COLUMBIA VAC OPC2000 Air Dehumidifier Instruction Manual
- September 28, 2024
- COLUMBIA VAC
Table of Contents
- OPC2000 Air Dehumidifier
- SAFETY INSTRUCTIONS
- SAFETY WARNINGS FOR SERVICING
- SPECIAL RECOMMENDATIONS:
- POWER SOURCES
- GENERAL DESCRIPTION (fig.1)
- TECHNICAL DATA
- CHOOSING THE PLACE FOR INSTALLATION (fig.2)
- OPERATION OF THE DEVICE
- CONTROL PANEL (fig.3)
- HUMIDITY INDICATOR (3)
- PROGRAMMES
- OPERATION
- EMPTYING THE TANK (8) (fig. 4)
- CONTINUOUS WATER OUTLET (7) (fig. 5)
- MAINTENANCE **
- CLEANING
- AIR FILTER (6)
- OPERATING TEMPERATURE
- AUTOMATIC DEFROSTING
- STORING THE DEVICE
- TROUBLE SHOOTING
- WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
OPC2000
AIR DEHUMIDIFIER
Eldom Sp. z o.o. • ul. Pawła Chromika 5a • 40-238 Katowice, POLAND
tel: +48 32 2553340 • fax: +48 32 2530412 •
www.eldom.eu
OPC2000 Air Dehumidifier
SYMBOLS ON THE APPLIANCE AND IN THE OPERATING INSTRUCTIONS
The drawings in this manual may differ slightly in appearance from those on
the appliance. Please refer to the actual drawings.
CAUTION: RISK OF FIRE
Disposal of used electrical and electronic equipment (applies to the
European Union countries and other European countries with separate waste
collection systems).
The symbol on the product or its packaging indicates that the product should
not be classified as household waste. It should be handed over to a
collection point that deals with the collection and recycling of electrical
and electronic devices. Correct disposal of the product prevents potential
negative consequences for the environment and human health that could be
caused by improper disposal of the product. Material recycling helps to
preserve natural resources. For detailed information on recycling of this
product, please contact your local authority, a cleaning service provider or a
shop where the product has been bought.
Appliance is filed with flammable gas R290.
Before using the appliance, read the mannual.
Before installing the appliance, read the installation mannual.
Any repairs you need, contact the nearest authorized Service Centre and
ctrictly follow manufacturer’s instruction only.
SAFETY INSTRUCTIONS
PRECAUTIONS
- Carefully read the Instructions Manual, and familiarise yourself with the warnings on the device before installing and commissioning. The Instructions Manual contains the correct installation and operation principles of the air conditioner. Non-observance of the principles can lead to voiding the warranty.
- This device can be used by children of at least 8 years of age; by persons with reduced physical and mental abilities; and by persons with no experience or knowledge of the equipment, if supervised or instructed on its safe use so that the risks associated with it are understood. Children should not play with the device. Unattended children should not be allowed to perform the cleaning and maintenance of the device.
- Unintended use of the air conditioner can lead to voiding the warranty.
- The device should not be operated by persons who have no knowledge of the equipment or have not read the Instructions Manual. This particularly applies to children.
- The device is intended for use only with R-290 (propane) gas as the refrigerant. R290 is a gaseous coolant which meets EU Environmental Directives.
Information on equipment using R290 gaseous refrigerant
-
Read all warnings carefully.
-
Do not pour the refrigerant into the atmosphere.
-
R-290 (propane) is flammable and heavier than air.
-
It first accumulates at the lower levels, but can be distributed by air movement (e.g., by fans).
-
If propane is present, or its presence is even just suspected, it is forbidden to allow unqualified personnel to try to find the cause.
-
The R-290 (propane) used in the device is odourless.
-
No odour does not mean that no gas is escaping.
-
In the event of leak detection, evacuate all persons from the room, ventilate the room, and contact the local fire service in order to report the propane leak.
-
Do not allow anyone into the room until a qualified service technician arrives and affirms that entering the room is safe.
-
Do not use tools other than those recommended by the manufacturer during defrosting and cleaning.
-
The device should be placed in the area free of fixed ignition sources (e.g., an open fire, or operating gas or electric equipment).
-
The device‘s components are specially designed for the use of propane, and have no ignition or sparking properties. Replace the components only with identical spare parts.
-
Do not allow the housing to be punctured. Do not burn the device.
-
The unit must be installed, operated, and stored in a room bigger than 4 m2.
-
If the unit is installed, operated, or stored in a room without ventilation, measures should be implemented preventing the accumulation of leaking coolant, the causing of a fire, or an explosion hazard due to the ignition of the coolant caused by an electric heater, stove, or other ignition sources.
-
Store the device in a way which avoids mechanical damage.
-
Persons operating or modifying the cooling circuit must hold the appropriate authorisations from an accredited organisation to guarantee the professional handling of the refrigerant, which must be confirmed by reputable industry organisations.
-
All repairs should be performed according to the manufacturer’s recommendations. Maintenance and repairs requiring the employment of experts in other fields should be carried out under the
supervision of a person authorised to use flammable refrigerants. -
This device is intended for home use only, as described in this Instructions Manual. Do not use the device for purposes other than those specified in this Instructions Manual.
-
Installing the air conditioner does not require special knowledge, and may be performed by the user in accordance with the guidelines and figures contained in the Instructions Manual. Improper installation can result in water leakage, or electrocution, or irreparable damage to the unit. Eldom Sp. z o. o. shall not be liable for any potential losses due to the improper use of the device.
-
The unit must be installed in accordance with the national regulations for electrical systems. Before connecting the device to the mains, check that the mains current parameters (voltage) correspond to the parameters indicated on the device. The device’s outlet plug should be completely plugged into the power socket. Do not use extension cords or multi-outlet adapters to connect the device’s power cord. Remove the outlet plug from the socket if the device is not to be used for an extended period. If the unit has not been used for a long time, check that the air inlets and outlets are unobstructed before starting the device.
-
Connect the device only to an earthed power socket.
-
Keep the device at least 50 cm away from flammable material and substances (e.g., alcohol, etc) or pressurised containers (e.g., aerosols).
-
The power cord and plug are intended for the final disconnection of the device from the power supply, which is why they must be easily accessible at all times.
-
Switch off the air conditioner and disconnect it from the power supply during a storm.
-
Do not insert hands or objects into the air outlets.
-
Do not put any objects on the device.
-
Do not step or sit on the device.
-
Do not insert fingers or other objects into the air outlet.
-
Do not touch the air inlet or the aluminium fins of the unit.
-
Before cleaning, repair, maintenance, or inspection, switch the air conditioner off and disconnect it from the power supply.
-
Clean the device with a dry, soft, cloth. If the unit’s housing is heavily soiled, you may use a cloth soaked in a household cleaning agent. Do not wipe or clean the air conditioner with chemical solvents such as petrol and alcohol.
-
Do not immerse or expose this unit to precipitation, moisture, or other liquids.
-
Do not operate with wet hands. Avoid water spillages on the unit.
-
Do not immerse or expose this unit to precipitation, moisture, or other liquids.
-
Do not leave the device unattended when it is running. Do not tilt or overturn the device.
-
Place and operate the unit away from splashes of water or oil.
-
If during the device’s operation, the user detects any irregularities, such as a strange odour or sound, smoke, steam, fire, over heating of housing or outlet plug, fuse failure, or interruptions to the operation of other devices, immediately switch the device off, disconnect from the power supply, and contact an authorised service centre.
-
Do not use if the power cord is damaged, or if the unit has been dropped or otherwise damaged. The repair of the device should be entrusted to an authorised service centre; see information on the warranty card and on the website www.eldom.eu.
-
All modifications, and the use of spare parts or device elements other than the original ones, are prohibited, and can pose a hazard to the safety of use.
-
Under the risk of voiding the warranty, the user may not perform any repairs, modifications, or disassembly, of the device’s housing.
-
There are no user-serviceable parts inside the unit.
-
All modifications, and the use of spare parts or device elements other than the original ones, are prohibited, and can pose a hazard to the safety of use.
Persons operating or modifying the cooling circuit must hold the appropriate
authorisations from an accredited organisation to guarantee the professional
handling of the refrigerant, which must be confirmed by reputable industry
organisations.
All repairs should be performed according to the manufacturer’s
recommendations.
Maintenance and repairs requiring the employment of experts in other fields
should be carried out under the supervision of a person authorised to use
flammable refrigerants.
If there is any lack of understanding of any information, or help is needed,
contact the dealer’s service centre
BEFORE THE FIRST USE OF THE DEVICE, MAKE SURE THAT IT HAS BEEN PLACED IN THE
VERTICAL POSITION FOR 24 HOURS; OTHERWISE, THE DEHUMIDIFIER COMPRESSOR CAN BE
DAMAGED.
SAFETY WARNINGS FOR SERVICING
Observe all these warnings when performing the following works while servicing the dehumidifier with R290.
-
Area inspections
Before performing any works on circuits containing flammable refrigerants, it is necessary to perform safety inspections of the area to make sure that the risk of ignition is minimised. When repairing the
cooling system, the following precautions must be implemented before working on the system. -
Working procedure
Tasks should be carried out under the controlled procedure so that the risk of the presence of flammable gas or vapours is minimised when work is being carried out. -
General workplace
All maintenance personnel and others working in the place should be instructed in the nature of the work. Avoid working indoors. The area around the workplace must be isolated. Make sure that conditions in the area have been secured by control flammable materials. -
Refrigerant-presence inspection
Before and during performing work, check the area with a suitable refrigerant detector to ensure that the technician is aware of potentially flammable atmospheres. Make sure that the leak-detection equipment used is suitable for use with flammable refrigerants, i.e., does not cause sparking, is properly sealed, and is intrinsically safe. -
Fire-extinguishing accessibility
If any hot operations are to be carried out on the cooling equipment or any associated parts, suitable fire-extinguishing equipment should be available. Dry powder or CO2 fire extinguisher should be placed adjacent to the charging area. -
No ignition sources
No persons performing work on cooling systems, which consists of uncovering pipes containing flammable refrigerant may use any ignition sources in a manner creating a risk of fire or explosion. All possible sources of ignition, including cigarette smoking, should be kept at a suitable distance from the place of installation, repair, removal, and disposal, during which the flammable refrigerant can be released into the environment. Before starting work, examine the area around the equipment to ensure that there is no fire or ignition hazard. Place “No smoking” signs. -
Ventilated area
Make sure that the area is outside or properly ventilated before performing any repair or maintenance works on the system or hot operations. A certain degree of ventilation should be maintained during the work-performing period. Ventilation should safely disperse the released refrigerant, and preferably release it outside into the atmosphere. -
Cooling equipment inspections
In the event of the replacement of electrical components, they should be appropriate for the purpose, and compliant with the relevant specifications. The manufacturer’s guidelines for maintenance and
servicing must be observed at all times. If any doubts, contact the technical department of the manufacturer.
The following inspections should be performed concerning the systems using flammable refrigerants:
– The size of the load is compliant with the room size in which components containing refrigerant are installed;
– Ventilation units and outlets are working properly, and are not clogged up;
– When using an intermediate cooling circuit, check for the refrigerant;
– The marking of the device is still visible and legible. Markings and signs which are illegible must be corrected;
– Cooling pipes or components should be installed in a place where there is a low likelihood of their coming into contact with any substance which can cause corrosion of components containing refrigerant, unless these components are made of materials inherently resistant to corrosion, or adequately protected against corrosion. -
Electrical-equipment inspections
Repairs and maintenance of the electric components include preliminary safety inspections and component-control procedures. In the instance of a fault which could risk safety, do not connect the power supply to the circuit until it has been satisfactorily rectified. If the fault cannot be rectified immediately, but further action is necessary, an appropriate temporary solution must be implemented. This should be reported to the device owner so that all parties are informed. Preliminary safety inspections include:
− condenser discharge: should be done in a safe way to avoid the possibility of sparking;
− no covering of live electrical components or wiring when charging, recovering, or cleaning the system;
− earthing continuity. -
Repairs to sealed components
During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation. Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc. Ensure that the apparatus is mounted securely. Ensure that seals or sealing materials have not degraded to the point that they no longer serve the purpose of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer’s specifications. -
Repair to intrinsically safe components
Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating. Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in the atmosphere from a leak. -
Cabling
Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such as compressors or fans. -
Detection of flammable refrigerants
Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. -
Removal and evacuation
When breaking into the refrigerant circuit to make repairs – or for any other purpose – conventional procedures shall be used. However, for flammable refrigerants it is important that best practice is followed since flammability is a consideration. The following procedure shall be adhered to:
– remove refrigerant;
– purge the circuit with inert gas;
– evacuate;
– purge with inert gas;
– open the circuit by cutting or brazing.
The refrigerant charge shall be recovered into the correct recovery cylinders. For appliances containing flammable refrigerants the system shall be purged with oxygen-free nitrogen to render the appliance safe for flammable refrigerants. This process may need to be repeated several times. Compressed air or oxygen shall not be used for purging refrigerant systems. For appliances containing flammable refrigerants, refrigerants purging shall be achieved by breaking the vacuum in the system with oxygen-free nitrogen and continuing to fill until the working pressure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until no refrigerant is within the system. When the final oxygen-free nitrogen charge is used, the system shall be vented down to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations on the pipe-work are to take place. Ensure that the outlet for the vacuum pump is not close to any potential ignition sources and that ventilation is available. -
Leak detection methods
The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak is suspected, all naked flames shall be removed/extinguished. If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the brazing process. -
Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed.
– Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimise the amount of refrigerant contained in them.
– Cylinders shall be kept in an appropriate position according to the instructions.
– Ensure that the refrigerating system is earthed prior to charging the system with refrigerant.
– Label the system when charging is complete (if not already).
– Extreme care shall be taken not to overfill the refrigerating system.
– Prior to recharging the system, it shall be pressure-tested with the appropriate purging gas. The system shall be leak-tested on completion of charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site. -
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant. It is essential that electrical power is available before the task is commenced.
a) Become familiar with the equipment and its operation.
b) Isolate system electrically.
c) Before attempting the procedure, ensure that:
– mechanical handling equipment is available, if required, for handling refrigerant cylinders;
– all personal protective equipment is available and being used correctly;
– the recovery process is supervised at all times by a competent person;
– recovery equipment and cylinders conform to the appropriate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f) Make sure that cylinder is situated on the scales before recovery takes place.
g) Start the recovery machine and operate in accordance with instructions.
h) Do not overfill cylinders (no more than 80 % volume liquid charge).
i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly and all isolation valves on the equipment are closed off.
k) Recovered refrigerant shall not be charged into another refrigerating system unless it has been cleaned and checked. -
Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. For appliances containing flammable refrigerants, ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. -
Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate
refrigerant recovery cylinders are employed. Ensure that the correct number of
cylinders for holding the total system charge is available. All cylinders to
be used are designated for the recovered refrigerant and labelled for that
refrigerant (i.e. special cylinders for the recovery of refrigerant).
Cylinders shall be complete with pressure-relief valve and associated shutoff
valves in good working order. Empty recovery cylinders are evacuated and, if
possible, cooled before recovery occurs. The recovery equipment shall be in
good working order with a set of instructions concerning the equipment that is
at hand and shall be suitable for the recovery of all appropriate refrigerants
including, when applicable, flammable refrigerants. In addition, a set of
calibrated weighing scales shall be available and in good working order. Hoses
shall be complete with leak-free disconnect couplings and in good condition.
Before using the recovery machine, check that it is in satisfactory working
order, has been properly maintained and that any associated electrical
components are sealed to prevent ignition in the event of a refrigerant
release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the
correct recovery cylinder, and the relevant waste transfer note arranged. Do
not mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have
been evacuated to an acceptable level to make certain that flammable
refrigerant does not remain within the lubricant. The evacuation process shall
be carried out prior to returning the compressor to the suppliers. Only
electric heating to the compressor body shall be employed to accelerate this
process. When oil is drained from a system, it shall be carried out safely.
SPECIAL RECOMMENDATIONS:
- Ambient temperature range for the device is 5°C -35°C.
- Install the portable air dryer on a flat location with a large space, without obstacles. Leave a 30cm minimum space between the unit and the wall.
- The device must be installed in accordance with national installation regulations.
- The plug shall be always accessible after its installation.
- Always place the appliance in a vertical position, in order to maintain the compressor in good working condition.
- Do not tilt the device in any direction as spilled water can damage the device.
- Do not use the appliance near gas or other inflammable liquids.
- Do not block the air outlet and inlet ventilation. Do not place heavy objects on the device.
- Do not use spray (insecticides, painting) or any other inflammable products near the appliance as the plastic case may be deformed. The unit may sustain electrical damage.
POWER SOURCES
- The plug has to be well fixed and should not be damaged.
- Do not plug in the appliance with an adaptor.
- Plug into the wall socket before switching on the appliance then press on the ON/OFF button.
INSTRUCTION MANUAL
AIR DEHUMIDIFIER OPC2000
GENERAL DESCRIPTION (fig.1)
1. Wheels
2. Body
3. Humidity indicator
4. Control panel
5. Handle| 6. Filter
7. Continuous drainage
8. Water tank
9. Air outlet
10. Hose
---|---
TECHNICAL DATA
Dehumidification capacity | 20l/24h (30°C, RH80%) |
---|---|
Rated voltage | 220-240V~ 50Hz |
Rated power / max | 290W / 330W |
Water tank | 6,5 l |
Noisiness | ≤45dB(A) |
Air flow | 165m 3/h |
Pressure (suction) | 0,7MPa |
Pressure (discharge) | 3,2MPa |
Maximum allowable pressure of heat exchange | 3,2MPa |
Unit weight | 14kg |
Refrigerant type | R290/55g |
CHOOSING THE PLACE FOR INSTALLATION (fig.2)
- The device must be positioned vertically on a flat, dry, and spacious surface.
- The room should be well-ventilated.
- Leave at least 20 cm of free space around the device.
- Water collects in the tank (8). You can use the provided hose (10) to drain the water.
- The installation method is described in the “CONTINUOUS WATER DRAINAGE” section.
- Before connecting to the power supply, ensure that the parameters of the power grid (voltage) match the parameters stated on the device.
- The power plug of the device should be fully inserted into the power outlet.
- Do not use extension cords or splitters to connect the power cord of the device.
- If the device will not be used for an extended period, unplug the power plug from the outlet.
- If the device has not been used for a long time, before restarting it, check if the air inlets and outlets are not blocked.
OPERATION OF THE DEVICE
- All changes in settings are signaled by sound.
- The device is programmed with a protective 3-minute compressor delay. Wait for 3 minutes for the dehumidifier to resume operation.
- After turning off the device, the fan continues to operate for approximately 30 seconds.
CONTROL PANEL (fig.3)
Display
- When powered on, it displays the room humidity.
- While adjusting the device operation parameters, it shows the selected operating values.
- In case of device malfunction, it displays an error code.
Indicator „Power” – indicates that the appliance is switched on.
Indicator – indicates that the continuous dehumidification programme is
on.
Indicator „Auto” – indicates that the manual programme is on.
Indicator – indicates that the function is activated:
– delayed start – when the unit is in standby,
– automatic switch off – when the device is operating.
Indicator – indicates filling of the water tank.
The indicator will light up red when the maximum capacity of the tank (8) is
reached.
The appliance will further signal this with an audible alarm and then switch
off.
To deactivate the audible alarm, press any button. Then empty the water tank
and put it back in the correct position.
Indicator – indicates activation of the button lock.
Indicator – indicates activation of ionisation.
Indicator – indicates that the filter (6) needs to be cleaned.
Indicators – indicates that the night programme is on.
Indicators and – indicate the selected fan speed.
HUMIDITY INDICATOR (3)
The colour of the indicator (3) indicates the humidity level:
- blue – humidity below 45%,
- green – humidity between 45 and 65%,
- red – humidity above 65%.
PROGRAMMES
When the ambient humidity is 3% lower than the selected humidity, the
compressor will stop and the fan will stop operating after approximately 30s.
When the ambient humidity is 3% higher than the selected humidity value the
compressor will restart.
NOTE. There is a protective 3-minute compressor delay programmed into the
unit, which means that the dehumidifier will not always switch on immediately,
despite the increase in humidity.
Continuous dehumidification programme
In continuous dehumidification mode, the compressor runs all the time. The
humidity level cannot be set.
Automatic programme „Auto”
In manual mode you can select the humidity level, which can be set between 30%
to 80% with intervals of 5%.
Night programme
In this programme the fan is automatically switched to low speed.
After 10 seconds of inactivity, the display and some controls are
extinguished.
The humidity level and fan speed CANNOT be changed.
In this programme the dehumidifier maintains a humidity level between 57% and
63%.
If the ambient humidity rises above 63%RH the unit will start dehumidifying to
an ambient humidity below 57%RH. The compressor will then stop and the fan
will continue to run for about 30 s. The unit will restart when the humidity
rises to 63%. If the ambient humidity is less than 63%, once connected the
unit will remain in standby mode until the humidity rises to 63%.
The sound signals are switched off. If the tank (8) overflows, the unit will
stop, the indicator will light up, but the alarm will not sound.
OPERATION
-
Connect the unit to the mains compatible with the parameters shown on the unit.
-
Press the button – the unit will start operating according to the pre-set parameters (selected programme and fan speed).
-
Press the button and select the fan speed – the (fast speed) or (slow speed) indicator will light up.
-
Press button and select continuous dehumidification programme or automatic programme „Auto”. After selecting the automatic programme, use the and buttons to set the desired humidity level from 30% to 80% (interval in 5% steps).
-
Press the button and select:
o Delayed start – this function allows you to set the time after which the dehumidifier will start automatically.
The function can only be started when the unit is switched off but connected to the power supply.
The function can be set between 1 and 24 hours by pressing the and buttons until the desired value appears on the display. Only full hours can be set. Setting a value of ‘00’ means that the setting is cancelled..
Activation of the function is indicated by the indicator light.
When the unit is switched on using the button, the time setting will be cancelled.
o Automatic switch off – this function allows you to set the time after which the unit will automatically switch off.
The function can be activated only when the unit is switched on (running).
The function can be set between 1 and 24 hours by pressing the and buttons until the desired value appears on the display. Only full hours can be set. Setting a value of ‘00’ means that the setting is cancelled..
Activation of the function is indicated by the indicator light.
When the unit is switched on using the button, the time setting will be cancelled. -
To switch on ionisation, press the button – the indicator will light up. To deactivate ionisation, press the button again.
-
To activate the button lock, press and hold the button – the indicator lights up.
When the button lock is activated, no buttons are active. To deactivate the button lock, press and hold the button again. -
To select the night program press the button for a few seconds until the indicator is illuminated on the control panel. To deactivate the night program, press the indicator again.
-
To reset the unit’s running time counting without cleaning the filter, press and hold the button .
When the unit has been running for 600 hours, the indicator will light up to remind you to clean the air filter (6) and the dehumidifier will switch off. In this case, clean the filter (6) (see ‘AIR FILTER (6)’) and reset the counter. -
To switch off the unit, press .
ATTENTION. Do not unplug the power cord directly to force the unit to stop.
EMPTYING THE TANK (8) (fig. 4)
ATTENTION. Water collected in the dehumidifier tank is not suitable for drinking and must not be allowed to come into contact with food.
-
Pull the water tank slightly at the back of the unit; the tank will slide out – fig. 4a.
-
Pour the water out of the tank – fig. 4b.
NOTE. Do not pull the float out of the water tank; otherwise the appliance will not stop working when the water tank fills. The water will then overflow, which may cause damage to the floor – fig. 4c. -
If the water tank is dirty, clean it with water. Do not use any harsh cleaning agents for cleaning. Do not use chemical solvents (e.g. benzene, alcohol, petrol) as the surface could be deformed, which could lead to leaks.
-
Place the tank in the unit in the correct position. Otherwise, the indicator will remain lit and the appliance will not be able to operate – fig. 4d.
CONTINUOUS WATER OUTLET (7) (fig. 5)
To use the appliance with the continuous water drain connected:
- Remove the water tank (8).
- Insert the hose (10) into the drain valve (7) located in the top of the tank compartment.
- Insert the container (8) and feed the tube (10) out through the cut-out.
- Insert the other end of the tube into a container such as a bucket.
CAUTION: Never bend the hose (10). The hose outlet must always be below the water outlet of the appliance (7). Never block the water outlet of the appliance or the hose (10).
MAINTENANCE **
**
CAUTION: Turn off the unit and unplug it before any maintenance or repair begins to avoid electric shock.
CLEANING
- Before cleaning, make sure to disconnect the device from the power source.
- Clean the casing with a soft damp cloth.
- Do not use chemical solvents (such as benzene, alcohol, gasoline), as they may damage the surface or deform the entire casing.
- Do not immerse the device in water.
- Cleaning the tank (8) – see EMPTYING THE TANK (8).
- Cleaning the filter (6) – see AIR FILTER (6).
AIR FILTER (6)
Check the condition of the filter (6) regularly. Do not use the device with
damaged filter.
The filter (6) clogged with dust reduces the efficiency of the device, so it
should be cleaned at least once every 2 weeks. Remove the filter from the
housing and rinse it under running water. Do not use chemical solvents (such
as benzene, alcohol, gasoline), as they may damage the surface or deform the
cover. Thoroughly dry before reinstallation. The installation of the filter
(6) is shown in fig. 6.
CAUTION: Do NOT use the device without the filter (6).
NOTE. The unit is equipped with a sensor that counts the operating time.
When the unit has been running for 600 hours, the indicator will light up to
remind you to clean the filter (6) and the dehumidifier will switch off. In
this case, clean the filter (6) and reset the counter by pressing and holding
the button.
OPERATING TEMPERATURE
When the ambient temperature is below 5°C or above 35°C, the dehumidifier stops.
AUTOMATIC DEFROSTING
When the ambient temperature is between 5°C and 22°C, the compressor
automatically defrosts at specified intervals.
During defrosting, the compressor stops and the fan continues to run.
STORING THE DEVICE
If the dehumidifier will not be used for an extended period:
- disconnect the power cable from the socket and coil it,
- completely empty the water tank (8) and ensure that no water has accumulated inside,
- optionally, remove the water drainage pipe,
- remove and clean the filter (6), thoroughly dry it, and reinstall it,
- store the dehumidifier in a cool, dry place, away from direct sunlight, high temperatures, and excessive dust accumulation.
TROUBLE SHOOTING
Before contacting the service centre, you should compare the symptoms given by the device with those listed below. The list includes normal situations which are not caused by a manufacturing defect or defective material.
Problem | Possible cause | Solution |
---|---|---|
The device won’t work | No power. | Connect to the power socket and switch on. |
Water fill indicator is flashing. | Check whether the water tank is correctly |
installed and empty the water tank
The temperature in the room is below 5°C or above 35°C.| The device’s
protective mechanism designed to safeguard the unit has been activated. The
device cannot operate in these temperatures
The dehumidifier function does not work or the device switches on/off
frequently| Air filter is clogged.| Clean the air filter according to the
instructions.
Door or window is open.| Close the door / window.
The device is near a heat source.| Place the device in the cooler location.
Inlet or outlet channel is obstructed.| Remove the obstruction from the inlet
or outlet channel.
The device makes excessive noise| The device is tilted or unstable.| Place on
an even, hard surface (with no vibrations).
Air filter is clogged.| Clean the air filter according to the instructions.
E1| Humidity sensor problem| Contact an authorised service centre.
LO| Environmental humidity is below 20%| Automatic device protection function
activated.
Ensure appropriate operating conditions of the device.
CL| Low temperature protection, the environmental temperaturę <5°C
CH| High temperature protection, the environmental temperaturę <38°C
WARRANTY
- This appliance is designed for domestic use only.
- It cannot be used for professional purposes or for other than the intended use.
- Improper use will nullify the guarantee.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>