APsmart RSD-D Rapid Shutdown Device and Transmitter Installation Guide
- September 26, 2024
- APsmart
Table of Contents
RSD-D Rapid Shutdown Device and Transmitter
“`html
Specifications:
- Product: APsmart Rapid Shutdown Device & Transmitter
- Model: RSD-D TRANSMITTER-PLC
- Version: Rev2.9 2023/10/07
Product Information:
The APsmart Rapid Shutdown Device & Transmitter consists of
the RSD-D and Transmitter components. The RSD-D meets SunSpec
requirements and executes rapid system shutdown when the
Transmitter signal is absent. The Transmitter-PLC sends a signal to
the RSD-D units to keep the PV modules connected and supplying
energy. This solution complies with NEC 690.12 specifications for
2017, 2020 & 2023 and supports SunSpec signaling for rapid
shutdown.
RSD-D Features:
-
Meets SunSpec requirements
-
Manual rapid system shutdown using the Transmitter breaker
switch -
No automatic shutdown function for arc detection
Transmitter-PLC Features:
- Part of a rapid shutdown solution when paired with RSD-D
- Sends signals to RSD-D units to maintain energy supply
- Comes with one or two cores and optional power supply for
residential or commercial use
Product Usage Instructions:
RSD-D Installation:
-
Ensure the RSD-D is installed according to the provided
manual. -
Connect the RSD-D to the PV modules as per the system wiring
diagram. -
Verify that the RSD-D receives a heartbeat signal from the
Transmitter for normal operation.
Transmitter-PLC Installation:
-
Install the Transmitter-PLC as instructed, ensuring it is on
the same AC branch circuit as the inverter. -
Connect one or two cores and the power supply based on
residential or commercial requirements.
Rapid Shutdown Procedure:
-
To execute rapid system shutdown, use the Transmitter breaker
switch manually. -
In case of abnormal system operation, triggering shutdown by
cutting off the Transmitter signal is necessary.
FAQ:
Q: What should I do if I encounter issues with the RSD-D or
Transmitter?
A: If you face any problems with the RSD-D or Transmitter,
contact customer support to obtain an RMA number and start the
replacement process. Remember that damaging or opening the RSD-D
will void the warranty.
“`
Installation /User Manual
APsmart Rapid Shutdown Device & Transmitter
Rev2.9 2023/10/07 RSD-D TRANSMITTER-PLC TRANSMITTER-PLC OUTDOOR KIT
© All Rights Reserve
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS———————————————————————-1 RSD
PRODUCTS———————————————————————————————–2 TRANSMITTER
PRODUCTS———————————————————————————-3 SYSTEM WIRING
DIAGRAM———————————————————————————4 RSD-D
INSTALLATION———————————————————————————-7 TRANSMITTER-PLC INSTALLATION
———————————————————————11 TECHNICAL DATA–RSD-D—————————————————————————-14
TECHNICAL DATA–TRANSMITTER-PLC—————————————————————–15 TECHNICAL DATA
–TRANSMITTER-PLC-OUTDOOR KIT———————————————-16
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions to be followed during installation
and maintenance of the APsmart RSD-D and Transmitter. To reduce the risk of
electrical shock and ensure the safe installation and operation of the APsmart
RSD-D and Transmitter, the following symbols appear throughout this document
to indicate dangerous conditions and important safety instructions.
Safety Instructions
· Do NOT disconnect the PV module from the RSD-D without first disconnecting
the AC power. · Only qualified professionals should install and/or replace the
APsmart RSD-D. · Perform all electrical installations in accordance with local
codes. · Before installing or using the RSD-D, please read all instructions
and cautionary markings in the
technical documents. · Be aware that the body of the operating RSD-D is a heat
sink and can reach high temperature.
To reduce risk of burns, do not touch the body of the RSD-D. · Do NOT attempt
to repair the RSD-D. If it fails, contact APsmart Customer Support to obtain
an
RMA number and start the replacement process. Damaging or opening the RSD-D
will void the warranty.
The power supply of the Transmitter-PLC and inverter MUST be on the same AC
branch circuit as the inverter to meet rapid shutdown requirements.
This device complies with part 15 of the FCC Rules, Operation is subject to
the following two conditions: (1)This device may not cause harmful
interference, and (2) this device must accept any interference receiver,
including interference that may cause undesired operation.
Qualified Personnel:
Person adequately advised or supervised by an electrically skilled person to
enable him or her to perceive risks and to avoid hazards which electricity can
create. For the purpose of the safety information of this manual, a “qualified
person” is someone who is familiar with requirements for safety, electrical
systems and EMC and is authorized to energize, ground, and tag equipment,
systems, and circuits in accordance with established safety procedures. The
inverter and balance of system may only be commissioned and operated by
qualified personnel.
1
User Manual
RSD PRODUCTS
RSD-D
· Meets NEC 2017, 2020&2023 (690.12) requirements · Executes rapid shutdown of
system when Transmitter-PLC signal is absent · Meets SunSpec requirements ·
Dual-input channel
The RSD-D meets SunSpec requirements, maintaining normal function by
continually receiving a heartbeat signal from the APsmart Transmitter. The
RSD-D executes rapid system shutdown when the Transmitter signal is absent.
Users can manually execute rapid shutdown using the Transmitter breaker
switch.*(1)(2)
(1) RSD-D does not have automatic shutdown function for arc detection. When the system is abnormal, the transmitter signal is cut off by pulling the gate, which triggers shutdown.
(2) RSD-D is designed to reduce the risk of fire suppression but does not solve the risk of a arc fire.
2
User Manual
TRANSMITTER PRODUCTS
Transmitter-PLC
· Meets NEC 2017, 2020&2023 (690.12) requirements · Switching off Transmitter-
PLC results in
rapid shutdown of the output of PV modules · Meets SunSpec requirements ·
Equipped with single/dual core · Optional 85-264VAC power supply · Optional
180-550VAC power supply
Transmitter-PLC-Outdoor Kit
· Meets NEC 2017, 2020&2023 (690.12) requirements · Switching off Transmitter-
PLC results in
rapid shutdown of the output of PV modules · Meets SunSpec requirements ·
Equipped with single/dual core · Optional 85-264VAC power supply · Optional
180-550VAC power supply
3
User Manual
SYSTEM WIRING DIAGRAM
The APsmart Rapid Shutdown System Transmitter-PLC is part of a rapid shutdown
solution when paired with the APsmart RSD-D, a PV module rapid shutdown unit.
While powered on, the Tansmitter-PLC sends a signal to the RSD-D units to keep
the PV modules connected and supplying energy.
RSD-D units automatically enter rapid shutdown mode when the Transmitter-PLC
is switched off and resume energy production when power is restored to the
Transmitter-PLC. This solution complies with NEC 690.12 specifications for
2017, 2020 & 2023 and supports the SunSpec signaling for rapid shutdown.
The Transmitter-PLC includes one or two cores and an optional power supply:
85-264VAC for residential, 180-550VAC for commercial.
The Transmitter-PLC Outdoor Kit includes a Transmitter-PLC with one or two
cores, outdoor enclosure, 85-264VAC or 180V-550VAC power supply. It could be
used in a residential or commercial project.
RSD-D Transmitter-PLC Inverter
PV1+ PV1PV2+ PV2-
*Homerun only PV+ cable through core
4
User Manual
SYSTEM WIRING DIAGRAM
RSD-D Transmitter-PLC-Outdoor Kit Inverter
PV1+ PV2+
*Homerun only PV+ cable through core
PV1+ PV2+
Homerun only PV+ cable through core optional
RSD-D Transmitter-PLC-Outdoor Kit Inverter Emergency stop button boxoptional:
Press the emergency stop button, the transmitter AC power
supply is disconnected, the RSD closes the output, and the system rapid
shutdown.
5
User Manual
SYSTEM WIRING DIAGRAM
PV1+ PV2+
RSD-D Inverter Inverter in diagram includes an integrated SunSpec-certified
Rapid Shutdown Transmitter.
6
User Manual
RSD-D INSTALLATION
INSTALLATION NOTES
Installation MUST comply with local regulations and technical rules
Perform all electrical installations in accordance with local codes. Be aware
that only qualified professionals should install and/or replace the RSD-D.
Before installing or using an RSD-D, please read all instructions and warnings
in the technical
documents and on the inverter system itself as well as on the PV array. Be
aware that installation of this equipment includes the risk of electric shock.
Do not touch any live parts in the system, including the PV array, when the
system has been
connected to the electrical grid. Ensure the PV module and inverter have been
disconnected before installing an RSD-D. Do not attaching negative power wires
in the homerun on any RSD devices or connectors.
Be sure to verify the voltage and current specifications of your PV module
match with those of the RSD-D.
The maximum open circuit voltage of the PV module must not exceed the
specified maximum input voltage of the APsmart RSD-D.
Additional installation components from APsmart
· DC extension cable (sold separately)
Required parts and tools to complete the installation
In addition to your PV array and its associated hardware, you will need a
torque wrench and a Phillips screwdriver.
7
User Manual
RSD-D INSTALLATION
Step 1: Install the RSD-D.
OUTPUT-
INPUT2+
INPUT1+
OUTPUT+
INPUT2-
INPUT1-
Mounting brackets
Buckle RSD-D onto the PV module frame.
NOTE: Do not place the RSD-D (including DC connectors) where exposed to the sun, rain or snow, even gap between modules. Allow a minimum of 3/4”(1.5cm.) between the roof and the bottom of the RSD-D to allow proper air flow.
8
User Manual
RSD-D INSTALLATION
Step 2. Connect the INPUT1 connectors of the RSD-D to the first PV module
junction box and connect the INPUT2 connectors to second PV module, the device
DC output voltage is within the range of 1.2 ~ 2v.
NOTE: Do not short-circuit the RSD-D output connectors, otherwise it will be
damaged. RSD-D cable length
NOTE: The output cable length of triad junction box PV module should be no
less than 1.2m.
1.2m
NOTE: The output cable length of integrated junction box PV module should be
no less than 0.9m.
0.9m
9
User Manual
RSD-D INSTALLATION
NOTE: When installing RSD-D cable, the bending radius of the cable near the
casing must be greater than 50 mm.
Step 3: Connect the output ports of two adjacent RSD-Ds in series and then
connect to the inverter with a self-made DC extension cable.
NOTE: Do not connect homerun to inverter before finishing all strings
connections and tests. WARNING: When connecting the RSD-D to only one PV
module, use INPUT1 port ONLY, then short both terminals of INPUT2 directly,
otherwise the RSD-D may be damaged. The DC output voltage remain same. NOTE:
Please use the same type of DC connector as the RSD in the system. The RSD
damage caused by using different type of DC connector will not be covered by
the warranty.
10
User Manual
TRANSMITTER-PLC INSTALLATION
Note: If there is only one core needed, connect using Core 1 terminal.
Transmitter-PLC power supply must be on same AC branch circuit as inverter to
meet rapid shutdown requirements. During operation, the Power LED should be
lit and the Signal LED should be blinking. If the TransmitterPLC fails to
work, the Signal LED will not be blinking. If the Power LED is also not lit,
check the power supply first. NOTE: Install the RSD-D before powering on the
Transmitter-PLC. · Mount Transmitter-PLC and power supply on DIN rail ·
Connect DC leads from power supply to Transmitter-PLC · Connect single/dual
core(Core 1 and Core 2) to Transmitter-PLC
Place rapid shutdown system label no more than 1m (3ft) from Transmitter-PLC
or AC disconnect if not at same location.
11
User Manual
TRANSMITTER-PLC INSTALLATION
Homerun only PV+ cable through core
NOTE: Install the RSD-D before powering the Transmitter-PLC.
NOTE: The waterproof jacket and related accessories are not configured before
delivery and customers need to buy by themselves.
· Pass either positive or negative cables through cores (either both positive
cables or both negative cables. Do not use one positive and one negative
cable.)
· Connect wires to AC side of power supply
Max number of Strings Per Core :
DC cable Diameter(without connector) 29mm Core 11mm Core
5.9mm 15 6
6.35mm 15 5
7mm 14 4
8.6mm 10 2
Max string length : 30 modules Max current per core : 160A(29mm)/75A(11mm) Max cable length from inverter(+) to inverter(-) : 1500ft (450m)
12
User Manual
TRANSMITTER-PLC INSTALLATION
Drilling Guide for .75″ Conduit
Drilling Guide for 1″ Conduit
NOTE: The Outdoor Kit was not punched before delivery and customer need to make it themselves according to the actual situation. The figure is only for reference.
13
User Manual
TECHNICAL DATA–RSD-D
Model Input Data (DC)
Range of Input Operating Voltage Maximum Cont. Input Current (Imax) Maximum
Short Circuit CurrentIsc
Output Data (DC) Range of Output Operating Voltage Maximum Output Current
Maximum System Voltage Maximum Series Fuse Rating
Mechanical Data Operating Ambient Temperature Range Dimensions (without cable
& connectors) Cable Length Cable Cross Section Size
Connector
Enclosure Rating Protection Temperature Features & Compliance Communication
Safety Compliance EMC Compliance
RSD-D-15
RSD-D-20
8-65V Per Channel
15A Per Channel
20A Per Channel
25A
16-130V
15A
20A
1000V/1500V
30A
-40 oF to +167oF (-40 °C to + 75 °C) 5.5″ x 2″ x 0.8″(140 mm x 50.6 mm x 20 mm)
Input 500mm/Output 2400mm TUV:4mm²/UL:12AWG
Input: Stäubli MC4 PV-KBT4&KST4 or Customize Output: APsystems specified or
Customized NEMA Type 6P/IP68 100°C
PLC
NEC 2017, 2020&2023 (690.12); UL1741; CSA C22.2 No. 330-17; IEC/EN62109-1
FCC Part15; ICES-003
14
User Manual
TECHNICAL DATA–TRANSMITTER-PLC
Model Main electrical data
Transmitter-PLC
Input Voltage Input Current Communication
Power Supply
Residentialoptional Commercialoptional
Core data
Max. Current Max. System Voltage Internal Opening for Wires/Outside Dimensions
Max. Supported PV Modules per String
3N0ummobdeurleOs f Strings Per Core
DC Cable Diameter(without connector) 29mm Core 11mm Core
Environmental
Temperature
Structure data
Dimensions (W x H x D) Enclosure Environmental Rating
Features & Compliance
Safety Compliance EMC Compliance
12VDC 0.8A PLC
85-264VAC Input, 12VDC Output, 90 mm x 17.5 mm x 58.4 mm
180-550VAC Input, 12VDC Output, 125.2 mm x 32 mm x 102 mm
29mm Core
11mm Core
320A (160A*2
150A (75A*2
~29mm/65mm
1500VDC 30 modules
~11mm/42mm
30 modules 5.9mm
15
6
6.35mm 15 5
7mm 14 4
8.6mm 10 2
-40°C+100°C
90 mm x 35 mm x 40 mm IP30
NEC 2017, 2020&2023 (690.12); UL1741; CSA C22.2 No. 330-17 FCC Part15; ICES-003
15
User Manual
TECHNICAL DATA–TRANSMITTER-PLC-OUTDOOR KIT
Model Main electrical data
Input Voltage Input Current Communication
Power Supply
Residentialoptional Commercialoptional
Core data
2M9amx.mCuCrroernet 1M5a0xA. SPyesrtecmoreVoltage 1In5t0e0rnVaDl COpening for
Wires/Outside Dimensions Max. Supported PV Modules per String
3N0ummobdeurleOs f Strings Per Core
30 modules DC Cable Diameter(without connector)
29mm Core
Environmental
Temperature
Structure data
Dimensions (W x H x D) Enclosure Environmental Rating
Features & Compliance
Safety Compliance EMC Compliance
Transmitter-PLC-Outdoor Kit
12VDC 0.8A PLC
85-264VAC Input, 12VDC Output, 90 mm x 17.5 mm x 58.4 mm 180-550VAC Input, 12VDC Output, 125.2 mm x 32 mm x 102 mm
320A (160A*2 1500VDC
~29mm/65mm 30 modules
5.9mm 15
6.35mm 15
7mm 14
8.6mm 10
-40°C+60°C
198.5 mm x 298 mm x 179 mm IP30
NEC 2017, 2020&2023 (690.12); UL1741; CSA C22.2 No. 330-17 FCC Part15; ICES-003