APsmart RSD-D Rapid Shutdown Device & Transmitter User Manual

June 5, 2024
APsmart

APsmart logo

Installation /User Manual
smart Rapid Shutdown Device & Transmitter
Rev1.9 2022/03/10

APsmart RSD D Rapid Shutdown Device &amp TransmitterAPsmart RSD D Rapid Shutdown Device &amp Transmitter -
2

RSD-D
TRANSMITTER-PLC
TRANSMITTER-PLC OUTDOOR KIT
© All Rights Reserve

IMPORTANT SAFETY INSTRUCTIONS

This manual contains important instructions to be followed during the installation and maintenance of the smart RSD-D and Transmitter. To reduce the risk of electrical shock and ensure the safe installation and operation of the smart RSD-D and Transmitter, the following symbols appear throughout this document to indicate dangerous conditions and important safety instructions.

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
sambyol

Safety Instructions

  • Do NOT disconnect the PV module from the RSD-D without first disconnecting the AC power.
  • Only qualified professionals should install and/or replace the APsmart RSD-D.
  • Perform all electrical installations in accordance with local codes.
  • Before installing or using the RSD-D, please read all instructions and cautionary markings in the technical documents.
  • Be aware that the body of the operating RSD-D is a heat sink and can reach a high temperatures. To reduce risk of burns, do not touch the body of the RSD-D.
  • Do NOT attempt to repair the RSD-D. If it fails, contact APsmart Customer Support to obtain an RMA number and start the replacement process. Damaging or opening the RSD-D will void the warranty.

The power supply of the Transmitter-PLC and inverter MUST be on the same AC branch circuit as the inverter to meet rapid shutdown requirements.
This device complies with part 15 of the FCC Rules, Operation is subject to the following two conditions:
(1)This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

Qualified Personnel:
Person adequately advised or supervised by an electrically skilled person to enable him or her to perceive risks and to avoid hazards that electricity can create. For the purpose of the safety information f this manual, a “qualified person” is someone who is familiar with requirements for safety, electrical systems, and EMC and is authorized to energize ground, and tag equipment, systems, and circuits in accordance with established safety procedures. The inverter and balance of the system may only be commissioned and operated by qualified personnel.

RSD PRODUCTS

RSD-D

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
2

  • Meets NEC 2017 & 2020 (690.12) requirements
  • Executes rapid shutdown of system when Transmitter-PLC signal is absent
  • Meets SunSpec requirements
  • Dual-input channel

The RSD-D meets SunSpec requirements, maintaining normal function by continually receiving a heartbeat signal from the APsmart Transmitter. The RSD-D executes a rapid system shutdown when the Transmitter signal is absent. Users can manually execute rapid shutdown using the Transmitter breaker switch.

TRANSMITTER PRODUCTS

Transmitter-PLC

APsmart RSD D Rapid Shutdown Device &amp Transmitter

  • Meets NEC 2017&2020 (690.12) requirements
  • Switching off Transmitter-PLC results in rapid shutdown of the output of PV modules
  • Meets SunSpec requirements
  • Equipped with single/dual core
  • Optional 85-264VAC power supply
  • Optional 180-550VAC power supply

Transmitter-PLC-Outdoor Kit

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig1

  • Meets NEC 2017&2020 (690.12) requirements
  • Switching off Transmitter-PLC results in a rapid shutdown of the output of PV modules
  • Meets SunSpec requirements
  • Equipped with single/dual core
  • Optional 85-264VAC power supply
  •  Optional 180-550VAC power supply

SYSTEM WIRING DIAGRAM

The smart Rapid Shutdown System Transmitter-PLC is part of a rapid shutdown solution when paired with the smart RSD-D, a PV module rapid shutdown unit. While powered on, the Transmitter-PLC sends a signal to the RSD-D units to keep the PV modules connected and supply energy. RSD-D units automatically enter rapid shutdown mode when the Transmitter-PLC is switched off and resume energy production when power is restored to the Transmitter-PLC. This solution complies with NEC 690.12 specifications for 2017 & 2020 and supports the SunSpec signaling for the rapid shutdown. The Transmitter-PLC includes one or two cores and an optional power supply: 85- 64VAC for residential,  180-550VAC for commercial.The Transmitter-PLC Outdoor Kit includes a Transmitter-PLC with one or two cores, an outdoor enclosure, 85-264VAC or 180V-550VAC power supply. It could be used in a residential or commercial project.

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig2

  1. RSD-D
  2. Transmitter-PLC
  3. Inverter

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig3

  1. RSD-D
  2. Transmitter-PLC-Outdoor Kit
  3. Inverter

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig4

  1. RSD-D
  2. Inverter
    Inverter in the diagram includes an integrated SunSpec-Certified Rapid Shutdown Transmitter.

RSD-D INSTALLATION

INSTALLATION NOTES
Installation MUST comply with local regulations and technical rules :

  1.  Perform all electrical installations in accordance with local codes.

  2. Be aware that only qualified professionals should install and/or replace the RSD-D.

  3.  Before installing or using an RSD-D, please read all instructions and warnings in the technical documents and on the inverter system itself as well as on the PV array.

  4. Be aware that the installation of this equipment includes the risk of electric shock.

  5.  Do not touch any live parts in the system, including the PV array, when the system has been connected to the electrical grid.

  6. Ensure the PV module and inverter have been disconnected before installing an RSD-D.

  7. Be sure to verify the voltage and current specifications of your PV module match those of the RSD-D.

  8. The maximum open circuit voltage of the PV module must not exceed the specified maximum input voltage of the APsmart RSD-D.

Additional installation components from APsmart
· DC extension cable (sold separately)
Required parts and tools to complete the installation
In addition to your PV array and its associated hardware, you will need a torque wrench and a Phillips screwdriver.

Step 1: Install the RSD-D.

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig5

Buckle RSD-D onto the PV module frame.
A. Back buckle

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig6

B. Front buckle

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig7

NOTE: Do not place the RSD-D (including DC connectors) where exposed to the sun, rain or snow, even gap between modules. Allow a minimum of 3/4’’(1.5cm.) between the roof and the bottom of the RSD-D to allow proper air flow.

Step 2. Connect the INPUT1 connectors of the RSD-D to the first PV module junction box and connect the INPUT2 connectors to second PV module, the device DC output
voltage is within the range of 1.2 ~ 2v.
NOTE: Do not short-circuit the RSD-D output connectors, otherwise it will be damaged.
RSD-D cable length
APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig8 Note: The output cable length of triad junction box PV module should be no less than 1.2m.

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig9

Note: The output cable length of the integrated junction box PV module should be no less than 0.9m.

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig10

NOTE: When installing RSD-D cable, the bending radius of the cable near the casing must be greater than 50 mm.

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig11

Step 3: Connect the output ports of two adjacent RSD-Ds in series and then connect to the inverter with a self-made DC extension cable.
NOTE: Do not connect homerun to the inverter before finishing all strings connections and tests.
WARNING: When connecting the RSD-D to only one PV module, use the INPUT1 port ONLY, then short both terminals of INPUT2 directly or by extension cable, otherwise the RSD-D may be damaged. The DC output voltage remains the same.
NOTE: Please use the same type of DC connector as the RSD in the system. The RSD damage caused by using a different type of DC connector will not be covered by the warranty.

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig12

TRANSMITTER-PLC INSTALLATION

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig13

The transmitter-PLC power supply must be on the same AC branch circuit as the inverter to meet rapid shutdown requirements.
During operation, the Power LED should be lit and the Signal LED should be blinking. If the TransmitterPLC fails to work, the Signal LED will not be blinking. If the Power LED is also not lit, check the power supply first.
Note: Install the RSD-D before powering on the Transmitter-PLC.

  • Mount Transmitter-PLC and power supply on DIN rail
  • Connect DC leads from power supply to Transmitter-PLC
  • Connect single/dual core(Core 1 and Core 2) to Transmitter-PLC
    Place rapid shutdown system label no more than 1m (3ft) from Transmitter-PLC or AC disconnect if not at same location.

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig14

Note: Install the RSD-D before powering the Transmitter-PLC.
Note: The waterproof jacket and related accessories are not configured before delivery and customers need to buy by themselves.

  • Pass either positive or negative cables through cores (either both positive cables or both negative cables. Do not use one positive and one negative cable.)
  • Connect wires to AC side of power supply

Max number of Strings Per Core :

DC cable Diameter(without connector) Φ5.9mm Φ6.35mm Φ7mm Φ8.6mm
29mm Core ≤15 ≤15 ≤14 ≤10
11mm Core ≤6 ≤5 ≤4 ≤2

Max string length: 30 modules
Max current per core: 150A
Max cable length from the inverter(+) to
inverter(-) : 1000ft (300m)

APsmart RSD D Rapid Shutdown Device &amp Transmitter -
fig15

Note: The Outdoor Kit was not punched before delivery and the customer need to make it themselves according to the actual situation. The figure is only for reference.

TECHNICAL DATA—RSD-D

Model

Range of Input Operating Voltage 8-65V Per Channel
Maximum Cont. Input Current (Imax) 15A Per Channel
Maximum Short Circuit Current(Isc) 25A

Output Data (DC)

Range of Output Operating  Voltage 16-130V
Maximum Output Current 15A 20A
Maximum System Voltage 1000V/1500V
Maximum Series Fuse Rating 30A

Mechanical Data

Operating Ambient Temperature Range -40 oF to +167 oF (-40 °C to + 75 °C)
Dimensions (without cable & connectors) 5.5″ x 2″ x 0.8″(140 mm x 50.6 mm x

20 mm)
Cable Length| Input 500mm/Output 2400mm
Cable Cross-Section Size| TUV:4mm²/UL:12AWG
Connector| Stäubli MC4 PV-KBT4&KST4 or Customize
Enclosure Rating| NEMA Type 6P/IP68
Over Temperature Protection| Yes

Features & Compliance

Communication PLC
Safety Compliance NEC 2017 & 2020 (690.12); UL1741; CSA C22.2 No. 33017;

IEC/EN62109-1
EMC Compliance| FCC Part15; ICES-003

TECHNICAL DATA—TRANSMITTER-PLC

Model
Main electrical data
Transmitter-PLC

Input Voltage 12VDC
Input Current 0.8A
Communication PLC

Power Supply

Residential(optional)| 85-264VAC Input, 12VDC Output, 90 mm x 17.5 mm x 58.4 mm
---|---
Commercial(optional)| 180-550VAC Input, 12VDC Output, 125.2 mm x 32 mm x 102 mm
Core data| 29mm Core| | 11mm Core
---|---|---|---
Max. Current| 150A Per core| | 75A Per core
Max. System Voltage| | 1500VDC|
Internal Opening for Wires/Outside Dimensions| ~29mm/65mm| | ~11mm/35mm
Max. Supported PV Modules per String| | 30 modules|

Number Of Strings Per Core

DC Cable Diameter(without connector) Φ5.9mm Φ6.35mm Φ7mm Φ8.6mm
29mm Core ≤15 ≤15 ≤14 ≤10
11mm Core ≤6 ≤5 ≤4 ≤2

Environmental

Temperature -40 ℃~+100℃

Structure data

Dimensions (W x H x D) 90 mm x 35 mm x 40 mm
Enclosure Environmental Rating IP30

Features & Compliance

Safety Compliance NEC 2017 & 2020 (690.12); UL1741; CSA C22.2 No. 330-17
EMC Compliance FCC Part15; ICES-003

TECHNICAL DATA —TRANSMITTER-PLC-OUTDOOR KIT

Model
Main electrical data
Transmitter-PLC-Outdoor Kit

Input Voltage 12VDC
Input Current 0.8A
Communication PLC

Power Supply

Residential(optional)| 85-264VAC Input, 12VDC Output, 90 mm x 17.5 mm x 58.4 mm
---|---
Commercial(optional)| 180-550VAC Input, 12VDC Output, 125.2 mm x 32 mm x 102 mm

Core data

Max.Current 150A Per core
Max. System Voltage 1500VDC
Internal Opening for Wires/Outside Dimensions ~29mm/65mm
Max. Supported PV Modules per String 30 modules

Number Of Strings Per Core

DC Cable Diameter(without connector) Φ5.9mm Φ6.35mm Φ7mm Φ8.6mm
29mm Core ≤15 ≤15 ≤14 ≤10

Environmental

Temperature -40℃~+60℃

Structure data

Dimensions (W x H x D) 198.5 mm x 298 mm x 179 mm
Enclosure Environmental Rating IP30

Features & Compliance

Safety Compliance NEC 2017 & 2020 (690.12); UL1741; CSA C22.2 No. 330-17
EMC Compliance FCC Part15; ICES-003

600 Ericksen Ave NE, Suite 200 Seattle, WA 98110 | +1-737-218-8486 |
+1-866-374-8538 | support@APsmartGlobal.com | APsmartGlobal.com

Read User Manual Online (PDF format)