, will the appliance go through an ignition
sequence.
45
6
7
2 1
8
9
12
3
10 11
F
1 Safety valve 2 Pressure transducer 3 Automatic by-pass 4 NTC delivery probe
5 Limit thermostat 6 Exchanger 7 NTC return probe 8 Air vent valve 9 Expansion
vessel 10 Circulator 11 Drain tap 12 Hydrometer R Return connection F Flow
connection
R Fig.3
10
2. SECTION – TECHNICAL DATA
2.1 CENTRAL HEATING
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Maximum heat input (kW)
20.00
25.00
32.00
Minimum heat input (kW)
1.90
2.70
2.70
Maximum heat output (kW) 60/80°C
19.53
24.42
31.19
Minimum heat output (kW) 60/80°C
1.77
2.57
2.57
Maximum heat output (kW) 30/50°C
21.31
26.51
33.70
Minimum heat output (kW) 30/50°C
1.96
2.84
2.84
Minimum working pressure
0.25÷0.45 bar
Maximum working pressure
3 bar
Minimum flow rate
450 l/h
2.2 GAS PRESSURES
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Inlet pressure (G20)
20.0 mbar
20.0 mbar
20.0 mbar
Heating maximum gas rate (m3/hr)
2.12
2.64
3.38
Minimum gas rate (m3/hr)
0.20
0.29
0.29
2.3 EXPANSION VESSEL
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Capacity
9 litres
Maximum system volume
74 litres
Pre-charge pressure
1 bar
2.4 DIMENSIONS
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Height (mm)
740
Width (mm)
420
Depth (mm)
275
Dry weight (kg)
28
28
29
2.5 CLEARANCES REQUIRED FOR MAINTENANCE
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Sides
5mm*
Top
150mm from casing or 25mm above flue elbow (whichever is applicable)
Bottom
200mm^
Front
420mm^^
- It may be necessary to remove adjacent components if component removal/replacement is required ** Consideration should be given to providing reasonable clearance for the insertion of a FGA probe. ^ This can be reduced to 4mm if a removal panel enables the required 200mm ^^ When installed in a cupboard, this dimension can be reduced to 4mm provided that the required 420mm is available when the door is opened/
removed.
2.6 CONNECTIONS
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Flow & return
22mm
Gas
15mm
Safety valve
21mm
Condense
21mm
2.7 ELECTRICAL
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Power consumption CH (Watts)
79
80
104
Voltage (V/Hz)
230/50
Internal fuse
4 A T (for PCB) – 3.15A F (for connections block)
External fuse
3A
2.8 FLUE DETAILS (CONCENTRIC 60-100)
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Maximum horizontal flue length (60/100mm)
10.0 m
8.0 m
8.0 m
Maximum vertical flue length (60/100mm)
11.0 m
9.0 m
9.0 m
2.9 EFFICIENCY
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
SEDBUK 2005 (%)
90.2
90.2
90.1
2.10 EMISSIONS
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
CO2 @ maximum output (%) (*)
8.8
8.8
8.8
CO2 @ minimum output (%) (*)
8.8
8.8
8.8
CO @ maximum output (ppm)
230
200
240
CO @ minimum output (ppm)
15
15
15
NOx rating
class 6
class 6
class 6
(*) CO2 tolerance= +1% -1%
2.11 FAN ROTATIONS
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Maximum number of heating fan rotations (rpm)
6,300
6,200
7,700
Minimum number of heating fan rotations (rpm)
1,000
1,100
1,100
2.12 GAS PRESSURE
PINNACLE 20S
PINNACLE 25S
PINNACLE 32S
Nominal methane gas pressure (G20 – I2H)
20 mbar
20 mbar
20 mbar
Nominal methane-hydrogen gas pressure (G20.2 – I2Y20)
20 mbar
20 mbar
20 mbar
Nominal liquid gas LPG pressure (G31 – I3P)
37 mbar
37 mbar
37 mbar
11
Parameter
Symbol
20S
25S
32S
Unit
Seasonal space heating energy efficiency class
–
A
A
A
–
Water heating energy efficiency class
–
–
–
–
–
Rated heat output
Pnominal
20
24
31
kW
Seasonal space heating energy efficiency
s
94
94
94
%
Useful heat output
At rated heat output and high-temperature regime (*)
P4
19.5
24.4
31,2
kW
At 30% of rated heat output and low-temperature regime (**)
P1
6.6
8.2
10.5
kW
Useful efficiency
At rated heat output and high-temperature regime (*)
4
87.9
87.9
87.8
%
At 30% of rated heat output and low-temperature regime (**)
1
98.8
98.7
98.8
%
Auxiliary electricity consumption
At full load
elmax
30.0
31.1
54.9
W
At part load
elmin
12.2
13.3
13.6
W
In Stand-by mode
PSB
3.0
3.0
3.0
W
Other parameters
Stand-by heat loss
Pstby
30.0
35.0
35.0
W
Pilot flame energy consumption
Pign
–
–
–
W
Annual energy consumption
QHE
60
75
96
GJ
Sound power level, indoors
LWA
47
45
48
dB
Emissions of nitrogen oxides
NOx
22
20
35
mg/kWh
For combination heaters
Declared load profile
–
–
–
Water heating energy efficiency
wh
–
–
–
%
Daily electricity consumption
Qelec
–
–
–
kWh
Daily fuel consumption
Qfuel
–
–
–
kWh
Annual electricity consumption
AEC
–
–
–
kWh
Annual fuel consumption
AFC
–
–
–
GJ
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet
(**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet)
Description
Technical data for typical installations: Temperature of combustion products @
Nominal heat output (at 80/60° C) – [°C] Mass flow rate [kg/h] @ Nominal heat
output [kW] Nominal heat output [kW] Overtemperature of the flue gases [°C]
Temperature of the flue gases at minimum heat output [°C] Mass flow rate
[kg/h] @ Minimum heat output [kW] Minimum heat output [kW] CO2 content @
Nominal heat output [%] CO2 at minimum heat output [%] Loss of minimum
permitted pressure (in air feed and flue gas pipe) [Pa] Loss of maximum
permitted pressure (in air supply and flue gas pipe) [Pa] Maximum permitted
pressure difference between combustion air inlet and flue gas outlet
(including wind pressure) [Pa] Maximum permitted combustion air temperature
[°C] C9 Minimum useful diameter of the flue/vertical technical compartment for
combustion air supply [mm]
20S
63 2.759 25.8
35.2 0.414 3.91 8.42 3.03 4.4 180
–
–
Boiler type PINNACLE S
25S 32S 20S 25S 32S 20S 25S 32S
C4
C6
C8
62.2 63.8 63.5 64.2 63.9 49.7 55.2 56.3
3.158 3.823 2.743 3.365 4.089 2.833 3.2618 3.944
30.15 35.67 25.55 30.96 38. 26.46 31.02 36.82
115
37 39.5 57 58.3 60.1 35.4 36.4 37.4
0.536 0.694 0.232 0.326 0.422 0.787 0.965 1.187
5.03 6.52 2.18 3.09 4 7.4 9.02 11.1
8.56 8.56 10.00 10.40 10.40 5.62 5.92 5.92
3.01 3.04 9.05 9.16 9.26 2.60 2.46 2.56
8.3 8.3 –
—
–
–
–
195 195 –
—
–
–
–
–
– 4.4 8.3 8.3 –
–
–
–
– 45 45 45 –
–
–
20S – 25S – 32S
240
Notes
C1: for the installation of the terminals on the wall and roof, refer to the specific instructions contained in the kits the terminals emerge from separate combustion and air supply circuits within a square area of 50 cm
C3: the terminals of the separate combustion and air supply circuits must lie within a square area of 50 cm, and the distance between the surfaces of the two holes must be less than 50 cm
C4: the boilers in this configuration, with the relative connection pipes, can be connected to only one natural draught stacke condensate flow inside the appliance is not permitted
C5: the terminals for combustion air supply and the evacuation of flue gases must not be installed on opposite walls of the building
C6: condensate flow inside the appliance is permitted maximum permitted
recirculation rate of 10% in windy conditions
the terminals for combustion air supply and the evacuation of flue gases must
not be installed on opposite walls of the building.
This type of configuration is not permitted in some countries; refer to the local regulations in force
C8: condensate flow inside the appliance is not permitted
12
Fig.4
Key Location
A Below an opening (window, air-brick, etc.) B Above an opening (window, air-
brick, etc.) C To the side of an opening (window, air-brick, etc.) D Below
gutter, drain-pipe, etc. E Below eaves F Below balcony, lowest point of
carport roof, etc. G To the side of a soil/drain-pipe, etc. H From
internal/external corner I Above ground, roof, or balcony level J From a
surface or boundary facing the terminal K From a terminal facing a terminal L
From an opening in the car-port into the building M Vertically from a terminal
on the same wall N Horizontally from a terminal on the same wall P From a
structure to the side of the vertical terminal Q From the top of the vertical
terminal to the roof flashing
R To the side of a boundary S To the side of an opening or window on a pitched
roof T Below an opening or window on a pitched roof V From a vertical terminal
to an adjacent opening (window, air-brick, etc.) W From a vertical terminal to
an adjacent vertical terminal
Minimum distance
300 mm 300 mm 300 mm 25 mm 25 mm 25 mm 25 mm (60mm for 80/125mm) 25 mm (60mm
for 80/125mm) 300 mm 600 mm* 1200 mm 1200 mm 1500 mm 300 mm 300 mm As
determined by the fixed collar of the vertical terminal 300 mm 600 mm 2000 mm
2000 mm 300 mm (only if both terminals are the same height)
*The possibility that this may be deemed as causing a nuisance, should be considered
Circulator residual discharge head The boiler is fitted with a high-efficiency
circulator already hydraulically and electrically connected. The relative
usable performance values are shown in the chart.
800
700
600
Residual head (mbar)
500
400
300
200
47 W
100
0
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
Flow rate (l/h)
13
3. SECTION – GENERAL REQUIREMENTS (UK)
BS 5440 BS 5440 BS EN 12828 BS 5546 BS 6798 BS 6891
BS 7074
PART 1 PART 2
PART 1
FLUES FLUES & VENTILATION DESIGN FOR WATER-BASED HEATING SYSTEMS INSTALLATION
OF GAS HOT WATER SUPPLIES FOR DOMESTIC PURPOSES
INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 70kW
LOW PRESSURE INSTALLATION PIPES APPLICATION, SELECTION, AND INSTALLATION OF
EXPANSION VESSELS AND ANCILLARY EQUIPMENT FOR SEALED WATER SYSTEM
This appliance must be installed by a competent person in accordance with the
Gas Safety (Installation & Use) Regulations.
3.1 RELATED DOCUMENTS
The installation of this boiler must be in accordance with the relevant
requirements of the Gas Safety (Installation & Use) Regulations, the local
building regulations, the current I.E.E. wiring regulations, the bylaws of the
local water undertaking, the Building Standards (Scotland) Regulation, and
Building Standards (Northern Ireland) Regulations. It should be in accordance
also with any relevant requirements of the local authority and the relevant
recommendations of the following British Standard Codes of Practice.
ATTENTION The use of PPE (Personal Protective Equipment) such as but not
limited to gloves, mask, safety glasses, etc. is strongly recommended whenever
carrying out the installation, repair, or maintenance of this appliance
please pay particular attention to: · Sharp edges that may be encountered
when:- handling or
lifting the appliance, removing parts, etc. during installation and
maintenance · Airborne particles that may be released and/or disturbed when
cleaning or removing components during maintenance · Water treatment chemicals
that could have been added to the system water may spill from the appliance
and or components during maintenance
Please refer to an appropriate Health and Safety document such as HSE L23 (UK)
or S.I. 299 (Ireland), for more detailed advice on safe working practices and
procedures.
3.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal space, although
particular attention is drawn to the requirements of the current I.E.E. wiring
regulations, and in Scotland, the electrical provisions of the Building
Regulations, with respect to the installation of the appliance in a room or
internal space containing a bath or shower. When an appliance is installed in
a room or internal space containing a bath or shower, the appliance or any
control pertaining to it must not be within reach of a person using the bath
or shower (refer to IEE regs). The location chosen for the appliance must
permit the provision of a safe and satisfactory flue and termination. The
location must also permit an adequate air supply for combustion purposes and
an adequate space for servicing and air circulation around the appliance.
Where the installation of the appliance will be in an unusual location special
procedures may be necessary, BS 6798 gives detailed guidance on this aspect. A
compartment used to enclose the appliance must be designed and constructed
specifically for this purpose. An existing compartment/cupboard may be
utilised provided that it is modified to suit. Details of essential features
of compartment/ cupboard design including airing cupboard installations are
given in BS 6798. This appliance is not suitable for external installation.
3.3 GAS SUPPLY
The gas meter as supplied by the gas supplier must be checked to ensure
that it is of adequate size to deal with the maximum rated input of all the
appliances that it serves. Installation pipes must be fitted in accordance
with BS 6891. Pipe work from the meter to the appliance must be of adequate
size. Pipes of a smaller size than the appliance gas inlet connection must not
be used. The installation must be tested for soundness in accordance with
BS6891. If the gas supply serves more than one appliance, it must be ensured
that an adequate supply is maintained to each appliance when they are in use
at the same time.
14
NOTE: It is recognised that pressure loss’ through the gas cock and gas valve may result in a pressure drop of approximately 2mbar between the gas meter and gas valve inlet test point; this will not impair the performance of the appliance, provided that a dynamic pressure of 18mbar is available at the appliance inlet. 3.4 FLUE SYSTEM The terminal should be located where the dispersal of combustion products is not impeded and with due regard for the damage and discoloration that may occur to building products located nearby. The terminal must not be located in a place where it is likely to cause a nuisance (see fig. 4). In cold and/or humid weather, water vapour will condense on leaving the terminal; the effect of such pluming must be considered. If installed less than 2m above a pavement or platform to which people have access (including balconies or flat roofs) the terminal must be protected by a guard of durable material. The guard must be fitted centrally over the terminal. Refer to BS 5440 Part 1, when the terminal is 0.5 metres (or less) below plastic guttering or 1 metre (or less) below painted eaves. 3.5 AIR SUPPLY The following notes are intended for general guidance only. This appliance is a room-sealed, fan-flued boiler, consequently it does not require a permanent air vent for combustion air supply. When installed in a cupboard or compartment, ventilation for cooling purposes is also not required. 3.6 WATER CIRCULATION Detailed recommendations are given in BS EN 12828 and BS 6798. The following notes are for general guidance only. 3.6.1 PIPEWORK It is recommended that copper tubing to BS 2871 Part 1 is used in conjunction with soldered capillary joints. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and that water flows naturally to drain cocks. Except where providing useful heat, pipes should be insulated to avoid heat loss and in particular to avoid the possibility of freezing. Particular attention should be paid to pipes passing through ventilated areas such as under floors, loft space, and void areas. 3.6.2 AUTOMATIC BY-PASS The appliance has a built-in automatic by-pass, consequently there is no requirement for an external by-pass, however the design of the system should be such that it prevents boiler
cycling’.
3.6.3 DRAIN COCKS These must be located in accessible positions to facilitate
draining of the appliance and all water pipes connected to the appliance. The
drain cocks must be manufactured in accordance with BS 2879.
3.6.4 AIR RELEASE POINTS These must be positioned at the highest points in the
system where air is likely to be trapped. They should be used to expel trapped
air and allow complete filling of the system.
3.6.5 EXPANSION VESSEL The appliance has an integral expansion vessel to
accommodate the increased volume of water when the system is heated. Refer to
the specification table for more detailed information.
3.6.6 FILLING POINT A method for initial filling of the system and replacing
water lost during servicing etc. directly from the mains supply, must be
provided (see fig. 5). This method of filling should comply with the current
Water Supply (Water Fittings) Regulations 1999 and Water Bylaws 2000
(Scotland).
3.6.7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system
would be from an independent make-up vessel or tank mounted in a position at
least 1 metre above the highest point in the system and at least 5 metres
above the boiler (see fig. 6). The cold feed from the make-up vessel or tank
must be fitted with an approved non-return valve and stopcock for isolation
purposes. The feed pipe should be connected to the return pipe as close to the
boiler as possible.
3.6.8 FREQUENT FILLING Frequent filling or venting of the system may be
indicative of a leak. Care should be taken during the installation of the
appliance to ensure all aspects of the system are capable of withstanding
pressures up to at least 3 bar.
3.7 ELECTRICAL SUPPLY
The appliance is supplied for operation on 230V @ 50Hz electrical supply; it
must be protected with a 3-amp fuse (supplied). The method of connection to
the mains electricity supply must allow for complete isolation from the
supply. The preferred method is by using a double-pole switch with a contact
separation of at least 3mm. The switch must only supply the appliance and its
corresponding controls, i.e. time clock, room thermostat, etc.
Warning! This appliance must be earthed.
3.8 MOUNTING ON A COMBUSTIBLE SURFACE
The appliance can be mounted on a wall of combustible material without any
requirement to fit any additional protective (fireresistant) material.
3.9 TIMBER FRAMED BUILDINGS
If the appliance is to be fitted in a timber framed building, it should be
fitted in accordance with the Institute of Gas Engineers publication
(IGE/UP/7) `Guide for Gas Installations in Timber Frame Buildings’.
3.10 WATER TREATMENT
Vokera recommend that water treatment be carried out in accordance with the
Benchmark Guidance on water treatment in central heating systems. If water
treatment products are to be used, then they must be entirely suitable for use
with a stainless-steel heat exchanger. Any water treatment product, must be
administered in strict accordance with the manufacturer’s instructions. If the
appliance is to be installed to an existing system; water treatment and
flushing of the complete heating system should be carried out in accordance
with BS 7593 and the Benchmark Guidance on water treatment in central heating
systems.
control valve
temporary connection
control valve
flow/return pipe
double check valve
Automatic air-vent
Make-up vessel or tank
supply pipe
Fig.5
Non-return Stopcock valve
5.0 metres minimum
Heating return
Fig.6
15
3A. SECTION – GENERAL REQUIREMENTS (EIRE)
This appliance must be installed by a competent person in accordance with and
defined by, the Standard Specification (Domestic Gas Installations)
Declaration (I.S. 813).
3A.1 RELATED DOCUMENTS
The installation of this boiler must be in accordance with the relevant
requirements of the local building regulations, the current ETCI National
Rules for Electrical Installations, and the bylaws of the local water
undertaking. It should be in accordance also with any relevant requirements of
the local and/or district authority.
ATTENTION The use of PPE (Personal Protective Equipment) such as but not
limited to gloves, mask, safety glasses, etc. is strongly recommended whenever
carrying out the installation, repair, or maintenance of this appliance
please pay particular attention to: · Sharp edges that may be encountered
when:- handling or
lifting the appliance, removing parts, etc. during installation and
maintenance · Airborne particles that may be released and/or disturbed when
cleaning or removing components during maintenance · Water treatment chemicals
that could have been added to the system water may spill from the appliance
and or components during maintenance
Please refer to an appropriate Health and Safety document such as HSE L23 (UK)
or S.I. 299 (Ireland), for more detailed advice on safe working practices and
procedures.
3A.2 LOCATION OF APPLIANCE
The appliance may be installed in any room or internal space, although
particular attention is drawn to the requirements of the current ETCI National
Rules for Electrical Installations, and I.S. 813, Annex K. When an appliance
is installed in a room or internal space containing a bath or shower, the
appliance or any control pertaining to it must not be within reach of a person
using the bath or shower. The location chosen for the appliance must permit
the provision of a safe and satisfactory flue and termination. The location
must also permit an adequate air supply for combustion purposes and an
adequate space for servicing and air circulation around the appliance. Where
the installation of the appliance will be in an unusual location special
procedures may be necessary, refer to I.S. 813 for detailed guidance on this
aspect. A compartment used to enclose the appliance must be designed and
constructed specifically for this purpose. An existing compartment/cupboard
may be utilised provided that it is modified to suit. This appliance is not
configured for external installation.
3A.3 GAS SUPPLY
The gas meter as supplied by the gas supplier must be checked to ensure
that it is of adequate size to deal with the maximum rated input of all the
appliances that it serves. Installation pipes must be fitted in accordance
with I.S. 813. Pipe work from the meter to the appliance must be of adequate
size. Pipes of a smaller size than the appliance gas inlet connection must not
be used. The installation must be tested for soundness in accordance with I.S.
813. If the gas supply serves more than one appliance, it must be ensured that
an adequate supply is maintained to each appliance when they are in use at the
same time.
NOTE: It is recognised that `pressure loss’ through the gas cock and gas valve
may result in a pressure drop of approximately 2mbar between the gas meter and
gas valve inlet test point; this will not impair the performance of the
appliance, provided that a dynamic pressure of 18mbar is available at the
appliance inlet.
3A.4 FLUE SYSTEM
The terminal should be located where the dispersal of combustion products is
not impeded and with due regard for the damage and discoloration that may
occur to building products located nearby. The terminal must not be located in
a place where it is likely to cause a nuisance (see I.S. 813). In cold and/or
humid weather, water vapour will condense on leaving the terminal; the effect
of such pluming must be considered. If installed less than 2m above a pavement
or platform to which people have access (including balconies or flat roofs)
the terminal must be protected by a guard of durable material. The guard must
be fitted centrally over the terminal. Refer to I.S. 813, when the terminal is
0.5 metres (or less) below plastic guttering or 1 metre (or less) below
painted eaves.
16
3A.5 AIR SUPPLY
The following notes are intended for general guidance only. This appliance is
a room-sealed, fan-flued boiler, consequently it does not require a permanent
air vent for combustion air supply. When installed in a cupboard or
compartment, ventilation for cooling purposes is also not required.
3A.6 WATER CIRCULATION
Specific recommendations are given in I.S. 813. The following notes are for
general guidance only.
3A.6.1 PIPEWORK It is recommended that copper tubing be used in conjunction
with soldered capillary joints. Where possible pipes should have a gradient to
ensure air is carried naturally to air release points and that water flows
naturally to drain cocks. Except where providing useful heat, pipes should be
insulated to avoid heat loss and in particular to avoid the possibility of
freezing. Particular attention should be paid to pipes passing through
ventilated areas such as under floors, loft space, and void areas.
3A.6.2 AUTOMATIC BY-PASS The appliance has a built-in automatic by-pass,
consequently there is no requirement for an external by-pass, however the
design of the system should be such that it prevents boiler cycling’. 3A.6.3 DRAIN COCKS These must be located in accessible positions to facilitate draining of the appliance and all water pipes connected to the appliance. 3A.6.4 AIR RELEASE POINTS These must be positioned at the highest points in the system where air is likely to be trapped. They should be used to expel trapped air and allow complete filling of the system. 3A.6.5 EXPANSION VESSEL The appliance has an integral expansion vessel to accommodate the increased volume of water when the system is heated. Refer to the specification table for more detailed information. 3A.6.6 FILLING POINT A method for initial filling of the system and replacing water lost during servicing etc. must be provided (see fig. 5). You should ensure this method of filling complies with the local water authority regulations. 3A.6.7 LOW PRESSURE SEALED SYSTEM An alternative method of filling the system would be from an independent make-up vessel or tank mounted in a position at least 1 metre above the highest point in the system and at least 5 metres above the boiler (see fig. 6). The cold feed from the make-up vessel or tank must be fitted with an approved non-return valve and stopcock for isolation purposes. The feed pipe should be connected to the return pipe as close to the boiler as possible. 3A.6.8 FREQUENT FILLING Frequent filling or venting of the system may be indicative of a leak. Care should be taken during the installation of the appliance to ensure all aspects of the system are capable of withstanding pressures up to at least 3 bar. 3A.7 ELECTRICAL SUPPLY The appliance is supplied for operation on 230V @ 50Hz electrical supply; it must be protected with a 3-amp fuse (supplied). The method of connection to the mains electricity supply must allow for complete isolation from the supply. The preferred method is by using a double-pole switch with a contact separation of at least 3mm. The switch must only supply the appliance and its corresponding controls, i.e. time clock, room thermostat, etc. Warning! This appliance must be earthed. 3A.8 MOUNTING ON A COMBUSTIBLE SURFACE The appliance can be mounted on a wall of combustible material without any requirement to fit any additional protective (fireresistant) material. 3A.9 TIMBER FRAMED BUILDINGS If the appliance is to be fitted in a timber framed building, it should be fitted in accordance with I.S. 813 and local Building Regulations. The Institute of Gas Engineers publication (IGE/ UP/7)
Guide for Gas
Installations in Timber Frame Buildings’ gives specific advice on this type of
installation.
3A.10 WATER TREATMENT
Vokera recommend that water treatment be carried out in accordance with the
Benchmark Guidance on water treatment in central heating systems. If water
treatment products are to be used, then they must be entirely suitable for use
with a stainless-steel heat exchanger. Any water treatment product, must be
administered in strict accordance with the manufacturer’s instructions. If the
appliance is to be installed to an existing system; water treatment and
flushing of the complete heating system should be carried out in accordance
with BS 7593 and the Benchmark Guidance on water treatment in central heating
systems.
3A.11 DECLARATION OF CONFORMITY
A Declaration of Conformity (as defined in I.S. 813) must be provided on
completion of the installation. A copy of the declaration must be given to the
responsible person and also to the gas supplier if required. This appliance
must be installed by a competent person in accordance with and defined by, the
Standard Specification (Domestic Gas Installations) Declaration (I.S. 813).
4. SECTION – INSTALLATION
NOTE
Please refer to 3/3A and use the appropriate PPE when carrying out any of the
actions or procedures contained within this section.
Fig.7
4.1 PREPARATION FOR MOUNTING THE
APPLIANCE
The appliance should be mounted on a smooth, vertical sur-
A
face, which must be capable of supporting the full weight of
the appliance. Care should be exercised when determining the
position of the appliance with respect to hidden obstructions
such as pipes, cables, etc.
When the position of the appliance has been decided using
the template supplied carefully mark the position of the anchor
holes (see Fig. 7) and flue-hole (if applicable).
Ensure that the anchors are securely fixed to support the appliance weight.
A
TIGHTENING TORQUE
Ø 3/4″ Ø 1/2”
35Nm 25Nm
17
4.2 FITTING THE FLUE
This appliance incorporates a `click-fit’ flue connection at the top of the
appliance.
NOTE: The boiler flue gas exhaust turret is sized for a concentric pipe with
an external diameter of the flue gas pipe 60 +0.6 -0.3 mm and an external
diameter of the air pipe 100 +0.3 -0.7 mm. Make sure the coupling is
watertight.
4.2.1 CONCENTRIC HORIZONTAL FLUE These instructions relate specifically to the
installation of this appliance with the Vokera 60/100mm `X-type’ (click-fit)
flue terminals accessories. For specific instructions on installing this
appliance with an alternative Vokera flue system, e.g. 80/125mm; please refer
to the instructions supplied with the specific flue system, or download the
instructions from the Vokera website. The appliance flue outlet elbow can be
rotated through 360º on its vertical axis. In addition the flue may be
extended from the outlet elbow in the horizontal plane. A reduction must also
be made to the maximum length (see table below) when ad-
ditional bends are used.
Reduction for additional bends
Bend
45º bend 90º bend
Reduction in maximum flue length for each bend 1.3 metre
1.6 metre
Horizontal/Vertical flue terminals and accessories
Part No. Description
Length/Size
20122759 XF Horizontal `Click fit’ Flue Kit 796mm C/E
20122761 XT Telescopic `Click fit’ Flue Kit 400-575mm C/E
20122763 XV Vertical `Click fit’ Flue Kit
1000mm + VC
20132060 0.5-Metre Extension
500mm
20132061 1.0-Metre Extension
1000mm
20132062 2.0-Metre Extension
2000mm
20132059 90-Degree Bend
N/A
20132058 45-Degree Bend x 2
N/A
20131979 Telescopic Extension
372/519mm
20142842 PMK Plume Kit
1370mm
20142841 45° Plume divertor
N/A
20132050 Pitched Roof Flashing
500mm x 500mm
20135582 Flat Roof Flashing
340mm Dia.
20135587 Wall Brackets
208mm C/E
20121903 Vert. Connector `Click Fit’ VC
131mm
Fig.7: referring to position A, mark and drill a hole for the passage of the
flue pipe. Both horizontal terminals (fixed & telescopic) have an eccentric
configuration, that enables condense fluid to drain back to the appliance;
consequently the terminals should be installed level.
NOTE: any horizontal runs that incorporate extensions, must have a 3-degree
fall-back to the appliance.
NOTE: Minimum horizontal flue length = 0.35m.
NOTE (Fig.8): The appliance incorporates a click-fit’ flue connection. Ensure that both screws
C’ on the click-fit’ have been slackened off. Ensure that the connector is correctly aligned with the
click-fit’ and insert it into the
click-fit’ until it clicks into position (this is when the tabs at points
A’
are located in the groove of the flue bend connector). Both screws (C) should
now be tightened. NOTE Fit the internal (white) trim to the flue assembly
prior to connecting the flue pipe to the bend. You must ensure that the entire
flue system is properly supported and connected. Seal the flue assembly to the
wall using cement or a suitable alternative that will provide satisfactory
weatherproofing. The exterior trim can now be fitted.
Fig.9
Fig.10 A
B A
C
A C
Fig.8
4.2.2 FITTING THE HORIZONTAL FLUE KIT Carefully measure the distance from the
centre of the appliance flue outlet to the edge of the finished outside wall
(dimension X). Add 65mm to dimension X to give you Dimension Y (see Fig.9).
Measure dimension Y from the terminal end of the concentric flue pipe and cut
off the excess ensuring any burrs are removed. Pass the concentric flue pipe
through the previously drilled hole. Fit the flue bend to the boiler flue
outlet and insert the concentric flue pipe into the flue bend ensuring the
correct seal is made.
18
4.2.3 EXTENDING THE FLUE Connect the bend supplied with the terminal kit
to the top
of the boiler (see Fig.8). The additional bends & extensions
have push-fit connections, care should be taken to ensure that the correct
seal is made when assembling the flue system. Connect the required number of
flue extensions or bends (up to the maximum equivalent flue length) to the
flue terminal (Fig.11). The flue system should have a 3º rise from the boiler
to outside, to ensure any condense fluid that forms, is allowed to drain back
to the appliance.
NOTE
When cutting an extension to the required length, you must
ensure that the excess is cut from the plain end of the exten-
sion (Fig.11). Remove any burrs, and check that all seals are
located properly. You must ensure that the entire flue system is properly
supported and connected. Seal the flue assembly to the wall using cement or a
suitable alternative that will provide
satisfactory weatherproofing. The interior and exterior trim can now be
fitted.
Fig.11
4.2.4 CONCENTRIC VERTICAL FLUE Using Fig.13 as a reference, cut a 110mm
diameter hole in the roof and/or ceiling to facilitate the route of the
vertical flue system. NOTE: ensure that the top of the appliance – if already
in position – is covered and protected from the possibility of any dust or
debris falling or entering the appliance via the flue outlet.
Fit the appropriate flashing to the roof and insert the vertical flue terminal
through the flashing from outside, ensuring that the collar of the terminal is
located over the outlet of the flashing.
The fixing holes for the appliance wall mounting bracket should now be drilled
and plugged. An appropriate type and quantity of fixing should be used to
ensure that the bracket is mounted securely. Once the bracket has been secured
to the wall, mount the appliance onto the bracket.
If the vertical flue system requires additional extensions or bends, connect
these to the vertical terminal, ensuring the following: – the maximum
permitted flue length is not exceeded – reductions to the maximum flue length
have been made for
any bends that are used on the vertical flue system – any horizontal sections
of the flue system, incorporate a
3-degree fallback to the appliance – the entire flue system is fully supported
and secured using
the appropriate brackets – if/when an extension is cut to a shorter length,
ensure that
the excess length is cut from the plain end of the extension, and that any
burrs or rough edges are removed – all seals are properly located before
assembling or connecting the flue system.
IMPORTANT: The VX flue terminal is supplied with a sachet of silicone
lubricant; smear a small amount of the lubricant around both inner and outer
connections, at both ends of the vertical flue connector (supplied with the VX
terminal).
NOTE (Fig.12): The appliance incorporates a click-fit’ flue connection. Ensure that both screws
C’ on the click-fit’ have been slackened off. Ensure that the connector is correctly aligned with the
click-fit’ and insert it
into the click-fit’ until it clicks into position (this is when the tabs at points
A’ are located in the groove of the vertical flue connector). Both
screws (C) should now be tightened.
NOTE: If more convenient, the vertical flue connector can be attached to the
vertical flue terminal/extension before connecting it to the appliance.
NOTE: Minimum length of vertical flue = 2m.
NOTE: Additional bends and/or extensions can be connected to the terminal
connector if desired, however if additional bends are fitted, a reduction must
be made to the maximum flue length (see table below).
Reduction for bends
Bend 45º bend 90º bend
Reduction in maximum flue length for each bend 1.3 metre 1.6 metre
Fig.13
IMPORTANT The vertical flue terminal is 1.0 metre in length and cannot be cut; therefore it may be necessary to adjust the height of the appliance to suit or use a suitable extension.
4.3 CONNECTING THE GAS & WATER (FIG.14)
The appliance is supplied with an accessory pack that includes service valves.
The service valves are of the compression type. The accessory pack contains
sealing washers’ etc, for use with the service valves. When connecting pipe
work to the valves, tighten the compression end first then insert the sealing
washers before tightening the valve to the appliance. NOTE: it will be
necessary to hold the valve with one spanner whilst tightening with another.
The valves must be fitted perpendicular with the rear of the appliance, in
order to avoid obstruction.
Fig.14
C/H return valve
Gas cock
C/H flow valve
vertical connection
Fig.12
B A C
A C
4.3.1 GAS The appliance is supplied with a 15mm service valve, connect a 15mm pipe to the inlet of the valve and tighten both nuts. NOTE: it will be necessary to calculate the diameter of the gas supply pipe to ensure the appliance has an adequate supply of gas.
flange installed as standard
19
4.3.2 FLOW & RETURN The appliance is supplied with 22mm service valves for the
flow and return connections, connect a 22mm pipe to the inlet of each valve
and tighten both nuts. NOTE: depending on system requirements, it may
necessary to increase the size of the flow & return pipe work after the
service valve connections.
4.3.3 SAFETY VALVE The appliance incorporates a combined pressure relief and
condensate discharge arrangement. Consequently the combined discharge pipe
must have a continuous fall away from the appliance and should be suitably
protected against the risk of freezing. Alternatively it is permissible to fit
a tundish, e.g. Mactun, Hotun, etc. close to or adjacent to the discharge pipe
where it exits the appliance.
The condensation exhaust system must be dimensioned and installed in such a way as to guarantee the correct evacuation of the condensation produced by the appliance and/or collected by the evacuation systems of combustion products. All the components of the condensation exhaust system must be made in a workmanlike manner using materials that are suitable for withstanding the mechanical, thermal and chemical stresses of the condensation produced by the appliance over time. Note: if the condensation exhaust system is exposed to the risk of frost, always provide an adequate level of insulation of the pipe and consider any increase in the diameter of the pipe itself. The condensation exhaust pipe must always have an adequate slope level to prevent the condensation from stagnating and its proper drainage. The condensation exhaust system must have an inspectable disconnection between the condensation exhaust pipe of the appliance and the condensation exhaust system.
Fig.15
4.3.4 CONDENSE PIPE This appliance will – under normal operating conditions
produce condensate fluid that will require to be disposed of via the
dwelling’s waste water drainage system. Vokera strongly recommends that the
condensate pipe is connected to the internal waste water pipework in
accordance with BS6798. BS6798 provides comprehensive instruction and advice
on all permissible condensate disposal methods; notwithstanding this, it is
essential that the following is strictly adhered to: – use only plastic
drainage pipe (minimum OD of 21.5mm) – horizontal runs must incorporate a
minimum 45mm fall per
metre, away from the appliance – external pipework and/or pipework in unheated
areas, must
have a minimum OD of 32mm and be insulated with Class-O pipe insulation – the
route, type, and termination of the condensate disposal method, must not
permit any spillage of condensate fluid, into the dwelling in the event of a
blockage or freezing of the condesate pipework
– if there is a risk of freezing, Vokera strongly recommends that a tundish is
incorporated within the discharge pipework (see section 4.3.3 above).
Should it not be possible to route and terminate the condensate pipework
internally using `gravity discharge’; Vokera recommends that the Vokera
condensate pump (code 404) be considered as an alternative solution. Ensure
that the end-user is aware of the effect/consequences of the condensate
pipework becoming blocked or frozen.
4.3.5 INSTRUCTION FOR CONDENSATION EXHAUST CONNECTION
b All components of the product condensation drain sy-
stem must be properly maintained in accordance with the manufacturer
instructions and cannot be modified in any way.
This product is designed to prevent the escape of gaseous products of
combustion through the condensation drain pipe with which it is equipped, this
is obtained by using a special siphon placed inside the appliance The
construction of the condensation exhaust system downstream of the appliance is
the responsibility of the installer.
4.4 ELECTRICAL CONNECTIONS
The boiler is supplied w ith a short fly-lead. This lead can be used for
connection to the electrical supply. Connect the fly-lead to a fused isolator
in the following way: · brown wire to LIVE supply · blue wire to NEUTRAL
supply · green/yellow to EARTH connection. Insert the supplied 3-AMP fuse into
the fused isolator. Should the fly-lead be unsuitable, refer to 4.6 for
details on how to connect the electrical supply directly to the boiler. The
electrical supply must be as specified in section 3/3A. A qualified
electrician should connect the appliance to the electrical supply. If controls
– external to the appliance – are required, a competent person must undertake
the design of any external electrical circuits, please refer to section 11 for
detailed instructions. ANY EXTERNAL CONTROL OR WIRING MUST BE SERVED FROM THE
SAME ISOLATOR AS THAT OF THE APPLIANCE. The supply cable from the isolator to
the appliance must be 3-core flexible seized 0.75mm to BS 6500 or equivalent.
Wiring to the appliance must be rated for operation in contact with surfaces
up to 90 ºC. NOTE: · See pages 22 & 43 for wiring of typical external controls
into
connector CE8. · Do not connect 230V to any of the CE8 terminals. · Do not
remove the white link wire from TBT unless it’s to be
used to connect an approved control.
MODBUS CONNECTION – CE4 The CE4 connector is located on the underside of the
appliance towards the front left.
b We recommend using conductors with a section no larger
than 0,5 mm2.
CE8 LOW-VOLTAGE CONNECTIONS The CE8 low-voltage connector is located on the
underside of the appliance; at the rear of the right hand side. There are
4-pairs of connectors: >TBT – Safety or alarm connector >TA – External control
(clock, etc.) >OT+ – Opentherm >SE – External sensor
20
NOTE: when an OT bus remote control is connected 1.2 to the system, the boiler display shows (see figure on bar the right):
Please note that, if OT bus remote control connected: – it is no longer
possible to set the boiler OFF/WINTER
status (which can now be set via the OT bus remote control) – the heating
setpoint value calculated by the OT bus remote control is displayed in the
“System Info” screen – it is only possible to set the heating setpoint in the
boiler if zone valve management is enabled.
12 Config aux 1
1.2 12 Config aux 1
1.2
39
bar 39
bar
Gio Set aux output
Gio Set aux output
14
JUL
Zone valve
14 JUL
Zone valve
Supplementary pump
Supplementary pump
12°C
12°C
4.6 CONNECTING THE MAINS (230V) INPUT
Unhook and remove the terminal block cover (230V).
Pass the cable through the cable anchorage point. Connect the supply cable
wires (LIVE, NEUTRAL, & EARTH) to their corresponding terminals (L, N, & E) on
the appliance high voltage terminal block (M3). When connecting the EARTH
wire, ensure that it’s left slightly longer that the others, this will prevent
strain on the EARTH wire should the cable become taut. Route the electrical
supply via the cable entry/exit point and secure to the sleeve using an
appropriate cable tie, and/or silicone sealant.
If it is anticipated that external controls will be required please refer to
the wiring diagrams in section 11 for more detailed information.
NOTE It is the installer’s responsibility to ensure that the appliance is
properly Earthed. Vokèra Ltd. cannot be held responsible for any damages or
injuries caused as a result of incorrect Earth wiring.
The value can be seen in the “System Info” screen
– to activate the COMBUSTION ANALYSIS, function, with OT bus remote control
connected, the connection must be temporarily disabled; remember to restore
this connection once the function has completed.
Alarm reset, INFO displays and settings remain active.
4.5 CASING REMOVAL
To gain internal access to the appliance you must first remove the front
cover, proceed as outlined below: · locate and unscrew the 2-screws that
secure the front cover
to the appliance · Disengage both clips at 1A to release the lower part of the
front cover · lift the cover upward to disengage it from the top locating
hooks and then remove · store the cover and screws safely until required. Re-
fit in the
reverse order · press and hold the spring tabs on either side of the control
panel where it meets the appliance side panels and gently lower it until it
rests.
3
1a
b To tighten the
2
1
screws, apply a torque of 0.6 –
0.8 Nm
1a
21
ACCESSORIES
X4
L-N antifreeze heaters
CE8
TA: (room thermostat)
CE8
OT+
CE8 SE: outdoor temperature sensor
CE8
TBT: Low temperature limit thermostat
X10
Alarm remote control
X11 Zone valve or additional pump
ATTENTION – Do not connect any high voltage (230V) power to the
connections on CE4 or CE8. – Any switched live’ (230v L/N) supply must only be connected to the CN1 terminals on relay board BE11 (see below). – Connect the Vokera external sensor to the SE connections on plug CE8 or terminals 3&4 (orange) on X18 of the PCB (see also 4.4). – Connect the Opentherm control, e.g. Hi COMFORT to the OT+ connections on plug CE8 or terminals 5 & 6 (pink) on X18 of the PCB (see also 4.4). – The TA connections on terminals 7 & 8 (black) of X18 are
voltage-free’ and MUST only
be used to switch a `voltagefree’ external control, e.g. 2-wire room
thermostat. – Do not remove the white link-wire from plug CE8.
NOTE – Only connect the Vokera external sensor if there is no
requirement for HW. – See 4.6 if the supplied `fly-lead’ is unsuitable or of
insufficient
length. – Please contact the Vokera technical helpline (0330 236
8630) if you require further information on any of the above.
22
5. COMMISSIONING & OPERATION
NOTE: please refer to 3/3A and use the appropriate PPE when carrying out any
of the actions or procedures contained within this section.
5.1 GAS SUPPLY INSTALLATION
Inspect the entire installation including the gas meter, test for tightness
and purge. Refer to BS 6891 (I.S. 813 in ROI) for specific instruction.
5.2 THE HEATING SYSTEM
The appliance contains components that may become damaged or rendered
inoperable by oils and/or debris that are residual from the installation of
the system, consequently it is essential that the system be flushed in
accordance with the following instructions.
5.3 INITIAL FILLING OF THE SYSTEM
Ensure both flow and return service valves are open, remove appliance casing
as described in 4.5, identify the automatic air release valves (AAV) and
loosen the dust cap/s by turning the cap anti-clockwise one full turn. Ensure
all manual air release valves located on the heating system are closed.
Connect the filling loop (not supplied), slowly proceed to fill the system by
firstly opening the inlet valve connected to the flow pipe, and then turning
the lever on the fill valve, to the open position. As water enters the system
the pressure gauge will begin to rise. Once the gauge has reached 1 BAR close
both valves and begin venting all manual air release valves, starting at the
lowest first. It may be necessary to go back and top-up the pressure until the
entire system has been filled. Inspect the system for water tightness,
rectifying any leaks.
5.4 INITIAL FLUSHING OF THE SYSTEM
The whole of the heating system must be flushed both cold and hot as detailed
in 5.6. Open all radiator or heating valves and the appliance flow & return
service valve. Drain the boiler and system from the lowest points. Open the
drain valve full bore to remove any installation debris from the boiler prior
to lighting. Refill the boiler and heating system as described in 5.3.
5.5 PRELIMINARY CHECKS
Before starting up the boiler, check: – confirm via the appliance data badge,
that the appliance is
suitable/configured for the gas type and electrical supply that has been
provided to the appliance – inspect the entire flue system and ensure that it
has been installed in accordance with these instructions and the relevant
standards that apply locally and/or nationally – that the required clearances
have been met in respect of the requirements for maintenance – inspect the
entire installation including the gas meter, test for tightness and purge.
Refer to BS 6891 (I.S. 813 in ROI) for specific instruction – ensure that the
rated delivery of the gas meter is adequate enough to serve this appliance and
any other gas appliance connected to the same meter – ensure that the gas
supply pipework is of adequate size to provide the maximum gas rate required
by this appliance – check that the siphon is completely filled with water,
otherwise fill it up (see chapter 5.7).
b Before connecting the “Hi, Comfort T300 or K100” de-
vices, the Connectivity Menu must be set up correctly to avoid communication
failure problems (see section section 8.10).
5.6 FINAL FLUSHING OF THE HEATING
SYSTEM
The system shall be flushed in accordance with BS 7593 (I.S. 813 ROI). Should
a cleanser be used, it must be suitable for stainless-steel heat exchangers.
It shall be from a reputable manufacturer and shall be administered in strict
accordance with the manufacturers’ instructions and the DWTA code of practice.
NOTE: Chemicals used to cleanse the system and/or inhibit corrosion must be pH
neutral, i.e. they should ensure that the level of the pH in the system water
remains neutral. Premature failure of certain components can occur if the
level of pH in the system water is out-with normal levels.
5.7 FIRST COMMISSIONING
On first ignition after prolonged inactivity and after maintenance, before
putting the appliance into operation it is essential to
proceed as described in the following paragraphs. At the first
start-up, the calibration procedure (GAC) is also recommen-
ded to allow the boiler to reach its optimal performance. If the
procedure is not performed, the display shows “CFG – GAC Not performed”. It is
also essential to fill the condensate collection siphon by pouring about 1
litre of water into the boiler combustion analysis take-off and check: – that
the float within the trap is free and moving – the correct flow of water from
the boiler outlet discharge
pipe
– there are no leaks of the condensate drain connection line.
Correct operation of the condensate drain circuit (siphon and
pipes) requires that the condensate level does not exceed the maximum level
(max). Prior filling of the siphon and the presence of the safety float inside
the siphon is designed to prevent the escape of combustion gases into the
environment.
High efficiency mode (SERVICE) In this mode, the boiler limits the power output in heating for 60 minutes to a minimum value. Activating the chimney sweep temporarily disables this function.
12 Service menu
39
Gio
Chimney sweep
14 JUL
Ipd
Alarm history
Call service
Call service
12°C
High efficiency enable Not active
Contact service
1.2 12 High efficiency enable
1.2
bar 39
Activate function
bar
Gio
14 JUL Siphon fill time
Siphon fill delay
12°C
12 High efficiency enable
39
Activate function
Gio
14
Siphon fill time
JUL 60 Min
Siphon fill delay
60 Days
1.2 12 bar 39
Gio 14 JUL
1.2 bar
High efficiency in pro-
1.2
bar
gress
45 52 °C
°C
.5
.5
Heating
Hot water
12°C
12°C
42.5°C
49.5°C
5.8 VENTING CYCLE
Turn the main system switch ON. Every time the boiler is powered up, a vent
cycle is run lasting 4 minutes.
12°C
75%
Air purging cycle
b When the vent cycle is running all heat requests are
inhibited except for DHW requests when the boiler is not in OFF.
If the boiler is not in the OFF condition, the vent cycle can be interrupted by tapping the “x” on the progress bar.
5.9 MANUAL CALIBRATION PROCEDURE
(GAC)
The GAC procedure, which is useful to calibrate the gas valve and combustion
control system, is mandatory following: gas conversion – gas valve replacement
– board replacement fan replacement – cleaning of primary heat exchanger
and/or burner – replacement of flame detection electrode (ionisation) –
replacement of burner insulation panel – modification of suction/exhaust
pipes.
23
The GAC procedure must also be carried out on first startup. If this procedure is not carried out in the time required, the boiler will still be safe however it may be limited in performance and may also process combustion control signals.
b The procedure must be performed with the casing
closed.
The msg “CFG – call for GAC” is only displayed on the home page if the function has never been performed.
12 39
Gio
45 14
°C
JUL
.5
Heating
1.2
bar
52 °C .5
Hot water
12°C
42.5°C
Cfg
49.5°C
call for gac
– Power up the boiler and wait for the vent cycle to run (see paragraph
section 5.8).
– If in the OFF condition, set the boiler to WINTER. – Generate a HEAT
request. Although there are no limitations on
the part of the system, except those foreseen by the ALARMS supervision,
however, it is advisable to do the GAC scan with boiler return system water
below 15°C or in any case with a temperature compatible with the flow rate of
system water towards the boiler. – Wait until the flame symbol appears on the
display. No key must be pressed at this stage.
12 Combustion
39
Gio 14
Gas – gas type Methane
JUL D52 – p1 GAS VALVE
45
Gac
1.2 12 Gac
1.2
bar 39
bar
Gio 14 JUL
Perform full calibration?
Apl – power
12°C 25 kW
12°C
OK
12 Gac 39
Gio 14 JUL
Please wait
1.2 12 bar 39
Gio 14 JUL
Gac
4950
1.2
bar RPM
12°C
12 39
Gac
Gio 14 JUL
Calibration carried out successfully
12°C 1.2
bar
Calibration in progress
12°C
NOTE: If it is not possible to dissipate heat, it is still possible for high-
temperature systems to carry out the GAC in a heating request by setting the
heating water setpoint to 80.5°C, or even better, by activating the chimney
sweep function and then, with the flame on, starting the GAC.
If the GAC is successfully completed, return to the main screen by pressing
the HOME button; if the message “Calibration failed. Retry?” is displayed, you
can repeat the procedure by pressing the OK button.
If the procedure is not carried out when it is mandatory to do so, this non-
compliance may lead to a limited operation and the possibility of abnormal
combustion control signals occurring.
If a fault occurs during the procedure or if the heat request is interrupted,
the procedure would be terminated prematurely by displaying the fault status
or automatically returning to the main screen. In this case, the procedure
must be repeated.
5.10 SETTING THE THERMOREGULATION
NOTE: Thermoregulation via an external sensor is unsuitable for systems that incorporate a domestic hot water cylinder.
Thermoregulation is only available with an outdoor temperature sensor connected and is only active for the HEATING function.
12 39
Gio 14 JUL
12°C
Heating
Type of heating High temperature Max temp 80.5°C
Min temp 40°C
Thermoregulation Activate
Hourly scheduling Activate
1.2 12 Thermoregulation
1.2
bar 39
bar
Gio Activate function
14
Climatic curve
JUL 0.4
Night compensation Not active
Building type
12°C
5 Min Outdoor reactivity
20
12 Thermoregulation
1.2
39
bar
Gio Activate function
14
Climatic curve
JUL 0.4
Night compensation Not active
Building type
12°C
5 Min Outdoor reactivity
20
With the function not enabled or an outdoor temperature sensor, the boiler works at a fixed-point. The electronic thermostat algorithm will not use the measured outdoor temperature value directly, but rather an average outdoor temperature value , which takes account of the insulation of the building: in well-insulated buildings, outdoor temperature variations have less influence on the ambient temperature than in less insulated buildings. This value together with the temperature detected by the outdoor temperature probe can be displayed in the following screen:
12 System info
39
Gio
Screed heating hours
14 JUL
Flow probe
Return probe
1.2
bar 0 21°C 22°C
Dhw probe
20°C
12°C Dhw set
Exhaust probe
44°C 33°C
REQUEST FROM OT CHRONOTHERMOSTAT In this case, the delivery setpoint is calculated by the timed thermostat on the basis of the outdoor temperature value, and by the difference between the real ambient temperature and the required ambient temperature.
REQUEST FROM ROOM THERMOSTAT
In this case, the delivery setpoint is calculated by the adjustment
board on the basis of the outdoor temperature value, to obtain an
estimated ambient temperature of 20° (reference ambient tem-
perature). There are 2 parameters that are used to calculate the
delivery setpoint: slope of the compensation curve (KT) – modifiable by
technical
personnel offset to reference ambient temperature – can be modified by
the user.
12 39
Building type
1.2 12 bar 39
Outdoor reactivity
1.2
bar
Gio
Gio
14
14
JUL
5
Min
JUL
20
12°C
12°C
OK
OK
12 Climatic curve
1.2
39
bar
Gio
14
0,2 JUL
12°C
OK
TYPE OF BUILDING It is indicative of the frequency with which the value of the calculated outdoor temperature for thermoregulation is updated, a low value for this value will be used for buildings that have little insulation.
24
REACTIVITY SEXT It is an indication of the speed with which variations of the measured outdoor temperature affect the calculated outdoor temperature value for thermoregulation, low values indicate high speeds.
CURVE SLOPE The heating thermoregulation curve maintains a theoretical temperature of 20°C in the room for outdoor temperatures between +20°C and -20°C. The choice of the curve depends on the minimum design outdoor temperature (and thus the geographical location) and the design flow temperature (and thereby the type of system) and should be carefully calculated by the installer, according to the following formula:
Tshift =
KT = Project delivery T. – Tshift 20- min. outdoor project T.
30°C standard system 25°C floor installations
If the calculation gives an intermediate value between two bends, you are advised to choose the thermoregulation bend closest to the value obtained.
Example: if the value obtained from the calculation is 1.3, it lies
between curve 1 and curve 1.5. Choose the nearest curve, i.e.
1.5. The settable KT values are as follows: standard system: 1,0÷3,0 free-
standing system 0,2÷0,8.
Delivery temperature (°C)
100 90 MAX 80 CH SET 70
60 MIN 50 CH SET 40
30
20 20 15
THERMOREGULATION CURVES 3,0 2,5
10 5 0 -5 -10 External temperature (°C)
2,0 1,5
1,0 0,8 0,6 0,4 0,2
-15 -20
Offset on the reference ambient temperature In any case, the user can indirectly modify the HEATING setpoint value by inserting an offset on the reference temperature (20°C). This offset may vary from -5 to +5 (offset 0 = 20°C). To correct the offset, refer to section section 8.4″.
Delivery temperature (°C)
CLIMATIC CURVE CORRECTION 90
80
70
60
50
40
30
+5°C
20
20°C
10
-5°C
30 25 20 15 10 5 0 -5 -10 -15 -20
External temperature (°C)
12 Night compensation 39
1.2
bar
Gio Activate function
14
JUL
12°C
NIGHT COMPENSATION If a time programmer is connected to the input ROOM
THERMOSTAT the night compensation can be enabled. In this case, when the
CONTACT is CLOSED, the heat request is made by the flow probe on the basis of
the outdoor temperature, to obtain a nominal ambient DAY temperature (20°C).
The OPENING OF THE CONTACT does not produce a switch-off, but rather a
reduction (parallel shift) of the climatic NIGHT curve (16°C).
Delivery temperature (°C)
PARALLEL NIGHT TIME REDUCTION 90
80
70
DAY TEMPERATURE CURVE
60
50
NIGHT TEMPERATURE CURVE
40
30
20
10 20 15 10 5 0 -5 -10 -15 -20 External temperature (°C)
In this case too, the user can indirectly modify the HEATING setpoint value by
inserting an offset on the reference DAY temperature (20°C) or NIGHT
temperature (16°C). This offset may vary from [-5 to +5]. NIGHT COMPENSATION
is not available if OT+ chrono is connected. To correct the offset, refer to
section section 8.3.
5.11 “COMFORT FUNCTIONS” & “SPECIAL DHW FUNCTIONS”
These functions apply only to the combi version of this appliance; if they are
displayed or activated, the appliance will require to be re-configured to the
correct hydraulic configuration.
5.12 SCREED HEATER FUNCTION
If the system is at low temperature the boiler provides a `screed heater’ function (function only available in OFF-state) which can be activated as follows:
12 39
1.2 bar
1.2 12 bar 39
Heating
Pump control type
1.2
bar
Gio
Gio 85
14 JUL
14 JUL
Ot cascade control Activate
Boiler off
Screed function
Antifreeze function
Anti cycle function
12°C
12°C 3Min
Reset ch timers
Activate
12 Screed function 39
1.2 12 bar 39
1.2 bar
1.2
bar
Gio
Gio
14
14
JUL
Proceeding with the screed
JUL
function?
Boiler off
Antifreeze function
12°C
OK
12°C
75%
Screed Function in progress
The screed heater function lasts 168 hours (7 days) during
which, in the zones configured as low temperature, a heating
request with initial zone delivery setpoint of 20°C is simulated,
subsequently increased according to the table indicated
below.
By accessing the `System Info’ menu, it is possible to display
the value for the number of hours that have elapsed since
the activation of the screed heater function. Once activated,
the function takes priority, if the machine is shut down by
disconnecting the power supply, when it is restarted the
function picks up from where it was interrupted. The function
can be interrupted before its end by switching the boiler to a
state other than OFF or by disabling the parameter.
DAY 1
TIME 0
TEMPERATURE 20°C
6
22°C
12
24°C
18
26°C
2
0
28°C
12
30°C
3
0
32°C
4
0
35°C
5
0
35°C
6
0
30°C
7
0
25°C
Note: The temperature and increase values can be set to different values only by qualified personnel, only if strictly necessary. The manufacturer declines all responsibility if the parameters are incorrectly set.
25
5.13 COMBUSTION CHECK
b The checks of the settings of CO2 in relation to the reference
parameters, indicated in the tables below, must be carried out with the casing
closed.
To carry out the combustion analysis, proceed as follows:
1 12 39 Gio 14 JUL
1.2 bar
1.2
bar
2
Boiler off
Antifreeze function
12°C
3
12 Service menu
39
Gio
Chimney sweep
14
Ipd
JUL
Alarm history
Call service
Call service
12°C
High efficiency enable Not active
Contact service
12 Fan revolutions 39 4950 RPM
Gio 14
JUL 4950
The probe for the fumes analysis must be inserted until it reaches the stop.
1.2 12 Chimney sweep
1.2
bar 39
bar
Gio 14 JUL
Start Combustion analysis now?
12°C
OK
1.2
bar
RPM
12°C
MIN
RATED
MAX
Holding down the heating and Wi-Fi keys will take you to the chimney sweep function page without going through the password-protected technical menu.
CO2* max
METHANE GAS (G20)
LIQUID GAS (G31)
20S
8,8
25S
8,8
32S
8,8
(*) CO2 tolerance = ±1%
10,0
%
9,9
%
9,9
%
CO2* min
METHANE GAS (G20)
LIQUID GAS (G31)
20S
8,8
25S
8,8
32S
8,8
(*) CO2 tolerance = ±1%
10,0
%
10,0
%
10,0
%
Check that the values of O2 (max, nominal and min) related to
20% hydrogen mixture are in accordance with the following.
20S 25S 32S
max
% 2,4 2,4 2,4
O2 value relative to the 20% hydrogen mixture
Qmax Qmin
nominal min max nominal
% 4,3 % 6,2 % 2,4 % 4,3
4,3 6,2 2,4 4,3
4,3 6,2 2,4 4,3
min
% 6,2 6,2 6,2
– The COMBUSTION ANALYSIS lasts a maximum of 15 minutes; the procedure can be
terminated prematurely by pressing the (HOME) key.
– If the system is in low temperature, live, without mixing or thermostatic
valves, the COMBUSTION ANALYSIS must be carried out in DHW request mode.
b COMBUSTION ANALYSIS is terminated prematurely if:
– the delivery temperature exceeds 95°C; it will ignite again when the
temperature falls below 75°C
– a flame is not detected resulting in an alarm
b – in the event of an alarm. With the “Config OT bus” function active,
combustion control is not possible. To carry out the flue gases analysis,
deactivate the function. Remember to reset the function once the combustion
check has been completed.
12 Ot config
1.2
39
bar
Gio Activate function 14
JUL
b With the chimney sweep function in progress, press the
HOME button to activate the “GAC” procedure (follow the indications provided
in section 5.9).
The display shows:
12 Chimney sweep 39 1400 rpm
Gio 14
JUL 1000
1.2 12 Chimney sweep bar 39 7843 rpm
Gio
14
7900 RPM
JUL
1.2
bar RPM
12°C
MIN
RATED
MAX
12°C
MIN
RATED
MAX
12°C
When the check has ended: exit the function by pressing “<” remove the
analyser probe and close the combustion analysis
outlet with the relative plugs and screw put the analysis probe adapter
(supplied with the boiler) in the
documentation envelope set the boiler to the required operating mode,
depending on
the season regulate the requested temperature values according to
needs.
By setting the maximum value, the boiler will operate at maximum output; by
setting the minimum value, the boiler will operate at minimum output.
Check on the analyser that CO2 max and minute values comply with the following
tables.
26
5.14 ADJUSTMENTS
The boiler has already been adjusted during manufacturing by the manufacturer. However, if it is necessary to carry out the adjustments again (for example after extraordinary maintenance, after replacing the gas valve, after a gas transformation or after replacing the board) follow the procedures described below.
Maximum and minimum power and maximum heating adjustments must be carried out only by qualified personnel:
– Power the boiler
12 39
Gio 14 JUL
12°C
Configuration
Min rpm 1000 RPM Max rpm 7900RPM Max ch rpm 6300 RPM Range rated 6300 RPM
1.2 12 Min rpm
1.2
bar 39
bar
Gio
14
1000 JUL RPM
12°C
OK
12 Max rpm 39
1.2 12 Max ch rpm
1.2
bar 39
bar
Gio
Gio
14
14
7900 JUL RPM
6300 JUL RPM
12°C
OK
12°C
OK
– set the desired values by referring to tables 1 and 2 – check that the
values on the two screens are the same.
b
The maximum heating fan speed used will be the one set in the RANGE RATED screen.
12 Max ch rpm 39
1.2 12 Range rated
1.2
bar 39
bar
Gio 14
6300 JUL RPM
Gio
14
6300 JUL
RPM
12°C
OK
12°C
OK
Once the gas conversion has been carried out: – check that the fan speed
corresponds to the indications pro-
vided in tables 1 and 2, section section 5.15 – carry out a new “GAC”
procedure (see section 5.9).
5.16 OUTPUT CHANGE
To change the boiler output type:
12 Combustion
1.2 12 Apl – power
1.2
39
bar 39
bar
Gio 14
Gas – gas type Methane
Gio
25 Kw
14
JUL D52 – p1 GAS VALVE
JUL
35 Kw
45
Gac
Apl – power
12°C 25 kW
12°C
Configure the fan speeds of your boiler as indicated in tables 1 and 2,
section section 5.15.
MODEL 20kW – select 25kW and modify the fan revolutions according to the
indications provided in tables 1 and 2 of the relevant model. MODEL 30kW –
select 35kW and modify the fan revolutions according to the
indications provided in tables 1 and 2 of the relevant model.
b Disconnect and reconnect power to the boiler after
changing the parameters.
5.17 SIGNALLING AND FAULTS
GREEN
DISPLAY WITH REGULAR OPERATION
ORANGE
RED
table 1 MAXIMUM NO. FAN
ROTATIONS 20S 25S 35S
table 2 MINIMUM NO. FAN
ROTATIONS 20S 25S 32S
METHANE GAS (G20)
6,300 6,200 7,700
METHANE GAS (G20)
1,000 1,100 1,100
LIQUID GAS
(G31)
6,100
rpm
5,800
rpm
7,500
rpm
LIQUID GAS
(G31)
1,250
rpm
1,250
rpm
1,250
rpm
5.15 GAS CONVERSION
b Conversion from a family gas to other family gas can be b performed easily
also when the boiler is installed.
This operation must be carried out by professionally qualified personnel.
The boiler is designed to operate with methane gas (G20) according to the product label. It is possible to convert the boiler to LPG (G31) as follows:
12 Combustion
1.2 12 Gas – gas type
1.2
39
bar 39
bar
Gio 14
Gas – gas type Methane
Gio
Methane
14
JUL D52 – p1 GAS VALVE
JUL
Lpg
45
Gac
Type gas 3
Apl – power
12°C 25 kW
Type gas 4
12°C
b Switch the boiler off and on again after changing
parameters.
DISPLAY WITH
A FAULT
PRESENT
12
1.2 12
1.2
39
bar
39
bar
Gio
Gio
14
14
JUL E077
Absence of communication with low temperature thermostat
JUL
E011 Parasitic flame
12°C
12°C
The presence of a fault is indicated with two different colours: – orange:
indicates that a self-resetting transient error is present
which could limit the correct operation of the boiler
– red (together with the symbol ) indicates the presence of an error which will put the boiler into a lockout condition.
Reset function To restore operation of the boiler in the event of a fault, press
. At this point, if the correct operating conditions have been
restored, the boiler will restart automatically. A maximum of 5
consecutive unlocking attempts can be made from the inter-
face, after which the interface displays
12
1.2
39
bar
Gio
14
JUL
E099 reset attempts exhausted
12°C
In this case, the boiler must be disconnected from the electricity supply and
then reconnected again, to reactivate operation.
b If the attempts to reset the boiler do not work, contact the
Technical Assistance Centre.
27
PRESSURE fault When the pressure value falls below 0.5 bar, the following situations can occur:
warning signal FIL
12
0.5
39
bar
Gio
FIL
14
JUL
FIL LOW WATER PRESSURE
CHECK THE HTG SYSTEM
12 °C
The boiler is operating normally, but it is still recommended to fill the system in the way described in section “4.1 HOW TO TOP-UP THE SYSTEM PRESSURE” page 8.
temporary fault – E041
12
0.2
39
bar
Gio 14 JUL
E041
Low water pressure
12°C
12 System info
39
Gio
Screed heating hours
14 JUL
Flow probe
Return probe
Dhw probe
12°C Dhw set
Exhaust probe
1.2
bar 0 21°C 22°C 20°C 44°C 33°C
5.18 REPLACING THE GAS VALVE
After replacing the gas valve it is necessary to reset the value P1 (see
photo) as follows:
The boiler is not working properly. Fill the system as described in the previous point; operation required within 10 minutes of the message appearing otherwise the anomaly becomes definitive (E040).
definitive fault – E040
12
0.2
39
bar
Gio
14
JUL
E040
Low water pressure
12°C
In the event of a permanent lockout, fill the system and then release the alarm.
Press to restore operation.
Once operation is restored, the boiler performs an automatic vent cycle.
b If the drop in pressure is very frequent, request the inter-
vention of the Technical Assistance Centre.
DHW PROBE fault (E060)
Indicates a possible configuration error; please contact Vokera Technical or
the Service Centre for assistance.
PRIMARY HEAT-EXCHANGER CLEANING fault (E091) The boiler has an auto-diagnostic system which, based on the total number of hours in certain operating conditions, can signal the need to clean the primary heat exchanger. Once the cleaning operation has been completed with the cleaning kit supplied as an accessory, it is necessary to reset the total hours meter as follows:
12 39
Configuration
Gio Config aux 1 14 Not set
JUL Exhaust probe reset
1.2 12 Exhaust probe reset
1.2
bar 39
bar
Gio
14
JUL Proceed with reset of the hour counter of the flue gas probe?
12°C
12°C
OK
NOTE: The meter resetting procedure should be carried out after each in-depth
cleaning of the primary exchanger or if this latter is replaced.
The fault occurs when the hour meter exceeds 2500 hours; this value can be
verified as follows: access the “System Info” menu to display the value of the
flue
gas probe meter (display/100, example 2500h = 25).
12 39
1.2 bar
1.2 12 Combustion bar 39
1.2
bar
Gio 14
Gio 14
Gas – gas type Methane
JUL
JUL D52 – p1 GAS VALVE
45
Boiler off
Gac
Antifreeze function
12°C
Apl – power
12°C 25 kW
12 Gac
1.2
39
bar
Gio 14 JUL
Perform full calibration?
12°C
OK
– using the arrows, enter the second and third digits of the value P1 (e.g.
034 becomes 34) shown on the gas valve present in the boiler (each gas valve
has its own offset P1 value), confirm.
b Disconnect the boiler from the power supply for at
least 10 seconds; then reconnect to the mains power supply.
Once the replacement is complete, a new “GAC” procedure must be carried out
(see section 5.9).
b If the gas valve is replaced, also replace the relative sealing
gaskets.
To tighten the gas valve ramp nut, apply a torque equal to 25 Nm, limiting the
rotation of the valve.
5.19 REPLACING THE INTERFACE
System configuration operations must be carried out by professionally
qualified personnel of the Technical Assistance Centre. If the interface card
is replaced, the user may be asked to reset the time and day of the week
values at power on (see section 5.7); also check and reset, if necessary,
information on hourly heating and DHW programming (see section 8.1) and the
Feeder Bottle function (see section 8.11); note that no reprogramming of the
configuration parameters is necessary, the value of which is retrieved from
the regulation and control board in the boiler. Instead, it may be necessary
to reset the DHW and/or heating setpoint values.
28
5.20 BOARD REPLACEMENT
If case of the control board is replacement and adjustment procedure, it may
be necessary to check the configuration parameters and possibly reconfigure
them. Consult the parameter table to identify the board default values, the
factory set values and the customized ones. The parameters to necessarily be
checked and possibly reset are: GAS – GAS TYPE d52 – P1 GAS VALVE (with boiler
in OFF) APL – POWER HYDRAULIC CONFIGURATION WATER PRESSURE TRANSDUCER (SERVICE) MIN FAN SPEED MAX FAN SPEED MAX FAN SPEED HTG RANGE RATED. Disconnect the boiler from the power supply for at least 10 seconds; then reconnect to the mains power supply. Once the replacement is complete, perform a new “GAC” procedure must be carried out (see section 5.9).
ERROR CODE E010 E011 E012 E013 E014 E015 E020 E021 E030 E031 E032 E033 E034
E035 E036 E037 E038 E039 E040 E042 E071 E075 E081 E088 E090 E092 E093 E094
E097 E098 E099 E041 E050 E051 E052 E055 E056 E060 E070 E071 E072 E077 E080
E081 E082 E090 E091 E095 E096 FIL
pressure value
COM
E065
FWER
CFS SFS
OBCD
LLL CFG
ERROR MESSAGE MAXIMUM NUMBER OF IGNITION ATTEMPTS
PARASITIC FLAME MAXIMUM NUMBER OF FLAME LOSSES
SERIAL PROTOCOL FLAME DETECT TEST FAILED VOLTAGE DETECT FLAME TEST FAILED
LIMIT THERMOSTAT GAS VALVE CONTROL MALFUNCTION
FAN ERROR FAN FAILURE MECHANICAL BLOCKAGE
ROTOR FAN FAILURE BLOCKED ROTOR FAN FAILURE DAMAGED CHIMNEY OBSTRUCTION IN
PREVENTILATION BLOCKAGE OBSTRUCTION FLUE GAS LOW POWER BLOCKAGE OBSTRUCTION
FLUE GAS HIGH POWER FAILED COMBUSTION CHECK LOW POWER COMBUSTION CHECK FAILED
HIGH POWER
ABNORMAL FLAME VALUE LOW WATER PRESSURE WATER TRANSDUCER – LWCO ERROR HEATING
TEMPERATURE OVER LIMIT VALVE OPENING LIMIT REACHED RETURN TEMPERATURE OVER
LIMIT
CAC FAILED EXHAUST PROBE ERROR
CALIBRATION FAILED TOO MANY CALIBRATION ATTEMPTS
LAMBDA OVER LIMIT Check FAILED GAC FAILED
RESET ATTEMPTS EXHAUSTED LOW WATER PRESSURE
SMOKE OBSTRUCTION ERROR LOW POWER SMOKE OBSTRUCTION ERROR HIGH POWER
HARDWARE ERROR OUT OF THRESHOLD NO CARD FAN COMMUNICATION
NO COMMUNICATION MICROPROCESSOR CARD CONFIGURATION ERROR CH PROBE ERROR
HEATING TEMPERATURE OVER LIMIT DELTA T RETURN OUT OF LIMIT
ABSENCE OF COMMUNICATION WITH LOW TEMPERATURE THERMOSTAT RETURN PROBE ERROR
RETURN TEMPERATURE OVER LIMIT WARNING DELTA TEMPERATURE EXHAUST PROBE ERROR
CLEAN PRIMARY HT EXCHANGER CALIBRATION FAILED LAMBDA OVER LIMIT
LOW WATER PRESSURE CHECK THE HTG SYSTEM HIGH WATER PRESSURE CHECK THE HTG
SYSTEM
APPLIANCE PCB COMMUNICATION LOST (more than 30 seconds)
IMOD ERROR
WARNING FIRMWARE VERSIONS NOT COMPATIBLE
CALL FOR SERVICE STOP FOR SERVICE
ON BOARD CLOCK DAMAGED
GENERIC FIRMWARE BLOCK GAC NOT EXECUTED
ERROR TYPE DESCRIPTION
DEFINITIVE
TRANSITORY
SIGNAL SIGNAL: (the boiler continues to operate
but with no display or keys) SIGNAL
SIGNAL: (the boiler continues to operate but with no display or keys) SIGNAL
DEFINITIVE
SIGNAL: (the boiler continues to operate but with no display or keys) SIGNAL
SIGNAL
29
6. MAINTENANCE AND CLEANING
Periodic maintenance is essential to the safety, efficiency and duration of
the boiler. It allows for the reduction of consumption, polluting emissions
and keeping the product safe and reliable over time. Before starting
maintenance operations: turn off the fuel and water taps of the heating and
domestic
hot water system. To ensure product characteristics and efficiency remain
intact and to comply with current regulations, it is necessary to render the
appliance to systematic checks at regular intervals. This normally means the
following tasks: removing any oxidation from the burner removing any scale
from the heat exchangers check the state of deterioration of the electrodes
and, if they
have deteriorated, replace them together with their seals check and general
cleaning of exhaust and intake pipes checking the external appearance of the
boiler checking the ignition, switch-off and operation of the appli-
ance, in heating mode checking the seal on the couplings and the
gas/water/conden-
sate connection pipes checking gas consumption at maximum and minimum output
checking the integrity of the insulation of electrical cables, par-
ticularly in the vicinity of the primary heat exchanger checking the gas
failure safety device checking and cleaning the siphon checking the
cleanliness of the fan, internal extraction (includ-
ing the air filter when provided)
b checking there is water in the drain-trap; if not, fill it. The electronic
board and the gas valve do not require a
b specific check aimed at evaluating aging and deterioration. When servicing
the boiler, the use of protective clothing is
b recommended in order to avoid personal injury. After maintenance work has
been carried out, an analysis of the combustion products must be carried out
to check
b that they are functioning properly. Do not clean the appliance or its parts
with inflammable
b substances (e.g. petrol, alcohol, etc.). Do not clean panels, painted parts
and plastic parts with
b paint thinner. Panel cleaning must be carried out only with soapy water.
Cleaning the primary heat exchanger Switch off the electrical supply by
turning the main system
switch OFF. Close the gas shut-off valve. Remove the casing as explained in
section 4.5. Disconnect the connection cable of the ignition and detection
electrodes. Disconnect the power cables of the fan. Remove the clip securing
the gas train from the mixer. Loosen the gas train nut. Extract the gas train
from the mixer and rotate it. Remove the 4 nuts that secure the combustion
unit. Remove the air/gas conveyor assembly including fan and
mixer, taking care not to damage the insulation panel and electrode. Remove
the siphon connecting pipe from the condensate drain fitting of the heat
exchanger and connect a temporary collecting pipe. At this point proceed with
the heat exchanger cleaning operations. Vacuum out any dirt residue inside the
heat exchanger, taking care NOT to damage the retarder insulating panel.
b Clean the coils of the heat exchanger with a soft bristled brush. DO NOT USE
METAL BRUSHES THAT COULD DAMAGE THE COMPONENTS.
Clean the spaces between the coils using a 0.4 mm thick blade or similar.
Vacuum away any residue produced by the cleaning intervention. Rinse with
water, taking care NOT to damage the retarder
insulating panel.
b If there are stubborn fuel gas deposits on the heat
exchanger surface, remove them by spraying with natural white vinegar, taking
care NOT to damage the retarder insulating panel.
Leave it to work for a few minutes. Clean the coils of the heat exchanger with
a soft bristled brush.
b DO NOT USE METAL BRUSHES THAT COULD DAMAGE
THE COMPONENTS.
Rinse with water, taking care NOT to damage the retarder insulating panel.
Make sure the retarder insulation panel is undamaged and replace it if
necessary following the relative procedure.
After cleaning, carefully assemble the components again repeating the
indications provided above but in the reverse order.
To tighten the fastening nuts of the air/gas conveyor assembly, use a
tightening torque of 6 Nm, following the sequence indicated on the die-cast
(1,2,3,4).
Turn the power and gas feeding to the boiler back on.
b It is necessary to carry out a new “GAR” procedure followed
b by the “GAC” procedure (see section 5.9). What is indicated is also valid in
the case of replacement of the conveyor alone, the exchanger or the conveyor
and exchanger assembly.
Cleaning the burner Switch off the electrical supply by turning the main
system
switch OFF. Close the gas shut-off valve. Remove the casing as explained in
section 4.5. Disconnect the connection cable of the ignition and detection
electrodes. Disconnect the power cables of the fan. Remove the clip securing
the gas train from the mixer. Loosen the gas train nut. Extract the gas train
from the mixer and rotate it. Remove the 4 nuts that secure the combustion
unit. Remove the air/gas conveyor assembly including the fan
and mixer, taking care not to damage the insulating ceramic panel and the
electrodes. At this point proceed with the burner cleaning operations. Clean
the burner with a soft bristle brush, taking care not to damage the insulation
panel and electrodes.
b DO NOT USE METAL BRUSHES THAT COULD DAMAGE
THE COMPONENTS.
Check that the burner insulating panel and the sealing gasket are undamaged
and replace them if necessary, following the relative procedure.
After cleaning, carefully assemble the components again repeating the
indications provided above but in the reverse order.
To close the fixing nuts of the air/gas conveyor assembly, use
a tightening torque of 6 Nm. Turn the power and gas feeding to the boiler back
on.
b Carry out an analysis of the combustion products. Only if it
returns values outside of tolerance, it is necessary to repeat a
new “GAR” procedure followed by the “GAC” procedure (see
section 5.9).
b What is indicated is also valid in the case of replacement
of the conveyor alone, the exchanger or the conveyor and
exchanger assembly.
Replacing the burner insulating panel Loosen the screws holding the
ignition/detection electrode,
and remove it. Remove the burner insulating panel by inserting a blade just
under the surface. Remove any residual fixing adhesive. Fit the new burner
insulating panel. The new insulating panel does not need to be fixed with an
adhesive as its geometric form ensures perfect coupling with
the heat exchanger flange. Refit the ignition and detection electrodes using
the screws
previously removed and replacing the relevant seal. To tighten
the screws, apply a torque of 2.3 Nm.
b Do not perform GAR and/or GAC.
30
Siphon check and cleaning
Cleaning the air filter
Disconnect the pipes (A – B), remove the clip (C) and remove
the drain-trap.
Clean the parts of the drain-trap to remove any solid residue.
b Carefully reposition the previously removed components.
b At the end of the cleaning sequence, fill the drain-trap with
A
b water (see section 5.7) before re-starting the boiler. Do not perform GAR and/or GAC.
b What is indicated also applies in the case of replacing the
siphon.
B A
C
Ignition and detection electrodes The ignition and detection/ionization sensor
electrodes perform an important function in the boiler ignition phase and in
maintaining correct combustion; in this regard, during annual maintenance, it
is necessary to always check that they are correctly positioned and that the
reference dimensions indicated in the figure are strictly respected.
Unscrew the fixing screw A and extract the air filter. Blow compressed air
over the filter to remove any impuri-
ties. In the event of persistent dirt, wash with water.
b It is necessary to carry out a new “GAR” procedure follo-
wed by the “GAC” procedure (see section 5.9).
Board replacement The control and regulation board does not provide a specific
procedure for verifying its deterioration. In case of replacement, refer to
section 5.21.
Interface board replacement The interface board does not provide a specific
procedure
for verifying its deterioration. In case of replacement, refer to section
5.20.
Gas valve replacement The gas valve does not provide a specific procedure for
checking its deterioration. In case of replacement, refer to section 5.19. The
gas valve does not provide a specific cleaning procedure.
a Do not sand the electrodes. If the electrodes need to be
cleaned, dust them using a soft bristle brush.
b In the event of deformation and deterioration of the elec-
trodes outside the tolerances, replace them.
To tighten the screws, apply a torque of 2.3 Nm.
b In order to prevent potential operating anomalies, the ignition
and detection/ionisation sensor electrodes must be replaced
b every 5 years. It is necessary to carry out a new “GAR” procedure followed
by the “GAC” procedure (see section 5.9).
31
7. PASSWORD SETTING FOR ACCESSING AND CHANGING PARAMETERS IN THE TECHNICAL
MENU
In the manual, follow the procedure described whenever a password needs to be
entered in order to access parameters:
12 39
1.2 bar
1.2
bar
Gio
45 14
°C
JUL
.5
52 °C .5
Heating
Hot water
12°C
42.5°C
49.5°C
12 Menu 39 Technical menu
Gio Blocked 14 JUL
12°C
1.2
12 Security password
1.2
bar
39
bar
Gio
14
JUL 0 0 0 0
12°C
OK
7.1 PROGRAMMABLE PARAMETERS
Below is a list and description of the programmable parameters: USER (always
available) and INSTALLER (access with psw 18): set the password as indicated
in the previous chapter.
b Some of the information and functions indicated be-
low may not be available depending on the access
level, status and type of machine or system configuration.
LEVEL PASSWORD
USER (always available) INSTALLER (psw 18)
SERVICE
USER X
WHICH PARAMETERS ARE VISIBLE/ACCESSIBLE
INSTALLER
SERVICE
X
X
X
X
X
USER MENU (access level USER)
12 39
Gio 14 JUL
12°C
Menu
Domestic water 52°C
Heating circuit 45°C
Boiler mode Winter
System info
1.2 12 Menu
bar 39 Comfort functions
Gio Preheat
14 JUL
Biberon Off
Guided tour On/active
Hourly scheduling
12°C On
1.2 12 bar 39
Gio 14
Menu
Time and date 12:39 thu 14 jul
JUL Screen lock
Off
Buzzer On/active
12°C
Language English
1.2 12 Menu
1.2
bar 39 Technical menu
bar
Gio Blocked
14
JUL
12°C
Domestic Hot Water
DHW Temperature: to set the DHW temperature (for more details please refer to “Heating and DHW setpoint setting”). NOT AVAILABLE ON THIS MODEL.
Heating Circuit
Heating Circuit Temperature: to set the temperature of the heating circuit (for more details please refer to “Heating and DHW setpoint setting”).
Boiler Mode
Boiler Mode: to set the boiler operating mode (for more details please refer to “Operating mode”).
System Info
Menu Info: to consult the system info (for more details please refer to “INFO Menu”).
Comfort Functions
Comfort Functions: to enable/disable comfort functions (for more details please refer to “Comfort Functions”). NOT AVAILABLE ON THIS MODEL.
Biberon Function
Biberon function: to enable/disable the bottle function (for more details please refer to “Feeder Bottle Function”). NOT AVAILABLE ON THIS MODEL.
Guided tour
Guided tour: to access the guided tour (for more details please refer to “GUIDED TOUR”).
Timer Programming
Timer Programming: to set the TIMER PROGRAMMING, when enabled.
Time and Date
Time and Date: to set TIME AND DAY (for more details please refer to “INSTRUCTIONS FOR USE”).
Key Lock
Key and Screen Lock: to lock/unlock keys and touch screen (for more details please refer to section “Keypad lock function”).
Buzzer
Buzzer: to enable/disable the buzzer (for more details please refer to “INSTRUCTIONS FOR USE”).
Factory setting = active
Language
Language: to set the desired language (for more details please refer to “INSTRUCTIONS FOR USE”).
Units of Measurement
Units of Measurement: to change the unit of measurement. NOT CURRENTLY AVAILABLE.
32
TECHNICAL MENU (access level INSTALLER)
12 Technical menu
1.2 12 Technical menu
1.2
39
bar 39
bar
Gio Guided tour
Gio Service
14
14
JUL Combustion
JUL Connectivity
Configuration
Heating
12°C
12°C
Dhw
Combustion
:
– GAS – GAS TYPE: parameter identifying the type of gas: Methane LPG Gas 3 Gas 4.
Factory setting = Methane
– d52 – P1 GAS VALVE: parameter for resetting the P1 value of the gas valve.
Factory setting = 45
– GAC – VALVE CALIBRATION: parameter used to calibrate the gas valve and combustion control system.
– APL – POWER: parameter used to set the boiler output: 25kW – 35kW.
Factory setting = 25kW
Configuration
:
– HYDRAULIC CONFIGURATION: to set the hydraulic configuration of the boiler: Heating only – Instantaneous with Flow switch – Instantaneous with Flow meter – Storage Cylinder with probe –
Storage Cylinder with Thermostat.
Factory setting = Heating only, do not modify. When replacing the circuit board, make sure that this parameter is set to Heating only.
– MIN FAN SPEED: to change the minimum fan speed.
Factory setting = see technical data table.
– MAX FAN SPEED: to change the maximum rpm of the fan.
Factory setting = see technical data table.
– MAX FAN SPEED HTG: to vary the maximum heating fan speed (this can be programmed within the minimum fan speed range – maximum fan speed).
Factory setting = see technical data table.
– Range Rated: RANGE RATED adjustment. DO NOT CHANGE.
– CONFIG AUX 1: to configure the operation of an additional relay (only if BE09 board is installed (accessory kit)) to feed a phase (230Vac) to a second heating pump (additional pump) or a zone
valve. It is to choose how to programme operation by choosing between: This depends on the wiring configuration of the BE09 board: cut jumper: additional pump – jumper present: zone valve
(factory setting) zone valve management additional pump management.
Factory setting = function not enabled.
– EXHAUST PROBE RESET: allows the operating hours counter to be reset under certain conditions (for more details please refer to “Warning signals and faults”, fault E091).
Factory setting = function not enabled.
Heating
:
– PUMP CONTROL TYPE: proportional variable speed pump.
Factory setting = 85.
– OT CASCADE CONTROL: allows the boiler to be set up for cascade applications via OT+ signal. NOT APPLICABLE TO THIS BOILER MODEL.
– SCREED FUNCTION: enables/disables the screed heater function (for more details please refer to “Screed heater function”).
Factory setting = function not enabled.
– ANTI CYCLE FUNCTION: allows the forced heating off time to be modified. This relates to the delay time introduced for re-ignition of the burner when the burner is switched off due to having
reached the heating temperature.
Factory setting = 3 minutes and can be set to a value between 0 min and 30 min.
– RESET CH TIMERS: Allows you to cancel the function HEATING RESET TIMING and REDUCED HEATING MAXIMUM OUTPUT, during which the fan speed is limited between the minimum
value and 60% of the set maximum heating power, with an increase of 10% every 15 minutes.
Factory setting = function not enabled.
– TYPE OF HEATING: allows you to specify the type of zone to be heated, choosing from the following options: HIGH TEMPERATURE LOW TEMPERATURE.
Factory setting = HIGH TEMPERATURE
– MAX TEMP: allows the maximum heating setpoint value to be specified: range 20°C – 80°C, default 80°C for high temperature systems range 20°C – 45°C, default 45°C for low temperature
systems. Note: The maximum heating setpoint value cannot be smaller than the minimum heating setpoint value.
– MIN TEMP: with this parameter you can specify the minimum settable heating setpoint: range 20°C – 80°C, default 40°C for high temperature systems range 20°C – 45°C, default 20°C for
low temperature systems. Note: The minimum heating setpoint value cannot be greater than the maximum heating setpoint value.
– THERMOREGULATION: enables thermoregulation when an outdoor temperature sensor is connected to the system.
Factory setting = function not active, the boiler always operates at fixed point. With the outdoor temperature sensor disconnected, the boiler works at a fixed setpoint. For more details, please
refer to the section ‘Setting the thermoregulation.
– HOURLY SCHEDULING: enables hourly heating programming.
Factory setting = DISABLE.
– MANUAL FORCING DURATION: with time programming enabled, this parameter allows you to set the switching mode from manual to automatic heating operating mode. The transition from
manual to automatic time programming occurs automatically at the first time slot change.
DHW
:
– ANTI LEGIONELLA FUNCTION: function linked to the availability of a storage cylinder. NOT AVAILABLE ON THIS MODEL.
– ANTI LEG. DELAY: function related to the availability of a storage cylinder. NOT AVAILABLE ON THIS MODEL.
– SUPPLY TEMPERATURE: function linked to the availability of a storage cylinder. NOT AVAILABLE ON THIS MODEL.
– TANK HYSTERESIS ON: function related to the availability of a storage cylinder. NOT AVAILABLE ON THIS MODEL.
– TANK HYSTERESIS OFF: function related to the availability of a storage cylinder. NOT AVAILABLE ON THIS MODEL.
– TANK FLOW TEMP : function related to the availability of a storage cylinder. NOT AVAILABLE ON THIS MODEL.
– MODULATING TANK SUPPLY TEMP: function related to the availability of a storage cylinder. NOT AVAILABLE ON THIS MODEL.
– MIN TEMP: to set the minimum DHW setpoint.
Factory setting = 37°C
– MAX TEMP: to set the maximum DHW setpoint.
Factory setting = 60°C.
– SPECIAL FUNCTIONS: to enable the special DHW functions. NOT AVAILABLE ON THIS MODEL.
Service
:
– CHIMNEY SWEEP: to carry out combustion analysis, only with the boiler in the OFF position. For more details, please refer to the section ‘Combustion control’.
33
TECHNICAL MENU (access level SERVICE)
12 Technical menu
1.2 12 Technical menu
1.2
39
bar 39
bar
Gio Guided tour
Gio Service
14
14
JUL Combustion
JUL Connectivity
Configuration
Heating
12°C
12°C
Dhw
Configuration
:
– WATER PRESSURE TRANSDUCER: to set the water pressure transducer type: water pressure switch – pressure transducer.
Factory setting = pressure transducer, do not modify. When replacing the circuit board, make sure that this parameter is set to ‘pressure transducer’.
– AUTO-FILL ENABLE: to enable the ‘semi-automatic filling’ function when a pressure transducer and a solenoid valve are installed in the boiler. NOT AVAILABLE ON THIS MODEL.
– BEGIN SYSTEM FILLING: only appears if ‘Semi-automatic filling’ is enabled. NOT AVAILABLE ON THIS MODEL.
– AIR PURGING CYCLE: to disable the vent cycle function.
Factory setting = “function enabled”. For more details, please refer to the section ‘Vent Cycle’.
Heating
:
– HYST ON HIGH TEMP: for high temperature systems, this parameter allows you to set the hysteresis value used by the control board to calculate the burner ignition delivery temperature: IGNITION
TEMPERATURE = HEATING SETPOINT – Hysteresis ON High temp.
Factory setting = 5°C, can be changed in the range 2°C- 10°C.
– HYST OFF HIGH TEMP : for high temperature systems, this parameter allows you to set the hysteresis value used by the control board to calculate the burner shutdown delivery temperature:
SWITCH-OFF TEMPERATURE = HEATING SETPOINT + Hysteresis OFF High temp.
Factory setting = 5°C, can be changed in the range 2°C- 10°C.
– HYST ON LOW TEMP: for low temperature systems, this parameter allows you to set the hysteresis value used by the control board to calculate the burner ignition delivery temperature: IGNITION
TEMPERATURE = HEATING SETPOINT – Hysteresis ON Low temp.
Factory setting = 3°C, can be changed in the range 2°C- 10°C.
– HYST OFF LOW TEMP: for low-temperature systems, this parameter allows you to set the hysteresis value used by the control board to calculate the burner shutdown delivery temperature:
SWITCH-OFF TEMPERATURE = HEATING SETPOINT + Hysteresis OFF Low temp.
Factory setting = 3°C, can be changed in the range 2°C- 10°C.
DHW
:
– DHW DELAY: through this parameter a delay in seconds is introduced on the activation of the pump and fan when there is a DHW request. NOT AVAILABLE ON THIS MODEL.
Factory setting = function not enabled.
– POST-CIRCULATION: through this parameter it is possible to enable/disable the DHW post-circulation function with heating start inhibition. When this function is active, it is it is possible to set
the duration of DHW post-circulation. NOT AVAILABLE ON THIS MODEL.
Factory setting = function not enabled.
Service
:
– ALARM HISTORY: to activate the storage of an alarm history.
Factory setting = function not enabled; the parameter is automatically enabled after 2 hours of operation. Disabling the parameter resets the alarm history. Please refer to the section ‘Alarm
History’ for more details.
– CALL SERVICE: this parameter allows periodic control of the boiler according to a pre-set operating period. With function enabled (factory setting) it is possible to set:
– “Call for service” (factory setting): the display shows CFS signalling without any operating stops. In this condition, the INFO menu displays the number of days that have elapsed since the
CFS alert appeared. The CFS signal occurs at 10 minute intervals for a duration of 1 minute, 1 month before the end of the period set in the parameter “Service expiry”
– “Stop for service”: the display shows the SFS signal indicating the permanent inhibition of all heating and DHW heat requests. Cannot be reset.
– “Service expiry”: pre-set period of operation for the service call. Factory setting: 52 weeks
– HIGH EFFICIENCY ENABLE: automatic function which activates when first powered on or after 60 days of non-use (boiler electrically powered). In this mode the boiler, for 60 minutes, limits
the power in heating to a minimum and the maximum temperature in DHW to 55°C. Activating the chimney sweep temporarily disables this function.
Factory setting = function not enabled. For more details, please refer to the section ‘Condensate trap filling – High efficiency mode’.
– CONTACT SERVICE: through this parameter you can enter the data of the Technical Assistance Centre.
Connectivity
:
– BUS 485 CONFIG: this parameter is used to enable remote boiler management. Three values are available:
– Wi-Fi key: management from boiler interface and APP if Wi-Fi key present (FACTORY SETTING)
– Ignore Wi-Fi key: management from boiler interface ONLY
– Modbus remote control: management from boiler interface and system manager (T300)
– OT CONFIG: this parameter is used to enable/disable the possibility of remote control of the boiler via an OpenTherm device.
Factory setting = function enabled.
34
7.2 INFO MENU
b If no buttons are pressed, after 120 sec, the interface automatically exits
the `System Info’ menu.
12 Menu
1.2
39
bar
Gio 14
Domestic water 52°C
JUL Heating circuit
45°C
Boiler mode Winter
System info
12°C
12 System info
39
Gio
Screed heating hours
14 JUL
Flow probe
Return probe
0 21°C
1.2 12 bar 39
Gio 14 JUL
22°C
System info
Oat Filtered oat Dhw flow rate
1.2 12 System info
3°C
bar 39
Gio
Ot main zone set
1°C
14 JUL
Water pressure
0.0
Dhw hour
1.2 12
—
bar 39
Gio
1.0bar
14 JUL
1
System info
Ch supply avg Dhw supply avg Ch return avg
Dhw probe
20°C
Fan revolutions
0
Ch hour
2
Dhw return avg
12°C Dhw set
44°C
Exhaust probe
33°C
12 System info
39
Gio
Comfort
14 JUL
Sun on
Pcb id
12°C Exhaust hours
0
Main zone set
72
1.2 12
0
bar 39
Gio
0
14 JUL
GP02
System info
Alarm 1 Alarm 2 Alarm 3
12°C Dhw modulation
98%
Ch modulation
40%
1.2 12
E040
bar
39
Gio
E041
14 JUL
E077
System info
Next legionella Rsc Rs
12°C Evg on cycles
High efficiency
1.2
bar 0 1289 8
Pcb fw
7
Alarm 4
E010
Rss
1260
12°C Interface fw
2.1.76
12°C Alarm 5
E077
12°C Rf
104
Radio signal
0
Clean exchanger
0
1.2
bar 28°C 45°C 21°C 34°C 21 0
INFO NAME
DESCRIPTION (only info related to the model configuration will be displayed)
SCREED HEATING HOURS
Number of hours spent with screed heater function (when in progress)
FLOW PROBE
Boiler flow sensor value
RETURN PROBE
Boiler return temperature sensor value
DHW PROBE
NOT AVAILABLE ON THIS MODEL
DHW SET
NOT AVAILABLE ON THIS MODEL
EXHAUST PROBE
Flue gas probe value
OUTDOOR TEMP PROBE
Instantaneous outdoor temperature sensor value
FILTERED OUTDOOR TEMP
Filtered outdoor temperature sensor value used in the temperature control algorithm to calculate the heating setpoint
DHW FLOW RATE
NOT AVAILABLE ON THIS MODEL
FAN SPEED
Number of fan rotations (rpm)
EXHAUST PROBE HOURS
Number of operating hours of the heat exchanger in “condensing mode” (the values are expressed in hundreds of hours, example: 01 = 100h)
MAIN ZONE SET
Main zone delivery setpoint
OT MAIN ZONE SET
Main zone delivery setpoint from OT+
WATER PRESSURE
System pressure
DHW HOUR
NOT AVAILABLE ON THIS MODEL
CH HOUR
Hours with burner on
References
- Vokera|Vokèra by Riello
- Vokera – Viridus Energy
- Home — Benchmark
- centralheating.co.uk
- hhic.co.uk
- Vokera|Vokèra by Riello
- Vokera – Viridus Energy
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>