CROWCON FGard IR3 Flame Detector Installation Guide

September 25, 2024
CROWCON

CROWCON FGard IR3 Flame Detector

Introduction

This safety and technical manual applies to the Crowcon IR3 Flame Detector (FGard IR3) hardware version 1.0 and above. The Crowcon FGard IR3 is a (triple) IR flame detector. It uses three IR sensors, digital signal processing hardware, and firmware algorithms to interpret the radiant characteristics of flame. FM Approvals ensure that our flame detection firmware and hardware are fit for purpose through rigorous research and testing of a range of fire types and various potential false alarm stimuli. This testing proves that the FGard IR3 has an unsurpassed false alarm immunity. The FGard IR3 has been designed for use in standalone operations.

Detector Features

  • The FGard IR3 has a 90° cone of vision with a range of 60 meters to a 0.1m2 pan fire of n-heptane.
  • Three detection sensitivity settings allow the user to select the sensitivity that is most suitable for their application.
  • Superior false alarm immunity to common sources of unwanted alarms such as hot process and hot work.
  • Advanced optical verification test assuring readiness to perform when needed.
  • Outputs include both relay contacts and 0-20mA.
  • Separate termination chamber for ease of installation.
  • Certified Flame Simulator FGard SIM verifies operation from distances of 3 to 8 metres.
  • FGard IR3 can operate via a standard 3 or 4-wire termination.
  • MiMicroprocessor-controlled heated optics increase resistance to moisture and ice.

2 Safety Instructions

For the correct and effective use of this equipment, to maintain safety and avoid hazards you must read and understand these instructions fully and act accordingly BEFORE installing, operating, or maintaining the equipment. PAY ATTENTION TO ALL SAFETY WARNINGS AND CAUTIONS

Specific conditions of use

  • This equipment is certified and intended for use in potentially hazardous areas. Install and use the equipment according to the latest regulations. The end user shall close any unused entries using suitably certified blanking elements to maintain the housing’s type of protection.
  • For European (ATEX) installations IEC/EN60079-14 ‘Electrical Installations in Hazardous Areas’ and
  • ICE/EN60079-17 ‘Inspection and Maintenance in Hazardous Areas’ should be strictly observed. The IR3 type flame detector; Crowcon FGard IR3, is to be installed in places where there is a low risk of mechanical damage.
  • For installations in North America, the National Electrical Code (NEC) should be strictly observed. In other countries, the appropriate local or national regulations should be observed.
  • The equipment must be properly earthed to protect against electrical shock and minimize electrical interference.
  • Do not drill holes in any housing or enclosure as this will invalidate the explosion protection. Ensure that the enclosure lid is fully tightened and locked into position before energizing the equipment.
  • Do not open the enclosure in the presence of an explosive atmosphere.
  • All permits and proper site procedures and practices must be followed, and the equipment must be isolated from the power supply before opening the enclosure in the field.
  • Operators must be properly trained and aware of what actions to take in the event of a fire being detected.
  • The cable to be used for installation is to be selected with a temperature rating of greater than 25 degrees Celsius above the maximum ambient temperature. The metric cable entries are fitted with an internal stop. This will result in threads of the cable gland being visible. Do not over-tighten.

Cautions

  • Use only approved parts and accessories with this equipment.
  • Do not attempt to replace the window as the sapphire and the front cover are individually matched pairs to meet the stringent requirement of the hazardous area certification.
  • The threaded portions of the detector are flame paths. These threads and the flame paths are not to be repaired.
  • To maintain safety standards, commissioning, and regular maintenance should be performed by a qualified person.

Important Safety Notices

  • Pay attention to the guidelines given throughout this document.
  • If in any doubt about the instructions listed within this manual, then please contact Crowcon. Crowcon takes no responsibility for the installation and/or use of its equipment if it is not by the appropriate issue and/or amendment of the manual. Crowcon reserves the right to change or revise the information contained herein without notice and without obligation to notify any person or organization of such action.
  • Only those parameters and configurations highlighted with the FM diamond ( ) have been tested and approved by Factory Mutual.

Warning
Do not open the detector assembly in a hazardous area. The detector contains limited serviceable components and should only be opened by trained personnel.

Caution
The wiring procedures in this manual are intended to ensure the functionality of the device under normal conditions. Due to the many variations in wiring codes and regulations, total compliance with these ordinances cannot be guaranteed. Be certain that all wiring complies with all local ordinances. If in doubt, consult the authority having jurisdiction before wiring the system. Installation must be done by trained personnel.

Caution
To prevent unwanted actuation or alarm, extinguishing devices must be inhibited/isolated before performance testing or maintenance.

Detector Orientation
Detectors should be mounted with the earth stud directly below the lens.

Detector Positioning

  • Detectors should be positioned to provide the best-unobstructed view of the area to be protected.
  • The following factors should also be taken into consideration:
  • Identify all high-risk fire ignition sources. Ensure that enough detectors are used to adequately cover the hazardous area.
  • Locate and position the detector so that the fire hazard(s) are within both the field of view and detection range of the device.
  • For best performance, the detector should be mounted on a rigid surface in a low-vibration area.
  • Extremely dense fog or blizzard conditions could eventually block the vision of the detector.
  • For indoor applications, if dense smoke is expected to accumulate at the onset of a fire, mount the detector on a side wall (approximately 1 to 2 meters) below the ceiling.
  • The FGard IR3 has three sensitivity settings, which may be changed via a Crowcon application.
  • The flame detector carries out continuous internal hardware diagnostic testing to ensure the correct operation is relayed to the control system.
  • The FGard IR3 is not designed to annunciate diagnostic failure of signal returns via external wiring. Control systems and fire panels generally have fault monitoring for such an eventuality.

EN 54-part 10 Limitation of use
The FGard IR3 is not approved for use in oxygen-enriched atmospheres. As the FGard IR3 responds to flame, it cannot be used in locations where flare stacks are within its field of view or a reflected view is present without triggering alarms. As the FGard IR3 responds to CO2 emissions of a flame the FGard IR3 cannot detect non-hydrocarbon fires, such as those using pure hydrogen, silane, and sulfur as fuel. The sensitivity of the FGard IR3 is reduced by obscurants such as smoke, fog, and other airborne particulates. The FGard IR3 may be blinded by extremely dense obscurants. Arc welding should not take place within 10m of the FGard IR3 when using the highest sensitivity setting.

Installation

The FGard IR3 design has been developed to allow simple installation. The detector comprises two key components, the detector enclosure, and the detector internal assembly. The detector assembly located in the front of the enclosure should not be removed except by trained personnel. Unauthorized removal or disassembly of the detector assembly will invalidate the warranty. Only the rear-end cap can be removed for terminal access.

Detector Enclosure
The detector electronics are housed in an enclosure certified for use in hazardous areas. For the exact certification and conditions of use see the certification label on the device, or the example drawing below:

The detector comprises the front window cover including the window, the rear enclosure cover, the enclosure body, the certification rating label (see above), and the mounting bracket. The flame detector is supplied preassembled and includes the mounting bracket. However, it is not supplied with mounting support and fixings, cabling, or glands.

Mounting & Orientation
The mounting bracket allows the detector’s vertical orientation to be adjusted from 0 to 45° and allows a horizontal rotation of +/-45° when mounted from above.

Figure 1: Detector Mounting Bracket

Firm, vibration-free mountings are essential for trouble-free operation of optical systems and the detector should be fixed to a rigid mounting. When mounting on a wall in this orientation allow for the cable gland and cable as this may restrict the downward rotation of the detector.

Wiring Procedure
The wiring terminals are in the rear section of the detector enclosure and are accessible by the removal of the end cap. The front section of the enclosure should only be accessed by trained personnel. The terminal schematic detailed below shows the view looking inside the detector following the removal of the end cap.
Figure 4: Terminal Schematic

The detector has two types of alarm output available simultaneously.

  • 0-20mA (source non-isolated)
  • Relay (Alarm & Fault)

Listed below are wiring options dependent on the functional requirements of the detector.

0-20mA Output
The following wiring connection diagram shows the correct wiring of the detector when a 0-20mA output is required.

Figure 5: 3 Wire Termination

Factory Fixed Values

Current Output Event
0mA Power/Detector Fault
1mA Low Supply Voltage Fault
1.5mA Optical Fault
4mA Healthy
18mA Alarm
21mA Over-range

Notes

  • Note 1 – The tolerance on the above outputs is +/- 0.3mA current with a maximum loop resistance of 500 ohms.
  • Note 2 – Additional 0-20mA values are configurable and must be specified when ordering if required. The optical fault signal may be configured at 2mA as opposed to 1.5mA and the alarm signal may be increased to 20mA.
  • Note 3 – The FGard IR3 can be factory-configured with an Aux alarm delay (20mA) of between 0 and 10 seconds in 1-second steps over and above the normal response times of the 18mA alarm signal. If the Aux alarm signal is delayed, the 18mA alarm signal will precede the 20mA signal giving the normal response times as tested by Factory Mutual to FM3260. If the 20mA alarm signal is delayed, it is considered an Aux alarm level.
  • Note 4 – The 0-20mA signal has HART ® 7 protocol superimposed on top of it to give access to more diagnostic information. See HART ® 7 Technical Note.

Relay Output
The following wiring connection diagrams show the wiring of the detector when a relay output is required. Reversal of polarity across terminals 1 & 2 enables Crowcon RS485 communication on terminals 3 & 4. This communication protocol when used with Crowcon applications allows configuration changes to the detector.

Figure 6: Relay Configuration Termination

NOTE: EOL and alarm resistor values are defined by the client and the control system/fire panel which the detectors are being integrated into.

Internal Inter-connections
The following diagram shows the internal interconnections of the alarm and fault relay contacts and jumpers. Each field connection is listed on this diagram for clarity.

Installation Checklist
Experience has shown that poor installation and commissioning practices may result in an unreliable fire detection system that fails to meet the site performance targets. Before installing the detector, it is important to consider where it is to be located and how it is to be mounted. To maintain compliance with the EMC regulations it is essential the electrical installation be engineered correctly.

Mechanical

Notes| When locating the detector consideration should be given to maintenance access to the detector. The detector mounting should be secure and vibration- free.

It is advisable to check the detection locations, before fabrication of the mounting supports, as changes are frequently made during construction at the site which can affect detector coverage.

The installation should allow space for subsequent detector removal, maintenance, or repair, to be easily achieved.

---|---
1| The detector should be fixed to a stable supporting structure using the mounting bracket provided. The supporting structure must allow for horizontal adjustment of the detector orientation. The support structure should be in place before detector installation. Information on mounting is available from Crowcon.
2| The threaded flame path of the enclosure cover and body must be protected from damage

during installation. Any such damage can destroy the validity of the enclosure.

3| The detector electronics shall be protected from mechanical damage and external sources of EMI such as X-rays, RFI, and electrostatic discharge. The detector should not face directly towards the sun.
4| Fit the mounting bracket to the support structure using 8mm bolts (not provided). The detector

(bracket) should be oriented to provide the desired coverage.

5| The detector enclosure body should be fitted to the mounting bracket. The boltsare locatede in the bracket. Twist the enclosure to locate the bolts; these are then tightened using a 6mm Allen key.
6| Ensure the detector is orientated such that the earthing stud is directly beneath the lens.
7| Glanding should be carried out by trained personnel. The gland should be fitted in line with installation standards for potentially explosive atmospheres that is 5 full threads minimum with the IP seal washer fitted at the bottom of the thread. This sealing arrangement will result in several threads of the cable gland being visible. The gland should be torqued between 15 to 20 N m (11 to 15 lb ft).

Note – The IP seal washer only applies to metric threads.

Electrical

Notes| It is advisable to check the detection locations, before the fabrication of the mounting supports, as changes are frequently made during construction at the site. Detector cabling must be segregated from cables carrying high-speed data or high energy and/or high-frequency signals and other forms of electrical interference. The detector requires a clear unobstructed view of the local hazard. To avoid local obstructions, such as pipework and cable trays, a 2m helix should be allowed in the detector cabling. The detector should only be fitted just before commissioning

the detector. Experience shows that the detector can be damaged due to cable testing operations (Insulation Tests, etc.).

---|---
1| Isolate all associated power supplies. Ensure that they remain OFF until required for commissioning.
2| The threaded flame path of the enclosure cover and body must be protected from damage

during installation. Any such damage can destroy the validity of the enclosure.

---|---
3| The electronics subassembly shall be protected from mechanical damage and external sources

of EMI such as X-rays, RFI, and electrostatic discharge.

4| The enclosure’s external earth stud should be connected to a local earth point.
5| Remove the transit plug(s) from the enclosure body gland entries.
6| Fit-approved cable glands.

System Design Guidelines

The following guidelines are intended to assist with the electrical design and engineering of systems where it is intended that flame detectors will be used.

Power Supply
The detector requires an absolute minimum supply voltage of 18Vdc, as measured at the detector terminals. The system power supply voltage and power distribution should be arranged such that on the longest cable run, the detector(s) has a supply voltage of greater than 18Vdc.

Cable Selection
The cable to be used for installation is to be selected with a temperature rating of greater than 25 degrees Celsius

above the maximum ambient temperature. The metric cable entries are fitted with an internal stop. This internal stop has an IP washer mounted directly above it. Ensure this is fitted to maintain the ingress protection. This will result in threads of the cable gland being visible. Do not over-tighten. The installation and local regulations and standards determine the overall cable specification. This section specifies suitable cable characteristics to ensure the correct operation of the flame detector.

DC Power

  • NOTE: Table 2 shows an absolute maximum for cable length; try not to approach this value. DO NOT ground any cable shields at the detector housing.

Table 2: Maximum Cable Lengths (24Vdc supply)

Installation based on 24V nominal supply| Number of Flame Detectors| Maximum Power (W)| Maximum Cable Length (m) with 1.5mm2 Conductors

(12Ω/km)

| Maximum Cable Length (m)with 2.5mm2 Conductors

(7.6Ω/km)

---|---|---|---|---
Heater on| 1| 12W @ 24Vdc| 500| 780
Heater off| 1| 3W @ 24Vdc| 2000| 3000

Table 3: AWG Conversions

Cross-Sectional Area (mm2)| American Wire Gauge (AWG)| Typical Conductor Resistance per km (3280 ft.)

DC Ω/km @ 20°C (Approx.)

---|---|---
0.5| 22| 36
1.0| 18| 19
1.5| 16| 12
2.5| 14| 7.6

Application Guidelines

In considering the application of the detector it is important to know of any conditions that may prevent the detector from responding. The detector provides a reliable response to hydrocarbon flames within its field of view and insensitivity to common false alarm sources. Solid obstructions or a direct view of intense light sources may result in a reduction in the coverage and/or a reduction in the detector sensitivity. Scaffolding or tarpaulins in the detector’s field of view may reduce coverage. Contamination of the detector window may result in a reduction in sensitivity. The detector has a 90° conical field of view. The location and orientation of the detectorint the protected area determine the actual footprint. Achieving the desired coverage depends on congestion within the protected space, the location of the detector(s), and the distance of the detector from the hazard. It may be necessary to install more than one detector within an area to achieve adequate coverage. The detector sensitivity, expressed as fire size at a distance, is determined by the radiant heat output of the fire. This is a function of the fuel source, how it is released, and the distance from the detector to the fire. In common with other forms of flame detection, the detector’s sensitivity is reduced and potentially blinded by dense obscurants such as smoke, fog, and other airborne particulates. The detector is insensitive to arc welding; however, this should not be conducted within 10m of the detector.

Positioning Requirements
The following guidelines have been based on operational feedback, reflecting commonly experienced problems that can be traced to a failure to observe the following:

  • Ensure the mounting position is free from vibration or movement.
  • Prevent accidental knocking or forcing out of alignment.
  • Isolate as far as possible from local electrical interference sources.
  • Ensure sufficient detection to achieve adequate coverage for all likely hazards.
  • Minimise exposure to contamination of the detector face plate.
  • Ensure ease of maintenance access to the detector (i.e., direct ladder or scaffold access).
  • Do not allow the FGard IR3 to have a direct view of hot surfaces.
  • Ensure that the FGard IR3 has no direct view or reflected view of friendly fire.
  • The detector should be aimed downward by at least 10° to 20°.

All these issues are of crucial importance to a successful installation and they should be afforded great attention during the detailed design, construction, and commissioning phases of the work.

Detection Coverage
Detector locations can be chosen from computer models or site surveys. The detectors should be aligned to view the intended hazard considering any obstruction and congestion. Software analysis of the actual detector coverage may be required to ensure adequate coverage of the hazards. This analysis can also be used to optimize the number of detectors and the loop configuration. The cones of vision are detailed in Appendix C.

Exposure to Flare Radiation
Flame detectors are frequently used where hydrocarbon fire hazards are expected; these are quite often processing plants where a flare stack is in use nearby. The detector shall not have a direct view of the flare or a reflected view of the flare.

Optical Contamination
There are many sources of contamination such as oil, water (deluge water, rain, and sea spray), snow, ice, and internal misting. Excessive contamination of the detector faceplate may result in an increased maintenance requirement and potentially reduce the detector’s sensitivity. Where detectors are mounted at low levels, care should be taken to avoid contamination (such as water and oil) from equipment above the detector. Care should be taken in sighting the detector to minimize the likelihood of such contamination. The detector is designed such that an optical fault is generated when half of the detection range remains. This is indicated by the fault output and is evident by the yellow color of the LED on the face of the detector. The optical fault condition indicates that the detector requires cleaning or service. The optical fault indication is self-clearing.

Enclosed Areas
In enclosed areas, if dense smoke is expected to accumulate at the onset of the fire, the detector should be mounted 1 to 2 meters below the ceiling level.

Detector Sensitivity
The detector’s response to a fire is a function of the fuel source and how it is released, fire size and distance, orientation to the detector, and local ambient conditions. The typical figures are based on in-house tests except when marked with the FM logo, these tests were conducted and certified by Factory Mutual. As with all tests, the results must be interpreted according to the individual application considering all possible variables. The detector’s sensitivity to different fuel sources is dependent on the radiant heat output of the flame and the detector’s typical response is shown below (see Table 4). The detector will only detect hydrocarbon fires.

Detector Alarm Delay
The Detector can be factory configured with an Aux alarm delay (20mA) of between 0 and 10 seconds in 1-second steps over and above the normal response times of the 18mA alarm signal. If the Aux alarm signal is delayed the 18mA alarm signal will precede the 20mA signal giving the normal response times as tested by Factory Mutual to FM3260. The 20mA alarm signal if delayed is considered an Aux alarm level.

Table 4: Typical FGard IR3 Response Characteristics High sensitivity (60 metres). For all FM-approved results see Appendix D

Maintenance and Commissioning

Procedure
This maintenance schedule/ commissioning procedure is intended for guidance only. The actual level of maintenance required will depend on the severity of the operating environment and the likelihood of damage or the rate of contamination from oil, sea spray, deluge system, etc. It is advisable to regularly review maintenance reports and adapt the maintenance period to the operating environment.

Step Periodic Inspection and Maintenance Suggested Interval
1 – 6 General Inspection and maintenance of the detector and faceplate. 6

monthly
6 – 14| Specific inspection and maintenance of the detector enclosure.| 12 monthly
16| Detector function testing.| 6 monthly
1 – 5

15 – 17

| Commissioning Procedure.| Post Installation
Step| Activity| Key Points

1

|

Detectors that require maintenance/commissioning should be taken offline and inhibited. Detectors which require to be opened will need to be isolated electrically.

| Ensure that panel wiring, and terminations associated with all units under test are in good

order.

2| Ensure that the detector mounting arrangements are secure and

undamaged.

|
3| Ensure that the detector enclosure is intact and undamaged.|
4| Ensure that all associated cables and glands are correctly made up,

secure and undamaged.

|
 | Clean the enclosure faceplate (outside) with a mild detergent solution.|
 | And a soft cloth until the window is clear of all contamination. Wash| Assess requirement for
 | the window thoroughly with clean water and dry it with a clean lint-free| opening the enclosure,
5| cloth or tissue.

Note: This MUST be carried out before the initial powering of

| for maintenance or cleaning, follow steps 6
 | The device. The FGard IR3 will carry out an automatic| to 14.
 | Optical Test Calibration at this point.|

6

| Open the detector enclosure if required, by removing the enclosure cover. This exposes the enclosure flame path and detector lens.| Avoid damage to the flame path, faceplate,

and lens.

7

| Clean the enclosure cover and body flame paths with a dry clean cloth to remove any contamination. If the flame path or threads are

badly pitted the components should be replaced.

|

8

| Check the ‘O’ ring seal on the enclosure cover is not damaged or perished, replace as required. Note the ingress protection is

compromised if the seal is not correct.

|

9

| Clean the enclosure faceplate (inside) with a mild detergent solution and a soft cloth until the window is clear of all contamination. Wash the window thoroughly with clean water and dry it with a clean lint-free

cloth or tissue.

|
10| Non–setting waterproof grease should be evenly applied to the flame

path on both the enclosure cover and body.

|
11| Clean the detector lens. This should be done with a soft, dry, and clean cloth.| Avoid touching the optics or electronics.
12| Clean the detector enclosure faceplate. Use a degreasing agent on the outside to remove deposits.|
13| The enclosure cover must be screwed on to a minimum of 5 full turns or until fully tight and secured using the locking screw provided.|
14| Reinstate the detector back into service.|

15

| Ensure that inhibits are applied, then, using the flame test torch, function tests the detector. Note the detector LED indicator, within the detector housing, changes color to RED. Check the mA output is

indicating 18mA.

| Check the complete display system for correct function and

indication.

---|---|---
16| Isolate the power to the detector and ensure a fault is initiated within

the control system. Check the Ma output is indicating 0mA.

|

17

| De-isolate the detector and ensure the status LED indicates green.

Reinstate the detector back into service. Check the mA output is indicating 4mA.

|

Functional Testing

The detector can be function tested using the FGard SIM Flame Simulator, which has been specifically designed to provide a convenient means of field testing the detector. Refer to the FGard SIM Flame Simulator user manual for instructions on its use. In the unlikely event of the detector failing to respond to the FGard SIM Flame Simulator please contact Crowcon (sales@crowcon.com). Please ensure that the flame detector and flame simulator are being used correctly in the first instance by referring to their manuals.

Detector/simulator returns along with a written statement describing any fault should be sent to the address listed below:

  • Crowcon Detection Instruments Ltd.
  • 172 Brook Drive,
  • Milton Park,
  • Abingdon,
  • Oxfordshire,
  • OX14 4SD,
  • United Kingdom.

Fault Finding

Removal of the Electronics
Warning there are no user replaceable parts within the electronic module. Any attempt to repair or dismantle the electronic sub-assemblies will void the warranty. If any fault is suspected within the electronics module the module is to be returned to Crowcon for investigation and repair if required. Any faults should be reported to Crowcon as per the instruction in section 6.2. Removal of the electronics should only be performed by competent personnel. The following is the procedure for the removal of the electronic module: –

  1. Loosen the Allen screw that secures the lens cap to the housing.
  2. Unscrew the lens cap assembly and remove.
  3. Gently unscrew the three screws indicated until they freely turn. Please note these screws are not removable.
  4. Grasp the two screws positioned at the bottom of the detector and pull the electronics module out of its housing.

Replacement of the Electronics
The following is the procedure for the installation of the electronic module: –

  1. Insert the electronic module with the centre sensor positioned at the top of the housing.

  2. Rotate the module clockwise and anti-clockwise until the locating pins click into position.

  3. Push the electronics assembly into the housing until the face plate is flush with the front of the housing.
    Note: This should take minimum force if the locating pins are in position.

  4. Gently screw the three screws until they bottom. Note: Do not over-tighten.

  5. Grease and replace the lens cap.

  6. Tighten the lens cap Allen locking screw.

Diagnostics
It is impossible to provide fault diagnostics for every possible detector fault. In all cases it is advised that the following best practice is followed:

  1. Only make one change at a time (changing more than one thing makes diagnosis very difficult).
  2. Check the most obvious possible cause first.
  3. Work systematically through the problem.
  4. Keep good notes on the original problem, each step taken, and the results observed.

LED Indication
The detector LED indicator is used to reveal the detector’s current state, as shown below:

Power Fault
If the detector LED indicator is OFF or flashing then there may be a power supply fault, as shown below:

Figure 10: Power Supply Diagnostic Chart

When investigating power supply faults, it is important to check that all voltages are within the detector’s operating range (18V to 32V) under full load conditions as the voltages measured under no load conditions can be misleading.

Technical Specification

Detector Information

Parameter Value
Model Crowcon IR3 flame detector FGard IR3
Type Triple IR Flame Detector – IR3
Spectral Range Three wavelengths in the range of 3 µm to 8 µm
Application Flame/fire detection of hydrocarbon fires only

Electrical Specification

Parameter Units Min Nominal Max Comment
Supply Voltage Vdc 18 24 32 Inc. ripple
Supply Ripple Vpk-pk 1.0 1.0 1.0
Detector Power Consumption no heaters W 3 3 3
Detector Power Consumption with heaters W 12 12 12
Detector shutdown voltage (low supply) Vdc <18    

Mechanical Specification

Parameter Units Value Comment
Enclosure    
Overall Dimensions mm 100 Diameter x 200 Length
Shipping Weight Kg 2.5 6
Material   HE30 Aluminium 316SS
Coating Color Red Epoxy Coated Finish
Cable Entries mm/inches M25, ¾ NPT Other variants on

request

Terminal Wire Size| mm2| 2.5|
Ingress Protection|  | IP66 (NEMA 4X)|
Mounting Bracket|  | See Figure 1 Mounting Bracket Page 9|
Support Fixings| mm| 2 x M8|
Vertical Adjustment| Degrees| 0 to 45|
Horizontal Adjustment| Degrees| 0| Provided by support
Axial (horizontal) Rotation| Degrees| +/- 45|

Environmental Specification

Parameter Units Min Min Comment
Operating Ambient Temperature oC -60 +85 T4
Storage Ambient Temperature oC -60 +85
Relative Humidity %RH 0 100 Non-condensing

Certification and Approvals

Parameter Authority/ Standard Approval Certificate*
Hazardous Area Certification ATEX Ex II 2 G Ex db IIC T4 Gb IP66

FM21ATEX0013X
Area Certification Hazardous| NEC 505| Class1 Zone 1 AEx db IIC T4|
Hazardous Area Certification| NEC 500| Class 1 Div 1, Groups B, C, D T4|
Hazardous Area Certification| IECEx| Ex II 2 G Ex db II C T4Gb IP66| IECEx FMG 21.0010X
American Fire Service Listing| FM| Class 3260, 3615, 3600|
European Fire Services Listing| FM| EN 54 Part 10 2002| 2809-CPR-E0021
CE Marked (Emissions)| Element| EN61000-6-3:2007A1:2011|
CE Marked (Immunity)| FM| EN50130-4 2011 A1:2014|
IEC 61508| exida| Certified SIL 2 Capable| CRO 21-01-151 C001
Hazardous Area Certification| PESO| Ex db IIC T4 Gb Ta|
Hazardous Area Certification| INMETRO| Ex db IIC T4|

Note – Certificate numbers are subject to change.

Operating Specification

Parameter Units Min Max Comment
Detector Range (depth of field) m 2.0 60
Horizontal Field of View Degrees 90 90
Vertical Field of View Degrees 90 90
Detector Response Time Seconds 4.0 30
Power on reset delay Seconds 5 5
Parameter Value
Detector sensitivity Low, Medium (Factory default) and High.
Alarm Setting Non-latching with automatic reset after 15 seconds (default) OR

latched until the power is removed from the detector.

Advanced Optical Verification| Yes – No mirror continuous automatic optical verification
Heated Optics| Yes – microprocessor-controlled
LED Status| Tri-state LED – Green HEALTHY; Amber FAULT; Red ALARM
Output Options| 0(4)-20mA, HART® 7, Relay contacts – alarm and fault
Relay| 2 Relay Contacts – Alarm and Fault. DPDT, 2A @ 30Vdc
Communication/ Configuration| RS485 and HART® 7

FGard IR3 Detector Ordering Information

Parameter Part Number
Crowcon IR3 flame detector – Stainless steel M25 FD-IR3-SS-M25
Crowcon IR3 flame detector – Stainless steel 3/4″ NPT FD-IR3-SS-NPT
Crowcon IR3 flame detector – Aluminium M25 FD-IR3-A-M25
Crowcon IR3 flame detector – Aluminium 3/4″ NPT FD-IR3-A-NPT

Note – additional cable entry variants are available upon request.

Detector Accessories and Spares

Parameter Part Number
Vertical to horizontal mounting adaptor FD-AC-01
Standard mounting bracket 316 stainless steel FD-AC-02
Marine bracket 316 stainless steel (Supplied loose – not fitted) FD-AC-03
Detector sealing kit – metric (IP washers and O-rings) FD-AC-04
FGard Sunshield FD-AC-05
Crowcon flame detector – Flame Simulator FGard SIM FD-AC-06
2” pole mount kit FD-AC-09
3” pole mount kit FD-AC-10
4” pole mount kit FD-AC-11
Flame simulator spare charger FD-AC-12

Appendix A – Acronyms, Terms & Abbreviations

Term Description
AC Alternating Current
ATEX Atmosphere Explosive
AWG American Wire Gauge
BS British Standard
CCTV Closed Circuit Television
CE European Conformity
CO2 Carbon Dioxide
CSA Canadian Standards Associated
dB Decibel
DC Direct Current
EMC Electromagnetic Compatibility
EN European Norm
FM Factory Mutual
FOV Field of View
HFT Hardware Fault Tolerance
I or A Electrical Current or Ampere
JB Junction Box
Km Kilometre
kW Kilo Watt
LED Light Emitting Diode
MEL Crowcon (Engineering) Ltd
mH Milli Henry – Inductance
MORE Meteorological Optical Range
NEC National Electrical Codes
nF, pF Nano Farad, Pico Farad – Capacitance
PC Personal Computer (IBM PC Compatible)
R or Ω Ohms (electrical resistance)
SFF Safe Failure Fraction
SIL Safety Integrity Level
V Voltage
Vs Versus
W Watts (Wattage)

Appendix B – Help us to help you

TO: QA Department From:

Crowcon Detection Instruments Ltd. 172 Brook Drive,

Milton Park, Abingdon, Oxfordshire, OX14 4SD,

United Kingdom.

| Tel: Fax: Email:
sales@crowcon.com|
I suggest the following corrections/changes be made to Section ……………
Marked-up copies attached (as appropriate):| Yes/No
Please inform me of the outcome of this change: Yes/No
For Crowcon

Action by:  Date:

Response: Date: __

Appendix C – Field of View
Horizontal field of view to a 0.1 m2 N-heptane pan fire with an alarm response at standard sensitivity. 100% = 30 metres.

Vertical Field of view to a 0.1 m2 N-heptane pan fire with an alarm response at standard sensitivity. 100%= 30 metres. Appendix D – FM Approval Performance Report

Alarm response to various stimuli.

Stimuli Low Alarm Distance Standard Alarm Distance High Alarm Distance
N-heptane 0.1m2 pan fire 15 metres 30 metres 60 metres
Ethanol 0.1m2 pan fire 15 metres 30 metres 42 metres
JP4 0.1m2 pan fire No test 30 metres 60 metres
Methane 0.6m plume fire 15 metres 30 metres 50 metres
100W incandescent Lamp steady state No Alarm 0.9m No Alarm 1.8m No Alarm

1.8m
100W incandescent Lamp modulated| No Alarm 0.9m| No Alarm 1.8m| No Alarm 1.8m
Two 40W Fluorescent lamps steady state| No Alarm 0.9m| No Alarm 1.8m| No Alarm 1.8m
Two 40W Fluorescent lamps modulated| No Alarm 0.9m| No Alarm 1.8m| No Alarm 1.8m
500W Quartz Halogen lamp steady state| No Alarm 0.9m| No Alarm 1.8m| No Alarm 1.8m
500W Quartz Halogen lamp modulated| No Alarm 0.9m| No Alarm 1.8m| No Alarm 1.8m
190 Amp Electric arc welding| No Alarm 6.0m| No Alarm 8.0m| No Alarm 10m
3000W electric space heater steady state| No Alarm 1.8m| No Alarm 1.8m| No Alarm 1.8m
3000W electric space heater modulated| No Alarm 1.8m| No Alarm 1.8m| No Alarm 1.8m
1500W electric heater steady state| No Alarm 1.8m| No Alarm 1.8m| No Alarm 1.8m
1500W electric heater modulated| No Alarm 1.8m| No Alarm 1.8m| No Alarm 1.8m
Reflected Sunlight| No Alarm| No Alarm| No Alarm
Reflected modulated Sunlight| No Alarm| No Alarm| No Alarm

Low sensitivity response to N-heptane 0.1m2 pan fire in the presence of false alarm stimuli.

False Alarm Stimuli Distance to False Alarm Distance to Fire
100W incandescent Lamp steady state 0.9m 15 metres Alarm
100W incandescent Lamp modulated 0.9m 15 metres Alarm
Two 40W Fluorescent lamps steady state 0.9m 15 metres Alarm
Two 40W Fluorescent lamps modulated 0.9m 15 metres Alarm
500W Quartz Halogen lamp steady state 0.9m 15 metres Alarm
500W Quartz Halogen lamp modulated 0.9m 15 metres Alarm
190 Amp Electric arc-wielding 6.0m 15 metres Alarm
3000W electric space heater steady state 1.8m 15 metres Alarm
3000W electric space heater modulated 1.8m 15 metres Alarm
1500W electric heater steady state 1.8m 15 metres Alarm
1500W electric heater modulated 1.8m 15 metres Alarm
Reflected Sunlight N/A 15 metres Alarm
Reflected modulated Sunlight N/A 15 metres Alarm

Standard sensitivity response to N-heptane 0.1m2 pan fire in the presents of false alarm stimuli.

False Alarm Stimuli Distance to False Alarm Distance to Fire
100W incandescent Lamp steady state 1.8m 30 metres Alarm
100W incandescent Lamp modulated 1.8m 30 metres Alarm
Two 40W Fluorescent lamps steady state 1.8m 30 metres Alarm
Two 40W Fluorescent lamps modulated 1.8m 30 metres Alarm
500W Quartz Halogen lamp steady state 1.8m 30 metres Alarm
500W Quartz Halogen lamp modulated 1.8m 30 metres Alarm
190 Amp Electric arc welding 8.0m 30 metres Alarm
3000W electric space heater steady state 1.8m 30 metres Alarm
3000W electric space heater modulated 1.8m 30 metres Alarm
1500W electric heater steady state 1.8m 30 metres Alarm
1500W electric heater modulated 1.8m 30 metres Alarm
Reflected Sunlight N/A 30 metres Alarm
Reflected modulated Sunlight N/A 30 metres Alarm

High Sensitivity response to N-heptane 0.1m2 pan fire in the presence of false alarm stimuli.

False Alarm Stimuli Distance to False Alarm Distance to Fire
100W incandescent Lamp steady state 1.8m 60 metres Alarm
100W incandescent Lamp modulated 1.8m 60 metres Alarm
Two 40W Fluorescent lamps steady state 1.8m 60 metres Alarm
Two 40W Fluorescent lamps modulated 1.8m 60 metres Alarm
500W Quartz Halogen lamp steady state 1.8m 60 metres Alarm
500W Quartz Halogen lamp modulated 1.8m 60 metres Alarm
190 Amp Electric arc welding 8.0m 60 metres Alarm
3000W electric space heater steady state 1.8m 60 metres Alarm
3000W electric space heater modulated 1.8m 60 metres Alarm
1500W electric heater steady state 1.8m 60 metres Alarm
1500W electric heater modulated 1.8m 60 metres Alarm
Reflected Sunlight N/A 60 metres Alarm
Reflected modulated Sunlight N/A 60 metres Alarm

Appendix E – IEC 61508 Failure Rate Data
IEC 61508: ed 2, 2010 Using reliability data extracted from the exida Electrical and Mechanical Component Reliability Handbook the following failure rates resulted from the FGard IR3 FMEDA. MAXIMUM DIAGNOSTIC TEST INTERVAL – 15 minutes. The useful lifetime of critical components is predicted to be 50 years (Ref: Report No.: MP 17/10-145 R001 V1 R1).

Failure Category Failure Rate (FIT)
Fail-Safe Undetected 42
Fail Dangerous Detected 544
Fail Detected (detected by internal diagnostics) 488
Fail High (detected by logic solver) 13
Fail low (detected by logic solver) 43
Fail Dangerous Undetected 117
No Effect 1547
Annunciation Undetected 11

The FGard IR3 is classified as a Type B Element according to IEC 61508, having a hardware fault tolerance of 0. Therefore, based on the SFF of 94.83% a design can meet SIL 2 @ HFT=0 when the FGard IR3 is used as the only component in a SIF Sub-assembly.

Proof testing should be carried out on a yearly basis, showing a probability of failure on demand average (PFDAVG) of 6.82E-03. The following represents a suggested proof test.

Proof Testing

Step Action
1 Bypass the safety function and take appropriate action to avoid false

trips.
2| (Optional) Use RS485 communications to retrieve and diagnostics and take appropriate action.
3| Use the test torch to force the FGard IR3 into an alarm state. Verify that LED, alarm relay/0-20mA

outputs indicate alarm (as required)

4| Wait for the detector alarm signal to unlatch. Verify that the LED, alarm relay/0-20mA outputs no longer indicate alarm.
5| Inspect the enclosure for any leaks, visible damage, or dirty optics.
6| Perform the periodic inspection and maintenance procedure from the FGard IR3 safety and technical

manual.

7| Remove the bypass and otherwise restore normal operation.

Personnel carrying out commissioning, testing and maintenance on this device shall be sufficiently competent and experienced to do so.

Appendix F – SIL 2 exida Certification

Appendix G – INMETRO Certification
Certificate to be added once process complete.

Appendix H – PESO Certification
Certificate to be added once process complete.

UK Office

  • Crowcon Detection Instruments Ltd 172 Brook Drive,
  • Milton Park,
  • Abingdon
  • Oxfordshire
  • OX14 4SD
  • Tel: +44 (0) 1235 557700
  • Fax: +44 (0) 1235 557749
  • Email: sales@crowcon.com
  • Website: www.crowcon.com

USA Office

  • Crowcon Detection Instruments Ltd
  • 1455 Jamike Ave, Suite 100
  • Erlanger
  • KY 41018
  • Tel: +1 859 957 1039 or 1 800 527
  • 6926
  • Fax: +1 859 957 1044
  • Email: salesusa@crowcon.com
  • Website: www.crowcon.com

Netherlands Office

  • Crowcon Detection Instruments Ltd
  • Vlambloem 129
  • 3068JG, Rotterdam
  • Netherlands
  • Tel: + 31 10 421 1232
  • Fax: + 31 10 421 0542
  • Email: eu@crowcon.com
  • Website: www.crowcon.com

Singapore Office

  • Crowcon Detection Instruments Ltd Block 194, Pandan Loop
  • 06-20 Pantech Industrial Complex

  • Singapore 128383
  • Tel: + 65 6745 2936
  • Fax: +65 6745 0467
  • Email: sales@crowcon.com.sg
  • Website: www.crowcon.com

China Office

  • Crowcon Detection Instruments Ltd (Beijing) Unit 316, Area 1, Tower B, Chuangxin Building
  • 12 Hongda North Road, Beijing Eco- nomic Technological Development Area
  • Beijing, China 100176
  • Tel: +86 10 6787 0335
  • Fax: +86 10 6787 4879
  • Email: saleschina@crowcon.cn
  • Website: www.crowcon.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals