Acrel BM200 Isolated Safety Barrier Instruction Manual
- September 21, 2024
- Acrel
Table of Contents
- BM200 Isolated Safety Barrier
- Specifications:
- Product Information:
- Product Usage Instructions:
- 1. General:
- 2. Executive Standard:
- 3. Type of Products:
- 4. Technical Parameters:
- 5. Install and Wiring:
- Q: What are the different types of products available in the
- Q: What are the technical parameters of the BM200 Isolated
BM200 Isolated Safety Barrier
“`html
Specifications:
- Product: Series BM200 Isolated Safety Barrier
- Manufacturer: Acrel Co. Ltd
- Version: V1.1
Product Information:
The BM200 Isolated Safety Barrier is designed to provide
protection in explosive atmospheres and industrial-process measure
and control systems.
Product Usage Instructions:
1. General:
The BM200 Isolated Safety Barrier is available in different
configurations based on input and output types.
2. Executive Standard:
The product complies with various standards related to explosive
atmospheres and equipment protection.
3. Type of Products:
The BM200 series includes different configurations like
single-way input and output, double-way input and output, with
various input and output signal types.
4. Technical Parameters:
The product supports current, voltage, thermal resistance, and
other input signals with high transmission accuracy and quick
response time. It operates within specified power supply and
temperature ranges.
5. Install and Wiring:
Refer to the outline dimensions provided for different types of
BM200 products for installation guidance. Follow the wiring
diagrams for safe and proper connections in hazardous and safe
areas.
FAQ:
Q: What are the different types of products available in the
BM200 series?
A: The BM200 series includes configurations like single-way
input and output, double-way input and output, with various input
and output signal types.
Q: What are the technical parameters of the BM200 Isolated
Safety Barrier?
A: The product supports current, voltage, thermal resistance,
and other input signals with high transmission accuracy, quick
response time, and operates within specified power supply and
temperature ranges.
“`
505
Series BM200 Isolated Safety Barrier
Installation and Operation Instruction V1.1
Acrel Co . , Ltd
DECLARATION
No part of this publication may be reproduced, stored in a retrieval system,
or transmitted in any form by any means, electronic, mechanical photocopying,
recording, or otherwise without prior permission of Acrel. All rights
reserved.
This company reserve power of revision of product specification described in
this manual, without notice. Before ordering, please consult local agent for
the latest specification of product.
CONTENTS
1 General………………………………………………………………………………………………………………………………………………………. 4 2
Executive standard………………………………………………………………………………………………………………………………………. 4 3
Type of products…………………………………………………………………………………………………………………………………………..4 4
Technical parameter…………………………………………………………………………………………………………………………………….. 5 5
Install and wiring………………………………………………………………………………………………………………………………………….5
5.1 Outline dimension……………………………………………………………………………………………………………………………… 5 5.2
Wiring……………………………………………………………………………………………………………………………………………….6 6
Precautions…………………………………………………………………………………………………………………………………………………. 8 7
Application examples…………………………………………………………………………………………………………………………………… 8
1 General
Series BM200 isolated safety barrier can transmit signals between the safe
area and the dangerous area, and limit the energy transfer from the safe area
to the dangerous area caused by the fault. The voltage, current, temperature,
resistance signals generated by the equipment (transmitter) on the dangerous
side are isolated and converted into corresponding linear voltage and current
signals outputting to the safe area. The product requires independent power
supply, and the input/output/power supply is isolated. It can be used in
current source, two-wire, three-wire transmitter equipment.
2 Executive standard
GB 3836.1-2010 “Explosive atmospheres–Part 1:Equipment–General requirements”
GB 3836.4-2010 “Explosive atmospheres–Part 4:Equipment protection by intrinsic
safety i” GBT 28471.1-2012 “Distributor for use in industrial-process measure
and control systems–Part 1:General technical specification” GBT 28471.2-2012
“Distributor for use in industrial-process measure and control systems–Part
2:Performance evaluation method ”
3 Type of products
BM200 – / –
11-Single-way input and single-way output 12-Single-way input and double-way output 22-Double-way input and double-way output
B-12.5mm case C-22.5mm case S-Output power supply
Output type I-DC current
V-DC voltage
S-Input power supply
Input type DI-DC current DV-DC voltage TC-Thermocouple R-Fixed resistance
Isolated safety barrier
TR-Thermal resistance VR-Potentiometer
4 Technical parameter
Channel type Input type Input signal
Output signal Transmission accuracy Temperature modulus
Response time Power supply Work temperature
Fix mode Dielectric strength
Single-way input and single-way output, single-way input and double-way
output, double-way input and double-way output Current/Voltage/Thermal
resistance Pt100/Resistance/Thermocouple
0~20mA /4~20mA 0~5V /0~10V /1~5V (Distribution voltage: 12V/20mA)
PT100 /0~10K/KETJNRSB 0~20mA /4~20mA (Safe side input); Load resistance: 550
0~5V /1~5V (Safe side input); Load resistance: 330K 0~10V (Safe side input);
Load resistance: 500K
0.2%
50ppm/ (The output signal is current) 5ms to reach 90% of final value
(RTD Pt100/resistance/thermocouple input: 1s to reach 90% of final value
20~35V DC
-20+60
Rail installation
Intrinsically Safe and Non-Intrinsically Safe 2500V AC; Power supply and Non-
Intrinsically Safe 500V AC
NoteIntrinsically Safe is input, Non-Intrinsically is output
5 Install and wiring
5.1 Outline dimension Product category
BM200
Type of products
BM200-/-B11(single-way input and single-way output)
BM200-/-C2 (single-way input and double-way output/double-way input and
single-way output)
Outline dimension 99mm114.5mm12.5mm
99mm114.5mm22.5mm
5.1.1 BM200-/-B11 outline dimension:
5.1.2 BM200-/-C2 outline dimension:
5.2 Wiring 5.2.1 BM200-DI/I-
Hazardous Area IN
+(1151)
+(1126) -10
(14)
-S(111026) (14)
Current Three-Wire
Source Transmitter
11 (15)
S
12 (16)
In1
In2 Two-Wire Transmitter
Safe Area
11(+) 12(S) 10(-) 15(+) 16(S) 14(-)
OUT
6(-) 5(+) Out1
8(-) 7(+) Out2
4(-) 3(+) Supply
5.2.2 BM200-DV/-:
Hazardous Area
Safe Area
IN
OUT
In1
V-
S Power In2 Analogue Distribution Voltage
11(+) 10(-)
12(S)
15(+) 14(-)
16(S)
6(-) 5(+) Out1
8(-) 7(+) Out2
4(-) 3(+) Supply
5.2.3 BM200-T/-:
Hazardous Area
IN
+ 12 (16) – 11 (15)
+ 12
(16)
– 11 (15)
In1
+ –
– 10 (14)
– 10 (14)
In2
+ –
Two-Wire Three-Wire
RTD
RTD
5.2.4 BM200-VR/-:
Hazardous Area
IN
+ 12 (16)
+ 12 (16)
In1
– 11 (15) – 10 (14)
– 11 (15) In2 – 10 (14)
Two-Wire Three-Wire
RP
RP
Safe Area
12 11 10 16 15 14
OUT
6(-) 5(+) Out1
8(-) 7(+) Out2
4(-) 3(+) Supply
Safe Area
12 11 10 16 15 14
OUT
6(-) 5(+) Out1
8(-) 7(+) Out2
4(-) 3(+) Supply
6 Precautions 6.1This product complies with GB3836.1-2010 “Distributor for use
in industrial-process measure and control systems–Part 1:General technical
specification “and GB3836.4-2010 “Explosive atmospheres–Part 4:Equipment
protection by intrinsic safety i “standards, and installation, operation and
maintenance should be carried out under the requirements of corresponding
standard. 6.2 This product must be installed in a safe area, and the
surrounding air does not contain any medium that is corrosive to chromium,
nickel and silver plating. 6.3 All instruments connected to the safety barrier
must be instruments with explosion-proof certificate. When the safety barrier
and a primary instrument form an intrinsically safe explosion-proof system,
they must be approved by the state-specified explosion-poof inspection. 6.4
When the wiring is not completely disconnected, it is strictly forbidden to
use a megohmmeter to directly test the insulation parameters between the
terminals, otherwise the internal fast fuse will be blown. 6.5 The wiring of
the intrinsically safe side power supply of the safety barrier should not be
mixed with other non-intrinsically safe side circuits. Any wrong wiring may
cause danger. The circuit wiring of the intrinsically safe and non-
intrinsically safe of this product should be laid separately in the line
groove.
7 Application examples E.g.1 Input: single-way 4-20mA , output: double-way
4-20mA , auxiliary power supply: 24V DC
Type: BM200-DI/I-C12 E.g.2 Input: double-way 0-5V, output: double-way 0-20mA ,
auxiliary power supply: 24V DC
Type: BM200-DV/I-C22 E.g.3 Input: single-way Pt100, output: double-way 0-20mA
, auxiliary power supply: 24V DC
Type: BM200-TR/I-C22
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>