Vent-Axia 437634C Lo Carbon MVDC and Sentinel Multivent Range Instruction Manual
- September 26, 2024
- Vent-Axia
Table of Contents
437634C Lo Carbon MVDC and Sentinel Multivent Range
“`html
Specifications:
-
Product Name: Lo-Carbon MVDC & Sentinel Multivent Range
Ventilation Systems -
Model Numbers: MVDC-MS, MVDC-MSH, MVDC-MSH UNIFLEX, Sentinel
Multivent Plus H -
Max Airflow: Up to 573 m3/hr
-
Speeds: 3-4 speeds depending on the model
-
Control Inputs: Switched Live Input, RS485 Connectivity,
Analogue Input 0-10V, Digital Input -
Special Features: Wireless controls and Bluetooth capability
for X-Units
Installation Instructions:
-
Position the unit considering the rooms to be ventilated,
exhaust position, and electrical services. -
Ensure adequate access for installation and maintenance.
-
If sited in a cold void, consider fitting a condensate drain or
externally insulating the unit and ducting to minimize
condensation. -
Reduce system resistance by following these guidelines:
-
Keep duct runs to a minimum length.
-
Use fully extended, uncrushed flexible ducting.
-
Minimize diffusers/valves and maintain similar length duct runs
to the inlets. -
Ensure bend radius is at least 1x the duct diameter.
-
Avoid obstructions within 250mm of fan inlets and outlet.
-
Set valves to maximally opened positions for minimal pressure
drop.
-
-
Securely mount the unit using appropriate fixings through the
mounting holes on the casing. -
Recommended to use anti-vibration mounts, acoustic mat, or
rubber bushes for mounting.
Frequently Asked Questions (FAQ):
Q: What are the key features of the Lo-Carbon MVDC &
Sentinel Multivent Range Ventilation Systems?
A: The key features include simultaneous
extract ventilation of multiple wet rooms, highly efficient
backward curved centrifugal motor impeller set, continuous 24-hour
use design, multiple settable speeds, and configurable speed
changes based on sensor or control inputs.
Q: Do all models in the range support wireless controls and
Bluetooth capability?
A: No, only the X-Units in the range have
wireless controls and Bluetooth capability.
“`
Lo-Carbon MVDC & SENTINEL MULTIVENT RANGE
VENTILATION SYSTEMS
Installation and Wiring Instructions
Original instruction
Stock Ref. N°
Lo-Carbon Multivent MVDC-MS Lo-Carbon Multivent MVDC-MSH Lo-Carbon Multivent MVDC-MSH UNIFLEX
437634C 443298B 498502
Lo-Carbon Sentinel Multivent H Lo-Carbon Sentinel Multivent HX Lo-Carbon Sentinel Multivent HX CO²
445655B 495360 495361
Lo-Carbon Sentinel Multivent Plus H Lo-Carbon Sentinel Multivent Plus HX Lo- Carbon Sentinel Multivent Plus HX CO²
407849A 495362 495363
(Ventair) Lo-Carbon Sentinel Multivent Plus H
496186
X-Units have wireless controls and Bluetooth capability.
DOWNLOAD THE APP HERE:
IPX2
PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE COMMENCING INSTALLATION OR
OPERATION.
PLEASE RETAIN THESE INSTRUCTIONS WITH THE PRODUCT.
Installation and Wiring Instructions for the Multivent Multi-Speed Extract
Fans.
IMPORTANT: READ THESE INSTRUCTIONS BEFORE COMMENCING THE INSTALLATION
· Do not install this product in areas where the following may be present or occur:
· Excessive oil or a grease laden atmosphere.
· Corrosive or flammable gases, liquids or vapours.
· Subject to direct water spray from hoses.
· Ambient temperatures higher than 40°C and lower than -20°C.
· Possible obstructions that may hinder access to or removal of the unit.
· All wiring must be in accordance with the current IET wiring regulations
BS7671, or appropriate standards of your country. Installation should be
inspected and tested by a suitably qualified person after completion.
· Ensure the mains supply (voltage, frequency and phase) complies with the
rating label.
· The unit should be provided with a local double pole fused spur fitted with
a 3A fuse having a contact separation of at least 3mm.
· Units showing on the rating label incorporate an earth connection for functional purposes only.
· Units showing on the rating label have a Protective Earth.
· Precautions must be taken to avoid the backflow of gases into the building
from the open flue of gas or other fuel-burning appliances.
· This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
· Young children should be supervised to ensure that they do not play with the
appliance.
· Cleaning and user maintenance shall not be made by children
· The installer is responsible for the installation and electrical connection
of the unit on site. It is the responsibility of the installer to ensure that
the equipment is safely and securely installed and left only when mechanically
and electrically safe.
· All regulations and requirements must be strictly followed to prevent
hazards to life and property, both during and after installation, and during
any subsequent servicing and maintenance.
· Certain applications may require the installation of sound attenuation to
achieve the sound levels required.
· The unit must not be connected directly to a tumble drier.
· The exhaust grille should be located in accordance with building regulation
and be at least 300mm away from any flue outlet.
· This product and associated duct installation should be carried out in
accordance with the Domestic Ventilation Compliance Guide. Models that support
Radio and Bluetooth communication the below applies
· Bluetooth variants contain FCC ID: S9NSPBTLERF
· Bluetooth LE: -12dBm EIRP (63W), nominal 2450MHz.
· Bluetooth v4.1 compliant
· Bluetooth and radio variants obtained RED certificate: No. 0051-RED-0011
REV. 0
· Zirconia Wireless: -14dBm EIRP nominal 868MHz.
· The manufacturer hereby assures that this type of Bluetooth radio and 868MHz
radio equipment complies with RED Directive 2014/53 / EU The full text of the
EU Declaration of Conformity can be found at the following URL:
https://www.vent-axia.com/range/centralised-mechanical-extract-ventilation-mev
2
INTRODUCTORY NOTES
The MVDC & Sentinel Multivent units are designed for simultaneous extract
ventilation of multiple wet rooms such as bathrooms, kitchens and toilets. The
units use a highly efficient backward curved centrifugal motor impeller set
and are designed for continuous 24-hour use.
Depending on the model, they feature either 3 or4 settable speeds and can be
configured to change speed based on a wide range of sensor or control inputs
as depicted below
Model
Speeds
Max airflow m3/hr (0Pa)
Switched Live Input (LS)
RS485 Connectivity Analogue Input 0-10V
Digital Input
MVDC-MS 3
430 Yes No Yes Yes
MVDC-MS H 3
SMV H
4
430
463
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Humidity Sensor
No
Yes
Yes
CO2 Sensor
No
No
No
Wireless Receiver
No
No
No
SMV HX
4 463
Yes
Yes Yes Yes Yes No Yes
SMV HX Co2
4 463
Yes
Yes Yes Yes Yes Yes Yes
SMV Plus H
4
573
SMV Plus HX
4
573
SMV Plus HX Co2
4
573
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
No
Yes
Yes
The units can be precisely programmed to determine how they respond to changes
in sensor values or the status of the various signal inputs. The units will
run at a normal flowrate until a sensor or input change causes it to change
speed. In the case of the Switched Live and Digital inputs the units will
perform a step change in speed to the appropriate new level. In the case of
the Analogue inputs, Humidity Sensor and CO2 sensor the unit can be programmed
to give a proportional response to the change in conditions.
INSTALLATION
Position the unit, taking into consideration the position of the rooms to be
ventilated, the exhaust position and the electrical services. Ensure there is
adequate access for installation and maintenance.
If the unit is sited in the heated void of the dwelling a condensate drain
should not be necessary. When sited in a cold void, consideration should be
given to fitment of a condensate drain. Alternatively, the unit and ducting
can be externally insulated to minimize condensation within the units housing.
To reduce the system resistance in your duct system, and therefore lower the
speed, power consumption and noise of the fan, follow these guidelines:
1.1. Keep the length of duct runs to a minimum, particularly the exhaust duct
run. 1.2. If you need to use flexible ducting, make sure that it is fully
extended and not crushed,
sagging or torn. 1.3. Try to minimize the use of diffusers/valves by having
similar length duct runs to the inlets. 1.4. The bend radius (measured to the
inside of the bend) should be at least 1x the duct diameter. 1.5. Avoid having
any bends, filters or other obstructions within 250mm of the fan inlets and
outlet. 1.6. Set the valves to their maximally opened positions for a minimal
pressure drop.
Securely mount the unit through the mounting holes on the casing using
appropriate fixings for the mounting substrate. It is recommended that anti-
vibration mounts, acoustic mat or rubber bushes are used.
Fixings (not supplied) to be capable of securing 4 x the weight of the unit.
Unit weight: 4.1kg
3
To maintain the IPx2 rating of the unit, the unit must NOT be mounted with the
cover removal slots facing upwards, or at an angle where they are visible from
above. All other orientations are acceptable.
See the dimensional details below for the mounting hole positions. -Spigot
diameters are 125mm
4
i. Base mounted Installation with ducting radiating out horizontally.
ii. Vertically mounted Installation with the exhaust spigot at top. The
electrical connections must come out of the bottom of the unit in order to
maintain the water ingress protection.
5
iii. Ceiling mounted Installation with ducting radiating out horizontally.
WIRING WARNING: THE UNIT AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM
THE POWER SUPPLY DURING THE INSTALLATION / OR MAINTENANCE. THIS UNIT MUST BE
EARTHED.
1. To remove the cover, use a coin or similar; depress the retaining tabs via
the slots in the side of the unit.
2. With the power off, connect a suitable mains power cable from a switched,
fused spur to the screw terminal block. Use the cable clamps and clip provided
to secure the lead.
3. Two mains voltage Live Switched (LS1 and LS2) connections are provided and
can be used to trigger a change in speed. Common inputs would be from a
bathroom lighting circuit. When commissioning the unit, a delay on timer and
an overrun timer can be selected and adjusted in the software using the
buttons and screen. See Commissioning section on page 9 of this document for
details.
4. The switched live output (230Vac) from any other switch or controller,
(such as a simple latching pull cord or push-button switch, humidistat or PIR
detector) can be connected to the LS terminal instead of connecting to a
lighting circuit.
5. Important: Use 4-core, low voltage, twisted pair, telecoms type cable for
accessories (Vent-Axia part number 459931). Accessories are connected via the
IO (Input Output) PCB; see the Low Voltage Connections diagram. Use the cable
clamp and grommet provided.
6. There are no delay-on or overrun timers with the volt-free connection as
the controller should determine when the fan is running at Boost or Normal
speeds. Use the LS connection described above if you want a timer.
7. Units showing on the rating label incorporate an earth connection for
functional purposes only. 8. Units showing on the rating label have a
Protective Earth.
6
CONNECTION DIAGRAM
A
Main power connections
A: Main power connections
The LS1, LS2 and NS terminals are electrically isolated.
B
Note: Neutral link between 2 & 6 should be removed if different RCD protection circuits arLeowusveoldtage
for mains power a & Live Switch connections.
connections,
Note: Ensure all live & neutral are isolated before servicing.
if fitted
· Units showing on the rating label incorporate an earth connection for functional purposes only. · Units showing on the rating label have a Protective Earth.
Connection
1
L
2
N
Description Live (220-240Vac) Neutral
Functional Earth
3 Protective Earth
1 2 3
6 5 4
4
LS1
Live Switched 1, (220-240Vac), isolated
7
5
LS2
Live Switched 2 (220-240Vac), isolated
6
NS
Neutral Switched, isolated
7 N + NS Link Wire
B: Low voltage connections
For best performance use 4-core, low voltage, twisted pair, telecoms type cable for accessories. (Available from Vent-Axia part number 459931).
A
P
D
ON
OFF
M
E
L
7
Position
A B C D E
F
G
H
I J K L M N O P
Label
5V
RS485
A+ B-
GND
COM
D IN 2
D IN 1
COM +
D OUT 2 D OUT 1
AN 2 AN 1
COM + COM + + GND + GND
Description
5V Output, Max 250mA Data Data Ground Digital input common
Digital input 2
Digital input common
Digital input 1
Digital output common Digital output 2 Digital output common Digital output 1
Analog input 2 Ground Analog input 1 Ground
Action
RS485 communication to wired accessories. Data connection (B, C) if available.
The 5V and Ground connections are available on all units.
Go to Boost speed (Min.1V, max. 6V).
The 5V output from the RS485 connection can be used as a power supply
Go to Low speed (Min.1V, max. 6V).
The 5V output from the RS485 connection can be used as a power supply
Unpowered Boost indicator Switch (Switching 6V 50mA max)
Unpowered LED fault indicator switch (Switching 6V 50mA max)
0-10V analogue input. Two user settable voltage thresholds with two user
settable actions. The unit will run at Normal when supplied voltage is between
the two thresholds.
RS485 Wired inputs The RS485 terminals are used to connect compatible sensors
and switches. The connection allows sensors be daisy chained to simplify
wiring. The maximum length of cable run from the unit is limited to 250m. Once
accessories are wired to the unit, they must be paired to the unit to
function correctly.
RS485 Wired input connection diagram
8
RF868 Wireless inputs Units that contain a Wireless receiver can be paired
with compatible sensors, these can be mains or battery powered depending on
the sensor.
A maximum of 15 wired and wireless sensors can be connected to a single unit.
Pairing sensors
To pair the unit with a wired or wireless sensor: – Press the Mode button to
turn on the display. – Press and hold the Mode button until the LED
illuminates solid White – Release the mode button, the LED will flash White to
indicate that it is in pairing mode. The unit will remain in pairing mode for
1 hour, or until the mode button is pressed again. – Activate the pairing
function on the sensor to be paired (see the instructions that came with the
sensor). – When a sensor is paired the total number of paired devices is
displayed on the unit.
Removing sensors
To remove paired sensors, the unit must be reset. Caution, this will reset all
values back to factory default. – Press the Mode button to turn on the
display. – Press and hold the Mode button until the LED illuminates solid Red
– Release the mode button, the LED will stay Red. – Pressing the Mode button
again will confirm the reset command. If a reset is not wanted, leave the unit
until the command times out and the LED turns off.
C: Sensor priorities
The unit set the motor speed based on the source in the following order: ·
User override · LS inputs (1 and 2) · Digital inputs (1 and 2) · Sensor
override: The Sensor override action is decided based upon the Sensor input
(Humidity Sensor, Co2 sensor, Analog inputs) whichever sets the motor to run
in Highest speed. · Default speed (run in normal speed)
Note: At each priority state, if more than one inputs are active (e.g. Digital
input 1 and 2 are active), then motor will always run at a speed from the
input which has highest speed level.
Example – LED Fault Indicator Connection (MVDC MS/H do not have this facility)
Example – LED Boost Indicator Connection (MVDC MS/H do not have this facility)
9
Low Voltage Switch’s Boost & Low Speed
FEATURE DESCRIPTIONS
If compatible, the unit can be controlled via the Bluetooth linked App. This is only available on Sentinel-X Wireless units.
Comfort mode
If Comfort mode is enabled the unit will behave as follows to all LS inputs:
Trigger LS input active less than 5 minutes LS input active more than 5
minutes but less than 20 minutes
LS input active more the 20 minutes
Action
No action (continue to run at Normal speed)
Once LS input is removed, fan will run at user selected speed for the length
of time LS was present plus the set over-run time (if over run is enabled).
Unit will Boost after 20mins. Once LS input is removed, fan will run at user
selected speed for 20 minutes plus the set overrun time (if over run is
enabled).
The above applies to all LS inputs. The times are not adjustable by the user.
Delay On
A delay can be set so that the unit will not respond to an input until after
the set delay has elapsed, applies to LS
inputs only.
Overrun Timer
The unit can be set to run for a defined period after the input is removed,
applies to LS inputs only.
Humidity Rapid rise*
Rapid Rise humidity response functions to detect rapid rises in humidity when
the ambient %RH is under the threshold
setting. If a rapid rise is detected the fan will boost until the humidity
lowers again.
Humidity Ambient response*
When ambient response is enabled the threshold set point is modified based on
the ambient temperature. This helps
to prevent nuisance boosting of the unit as temperatures changes during the
day.
Humidity Threshold*
The unit will boost when the RH is above the threshold set point.
10
CO2 threshold Boost / Purge*
The unit will go to Boost / Purge when the detected CO2 level exceeds the set
thresholds.
Analogue inputs Both analogue inputs have adjustable low and high trigger
voltages within the 0-10V range. The response to being above or below either
of the threshold voltages is user settable. Note: The display doesn’t show a
decimal point, for example at threshold voltage of 5.2V, is displayed as “52”
on the unit. Digital Inputs
The unit can be set to change speed (selectable), based on whether the digital
inputs are above or below the threshold voltage. See the table of Low Voltage
Connections for details.
Display Lock
To protect the settings on the MEV unit a pin code can be enabled via the main
menu. Once the lock function has been enabled the Pin code can be set. The
3-digit pin is A to F, 0 to 9, and the default is LoC.
- If external RH or CO2 sensors are fitted via RS485, they will have priority over the internal sensors, their value will also be displayed on the unit in preference to the internal sensor.
11
UNIT ADJUSTMENT 1. Commissioning and configuration on all products is
supported by the 3 digit user interface and associated push buttons. 2. When
powered on, the unit will display the firmware revision number, after a few
seconds the unit will display the first option in the menu structure (see
below). 3. The display will enter standby mode after defined timeout (default
10min) or user selects “END” option in menu, press the Mode button to turn the
display back on. 4. Changes to the settings can be made
via the + and buttons, the Mode button will
accept changes and move onto the next menu option. 5. When setting the speeds,
there is an internal logic: Low<Normal<Boost<Purge.
I.e., Boost is always higher than Normal. 6. The actions for each of the Live
Switched (LS), inputs are selectable. The setting for delays and
over run timers are applicable to all inputs. 7. To restore factory settings,
Press and hold “Mode” button for 10 seconds Wireless units can be commissioned
via the Bluetooth connected App. Links to the App are shown on the cover page
of this manual. The App must be installed before a connection to the unit is
possible. Bluetooth Pairing To enable Bluetooth pairing on the unit: – Press
the Mode button to turn on the display – Press and hold the Mode button until
the LED illuminates solid Blue
Release the mode button, the LED will flash Blue to indicate that it is in
pairing mode. – Follow the instruction on the App to connect to the unit.
12
User Configurable Parameters
Display text
Lxx nxx bxx Pxx LS1 LS2 LS3 c-n d-n dxx o-n oxx r-y A-n hxx
C2b
C2P
A1LA A1HA A1tL A1tH A2LA A2HA A2tL A2tH D1 D2 unl PIn dtxx rot hu tu CO2 rEf
cAL end
Function
Low speed Normal speed Boost speed Purge Speed Live switch 1 Live switch 2
Live switch 1&2 Comfort mode Delay On Delay On time Overrun Overrun time
Humidity Rapid Rise Humidity Ambient Response Humidity threshold
CO2 threshold boost
CO2 threshold purge
Analogue 1 – low action Analogue 1 – high action Analogue 1 – low threshold
Analogue 1 – high threshold Analogue 2 – low action Analogue 2 – high action
Analogue 2 – low threshold Analogue 2 – high threshold Digital input 1 Action
Digital input 2 Action Unlock code Display Pin Display time Rotate display
Humidity temperature CO2 Calibration reference value Calibration Mode end
Selections
1 to 97% motor speed 2 to 98% motor speed 3 to 99% motor speed 4 to 100% motor
speed Low, Boost or Purge speed Low, Boost or Purge speed Low, Boost or Purge
speed Comfort mode – yes or no Delay on – yes or no Delay to boost duration 1
to 60 minutes Overrun – yes or no Overrun duration 1 to 60 minutes Rapid rise
– yes or no Ambient response – yes or no Ambient response threshold 40 to 90%
RH Boost threshold 650 4950 PPM in increments of 50 Purge threshold 700
5000 PPM in increments of 50 Low, Normal, Boost or Purge speed Low, Normal,
Boost or Purge speed Analogue Input Threshold Low 1 – 99 Analogue Input
Threshold High 1 – 99 Low, Normal, Boost or Purge speeds Low, Normal, Boost or
Purge speeds Analogue Input Threshold Low 1 – 99 Analogue Input Threshold High
1 – 99 Low, Boost or Purge speeds Low, Boost or Purge speeds Turn on/off the
menu lock 3 characters A to 9 Adjust how long the display is illuminated
Invert the display Show the current internal humidity Show the current
internal temperature Show the current CO2 level 40 to 200 Y to enable End of
menu (loop to start)
Default
10% 25% 35% 50% Low Boost Purge No No 10m No 10m No No 70%
100
120
Low Boost
15 75 Low Boost 15 75 Low Boost – – LoC 10m rot % °C PPM 40 (400ppm) n
If the unit being commissioned is not fitted with the relevant hardware, the associated menu options will not be available.
CO2 Calibrations
The following instructions describe the actions required to calibrate the CO2 sensors used within the MEV unit (if fitted), and the Room Sensor accessories in two steps:
13
1. MEV Unit Internal sensor Step 1 can be done by either Exposure method or
Measurement method, the baseline step 2 is actioned once either step 1 options
are complete.
1.1 Exposure method step 1 Exposure method assumes that the outside CO2
concentration is 400 PPM in the rooms in which the MEV extracts air from, the
Rooms must be well ventilated by opening any external windows and doors for 10
to 15 minutes. The room must remain well ventilated and unoccupied until after
the baseline step has been actioned.
1.2 Measurement method step 1 If the Engineer has a calibrated CO2 meter, they
simply need to measure the CO2 in accordance to the CO2 meters instructions
within the rooms the MEV extract air from. Measurement taken from each room
should be recorded and then averaged. Example: Room 1 450ppm + Room 2 440ppm
- Room 3 460ppm = 1350ppm / 3 = 450ppm The averaged value is then used
during the baseline step.
1.3 Baseline step 2
MEV On-Board display method Within the MEV menu there is rEF which has a default value of 40 (=400ppm), if using the Exposure method of calibration this does not need to be changed. For the Measurement method of calibration, the value within rEF should be changed to the recorded average PPM, using the example value this would be 45 (=450ppm). With the rEF value set as required, the user should navigate to the cAl menu and use the up/down arrow to select y (=Yes). The status LED will start blinking Magenta colour signifying the start of the calibration, the MEV will repeatedly read the CO2 sensor for 3 minutes to obtain a stable reading, once the status LED stops flashing the Calibration value has been set.
MEV Mobile App method Once the app is connected to the MEV navigate to the CO2 screen from the home screen. On the CO2 screen enable Set CO2 calibration at the bottom of the page. An additional slide bar will appear with a default value set to 400ppm, if using the measurement method, the value should be changed to match the measured averaged recorded PPM, using the example value this would be 450ppm. For the Exposure method the value should be unchanged at 400ppm. With the value set the Save button should be pressed in the top right of the screen to start the calibration process, the status LED will start blinking Magenta colour signifying the start of the calibration, the MEV will repeatedly read the CO2 sensor for 3 minutes to obtain a stable reading, once the status LED stops flashing the Calibration value has been set.
2. Room Sensor Calibration The Room sensor can only be calibrated using the Exposure method and will have Auto Background Calibration (ABC) by default.
2.1 Exposure method Step 1 Exposure method assumes that the outside CO2 concentration is 400 PPM in the room which the Sensor is fitted, the room must be well ventilated by opening any external windows and doors for 10 to 15 minutes. The room must remain well ventilated and unoccupied until after the baseline step is complete.
2.2 Baseline method Step 2 With the Room sensor paired to the system the status LED will be Green when the button is pressed, in this condition the button should be pressed and held (8 Seconds) until the status LED is Magenta, the button should then be released and the LED will be blinking Magenta to signify the start of the calibration process, the room should be unoccupied once the calibration has started and should remain so for 5 minutes. During the calibration process the Room sensor will repeatedly read the CO2 sensor for 3 minutes to obtain a stable reading, once the status LED stops flashing the Calibration value has been set.
14
FAULT CODES
If the MEV unit detects a fault it will display an error message on the HMI display: Fault Code Description
F01
Control fault Unit failed startup check Turn the power off and on again.
F02
Motor Fault No RPM
Check that the impellor has free movement.
(MVDC MS/H don’t have this facility) Check internal motor wiring.
F03
Humidity/Temp sensor Fault No value internal sensor
Contact tech support, scroll part.
F04
CO2 sensor Fault No value internal sensor
Check the internal wiring to the sensor
F05
Temp or Humidity sensor connected via Check that the sensor is turned on.
RF/RS485 is offline/Lost
Re-pair the sensor to the unit, see page 10.
F06
CO2 sensor connected via RF/RS485 is Check that the sensor is turned on.
offline/Lost
Re-pair the sensor to the unit, see page 10.
F07
4-Way Speed Switch
SSU offline or lost Please reconnect
F08
AIM (Alarm Interface Module)
AIM Sensor triggered / offline or lost Verify Issue
If a fault persists, contact your local technical support, see the back cover of this manual for details.
SPARE PARTS
WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE
POWER SUPPLY DURING PART REPLACEMENT.
1. Individual faulty parts should not be replaced due to complexity of
assembly. Only the full scroll assembly is replaceable.
2. To remove the scroll assembly, isolate the power, then use a coin or
similar to depress the cover retention clips and remove the cover.
3. Disconnect and remove the power supply and signal leads. 4. Remove the
scroll assembly by unscrewing the two screws and unclipping the clips in the
opposite
two corners and lift the scroll assembly out of the housing. 5. The fan has
sealed for life bearings, which do not require lubrication. Expected service
life is at least
45,000 hours continuous running. 6. Upon reassembly, check all fixings are
tight and secure.
For a replacement Scroll assembly please contact: Vent-Axia Technical support
+44 (0)344 856 0594 Email: vatechsupport@vent-axia.com
Please take note of the model’s name and number to ensure the correct scroll
assembly is supplied.
15
ACCESSORIES
Sensor/Controller Name / Function
Temp/RH
CO2 (+RH) 0-10V PIR
AIM (Alarm interface module) External Temp/RH battery powered MEV Controller
RH
RS485 & RF868 Speed Switch
4 way
MVDC-MS / H Wired 0-10V
496428 (240V)
496432 (240V) –
–
–
–
SMV H
SMV PLUS H
Wired
Wired
0-10V
RS485
496428 (240V) 496429 (240V)
496432 (240V) 496433 (240V)
–
496438 (240V)
–
–
–
–
–
496442 (240V)
–
496621 (240V)
SMV HX / CO2
SMV PLUS HX / CO2
Wired RS485
Wireless RF868
496429 (240V)
496429 (240V) 496431 (Battery)
496433 (240V) 496433 (240V)
496438 (240V) 496438 (240V)
–
496441 (240V)
–
496442 (Battery)
496442 (240V) 496442 (240V)
496621 (240V)
496620 (240V) 496437 (Battery)
All units
Sensor/Controller Name
4-way analogue speed switch Timespan controller Air Quality Sensor
Ambient response Humidity sensor Ecotronic Humidity sensor ThermoSwitch 7 Day
timer switch Visionex PIR 3-pole Isolator switch Remote delay timer Isolator
relay Normal/boost switch Normal/boost/purge switch 2-way switch with neon 3
speed controller switch
Normal / boost switch stainless Normal / boost switch with Neon
LED Fault indicator
Part Number 496622 563519 563506 563550 563532 563502 563515 459623 563518 457986 442030 455213 5108454 459746 563533 437320 449060 448356
16
Product Fiche
Name:
Model ID (Stock Ref.)
437634C
443298B
SEC Class
SEC Value (‘Average’)
SEC Value (‘Warm’)
SEC Value (‘Cold’) Label Required? (Yes/No=Out of scope) Declared as: RVU or
NRVU/UVU or BVU Speed Drive
Type HRS (Recuperative, Regenerative, None) Thermal Eff: [ (%), NA(if none)]
Max. Flow Rate (m3/h)
Max. Power Input (W): (@Max.Flow Rate)
LWA: Sound Power Level dB)
Ref. Flow Rate (m3/s)
Ref. Pressure Diff. (Pa)
SPI [W/(m3/h)] Control Factor & Control Typology: (CTRL/ Typology) Control
Factor; CTRL
Control Typology
Declared: -Max Internal & External Leakage Rates(%) for BVUs or carry over
(for regenerative heat exchangers only), Ext. Leakage Rates (%) for Ducted
UVUs; Mixing Rate of Non-Ducted BVUs not intended to be equipped with one duct
connection on either supply or extract air side; Position and description of
visual filter warning for RVUs intended for use with filters, including text
pointing out the importance of regular filter changes for performance and
energy efficiency of the unit
For UVUs (Instructions Install Regulated Supply/Extract Grilles Façade)
Internet Address (for Disassembly Instructions) Sensitivity p.
Variation@+20/20 Pa: (for Non-Ducted VUs) Air Tightness-ID/OD-(m3/h) (for Non-
Ducted VUs) Annual Electricity Consumption: AEC (kWh/a) Annual Heating Saved:
AHS (kWh/a)
AHS: Average
AHS: Warm
AHS: Cold
B -27.2 -11.7 -54.3
338.8 43 46.4
0.066 201 0.07
0.4 28.3 12.8 55.4
Vent-Axia
445655B 495360
495361
B -27 -11.5 -54.1
Yes
RVU/UVU Multi Speed
None
N/A 400 52 50.7 0.078 203 0.08
407849A 496186
0.65 Local Demand Control
<5% Internal, <5% External
N/A
N/A
In F&W
www.vent-axia.com N/A N/A
0.5
28.3 12.8 55.4
495362 B
-26.9 -11.4 -54.0
505.1 85 52.2
0.098 206 0.09
0.6 28.3 12.8 55.4
495363
17
Disposal
This product should not be disposed of with household waste. Please recycle
where facilities exist. Check with your local authority for recycling advice.
The
Guarantee
Applicable only to products installed and used in the United Kingdom. For details of guarantee outside the United Kingdom contact your local supplier.
Vent-Axia guarantees its products for two years from date of purchase against
faulty material or workmanship. In the event of any part being found to be
defective, the product will be repaired, or at the
Company’s option replaced, without charge, provided that the product: –
· Has been installed and used in accordance with the instructions given with
each unit. · Has not been connected to an unsuitable electricity supply. (The
correct electricity supply voltage is
shown on the product rating label attached to the unit). · Has not been
subjected to misuse, neglect or damage. · Has not been modified or repaired by
any person not authorised by the company.
IF CLAIMING UNDER TERMS OF GUARANTEE
Please return the complete product, carriage paid to your original supplier or
nearest Vent-Axia Centre, by post or personal visit. Please ensure that it is
adequately packed and accompanied by a letter clearly marked “Guarantee Claim”
stating the nature of the fault and providing evidence of date and source of
purchase.
The guarantee is offered to you as an extra benefit and does not affect your
legal rights.
Head Office: Fleming Way, Crawley, West Sussex, RH10 9YX
EU Authorised Representative: Vent-Axia Sigarenmaker 5 – 5521DJ Eersel Nederland authorisedrep@vent-axia.nl
UK NATIONAL CALL CENTRE: –
Sales Enquiries: Technical Support:
Tel: 0344 8560590 Tel: 0344 8560594
Email: sales@vent-axia.com Email: vatechsupport@vent-axia.com
Ventair Australia
Tel: +61 3 9775 0556 Fax: +61 39775 0775 Email: info@ventair.com.au 4 Capital
Place, Carrum Downs, VIC 3201, Australia
As part of the policy of continuous product improvement Vent-Axia reserves the
right to alter specifications without notice.
495584 G
0623 18
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>