APsmart RSD-S-PLC Rapid Shutdown System User Manual
- June 6, 2024
- APsmart
Table of Contents
- APsmart RSD-S-PLC Rapid Shutdown System User Manual
- IMPORTANT SAFETY INSTRUCTIONS
- Safety Instructions
- Symbols replace words on the equipment, on a display, or in manuals
- Qualified personnel:
- RSD PRODUCTS RSD-S-PLC
- TRANSMITTER PRODUCTS
- Transmitter-PLC:
- Transmitter-PLC-Outdoor Kit:
- SYSTEM WIRING DIAGRAM
- RSD-S-PLC INSTALLATION
- INSTALLATION NOTES
- Additional installation components from APsmart
- Step 1: Install the RSD-S-PLC
- self-made DC extension cable
- TRANSMITTER-PLC INSTALLATION
- Note Install RSD-S-PLC before powering on Transmitter.
- Note: Install RSD-S-PLC before powering on Transmitter.
- Max number Of Strings Per Core :
- Drilling Guide for .75″ Conduit
- Drilling Guide for 1″ Conduit
- TECHNICAL DATA-RSD-S-PLC
- TECHNICAL DATA—TRANSMITTER-PLC
- TECHNICAL DATA—TRANSMITTER-PLC OUTDOOR KIT
- ORDERING INFORMATION
- RSD-S-PLC
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
APsmart RSD-S-PLC Rapid Shutdown System User Manual
IMPORTANT SAFETY INSTRUCTIONS
This manual contains important instructions to be followed during installation
and maintenance of the
APsmart RSD and Transmitter. To reduce the risk of electrical shock and ensure
the safe installation and operation of the APsmart RSD and Transmitter, the
following symbols appear throughout this document to indicate dangerous
conditions and important safety instructions.
Safety Instructions
- Do NOT disconnect the PV module from the RSD-S-PLC without first disconnecting the AC power.
- Only qualified professionals should install and/or replace the APsmart RSD-S-PLC.
- Perform all electrical installations in accordance with local codes.
- Before installing or using the RSD-S-PLC, please read all instructions and cautionary markings in the technical documents.
- Be aware that the body of the running RSD-S-PLC is the heat sink and can reach high temperatures.
- To reduce risk of burns, do not touch the body of the RSD-S-PLC.
- Do NOT attempt to repair the RSD-S-PLC. If it fails, contact APmart Customer Support to obtain an
RMA number and start the replacement process. Damaging or opening the RSD-S-PLC will void the warranty.
The Transmitter-PLC control power supply MUST be on the same AC branch circuit as the inverter to meet rapid shutdown requirements.
Symbols replace words on the equipment, on a display, or in manuals
Qualified personnel:
- Person adequately advised or supervised by an electrically skilled person to enable him or her to perceive risks and to avoid hazards which electricity can create. For the purpose of the safety information of this manual, a “qualified person” is someone who is familiar with requirements for safety, refrigeration system and EMC and is authorized to energize, ground, and tag equipment, systems, and ircuits in accordance with established safety procedures. The inverter and endues system may only be commissioned and operated by qualified personnel.
RSD PRODUCTS RSD-S-PLC
- Meets NEC 2017 (690.12) requirements
- Executes rapid shutdown of system
- Meets SunSpec requirements 2 when Transmitter-PLC signal is absent
RSD-S-PLC meets SunSpec requirements,maintaining normal function by
continually receiving a heart-beat signal from the APsmart Transmitter. The
RSD executes rapid system shutdown when
Transmitter signal is absent. Users can manually execute rapid shutdown using
Transmitter breaker switch.
TRANSMITTER PRODUCTS
Transmitter-PLC:
- Meets NEC 2017 (690.12) requirements
- Switch oTransmitter, rapid shutdown the output of PV modules
- Meets SunSpec requirements
- Equipped with single/dual core
- Optional 85-264VAC power supply
- Optional 180-550VAC power supply
Transmitter-PLC-Outdoor Kit:
- Meets NEC 2017 (690.12) requirements
- Switch oTransmitter, rapid shutdown the output of PV modules
- Meets SunSpec requirements
- Equipped with single/dual core
- Optional 85-264VAC power supply
- Optional 180-550VAC power supply
SYSTEM WIRING DIAGRAM
The APsmart Rapid Shutdown System Transmitter-PLC is part of a rapid shutdown
solution when paired with APsmart RSD-S-PLC, a PV module rapid shutdown unit.
While powered on, the
Transmitter-PLC sends a signal to the RSD-S-PLC units to keep their PV modules
connected and supplying energy.
RSD-S-PLC units automatically enter rapid shutdown mode when the Transmitter-
PLC is switched o and resume energy production when power is restored to the
Transmitter-PLC. This solution complies with NEC 690.12 specifications for
2017 and supports the SunSpec signaling for rapid shutdown.
The Transmitter-PLC includes one or two cores and an optional power supply:
85-264VAC for residential, 180-550VAC for commercial.
Transmitter-PLC Outdoor Kit includes a Transmitter-PLC with one or two Cores,
outdoor enclosure, 85-264VAC or 180V-550VAC power supply. It could be used in
residential or commercial project.
① RSD-S-PLC
② Transmitter-PLC
③ Inverter
① RSD-S-PLC
② Transmitter-PLC-Outdoor Kit
③ Inverter
RSD-S-PLC INSTALLATION
INSTALLATION NOTES
Installation MUST comply with local regulations and technical rules:
-
Perform all electrical installations in accordance with local codes.
-
Be aware that only qualified professionals should install and/or replace the RSD-S-PLC.
-
Before installing or using an RSD-S-PLC, please read all instructions and warnings in the technical documents and on the inverter system itself as well as on the PV array.
-
Be aware that installation of this equipment includes the risk of electric shock.
-
Do not touch any live parts in the system, including the PV array, when the system has been connected to the electrical grid.
-
Ensure the solar module and inverter has been disconnected before installing an RSD-S-PLC.
-
Be sure to verify the voltage and current specifications of your PV module match with those of the RSD-S-PLC.
-
You must match the DC operating voltage range of the PV module with the allowable inpust voltage range of the RSD-S-PLC.
-
The maximum open circuit voltage of the PV module must not exceed the specified maximum input voltage of the APsmart RSD-S-PLC.
Note: RSD-S-PLC units could be installed only on some strings, NO need to be all in an inverter. With our patented proprietary design, there is no risk.
Additional installation components from APsmart
- DC extension cable (sold separately)
Required parts and tools to complete the installation
In addition to your PV array and its associated hardware, you will need the following items:
- Rapid shutdown device installation kit (screw, nut)
- A torque wrench and a Phillips screwdriver
Step 1: Install the RSD-S-PLC
Note: Both installations can be installed anywhere on the PV module frame.
Step 2: According to the component arrangement, connect the output port of the RSD-S-PLC and connect the input port to the junction box.
Step 3: Connect the RSD-S-PLC serially connected output to the inverter with a self-made DC extension cable.
self-made DC extension cable
TRANSMITTER-PLC INSTALLATION
Note: If there is only one core need to connect, please connect Core 1 first.
T During operation, the Power LED should be lit and the Signal LED should be
blinking.
When Transmitter fails to work, the Signal LED will not be blinking. If the
Power LED is also not lit, check the power supply first.
ransmitter power supply must be on same AC branch circuit as inverter to meet
rapid shutdown requirements.
Note Install RSD-S-PLC before powering on Transmitter.
- Mount Transmitter-PLC and power supply on DIN rail
- Connect DC leads from power supply to Transmitter-PLC
- Connect single/dual core(Core 1 and Core 2) to Transmitter-PLC
Place rapid shutdown system label no more than 1m (3ft) from Transmitter or AC disconnect if not at same location.]
Note: Install RSD-S-PLC before powering on Transmitter.
• Pass either positive or negative homerun through Cores • Connect wires to AC side of Plower supply
Max number Of Strings Per Core :
DC cable Diameter Number Of Strings Per Core (without connector) ≤15 ≤15 ≤14 ≤10 5.9mm 6.35mm 7mm 8.6mm
Drilling Guide for .75″ Conduit
Drilling Guide for 1″ Conduit
TECHNICAL DATA-RSD-S-PLC
TECHNICAL DATA—TRANSMITTER-PLC
TECHNICAL DATA—TRANSMITTER-PLC OUTDOOR KIT
ORDERING INFORMATION
Transmitter
406000 | 29mm Dual Core Transmitter-PLC (no power supply) |
---|---|
406001 | 29mm Single Core Transmitter-PLC (no power supply) |
406002 | 11mm Dual Core Transmitter-PLC (no power supply) |
406003 | 11mm Single Core Transmitter-PLC (no power supply) |
408004 | Single Core Transmitter-PLC Outdoor Kit, 180-550VAC Power Supply |
408005 | Dual Core Transmitter-PLC Outdoor Kit, 180-550VAC Power Supply |
408006 | Single Core Transmitter-PLC Outdoor Kit, 85-264VAC Power Supply |
408007 | Dual Core Transmitter-PLC Outdoor Kit, 85-264VAC Power Supply |
RSD-S-PLC
405002 | 1500V UL/1000V TUV, 1.2m cable, MC4 |
---|---|
405001 | 1000V UL/TUV, 1.2m cable, MC4 compatible |
405003 | 1500V UL/TUV, 1.2m cable, MC4-Evo2 |