Acrel BM200 Isolated Safety Barrier Instruction Manual

September 21, 2024
Acrel

BM200 Isolated Safety Barrier

“`html

Specifications:

  • Product: Series BM200 Isolated Safety Barrier
  • Manufacturer: Acrel Co. Ltd
  • Version: V1.1

Product Information:

The BM200 Isolated Safety Barrier is designed to provide
protection in explosive atmospheres and industrial-process measure
and control systems.

Product Usage Instructions:

1. General:

The BM200 Isolated Safety Barrier is available in different
configurations based on input and output types.

2. Executive Standard:

The product complies with various standards related to explosive
atmospheres and equipment protection.

3. Type of Products:

The BM200 series includes different configurations like
single-way input and output, double-way input and output, with
various input and output signal types.

4. Technical Parameters:

The product supports current, voltage, thermal resistance, and
other input signals with high transmission accuracy and quick
response time. It operates within specified power supply and
temperature ranges.

5. Install and Wiring:

Refer to the outline dimensions provided for different types of
BM200 products for installation guidance. Follow the wiring
diagrams for safe and proper connections in hazardous and safe
areas.

FAQ:

Q: What are the different types of products available in the

BM200 series?

A: The BM200 series includes configurations like single-way
input and output, double-way input and output, with various input
and output signal types.

Q: What are the technical parameters of the BM200 Isolated

Safety Barrier?

A: The product supports current, voltage, thermal resistance,
and other input signals with high transmission accuracy, quick
response time, and operates within specified power supply and
temperature ranges.

“`

505
Series BM200 Isolated Safety Barrier
Installation and Operation Instruction V1.1
Acrel Co . , Ltd

DECLARATION
No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of Acrel. All rights reserved.
This company reserve power of revision of product specification described in this manual, without notice. Before ordering, please consult local agent for the latest specification of product.

CONTENTS
1 General………………………………………………………………………………………………………………………………………………………. 4 2 Executive standard………………………………………………………………………………………………………………………………………. 4 3 Type of products…………………………………………………………………………………………………………………………………………..4 4 Technical parameter…………………………………………………………………………………………………………………………………….. 5 5 Install and wiring………………………………………………………………………………………………………………………………………….5
5.1 Outline dimension……………………………………………………………………………………………………………………………… 5 5.2 Wiring……………………………………………………………………………………………………………………………………………….6 6 Precautions…………………………………………………………………………………………………………………………………………………. 8 7 Application examples…………………………………………………………………………………………………………………………………… 8

1 General
Series BM200 isolated safety barrier can transmit signals between the safe area and the dangerous area, and limit the energy transfer from the safe area to the dangerous area caused by the fault. The voltage, current, temperature, resistance signals generated by the equipment (transmitter) on the dangerous side are isolated and converted into corresponding linear voltage and current signals outputting to the safe area. The product requires independent power supply, and the input/output/power supply is isolated. It can be used in current source, two-wire, three-wire transmitter equipment.

2 Executive standard
GB 3836.1-2010 “Explosive atmospheres–Part 1:Equipment–General requirements” GB 3836.4-2010 “Explosive atmospheres–Part 4:Equipment protection by intrinsic safety i” GBT 28471.1-2012 “Distributor for use in industrial-process measure and control systems–Part 1:General technical specification” GBT 28471.2-2012 “Distributor for use in industrial-process measure and control systems–Part 2:Performance evaluation method ”

3 Type of products

BM200 – / –

11-Single-way input and single-way output 12-Single-way input and double-way output 22-Double-way input and double-way output

B-12.5mm case C-22.5mm case S-Output power supply

Output type I-DC current

V-DC voltage

S-Input power supply
Input type DI-DC current DV-DC voltage TC-Thermocouple R-Fixed resistance
Isolated safety barrier

TR-Thermal resistance VR-Potentiometer

4 Technical parameter
Channel type Input type Input signal
Output signal Transmission accuracy Temperature modulus
Response time Power supply Work temperature
Fix mode Dielectric strength

Single-way input and single-way output, single-way input and double-way output, double-way input and double-way output Current/Voltage/Thermal resistance Pt100/Resistance/Thermocouple
0~20mA /4~20mA 0~5V /0~10V /1~5V (Distribution voltage: 12V/20mA)
PT100 /0~10K/KETJNRSB 0~20mA /4~20mA (Safe side input); Load resistance: 550
0~5V /1~5V (Safe side input); Load resistance: 330K 0~10V (Safe side input); Load resistance: 500K
0.2%
50ppm/ (The output signal is current) 5ms to reach 90% of final value
(RTD Pt100/resistance/thermocouple input: 1s to reach 90% of final value
20~35V DC
-20+60
Rail installation
Intrinsically Safe and Non-Intrinsically Safe 2500V AC; Power supply and Non- Intrinsically Safe 500V AC
NoteIntrinsically Safe is input, Non-Intrinsically is output

5 Install and wiring
5.1 Outline dimension Product category
BM200

Type of products
BM200-/-B11(single-way input and single-way output)
BM200-/-C2 (single-way input and double-way output/double-way input and single-way output)

Outline dimension 99mm114.5mm12.5mm
99mm114.5mm22.5mm

5.1.1 BM200-/-B11 outline dimension:

5.1.2 BM200-/-C2 outline dimension:

5.2 Wiring 5.2.1 BM200-DI/I-

Hazardous Area IN

+(1151)

+(1126) -10
(14)

-S(111026) (14)

Current Three-Wire

Source Transmitter

11 (15)

S

12 (16)

In1

In2 Two-Wire Transmitter

Safe Area
11(+) 12(S) 10(-) 15(+) 16(S) 14(-)

OUT
6(-) 5(+) Out1
8(-) 7(+) Out2
4(-) 3(+) Supply

5.2.2 BM200-DV/-:

Hazardous Area

Safe Area

IN

OUT

In1

V-

S Power In2 Analogue Distribution Voltage

11(+) 10(-)
12(S)
15(+) 14(-)
16(S)

6(-) 5(+) Out1
8(-) 7(+) Out2
4(-) 3(+) Supply

5.2.3 BM200-T/-:

Hazardous Area

IN

+ 12 (16) – 11 (15)

+ 12

(16)

– 11 (15)

In1

+ –

– 10 (14)

– 10 (14)

In2

+ –

Two-Wire Three-Wire

RTD

RTD

5.2.4 BM200-VR/-:

Hazardous Area

IN

+ 12 (16)

+ 12 (16)

In1

– 11 (15) – 10 (14)

– 11 (15) In2 – 10 (14)

Two-Wire Three-Wire

RP

RP

Safe Area
12 11 10 16 15 14

OUT
6(-) 5(+) Out1
8(-) 7(+) Out2
4(-) 3(+) Supply

Safe Area
12 11 10 16 15 14

OUT
6(-) 5(+) Out1
8(-) 7(+) Out2
4(-) 3(+) Supply

6 Precautions 6.1This product complies with GB3836.1-2010 “Distributor for use in industrial-process measure and control systems–Part 1:General technical specification “and GB3836.4-2010 “Explosive atmospheres–Part 4:Equipment protection by intrinsic safety i “standards, and installation, operation and maintenance should be carried out under the requirements of corresponding standard. 6.2 This product must be installed in a safe area, and the surrounding air does not contain any medium that is corrosive to chromium, nickel and silver plating. 6.3 All instruments connected to the safety barrier must be instruments with explosion-proof certificate. When the safety barrier and a primary instrument form an intrinsically safe explosion-proof system, they must be approved by the state-specified explosion-poof inspection. 6.4 When the wiring is not completely disconnected, it is strictly forbidden to use a megohmmeter to directly test the insulation parameters between the terminals, otherwise the internal fast fuse will be blown. 6.5 The wiring of the intrinsically safe side power supply of the safety barrier should not be mixed with other non-intrinsically safe side circuits. Any wrong wiring may cause danger. The circuit wiring of the intrinsically safe and non- intrinsically safe of this product should be laid separately in the line groove.
7 Application examples E.g.1 Input: single-way 4-20mA , output: double-way 4-20mA , auxiliary power supply: 24V DC
Type: BM200-DI/I-C12 E.g.2 Input: double-way 0-5V, output: double-way 0-20mA , auxiliary power supply: 24V DC
Type: BM200-DV/I-C22 E.g.3 Input: single-way Pt100, output: double-way 0-20mA , auxiliary power supply: 24V DC
Type: BM200-TR/I-C22

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals